Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission Lines

Similar documents
Comparison between Different InstallationLocations of Surge Arresters at Transmission Line Using EMTP-RV

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

Accuracy of Lightning Surge Analysis of Tower Surge Response

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

Back-flashover Investigation of HV Transmission Lines Using Transient Modeling of the Grounding Systems

Study of Tower Grounding Resistance Effected Back Flashover to 500 kv Transmission Line in Thailand by using ATP/EMTP

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines

Lightning performance of a HV/MV substation

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Sensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves

Effective Elimination Factors to the Generated Lightning Flashover in High Voltage Transmission Network

Lightning transient analysis in wind turbine blades

ABSTRACTS of SESSION 6

Estimating the Lightning Performance of a Multi- Circuit Transmission Tower

Modeling insulation in high-voltage substations

New Modeling of Metal Oxide Surge Arresters

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

ATP SIMULATION OF FARADAY CAGE FOR THE ANALYSIS OF LIGHTNING SURGES

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise

Mitigation Methods to Improve the Lightning Performance of Hybrid Transmission Line

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

Software Development for Direct Lightning Stroke Shielding of Substations

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

Mitigation of Back-Flashovers for 110-kV Lines at Multi-Circuit Overhead Line Towers

HIGH VOLTAGE Insulation Coordination

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

Ferroresonance Experience in UK: Simulations and Measurements

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

The Simulation Experiments on Impulse Characteristics of Tower Grounding Devices in Layered Soil

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

Experimental Study on Lightning Surge Response of 500kV Transmission Tower with Overhead Lines

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

Analysis of Electromagnetic Transients in Secondary Circuits due to Disconnector Switching in 400 kv Air-Insulated Substation

Including Surge Arresters in the Lightning Performance Analysis of 132kV Transmission Line

SURGES TRANSFERRED TO THE LOW-VOLTAGE NETWORK VIA TRANSFORMER THE INFLUENCE OF THE LOAD CONNECTED TO THE SECONDARY

A Study of Lightning Surge on Underground Cables in a Cable Connection Station

Lightning overvoltage and protection of power substations

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Electric Stresses on Surge Arrester Insulation under Standard and

X International Symposium on Lightning Protection

Investigation on the Performance of Different Lightning Protection System Designs

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

OVERVOLTAGE MEASUREMENTS RELATED TO LIGHTNING- DETECTION SYSTEMS IN NORWAY

B2-301 IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

GIS Disconnector Switching Operation VFTO Study

MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

Transmission of Electrical Energy

ACCURATE SIMULATION OF AC INTERFERENCE CAUSED BY ELECTRICAL POWER LINES: A PARAMETRIC ANALYSIS

Introduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow

Pre location: Impulse-Current-Method (ICE)

Electric Power Systems Research

Technical and Economic Assessment of Upgrading a Double-circuit 63kV to a Single-circuit 230kV Transmission Line in Iran

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

The Influences of Soil Ionization in the Grounding System and Corona Phenomena on the Injection Lightning Current of 1000 KV UHV Transmission Line

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

Lightning current waves measured at short instrumented towers: The influence of sensor position

AORC Technical meeting 2014

Three-Phase/Six-Phase Conversion Autotransformers

The Lightning Event. White Paper

Journal of Applied Research and Technology 15 (2017)

EXPERIMENTAL ISSUES OF OVERVOLTAGE COORDINATION

Comparison of metal oxide surge arrester models in overvoltage studies

Study of Insulator to Withstand Switching Surges in Conversion Three to Six-Phase Transmission Line: Computer Simulation Analysis

Lightning Current Observation on UHVAC Transmission Lines by Improved Magnetic Steel Rod Method

Limitation of Transmission Line Switching Overvoltages using Switchsync Relays

A SIMPLIFIED LIGHTNING MODEL FOR METAL OXIDE SURGE ARRESTER. K. P. Mardira and T. K. Saha s: and

2. Current interruption transients

EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA

High Voltage Induced By Transmission Lines Due To Lightning Case Study

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Experimental Study and Circuit Analysis Model of Lightning Isolation Transformer for Railway Signal System

The line-lightning performance and mitigation studies of shielded steelstructure

Electromagnetic Shielding Analysis of Buildings Under Power Lines Hit by Lightning

Aalborg Universitet. Ground Loop Impedance of Long EHV Cable Lines Ohno, Teruo; Bak, Claus Leth; Sørensen, Thomas K.

