THE MEASUREMENT OF MAGNETIC FIELD IN TWO POWER DISTRIBUTION SUBSTATIONS

Similar documents
ANALYSIS OF DISTURBING MAGNETIC FIELD ASSOCIATED WITH ELECTROSTATIC DISCHARGES

ELECTROSTATIC DISCHARGE E-FIELD SPECTRUM ANALYSIS AND GRAPHICAL INTERPRETATION

ASPECTS REGARDING THE ELECTRICAL RESISTIVITY SOFTWARE MEASUREMENTS ON INSULATING MATERIALS USING 6517A HI-R SWEEP TEST PROGRAM

AN ALGORITHM FOR THE ADAPTIVE CONTROL OF ANTI HAIL MISSILE LAUNCH RAMPS

THREE CHANNELS ANALYSIS SYSTEM FOR ELECTRICAL POWER SYSTEM DISTURBANCES MEASUREMENT

A NOVEL ACTIVE INDUCTOR WITH VOLTAGE CONTROLLED QUALITY FACTOR AND SELF-RESONANT FREQUENCY

THE THICKNESS MEASUREMENT OF WEFT KNITTED STRUCTURES MADE WITH ELASTOMERIC YARNS

LINEAR CURRENT-TO-FREQUENCY CONVERTER WITH WIDE OUTPUT RANGE

D.C. DRIVE SYSTEM USING FOUR-QUADRANT CHOPPER

FINITE ELEMENT METHOD MODELING OF BRUSHLESS DC SERVOMOTOR WITH FRACTIONAL NUMBER OF SLOTS PER POLE

MASKING THE INSTRUCTIONS OF A MICROCONTROLLER USING A CHAOTIC POWER SUPPLY

COMPARISON OF CONCENTRATED AND DISTRIBUTED WINDING IN TERM OF THE MAGNETIC FIELDS

The Survey of Electromagnetic Environment near RF Transmitters

RESEARCH CONCERNING THE INFLUENCE OF ANGLE OF FILING FROM THE KNIFE BLADES VINDROVERS ON THE MECHANICAL WORK ON CUTTING

EXPERIMENTAL RESULTS REGARDING STRUCTURAL RESPONSE OF BOLTED AND HYBRID CONNECTIONS FOR PULTRUDED ELEMENTS

SINGLE-PHASE AC-AC CONVERTER

EVALUATION OF THE YARN QUALITY CHARACTERISTICS THROUGH SYNTHETIC INDICATORS

DISTORTING STATE ANALYSIS IN ELECTRIC ENERGY DISTRIBUTION NETWORKS

OPTIMIZING TOOLS DIAMETERS AND TOOL PATH STYLE TO IMPROVE TIME MACHINING

LINEAR VOLTAGE-TO-CURRENT CONVERTER WITH SMALL AREA

CMOS DELAY CELL WITH LARGE TUNING RANGE

USING SERIAL INDUSTRIAL ROBOTS IN CNC MILLING PROCESESS

RULES FOR LIMITING RISK EXPOSURE OF THE HUMAN BODY TO ELECTROMAGNETIC FIELDS

SOFTWARE CONTROL USED FOR AC MOTORS

Electromagnetic shielding proprieties evaluation of buildings situated near radio frequency transmitters

OUTER GATE AUTOMATION USING MICROCONTROLLERS AND RADIO FREQUENCY COMMUNICATION

Specific Equipment and Area - EAC District Office Substation

DETERMINING ADDITIONAL POWER AND ENERGY LOSSES IN LOW VOLTAGE ELECTRICITY DISTRIBUTION NETWORKS OPERATED IN DISTORTED AND UNBALANCED OPERATION STATES

ELECTROMAGNETIC POLLUTION INSIDE HIGH VOLTAGE SUBSTATION

CMOS SCHMITT TRIGGER WITH CURRENT-CONTROLLED HYSTERESIS

COMPARISON OF PITCH CONTROL SYSTEM FOR AN UNMANNED FREE-SWIMMING SUBMERSIBLE VEHICLE WITH PD CONTROLLER AND LINEAR QUADRATIC REGULATOR USING MATLAB

