THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

Similar documents
Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System

Wide Area Monitoring with Phasor Measurement Data

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011

BUS2000 Busbar Differential Protection System

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Distance Relay Response to Transformer Energization: Problems and Solutions

Bus Protection Fundamentals

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit

Measurement tools at heart of Smart Grid need calibration to ensure reliability

Synchrophasors and the Smarter Grid

Relaying 101. by: Tom Ernst GE Grid Solutions

Synchrophasors: Definition, Measurement, and Application

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

Southern Company Interconnection Requirements for Inverter-Based Generation

Babak Enayati National Grid Thursday, April 17

S1-3: New and re-discovered theories and practices in relay protection

Line Protection Roy Moxley Siemens USA

UNIT-4 POWER QUALITY MONITORING

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Synchrometrology and PMU Testing at NIST

Busbars and lines are important elements

Task Force on Synchrophasor Protection Applications NASPI Engineering Analysis Task Team Matthew Rhodes 3/22/16

State Estimation Advancements Enabled by Synchrophasor Technology

PRECISE SYNCHRONIZATION OF PHASOR MEASUREMENTS IN ELECTRIC POWER SYSTEMS

Smart Grid Where We Are Today?

New Smart Multi-Ended Differential Solution for Power Networks. GE Grid Solutions, UK

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

New Standards for Test and Calibration of Phasor Measurement Units

Phasor Measurement Unit and Phasor Data Concentrator test with Real Time Digital Simulator

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

Experiences of Using Synchrophasors at Duke Energy

Power System Protection Where Are We Today?

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Summary Paper for C IEEE Guide for Application of Digital Line Current Differential Relays Using Digital Communication

Anti-IslandingStrategyforaPVPowerPlant

RT- HIL Implementation of Hybrid Synchrophasor and GOOSE- based Passive Islanding Schemes

Algorithms to Improve Performance of Wide Area Measurement Systems of Electric Power Systems

GRID RELIABILITY MONITORING

Engineering Thesis. The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Comparative Testing of Synchronized Phasor Measurement Units

Testing and Calibration of Phasor Measurement Units

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

1

Protection of Microgrids Using Differential Relays

Detecting and Managing Geomagnetically Induced Currents With Relays

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

Electrical Protection System Design and Operation

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

6135A/PMUCAL Phasor Measurement Unit Calibration System

Qualitrol s PMU Technologies

In addition to wide-area monitoring systems, synchrophasors offer an impressive range of system benefits, including:

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS

Accurate Synchrophasor Estimation to Support the Islanding Maneuver of Active Distribution Networks

Experiences on using gapless waveform data & synchronized harmonic phasors

The Future of Substations: Centralized Protection and Control

Protection of a 138/34.5 kv transformer using SEL relay

Microgrid Islanding with a Battery Energy Storage System (BESS) Gabriel Haines

Transmission Protection Overview

System Protection and Control Subcommittee

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

Wind Power Facility Technical Requirements CHANGE HISTORY

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Power Quality Basics. Presented by. Scott Peele PE

PHASOR TECHNOLOGY AND REAL-TIME DYNAMICS MONITORING SYSTEM (RTDMS) FREQUENTLY ASKED QUESTIONS (FAQS)

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Generator Protection GENERATOR CONTROL AND PROTECTION

Table of Contents. Introduction... 1

PROTECTION of electricity distribution networks

Enhanced DFT Algorithm for Estimation of Phasor by PMU under Power Quality Events

Protective Relaying for DER

Transformer differential protection

PMU Implementation Issues

Transmission Interconnection Requirements for Inverter-Based Generation

Transformer Protection

E N G I N E E R I N G M A N U A L

Application of Low-Impedance 7SS601 Busbar Differential Protection

Protective Relaying of Power Systems Using Mathematical Morphology

Summary Paper for C IEEE Guide for Application of Digital Line Current Differential Relays Using Digital Communication

Testing and Validation of Synchrophasor Devices and Applications

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Transformer protection IED RET 670

COPYRIGHTED MATERIAL. Index

Centralized busbar differential and breaker failure protection function

SYNCHRONIZED PHASOR MEASUREMENT TECHNIQUES. A.G. Phadke

Fault Location Using Sparse Wide Area Measurements

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Algorithms for the synchrophasor measurement in steady-state and dynamic conditions

Adamantios Marinakis, Scientist, 12 th IEEE SB Power Engineering Symposium, Leuven, Enhancing Power System Operation with WAMS

Transcription:

THE OLE OF SYNCHOPHASOS IN THE INTEGATION OF DISTIBUTED ENEGY ESOUCES Alexander APOSTOLOV OMICON electronics - USA alex.apostolov@omicronusa.com ABSTACT The introduction of M and P class Synchrophasors in the IEEE C37.118.1 standard allows the development and implementation of synchrophasors based, automation and control solutions that significantly improve the efficiency of the integration of distributed energy resources in the electric power system. INTODUCTION Distributed Energy esources are becoming a major part of the drive towards a cleaner environment within the context of the Smart Grid. They are of different sizes and types and are being connected at all different levels of the electric power system transmission, distribution and low voltage. This introduces significant challenges for systems at the transmission and distribution level of the system which need to be considered in the engineering and testing of the devices and systems. Since in many cases the distributed energy resources are not only used to partially cover the energy needs of the user, but also to export power to the electric power system, they need to be integrated into the different and distribution automation systems. The developments of multifunctional intelligent electronic devices for and other applications that perform synchrophasor calculations and the improvements in inter and intra-substation communications bring the industry to a time when many specialists are thinking about the use of synchrophasors for applications. They can definitely help with the integration of DEs. The paper describes first the introduction of two synchrophasor performance classes defined in IEEE PC37.118.1. The P class is intended for applications such as that requiring fast response, while the M class is intended for applications which could be adversely affected by aliased signals but do not require the fastest reporting speed. Synchrophasors based applications related to the integration of DEs are later discussed. Examples considered in the paper include differential and synchrocheck. The requirements for synchrophasors' reporting rate, time synchronization and communications architecture are discussed. Feeder using synchrophasors for the calculation of the differential current is later described. equirements for the communications interface between the substations and the DE sites are analyzed. The impact of loss of time synchronization in one of the sites is also discussed. The testing of synchrophasors based systems is described at the end of the paper. POTECTION EQUIEMENTS FO SYSTEMS WITH DISTIBUTED GENEATION Distributed generators are being typically connected to sub-transmission or distribution systems. The definition of such systems varies between utilities and in some cases systems with voltages as high as 138 kv may be considered as distribution. The addition of distributed generators has a significant effect on the system. The levels of short circuit currents, the dynamic behavior of the system following such faults, the coordination of protective relays are affected and have to be considered in the selection of the system. Line settings and criteria should take into account in-feed effect, possible power swings and generator out-of-step conditions. Fig. 1 Typical distribution feeder The increased fault clearing times that are caused by the in-feed effect of a distributed generator may not be acceptable to customers with sensitive loads. The voltage sag is experienced not only by users on the faulted feeder, but also on the adjacent feeders, connected to the same distribution system. Figure 2 shows the areas of impact of voltage sags or swells on sensitive equipment and demonstrates that the impact depends on two characteristics. The first characteristic of a voltage sag the depth is a function of the type of fault, fault location and the system configuration. It will also be affected by the state of the distributed generator if it is in service or not. Single phase-to-ground faults lead to voltage sag in the faulted CIED 2015 1/5

phase and to voltage swell in the healthy phases. The level of voltage increase is also affected by the grounding of the interface transformer and should also be taken into consideration. parameter that we can control by properly applying the advanced features of multifunctional relays. The distributed generator interconnection is subject to many papers, as well as standardization work, such as IEEE P-1547. It is clear that the location of the fault and the infeed from the generator will lead to increase of the fault clearing time and coordination problems. This depends more specifically on the type of distributed generator and its interconnection with the electric power system. IOC DTOC F1 ITOC F2 Y Fig. 4 Distribution system with distributed generator and zones of overcurrent DG Fig. 2 ITI (CBEMA) curve The same two characteristics of the fault also have an impact on the ride-through capability of the DE. Figure 3 shows an example of a ride-through characteristic. Fig. 3 ide-through characteristic This is something that we can t control, but we have to study in order to be able to predict or estimate the effects of different faults on the sensitive equipment. The second characteristic of the voltage sag duration is the Figure 4 shows the distribution system from Figure 1 with the addition of a distributed generator, connected to the system with a step-up transformer. The typical phase, ground and negative sequence overcurrent of a distribution feeder is part of the functionality of most microprocessor based relays. The zones of of the different overcurrent elements is shown in the figure as: IOC instantaneous overcurrent DTOC definite time-delayed overcurrent ITOC inverse time-delayed overcurrent The interconnection transformer is with a grounded wye high-side connection. As a result, there will be infeed for ground faults beyond the interconnection point (F2 in Fig. 4) even when the generator is out of service. Using some of the advanced features in multifunctional relays improves the and reduces this time. However, it may still be unacceptable to sensitive loads. The islanding of part of a distribution system with a nonutility generator is unacceptable in most of the cases. This condition may not be always detected by the of the interconnection. That is why, it is a typical requirement to send a Direct Transfer Trip signal from the substation to the generator interconnection breaker in order to ensure that it is disconnected from the system. The Transfer Trip function requires the availability of communications equipment and channel between the two sites. The communications links can be quite expensive if based on direct fiber over longer distances. For shorter CIED 2015 2/5