Transcription:

International Journal of Science and Engineering Investigations vol. 2, issue 19, August 2013 ISSN: 2251-8843 Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission Lines Mansour Moradi 1, Hamdi Abdi 2, Arash Atefi 3 1 Electrical Engineering Department, Science and Research Branch, Islamic Azad University, Kermanshah, Iran 2 Electrical Engineering Department, Engineering Faculty, Razi University, Kermanshah, Iran 3 Bisetoon Power Generation Management, Zagross Power Plant, Kermanshah, Iran ( 1 Mansour.Moradi.Ir@gmail.com, 2 HamdiAbdi@gmail.com, 3 Arash_Atefi@yahoo.com) Abstract- Nowadays over voltages caused by lightning in transmission line located in mountainous regions are very important in power system transient studies. This study aims to present and investigate modeling 400 KV single circuit transmission lines. Hence this study, the performed analysis for assessing single phase ignition and back flash over, three common models of the tower in transient studies including Multistory, simplified Multistory and simplified wide line models have been used. The paper illustrates the benefit of ATP / EMTP to finding the best type of line against the lightning. The paper has proven that for negative polarity of current wave, range of overvoltage caused by lightning is the lowest for the Multistory model, Moreover the paper considering the same negative polarity, range of voltages from arms to earth is the lowest for. Also results of this study show that Multistory is better and more acceptable than the other two models for the studied line. Keywords- Over-voltages, lightning, Transient behavior,, simplified Multistory, simplified wide line, ATP / EMTP. causes an increase of voltage and this issue cause's back flash over [2]. Ignition occurs in high heights, therefore, short and H- shaped towers seldom collide with ignition. Shorter length of spin and higher number of towers can cause a decrease of the number of collisions. Shield Wires installed on top of phases effectively prevent collision of the lightning with conductors. Figure 1 shows the effect of shield wires. I. INTRODUCTION Lightning is very important as it is the most important external source of transient overvoltage in the power network. Importance of transient voltages caused by lightning can be found in their destructive role in power networks. By developing power transmission lines and the importance of power supply to different regions, power transmission line outages caused by lightning have been considered by engineers and designers of power systems. Lightning causes destruction of conductors in the network and this issue mostly leads to the outage of transmission lines and finally, the subscribers power outage [1]. On this basis, it is very important to identify phenomenon of lightning and calculate density of lightning in different regions in order to take necessary measures for protecting power network equipment. The modeling transient behavior of a tower is very important at time of lightning and for a transmission line which has been designed well, direct collision of lightning with conductors of phases seldom occurs. Lightning causes many outages due to back flash over. When lightning collides with shield wire or tower, the injected current on tower to earth and Figure 1. Effect of shield wires It has been shown that probability of direct collision of lightning with the phase conductor which is inside arc of shield wires decreases by 1000 times. When lightning collides with shield wire considering that shield wire is directly connected to the tower, the wave which enters into the tower is conducted to earth through it. However, if tower impedance or tower to earth impedance is very high, the created voltage causes insulation resistance failure of phase insulators. The number of insulators in each chain should be selected such that string of insulator is not subject to insulation failure. Tower impedance and resistances of the tower shall be as small as possible and in case tower structure naturally has no low resistance against earth, earth rods are used to decrease earth resistance. Field tests are effective tools for evaluation and access to the transient structure of a tower but since this method is difficult and expensive, it is better to use computer simulation for completion of results [3]. To design insulator of power systems, study of lightning behavior and overvoltage resulting from it is an important factor 61