VIRTUAL INSTRUMENTATION IN THE DRIVE SUBSYSTEM MONITORING OF A MOBIL ROBOT WITH GESTURE COMMANDS

ELECTRIC AND MAGNETIC FIELD MEASUREMENTS ON BOARD A SHIP

A MATLAB Graphical User Interface Dedicated to the Optimal Design of the High Power Induction Motor with Heavy Starting Conditions

Characterizing the Sensitivity of a Hall Sensor

ELECTRIC AND MAGNETIC FIELD MEASUREMENTS FROM A SHIP FOUND IN THE PORT AREA

DIGITAL CONTROL OF A BRUSHLESS DC SERVOMOTOR ELECTRICAL DRIVE SYSTEMS CLOSED-LOOP CONTROL

MAGNETIC FIELD METER Operator s Manual

SPEED CONTROL OF DC MOTOR USING FOUR-QUADRANT CHOPPER AND BIPOLAR CONTROL STRATEGY

Regulatory Authority of Bermuda report on

Advanced Test Equipment Rentals ATEC (2832)

MEETING THE RECENT REQUESTS ORIGINATED BY THE INCOMING EDITION OF EN

BIODEGRADABLE YARNS FOR WEAVES USED FOR COMPOSITE MATERIALS

Research Activities Plan. Appendix K Magnetic Fields from Submarine Cables

SECULIFE SR PC Controllable Instrument for Measuring Safety-Relevant Characteristic Values of Electrical Devices /2.

ENVIRONMENTAL PARAMETERS LABORATORY MEASUREMENTS WITH VIRTUAL INSTRUMENTATION

Analytical Design Optimization of 765 kv Transmission Line Based on Electric and Magnetic Fields for Different Line Configurations

MESUREMENTS OF ELECTRICAL AND MAGNETIC FIELDS ON BOARD CONTAINER SHIPS

Safety Code 6 (SC6) Measurement Procedures (Uncontrolled Environment)

CONSIDERATIONS REGARDING THE SMALL POWER

Low Frequency. Precision test equipment for safety in electric and magnetic fields

Analysis of static and time-variable magnetic fields

MODELLING PATTERNS FOR FABRIC REINFORCED COMPOSITES

Buletinul AGIR nr. 3/2012 iunie-august. Assis. Eng. Ciprian AFANASOV PhD. University "Ştefan cel Mare" Suceava

MATHEMATIC MODEL AND APLICATION FOR HARMONIC STEADY-STATE OF THE POWER TRANSMISSION LINE

VOLTAGE QUALITY ANALYSIS IN LOW VOLTAGE PUBLIC ELECTRIC DISTRIBUTION NETWORKS OPERATED IN DISTORTED AND UNBALANCED CONDITIONS

TVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active

Wireless System Collocation Presents New Issues For Worker Protection

Where Safety Matters, Use The Latest Technology

Mobile Phone Base-Station Audit

LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

Inductive sensor slot-type SI2-K08-AP7

ELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE

Technical Note 2. Standards-compliant test of non-ionizing electromagnetic radiation on radar equipment

LEAKAGE FLUX CONSIDERATIONS ON KOOL Mµ E CORES

For Isotropic Measurement of Magnetic and Electric Fields

Single-Channel Safety Barriers Series 9001

HIGH CURRENT PWM BIPOLAR STEPPER MOTOR CONTROL AND DRIVE

Product Data Sheet 8452/2HHP. The engineer's choice

Overhead Power Lines: Argaki area in Moni, Limassol

KEY WORDS: conductive, clothing, live, line, maintenance, high, voltage

Mobile Phone Base-Station Audit

EXPOSURE TO RADIOFREQUENCIES IN HOSPITAL REHABILITATION SERVICES

Power Quality Survey in a Distribution System, Standard Procedures and Limitations. H. Mokhtari S. Hasani and M. Masoudi