distances it will be the ideal solution, since it provides high-speed and is not affected by ground potential rise or electromagnetic interference. However the use of synchrophasors can help in the detection of the islanding condition and may change communications requirements. Other less expensive communications options such as spread-spectrum radio, pilot wire or whatever other communications media is available should be considered when analyzing the interconnection of the distributed generator to the utility system. Since a communications link will be available between the substation and the interconnection point it is worth to take a look into the application of communications based and see if it can improve the of the circuit with the distributed generator and reduce the total fault clearing time. Multifunctional line differential relays can be used for circuits with distributed generation. Their application with different communication channels is discussed in the following sections of the paper. Depending on the location of the distributed generator and other equipment on the distribution circuit, in some cases the differential element may be time delayed with a definite time or inverse time characteristic. When a trip is issued by the differential element, in addition to tripping the local breaker, the relay will send a differential intertrip signal to the remote relay. This will ensure tripping of both ends of the protected line, even for marginal fault conditions. The relay receiving the intertrip signal will indicate that it has operated due to a differential element. PHASO MEASUEMENT CONCEPT PMUs are installed at all important locations of the network to be observed. These PMUs are accurately time synchronized, typically through the Global Positioning System (GPS). Based on this time reference, the magnitudes and phases of voltages and currents at the PMU locations are measured, at exactly the same times in all locations. The measured quantities are transferred over fast communication links to a monitoring center. In the monitoring center, the data from the connected PMUs are collected, aligned, archived and provided to the SCADA applications. A new quality of data is obtained by measuring precisely time synchronized signals at different locations in the power network and through the time stamping of the data: Measured values of voltages and currents are available as complex phasors Synchronously measured values can be directly compared and easily processed Classical protective relays perform the of single elements of a power system, as generators, transformers, lines or busbars. For the of such objects, locally measured values are sufficient in most cases. The response times of such devices are typically in the range of one cycle. SCADA systems however, have system wide view on the power system, but due to limited data rates this view is relatively static. The data from the PMUs enable the SCADA applications to obtain a dynamic view of the network. F1 F2 Differential Differential Y Fig. 5 circuit DG Differential in distributed generation Since the operation of the differential element is based on the exchange of messages between the relays on both ends of the protected circuit, the operating time will be affected by the communications speed. Later in the paper we discuss how it changes as a function of the available communications link. Analyzing Fig. 7 we can see that both a fault before the interconnection point (F1) and beyond the interconnection point (F2) will be seen as internal faults to the differential. As a result the effect of the infeed that is a problem for the overcurrent at the substation is not an issue for the differential. Fig. 6 circuit Differential in distributed generation The dynamic observation of the state of the electric power system can be achieved using synchrophasor measurements in what is known as WAMPCS. This CIED 2015 3/5

abbreviation stands for the following main applications: Network monitoring and fault analysis (Wide Area Monitoring) Network/System (Wide Area Protection) Network operation and control (Wide Area Control) Synchrophasor measurements thus can be also used to monitor the state of individual DEs, as well as the interconnection point of a wind or solar farm with the electric power system. IEEE C37.118 STANDAD The IEEE C37.118 standard is currently the only standard world-wide for measuring synchrophasors in electrical energy systems. Throughout the following text, it will be commonly referred as "the standard". Basically, it defines the following: Time reference: UTC ate of measurement Phase reference: co-sine Accuracy metrics: TVE (Total Vector Error) Communication model (format of telegrams) The standard does not specify: Speed of measurement Accuracy under transient conditions Hardware / Software of the devices Measurement algorithms The specifications allow a simple processing of the synchrophasors from different measuring systems, in realtime as well as off-line. In 2011, as a result of decisions to harmonize IEEE and IEC standards development, the original standard was split in two standards: C37.118.1-2011 - IEEE Standard for Synchrophasor Measurements for Power Systems and C37.118.2-2011 - IEEE Standard for Synchrophasor Data Transfer for Power Systems. Definition of the Synchrophasor According to IEEE C37.118.1 the sinusoidal waveform defined by (1) is commonly represented as the Phasor (2) The value of φ depends on the time scale, particularly where t = 0. It is important to note this phasor is defined for the angular frequency ω; evaluations with other phasors must be done with the same time scale and frequency. The synchrophasor representation of the signal x(t) in (1) is the value X in (2) where φ is the instantaneous phase angle relative to a cosine function at the nominal system frequency synchronized to UTC. Under this definition, φ is the offset from a cosine function at the nominal system frequency synchronized to UTC. A cosine has a maximum at t = 0, so the synchrophasor angle is 0 degrees when the maximum of x(t) occurs at the UTC second rollover (1 PPS time signal), and -90 degrees when the positive zero crossing occurs at the UTC second rollover (sin waveform). Figure 2 illustrates the phase angle/utc time relationship. Fig. 7 Synchrophasor measurement principle C37.118.1-2011 defines synchrophasors, frequency, and rate of change of frequency (OCOF) measurement under all operating conditions. It specifies methods for evaluating these measurements and requirements for compliance with the standard under both steady-state and dynamic conditions. Time tag and synchronization requirements are included. Performance requirements are confirmed with a reference model, provided in detail. This document defines a phasor measurement unit (PMU), which can be a stand-alone physical unit or a functional unit within another physical unit. This standard for the first time introduces two performance classes. As the letter indicates, the P class is intended for types of applications requiring fast response and does not require explicit filtering. M class is intended for applications which could be adversely affected by aliased signals but do not require the fastest reporting speed, thus the M class requires anti-alias filtering. All standard compliance requirements are specified by performance class. The standard requires that if a supplier provides both P and M class performance in a device, these shall be user selectable. IEEE C37.118.1 does not specify hardware, software, or a method for computing phasors, frequency, or OCOF. Line Differential Protection Line differential is typically achieved based on the calculation of the differential current using the individual current measurements from all ends of the protected line. The following steps are common: Calculation of current phasors Communications of current phasors CIED 2015 4/5