in protection of different tools of substations and power plants. Lightning seldom directly collides with a transmission line. Lightning almost collides on top of tower of transmission line or shield wires and lightning currents flow on top of tower downward. This major current increases its voltage considering impedance of the tower. With increase of tower voltage, ignition may be created between the arms of the tower and earth and between two arms of the tower [4]. For this reason, a combined model of a transmission line and tower has been applied for analyzing the effect of lightning on the power system and some studies have been conducted on it. Depending on the applied model for the tower, results are expected to be different from each other. One of the proposed suitable models of the tower is Multi story model which is parallel R-L and has been widely used in Japan for analysis of lightning [5]. In the present paper, the characteristics of the Multi story tower model on 400 kv transmission line have been presented based on lightning simulation with ATP / EMTP with negative polarity. The paper is organized as follows: in section 2, the system model is presented. Three different models of tower including Multistory, simplified Multistory and simplified wide line are evaluated in section 3. Result of three models included in the paper is mentioned in section 4 and finally the most important results are elaborated in section 5. II. SYSTEM MODEL 400 kv single circuit transmission line has triplet bundle conductors. Tower resistance of this system is 10 ohms and range of lightning current is 50 ka with negative peak. Figure 2 shows the structure of the studied tower. Physical specifications of conductors are given in table 1 and geometrical parameters of the tower are given in table 2. TABLE II. GEOMETRICAL PARAMETERS OF TOWER SHOWN IN FIG 2 H h 1 h 2 h 3 A B 2r 44.6 4.6 5.6 34.4 7.9 10.4 4.0 All dimensions are in m. III. EVALUATION OF THREE DIFFERENT MODELS OF TOWER In order to model the tower as a transmission line, it is necessary to determine characteristic impedance and wave velocity and then to model it with help of uniform or nonuniform transmission line. Later, different types of models are studied for tower modeling and they have been obtained using laboratory theory approximations. A. Multistory Model Tower model and its multistory model are shown in Figure 3. In this model, transmission line tower is considered as a set of serial circuits with parallel R-L circuits. The above circuits indicate weaknesses of fluid wave across the tower [6,7]. Because R-L parameters are accessible for 500 kv transmission line, it is necessary to convert its geometrical dimensions in order to be used in 400 kv voltage level. For this reason, relations (1) - (4) have been used. ( ) ( ) (1) (2) (3) (4) In which, is d the diffusion coefficient equal to 0.8, is damping coefficient equal to 1 and is wave velocity equal to. It should be noted that values corresponding to each tower are given in table 3. Figure 2. Structure of the studied tower TABLE I. PHYSICAL SPECIFICATIONS OF CONDUCTOR GMR (cm) Resistance dc AREA (MM2) Stranding Conductor 1.2161 599 523.68 AL54/3.5 ST 7/3.52 CURLEW Figure 3. Tower model and its International Journal of Science and Engineering Investigations, Volume 2, Issue 19, August 2013 62

R 1 R 2 R 3 R TABLE III. 22.1393 26.9522 33.472 1 R 1, R 2, R 3, R, Zt 1, Zt 2, and Zt 3 are all in Ω. L 1, L 2, and L 3 are all in h. EQUIVALENT PARAMETERS OF MULTISTORY MODEL L 1 L 2 L 3 6.5827 8.0138 9.9523 Zt 1 Zt 2 Zt 3 220 220 150 In Figure 4, simulated model in ATP / EMTP is shown for multistory tower. C. Wide line simplified model Because multistory model has been designed for 500 kv line and height of the 500 kv tower is more than that of 400 kv tower, therefore, it is necessary to evaluate characteristic impedance of the tower. In order to calculate characteristic impedance of the tower in papers and references, different relations have been presented. The presented relation for tower as relation 5 is in agreement with results obtained from measurement of characteristic impedance of the tower in addition that it is simple and easy. The desired formula is generally obtained as the following relation and from Figure 6 [9]. The tower model used in ATP / EMTP is shown in Figures 7 and 8. In all simulations, wave velocity was considered equal to the speed of light and 300. Figure 4. Equivalent Multistory circuit B. Simplifiet Multistory Model In this model, parallel R-L circuits available in multistory model are deleted. One of the reasons for creation of ignition in multistory model is the presence of parallel R-L circuits. For this reason, analyze has been done using simplified Multistory model i.e. model without parallel R-L circuits [7,8]. Characteristic impedance and other simplified parameters are the same values of multistory model. The equivalent circuit used in ATP / EMTP software is shown in Figure 5. Figure 6. Tower equivalent structure Figure 7. Simplified wide line equivalent circuit Zt 1= Zt 2= Zt 3 = 188.6585 Ω Figure 5. Simplified Multistory equivalent model Figure 8. Simplified wide line equivalent impedance International Journal of Science and Engineering Investigations, Volume 2, Issue 19, August 2013 63