FLAX AND HEMP NATURAL ALTERNATIVES IN THE FIELD OF MEDICAL TEXTILES

Magnetic Field Measurement in Residential Areas Göteborg, Borås and Mark Residential Area Measurements SEYED REZA ATEFI

Data Sheet. Hall effect transducers, current and voltage

THE RUSSIAN STANDARDS AND THE OPINION ABOUT INTERNATIONAL HARMONIZATION OF ELECTROMAGNETIC STANDARDS

DRIVEN ASYNCHRONOUS MOTORS

3D-magnetic field probes AS-U3D GEO-X for ±200 µt

2 Safety Barriers. Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

Mobile Phone Base-Station Audit

SAG MITTIGATION TECHNICS USING DSTATCOMS

BIODEX MULTI- JOINT SYSTEM

v1.0.1 March AlphaLab, Inc. All rights reserved. TriField EMF Meter Owner s Manual

NEURAL NETWORKS USED IN THE EVALUATION OF POWER QUALITY

Mobile Phone Base-Station Audit

Electric and magnetic field levels around Christchurch

DETECTION OF ERRONEOUS OPERATION IN TTL INTEGRATED CIRCUITS USING MODULUS FUNCTIONS OF NOISE MARGINS

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER

F1A Magnetic Field Transducers

INDUCTION ENGINE,PHYSICAL

Mobile Phone Base-Station Audit

Evaluation on the Potential Risk Hazards of Magnetic Field Radiated from Cast Resin Transformer Electric Substation

The SEMONT Network Utilization for the Lowfrequency

7P Series - Surge Protection Device (SPD) Features 7P P P

ON THE TRANSIENTS OPTIMIZATION AND THE POWER FACTOR CORRECTION OF THE STATIC CONVERTERS

EXPOSURE to electromagnetic fields (EMFs) is not a

Product Data Sheet 3254 J/2H3P

Transcription:

BULETINUL INSTITUTULUI POLITEHNIC DIN IAŞI Publicat de Universitatea Tehnică Gheorghe Asachi din Iaşi Volumul 62 (66), Numărul 4, 2016 Secţia ELECTROTEHNICĂ. ENERGETICĂ. ELECTRONICĂ THE MEASUREMENT OF MAGNETIC FIELD IN TWO POWER DISTRIBUTION SUBSTATIONS BY IONEL PAVEL * and VALERIU DAVID Technical University Gheorghe Asachi of Iaşi, Faculty of Electrical Engineering Received: November 8, 2016 Accepted for publication: December 15, 2016 Abstract. In this paper we present the measurements results of low frequency magnetic fields in two power distribution substations from Iasi city. We made both spot measurements and long term survey in different areas, considering spatial variability and field variability with height. The measurements were performed near various field sources, in control rooms and in technological space by using three different measurement equipments including an instrument for automatic field survey. In view of the spatial variability, we made a few maps of the magnetic field in some areas and graphical representations of the magnetic field variability with height from the floor. Even the highest values were recorded in Station 1 on the section with current transformers (9845 nt) and in Station 2 near the electrical transformer (7408 nt) are much below the ICNIRP reference levels. Key words: background magnetic field; distribution substation; long term survey; magnetic field measurements; map of magnetic fields. 1. Introduction The human exposure to low frequency magnetic field is still great concern and also were made various studies on this domain (Morega et al., 2014; * Corresponding author: e-mail: ionelpavel7@tuiasi.ro