Calculation of differential current Differential characteristic based operation The primary element of a multifunctional transmission line relay should be a segregated phase current differential. This technique involves the comparison of the currents of each phase at each line terminal. A communications path is therefore an essential requirement of any such scheme. The differential current is calculated as the vector summation of the currents entering the protected zone. The restrain current is the average of the measured current at each line end. It is found by the scalar sum of the current at each terminal, divided by two. Each of these calculations is done on a phase by phase basis differential function with transient shift The level of restrain used for each element is the highest of the three calculated for optimum stability. When a trip is issued by the differential element, in addition to tripping the local breaker, the relay will send a differential inter-trip signal to the remote terminals. This will ensure tripping of all ends of the protected line, even for marginal fault conditions. An unrestrained differential high set element can provide high-speed operation in the event of CT saturation. Where transformer inrush restraint is used, the resultant second harmonic current produced from CT saturation may cause slow relay operation. To calculate differential current between line ends it is necessary that the current samples from each end are taken at the same moment in time. This can be achieved by time synchronizing the sampling. In the case of use of synchrophasors, by their definition they are calculated based on an accurate time synchronization of the PMUs and using a fixed calculation and transmission rate. Since many line differential relays have been using direct fiber for their communications interface for many years, we can assume that the same approach will be applied when using synchrophasors, i.e. the delay between the relays at all ends of the protected line will be the same with minimal latency. To calculate the differential and restrain currents, the phasor samples at each line end must correspond to the same point in time. It this case each relay calculating the differential current will need to use the synchronized measured currents with the same time stamp. The need for accurate time synchronization (1 µsec) requires the use of GPS technology. Using 4 calculations of P class synchrophasor currents per cycle should provide sufficient performance for the line differential to ensure the stability of the electric power system. The communications method in case of direct fiber between the substations at the ends of the line included in the zone of is defined as tunneling according to IEC 61850 Part 90-1 Use of IEC 61850 for the communication between substations. The message format and the communications are based on IEC 61850-9-2 SV packets. Fig. 8 Communications tunnel between substations The implementation of such distributed synchrophasor based applications using a centralized system (for example located in the substation where the distribution feeders with the DEs are connected) requires the use of a Phasor Data Concentrator which will receive the streams of synchrophasors and feed them into the centralized distribution and control system (DSPACS). It can also use the received synchrophasor measurements to perform the synchrocheck functions for the interconnection points to the electric power system. Fig. 9 Communications architecture TESTING EQUIEMENTS Testing of synchrophasor based schemes for systems with DEs requires good understanding of the functionality and the components of the system. Different methods are used for testing of the PMUs, PDCs and the and control functions of the system. Bottom-up testing is used at the initial phases of development and implementation of the system and especially for the acceptance of IEDs to be used at the system monitoring and process control levels of the system. Black box and top-down testing can be used during the factory and site acceptance testing stages. End-to-end testing is required for the final acceptance test of the system before it can be put in service. CONCLUSIONS The integration of DEs in distribution systems requires a new approach to their in order to improve power quality and meet the ride-through requirements. The availability of P class synchrophasors makes it possible to develop and implement advanced, automation and control functions using high-speed peerto-peer communications. CIED 2015 5/5