IV. RESULTS OF STUDY In this section, results of study are based on ATP / EMTP software. Impulse wave has a range of -50 kilo amperes, front of the impulse is 1 microsecond and tail of impulse is 70 microseconds. Lightning current at time of collision reaches its peak value within 1 and 10 microseconds (front of impulse) and then is reduced to half of this value within 20 and 100 microseconds (back on impulse). Distribution of this current is shown in Figure 9. 50% of all lightnings have a peak voltage of above 50 kilo amperes. Rarely, peak voltage can exceed 200 kilo amperes. Laboratory results show that almost 90% of all lightnings are negative [10]. Therefore, negative peak of lightning is tested in this paper. -2.5 Figure 11. Range of voltage in lightning collision place in simplified Multistory model 0 [ka] -10-20 0.60-8 -30-0.76-40 -1.44-50 -60 0 5 10 15 20 [us] 25 (f ile surge-f inall.pl4; x-v ar t) c:i -GARD Figure 9. Impulse wave with negative peak Figures 10-12 show range of overvoltage created on top of the tower (collision of lightning). As the above Figures show, the highest range of overvoltage created on top of tower relates to simplified wide line model and the lowest one relates to of the tower and simplified is between these two ranges. -2.12-2.80 Figure 12. Range of voltage in lightning collision place in simplified wide line model of tower Figures 13-15 show overvoltage of the tower arm relative to the earth. As it is evident, difference between arms relative to the earth is low in multistory model and possibility of ignition of the phase is lower in this model. In two other models, there is a high difference between the voltages of arms. Figure 10. Range of voltage in lightning collision place in Figure 13. Voltage range created in the arms of tower relative to earth in International Journal of Science and Engineering Investigations, Volume 2, Issue 19, August 2013 64

150 50-50 -150-250 -2.5 (f ile Exa_9.pl4; x-v ar t) t v :1 Figure 14. Voltage range created in the arms of tower relative to earth in the simplified -350 Figure 17. Range of voltages created on insulator from a tower in the simplified 150 75-2.5-3.0 Figure 15. Voltage range created in the arms of tower relative to earth in a simplified wide line model of the tower Figures 16-18 show range of voltages created on the insulator in different tower models. 100 50 0-50 -100 0-75 -150-225 -300 (f ile m.pl4; x-v ar t) t v :GARD -1 Figure 18. Range of voltages created on the insulator of the tower in a simplified wide line model of the tower Figures 19-21 show waveforms of the voltage created on top of the adjacent tower with which lightning collides. It is clear that overvoltage created in this tower is below the tower with which lightning directly collides and it can be concluded that the major part of the voltage is discharged through the tower which is directly collided by lightning. 300 100-150 -100-200 -250 (f ile surge-f inall.pl4; x-v ar t) t v :GARD -1 Figure 16. Range of voltages created on insulator from a tower in Multistory model -300-500 -700 (file surge-finall.pl4; x-var t) t v:2 Figure 19. Range of voltage created on top of the lateral tower in Multistory model International Journal of Science and Engineering Investigations, Volume 2, Issue 19, August 2013 65

0 0.15 200-20 -0.20-240 5-460 -0.90-680 -1.25 Figure 20. Range of voltage created on top of the lateral tower in the simplified -900 (f ile Exa_9.pl4; x-v ar t) t v :PHASA v :PHASB v :PHASC Figure 23. Voltage created in phases relative to earth in the simplified 0 0.25 0 200-20 -0.25 0-240 -0.75 0-1.25-460 -680 0 Figure 21. Range of voltage created on top of the lateral tower in a simplified wide line model of the tower Figures 22-24 show single phase voltages in three models and diagram of phases A and B is placed on top of each other due to the physical structure of these towers. 200 50-100 -250-400 -550-700 (f ile surge-f inall.pl4; x-v ar t) t v :PHASA v :PHASB v :PHASC Figure 22. Voltage created in phases relative to earth in Multistory Figure 24. Voltage created in phases relative to earth in a simplified wide line model of the tower CONCLUSION Considering the results of the performed simulations for all types of tower models and by applying waves with negative polarity on the tower, the following results are obtained. -900 (f ile m.pl4; x-v ar t) t v :PHASA v :PHASB v :PHASC For negative polarity of current wave, range of overvoltage caused by lightning is the lowest for the multistory model because parallel R-L circuits can model its transient behavior and simplified wide line model is between these two values. Considering the same negative polarity, range of voltages from arms to earth is the lowest for multistory model, highest for the simplified wide line model and the simple multistory model is between these two models. Because the difference between the ranges of phases is not high, it causes almost the equal possibility of back flash in all three phases. Range of voltage caused by lightning on the insulator is the lowest in multistory model, highest in wide line model and the simplified multistory model is between these two values. Results show that Multistory is better and more acceptable than the other two models for the studied line because this model has been designed for 500 kv lines, therefore, one can use it for analyzing 400 kv lines. Despite parallel R L International Journal of Science and Engineering Investigations, Volume 2, Issue 19, August 2013 66