22 Ionel Pavel and Valeriu David Munteanu et al., 2010; Safigianni et al., 2012). Supplementary, the magnetic fields generated by power line can disturb sensible equipment in home and others environments (Breniuc & Haba, 2014; Haba et al., 2017). The values of the magnetic field recorded in various areas and near some sources inside the substations and power distribution are compared with the maximum values allowable by some standards (Hotărâre nr. 520/2016; ICNIRP, 2010). The difficulties encountered at measurements in substations are due to spatial variability in different areas and the magnetic field variability with height. That s why more accurate representation of measurements in the maps or graphs is goods solutions (Nicolaou et al., 2012). In this paper we present some results and maps of the magnetic fields obtained in two stations from Iasi city. For the entire study we used two conventional measurements and one automatic instrument made in our laboratory which perform both spot measurement and long-term survey of background magnetic field (David et al., 2009; Nica et al., 2016). Beside the spot measurements with spatial variability study, for some points, we made an automatic fields survey with time and frequency domain representation. In Section 2 we present the instrumentation and methods which were used for implementation the entire study. Section 3 will mention the collecting results from the stations by using three different measurement equipments, and we present those results in maps form, graphs, and statistical processing. 2. Instrumentation and Methods For determination of the magnetic field in the two considered transformer stations, we have conducted several measurements in some areas of interest by using three different measurement equipments. Thus, we used in measurements the gauss meter CA 40 with uniaxial sensor (M1), the gauss meter PCE-G28 with triaxial sensor (M2) and an automated magnetic field measurement system realized in our laboratory. (David et al., 2009; David et al., 2010). For magnetic field measurements we selected some areas based on the degree of magnetic pollution, namely near transformers, autotransformers, where the field reaches the highest values and also in personnel/workers areas (control rooms, offices, equipment panels). In control rooms we made both spot measurements and an automatic survey of magnetic field with a statistical processing. In 2015 we made some magnetic field measurements inside FAI station (Station 1, Fig.1), located in Valea Lupului in Iasi city. As is indicated in Fig. 1 we performed magnetic field measurements in some areas where the workers have access: all five sections (1, 2, 3, 4, and 5), control room/office (CR S1 ) and technological space (TS S1 ). Over the all sections were made measurements at a distance of one meter and one meter height. The second location, the Station 2, is situated in Industrial Area from Iasi, and the measurements were made on a portion of network CEL110 kv LAMINOR (1, in Fig. 2), near the electric transformer (T S2, in Fig. 2), in control

Bul. Inst. Polit. Iaşi, Vol. 62 (66), Nr. 4, 2016 23 room (CR S2, in Fig. 2) and in a point P2 situated on the route of personnel/workers. Fig. 1 Map of Station 1, with the 5 Sections, control room and technological space. Fig. 2 Map of Station 2 from industrial area, Iaşi. For Zones 1 and Ts 2 there were realized only spot measurements of magnetic field by using the first two measurement instruments. For CRs 2 and P2 more attention was paid, because the staff is working most part of the days. First, we made spot measurements considering spatial variability in this areas and the magnetic field variability with height from the ground. Then, we made an automatic survey of background magnetic fields, with the time domain and frequency domain representations and a statistical processing.

24 Ionel Pavel and Valeriu David 3. Results 3.1. Station 1 (FAI station) Section 1 contains four transformers (110 kv / 20 kv) and the maximum value obtained on this area is 2920 nt. For Section 2 where are situated the current transformers, the entire longitudinal profile section can be seen in Fig. 3. In this section the highest value of magnetic field is 9845 nt. In Section 3, where are present voltage transformers and arresters, the maximum value of magnetic field is 4120 nt. In Section 4 of the FAI station, the greatest values of magnetic induction of about 6300 nt in a point situated near the two autotransformers (220/110 kv-200 MVA). In the last section studied, Section 5, where are situated the current transformers, the greatest value of the field is 7890 nt. Fig. 3 The longitudinal profile, Section 2 of FAI Station. In CR S1 were made measurements of magnetic field in some points (in the central of room, C, and in every corner of the control room, P1, P2, P3 and P4) and at different heights (zero meters, one meter and two meters). The highest values of magnetic field were recorded in P2 (140 nt) and P3 (190 nt) because these points are located near the corners of the wall of the technological space. As a result of the measurements, we find that the magnetic field values are higher at the floor level, decreasing with the height; due to the fact that the indoor electrical installation is mostly made on the floor. This representation can be seen in Fig. 4. Fig. 4 The magnetic field measured in CR S1 in some points at different heights. Technological space (TS S1 ) is located besides the control room, here being placed control panels of station, converters and inverters. Also the measurements were made by the same method related to the control room. The

Bul. Inst. Polit. Iaşi, Vol. 62 (66), Nr. 4, 2016 25 highest value of the magnetic field measured in all five points was indicated in the center of the control room (C), there being located the control panels of station as is shown in Fig. 5. Fig. 5 The magnetic field measured in TS S1 in some points at different heights. Further, the magnetic field measurements were made near rectifiers and inverters. These sources are found in the technological space where workers have access throughout the entire working day. So, they may be subjects of the long term exposure of magnetic field generated by these sources. We made the measurements at different heights to observe its spatial variability and to find some protection methods. The values of magnetic field collected in these areas are represented in Table 1. It was observed that, with increasing height, the field values are decreasing with the removal from the source. Table 1 The Magnetic Field Measurements Near Rectifiers and Inverters Survey zone B r.m.s., [nt] 1 meter height 2 meters height Rectifier1 800 762 Rectifier 2 1,225 1,129 Inverter 1 5,447 1,471 Inverter 2 6,634 1,713 3.2. Station 2 (Industrial Area) We performed field measurements in Zone 1 at different points and we draw a map which represents the spatial variability of the magnetic field from this area, as shown in Fig. 6. The size of the area of interest is 7 m 17 m and contains: phases bar R, S, T, a separator of 110 kv, Iasi South and the earth lead. All these measurements were made at a height of one meter above the ground by using successively the first two measurement instruments (at the same point, but at different times). The highest values of the field in this perimeter have been identified under each phase of the aerial power line (836 nt, 994 nt, 911 nt). We made also a comparison between the results obtained with instrument M1 (Pavel & David, 2016) and the instrument M2. We made measurement of the magnetic field with different instruments to accurately determine the spatial variability of the magnetic field. The maximum

26 Ionel Pavel and Valeriu David differences of magnetic fields obtained with the two considered instruments are under 3%, as shown in Fig. 7. Fig. 6 The map of magnetic field measurements in Zone 1, Station 2. Fig. 7 The differences between the result obtained with M1 and M2. The following magnetic field measurements were made in Ts 2 area, where the electrical transformer is located. Due to the fact that the electrical transformer is situated at the exit of the control room, the workers are subjects to long term exposure of the magnetic field. For a most relevant survey and a good representation of the field, it was conducted the longitudinal and perpendicular profile of the magnetic field to the transformer. The measurements were taken at a distance of one meter from the transformer and one meter above the ground. The results are represented in Fig. 8. In this area, we have identified the highest values of the magnetic field of the station, namely 7409 nt. It is collected under the current bar which is situated between the transformer and the control room. Fig. 8 The Longitudinal and Perpendicular profile of electrical transformer in Ts 2 area, Station 2. In the control room, spot measurements and an automatic survey have been carried out. More attention was paid to this area because the workers spend

Bul. Inst. Polit. Iaşi, Vol. 62 (66), Nr. 4, 2016 27 most of the time on a working day and this fact represents a risk in terms of long-term exposure to the magnetic field. Referring to spot measurements, we determined the magnetic field values in the CR S2 in some points at various heights, as is shown in Fig. 9. The measurements were made with the first two equipments in the following points: the access zone of CR S2 (ACC), the left part of the control panel (LP), the right part of the control panel (RP), the command centre (COM) and the middle of the control room (MD). The highest values of the magnetic field in this area have been identified in RP and ACC at 2 meters height, due to the fact that the connection between the external sources and the control room is aerial. Fig. 9 The magnetic field measurements in CR S2 in some points at different heights. It is observed that a large variation of field with the height exists, which can reach even up to 30% of the measured value at one meter height. A survey of background magnetic field was conducted in the control room (CR S2 ) and point P 2 of Station 2 by using an automatic measurement system. CR S2 is located in the building near the electrical transformers and P 2 point near Zone 1, on the route where the workers are crossing to survey the entire station. These areas received more attention because the staff may be exposed at magnetic field. In Fig. 10 it is shown the time domain and frequency domain representations of the three perpendicular components of the maximum values collected of the magnetic fields in COM point from control room. A recording of the root mean square values of background magnetic fields (B r.m.s. ) for 15 minutes automatic survey in COM point from control room is shown in Fig.11. This point was selected to be surveyed because the worker is here present during the largest period of a normal working day. The highest value of the magnetic field in this area is 235 nt. Fig. 10 Time domain and frequency domain representation of magnetic fields for the control room, Station 2.