circuits, wave motion of voltage is modeled along the tower. Generally, it can be concluded that multistory model is the best model for studying behavior, analyzing and modeling single circuit 400 kv transmission line. The simplified multistory model can be used under special condition. REFERENCES [1] S.E. Naghib, S. Najafi, S.A. Sajadi, Sub transmission system tower model for lightning surge over voltage analysis In: PSC of 21 th Power System Conference, pp. 1856-1863. [2] Ito, T. Ueda, T. Watanabe, H. Funabashi, T. Ametani, A. Lightning flashovers on 77-kV systems: observed voltage bias effects and analysis IEEE Transactions on Power Delivery, Vol. 18, pp. 545-550, April 2003. [3] M. Ishii, T. Kawamura, T. Kouno, O. Eiichi, K. Shiokawa, K. Murotani, T. Higuchi, Multistory transmission tower model for lightning surge analysis IEEE Transactions on Power Delivery, Vol. 6, pp. 1327 1335, Jul 1991. [4] N. Nagaoka, A development of frequency dependent tower model IEE Transactions on Japan, Vol. B-111, pp. 51 56, Jul 1991. [5] T. Hara, O. Yamamoto, M. Hayashi, T. Nagai, Modelling of a transmission tower for lightning-surge analysis IEE Proc.-Cener. Transm. Distrib., Vol. 143, pp. 283-289, Ma y 1996. [6] J.W. Woo, J.S. Kwak, H.J. Ju, H.H. Lee, J.D. Moon, The analysis results of lightning over voltages by EMTP for lightning protection design of 500 kv substation In: IPST International Conference on Power Systems Transients, June 2005, pp. 1-5. [7] T. Ueda, M. Yoda, I. Miyachi, Characteristics of lightning surges observed at 77 kv substations Electrical Engineering in Japan, Vol. 124, pp. 40-48, August 1998. [8] T. Ueda, S. Neo, T. Funabashi, T. Hagiwara, H. Watanabe, Flashover model for arcing horns and transmission line arresters In: IPST 95 International Conference on Power System Transients, September 1995, pp. 328 333. [9] P.C.A. Mota, M.L.R. Chaves, J.R. Camacho, Power line tower lightning surge impedance computation, a comparison of analytical and finite element methods In: ICREPQ 12 International Conference on Renewable Energies and Power Quality, March 2012, pp. 1-6. [10] K.L. Cummins, E.P. Krider, M.D. Malone, The US national lightning detection network TM and applications of cloud-to-ground lightning data by electric power utilities IEEE Transactions on Electromagnetic Compatibility, Vol. 40, pp. 465-480, Nov 1998. Mansour Moradi was born in Kermanshah, Iran in 1987. Received the B.Sc. degrees in electrical engineering from Islamic Azad University, Brojerd branch in 2010. He is doing M.Sc. degree in the Department of Electrical Engineering, Science and Research Branch, Islamic Azad University, Kermanshah, Iran. Also he is working as lecturer in the Electrical Engineering Department Imam Reza Center of Applied Science and Technology & Islamic Azad University, Eslam Abad Gharb branch. His research interests are: Transient effects in power system, power system operation and planning, transmission expansion planning in power system, renewable energies, and Smart Grid. Hamdi Abdi received his B.Sc. degree from Tabriz University, Tabriz, Iran in 1995; M.Sc., and Ph.D. degrees from Tarbiat Modares University, Tehran, Iran, in 1999 and 2006, all in Electrical Engineering. Currently, he is an assistant professor in the Department of Electrical Engineering, Razi University, Kermanshah, Iran. His research interests include power system operation and planning, restructuring and market design, transmission expansion planning, renewable energies, optimization and application of computational intelligence and design of electrical and control systems for industrial plants. Arash Atefi received the B.Sc. degrees in electrical engineering from Islamic Azad University, South Tehran branch in 2009. He is currently pursuing the M.Sc. degree in the Department of Electrical Engineering, Science and Research Branch, Islamic Azad University, Kermanshah, Iran. Also he is working in Bisetoon Power Generation Management, Zagross Power Plant, Kermanshah, Iran. His research interests are: transmission expansion planning in power system, compound cycle, power network equipments, distribution system control and distributed generation. International Journal of Science and Engineering Investigations, Volume 2, Issue 19, August 2013 67