28 Ionel Pavel and Valeriu David Because the P2 point is situated on the route where the workers are crossing to survey the entire station, we made also a 17 minutes automatic survey of background magnetic fields. The time and frequency domain representations of magnetic field from this point is shown in Fig. 12 whereas the recording of B r.m.s. values for 17 minutes field survey is presented in Fig. 13. Fig. 11 Recording of B r.m.s. values for 15 minutes field surveying in the control room, Station 2. Fig. 12 Time domain and frequency domain representation of magnetic fields for point P2, Station 2. Fig. 13 Recording of B r.m.s. values for 17 minutes field surveying on point P2, Station 2. Finally, we made a statistical proceeding of magnetic induction survey (B r.m.s. ) on these two considered zones. In Table 2 is presented the survey period, number of measurements, the minimum values Min., average, the maximum values Max., standard deviation and survey time (in percentage) when the values of B r.m.s are over average. As a conclusion, we found that both on workers routes where the maximum values are collected and in the control room or in the technological spaces, the levels of magnetic field are much bellow the allowed reference levels established by ICNIRP and Hotărâre nr. 520/2016.

Bul. Inst. Polit. Iaşi, Vol. 62 (66), Nr. 4, 2016 29 Table 2 A Statistical Processing of Data for Several Minutes of Magnetic Induction Survey in CR S2 and P 2 Point Survey B r.m.s., [nt] t overaverage Number of 100 Standard tsurvey Zone Period measurements Min. Average Max. deviation [%] 15 CR S2 min 125 213.65 224.21 234.41 4.51 49.13 17 P 2 min 142 272.39 284.79 294.07 8.49 49.97 4. Conclusion We made magnetic fields measurements in some points of two transformer stations from Iasi city, considering both the spatial and temporal variations of the fields. To achieve measurements were used several types of equipments including one automatic instrument made by authors, which allows both spot measurements with time and frequency representation and automatic long term survey with a statistical processing. The differences between the results obtained with three different measurement instruments used in our study were below 3%. The maximum values of magnetic induction recorded in the access areas of staff working were 9845 nt for Station 1 and 7408 nt for Station 2, being much bellow the reference levels for occupational exposure (ICNIRP, 2010), (Hotărâre nr. 520/2016). A special attention was paid to the command and control rooms where we found a large spatial variation of the magnetic field and a field variation with height which can reach at 30%. The average values of the background magnetic field obtained from automatic survey for about 15 minutes were 224.21 nt for control room and 284.79 nt for one specific area on the route of personnel/workers. Part of research from this article was presented at the 2016 International Conference and Exposition on Electrical and Power Engineering, EPE2016, event organized by the Faculty of Electrical Engineering, "Gheorghe Asachi" Technical University of Iaşi. Acknowledgements. The authors wish to thank to the leadership and the staff of transformer and distribution stations from Iaşi, for support and permission of access for achieve the entire study. REFERENCES Breniuc L., Haba C.G., Embedded System for Increasing Home Comfort and Security, 2014 Internat.l Conf. a. Exposition on Electrical and Power Engng. (EPE), 16-18 October, 2014, Iaşi, 881-886.

30 Ionel Pavel and Valeriu David David V., Nica I., Sălceanu A., Breniuc L., Monitoring of Environmental Low Frequency Magnetic Fields, Environ. Engng. a. Manag. J., 8, 5, 1253-1261 (2009). David V., Nica I., Sălceanu A., Paval M., Dafinescu V., The Measurement of Magnetic Fields Generated by Electrical Installations, Measuring of Magnetic Fields of the Electric Installations, Energetica, 5, 58, 230-237 (2010). Haba G.C., Breniuc L., David V., Developing Embedded Platforms for Ambient Assisted Living, Ambient Assisted Living and Enhanced Living Environments: Principles, Technologies and Control, Edited by Ciprian Dobre, Constandinos X. Mavromoustakis, Nuno M. Garcia, Rossitza I. Goleva, George Mastorakis, Elsevier, 2017 Morega M., Baran I.M., Morega A.M., Evaluation of Environmental Low Frequency Magnetic Fields in Occupational Exposure, Proc. 8th Int. Conf. and Exposition on Electrical and Power Engineering EPE-2014, Iaşi, 522-527. Munteanu C., Vişan G., Pop T.I., Electric and Magnetic Field Distribution Inside High Voltage Power Substations. Numerical Modeling and Experimental Measurements, Transactions on Electrical and Electronic Engineering, 5, 40-45 (2010). Nica I., David V., Pavel I., Sălceanu A., Automatic Long Term Survey of Magnetic Fields in Residential Areas. Instrumentation and Measurements, Environ. Engng. a. Manag. J., 12, 15, 2631-2640 (2016). Nicolaou Ch.P., Papadakis A.P., Razis P.A., Kyriacou G.A., Sahalos J.N., Experimental Measurement, Analysis and Prediction of Electric and Magnetic Field in Open Type Air Substations, Electric Power System Research, 90, 42-54 (2012). Pavel I., David V., On the Survey of the Magnetic Fields in Power Distribution Substations, 2016 Internat. Conf. a. Exposition on Electrical a. Power Engng. (EPE 2016), 20-22 October, Iaşi, 413-417. Safigianni A.S., Spyridopoulos A.I., Kanas V.L., Electric and Magnetic Field Measurement in a High Voltage Center, Ann. Occup. Hyg., 1, 56, 18-24 (2012). * * * Cerinţele minime de securitate şi sănătate referitoare la expunerea lucrătorilor la riscuri generale de câmpuri electromagnetice, Hotărâre nr. 520/2016, Monitorul Oficial, 2016, nr. 576. * * * Guidelines for Limiting Exposure to Time-Varying Electric and Magnetic Fields (1 Hz to 100 khz), International Commission on Non-ionizing Radiation Protection, Health Physics, 2010, 99, 818-836. MĂSURAREA CÂMPULUI MAGNETIC ÎN DOUĂ STAŢII DE TRANSFORMARE ŞI DISTRIBUŢIE (Rezumat) Sunt prezentate rezultatele măsurătorilor câmpurilor magnetice de joasă frecvenţă în două staţii de transformare şi distribuţie din oraşul Iaşi. Am efectuat măsurători la faţa locului şi o supraveghere pe termen lung, în diferite zone, luând în considerare variabilitatea spaţială şi variabilitatea câmpului cu înălţimea. Măsurătorile s-au efectuat în apropierea diferitelor surse de câmp, în camerele de comandă şi în spaţiul tehnologic utilizând trei echipamente de măsurare diferite, inclusiv un instrument pentru supravegherea automată a câmpului. Având în vedere variabilitatea

Bul. Inst. Polit. Iaşi, Vol. 62 (66), Nr. 4, 2016 31 spaţială, am făcut câteva hărţi ale câmpului magnetic în unele zone şi reprezentări grafice ale variabilităţii câmpului magnetic cu înălţimea, faţă de pardoseală. Chiar şi cele mai ridicate valori care au fost înregistrate în Staţia 1 pe tronsonul cu transformatoarele de curent (9845 nt) şi în Staţia 2 langă transformatorul electric (7408 nt), sunt cu mult sub nivelurile de referinta admise de catre standardul ICNIRP.