Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) X X X X X X X X X X

Size: px
Start display at page:

Download "Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) X X X X X X X X X X"

Transcription

1 Adopting Agency BSC SFM Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below) Adopt only those sections that are listed below CALIFORNIA MECHANICAL CODE MATRIX ADOPTION TABLE CHAPTER 6 DUCT SYSTEMS HCD DSA OSHPD 1 2 1/AC AC SS SS/CC X X X X X X X X X X Article/Section 601.2, Exception X X X X X X X X X X X X X X X X X X X X X X 602.1, Exception X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X CA DPH 2010 CALIFORNIA MECHANICAL CODE 103

2 CALIFORNIA MECHANICAL CODE

3 CHAPTER 6 DUCT SYSTEMS Scope Ducts and plenums that are portions of a heating, cooling, absorption or evaporative cooling, or productconveying system shall comply with the requirements of this chapter Sizing Requirements. Duct systems used with blowertype equipment that are portions of a heating, cooling, absorption, evaporative cooling, or outdoor-air ventilation system shall be sized in accordance with Chapter 17, or by other approved methods. Exception: [HCD 1 & HCD 2] Duct sizing calculations are not required for existing duct systems The performance criteria and requirements herein contemplate a duct that is a structural assembly having the capacity to support occupant health and safety while minimizing its own contribution to property damage under emergency conditions. Ducts can supply fresh or treated air in support of life and health, can convey products of combustion away from a fire zone, can maintain a pressure differential that facilitates evacuation and reduces the spread of fire and smoke, and can facilitate firefighter access to a fire source Material General. Supply air, return air, and outside air for heating, cooling, or evaporative cooling systems shall be conducted through duct systems constructed of metal as set forth in the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible, or another approved duct construction standard. Rectangular ducts in excess of two (2) inches w.g. shall comply with the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible, or another approved duct construction standard. Ducts, plenums, and fittings may be constructed of concrete, clay, or ceramics when installed in the ground or in a concrete slab, provided the joints are tightly sealed. In other than Group A, E, H, I, L, and R occupancies, high-rise buildings, and other applications listed in Section regulated by the Office of the State Fire Marshal, corridors shall not be used to convey air to or from rooms if the corridor is required be of fire-resistive construction per the Building Code. In Group A, E, H, I, L, and R occupancies, high-rise buildings, and other applications listed in Section regulated by the Office of the State Fire Marshal, corridors shall not be used to convey air to or from rooms except where permitted in accordance with Section of the California Building Code. Exception: [OSHPD 1, 2, 3 & 4] (See Section ). Not permitted for [OSHPD 1, 2, 3 & 4] Concealed building spaces or independent construction within buildings may be used as ducts or plenums. When gypsum products are exposed in ducts or plenums, the air temperature shall be restricted to a range from 50 F (10 C) to 125 F (52 C), and moisture content shall be controlled so that the material is not adversely affected. For the purpose of this section, gypsum products shall not be exposed in ducts serving as supply from evaporative coolers, and in other air-handling systems regulated by this chapter when the temperature of the gypsum product will be below the dew point temperature. See Chapter 8 for limitations on combustion products venting systems extending into or through ducts or plenums. See Chapter 5 for limitations on environmental air systems exhaust ducts extending into or through ducts or plenums. Exhaust ducts under positive pressure and venting systems shall not extend into or pass through ducts or plenums. For appliance vents and chimneys, see Chapter Combustibles Within Ducts or Plenums. Materials exposed within ducts or plenums shall be noncombustible or shall have a flame spread index not greater than twenty-five (25) and a smoke developed index not greater than fifty (50), when tested as a composite product in accordance with one of the following test methods: NFPA 255, Method of Test of Surface Burning Characteristics of Building Materials, ASTM E 84, Surface Burning Characteristics of Building Materials, or UL 723, Test for Surface Burning Characteristics of Building Materials, except as indicated below. Exceptions: (1) Return-air and outside-air ducts, plenums, or concealed spaces that serve a dwelling unit shall be permitted to be of combustible construction. (2) Air filters meeting the requirements of Sections and (3) Water evaporation media in an evaporative cooler. (4) Charcoal filters when protected with an approved fire suppression system. (5) Electrical wiring in plenums shall comply with NFPA 70, National Electrical Code. Electrical wires and cables and optical fiber cables shall be listed and labeled as suitable for use in plenums and shall have a flame spread distance not greater than five (5) feet (1,524 mm), an average optical density not greater than 0.15, and a peak optical density not greater than 0.5, when tested in accordance with NFPA 262, Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces. (6) Nonmetallic fire sprinkler piping in plenums shall be listed and labeled as suitable for use in plenums and shall have a flame spread distance not greater than five (5) feet (1,524 mm), an average optical density not greater than 0.15 and, a peak optical density not greater than 0.5, when tested in accordance with UL 1887, Fire Test of Plastic Sprinkler Pipe for Visible Flame and Smoke Characteristics CALIFORNIA MECHANICAL CODE 105

4 (7) Nonmetallic pneumatic tubing in plenums shall be listed and labeled as suitable for use in plenums and shall have a flame spread distance not greater than five (5) feet (1,524 mm), an average optical density not greater than 0.15, and a peak optical density not greater than 0.5, when tested in accordance with UL 1820, Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics. (8) Loudspeakers and recessed lighting fixtures, including their assemblies and accessories, in plenums shall be listed and labeled as suitable for use in plenums and shall have a peak rate of heat release not greater than 100 kilowatts, an average optical density not greater than 0.15, and a peak optical density not greater than 0.5, when tested in accordance with UL 2043, Fire Test for Heat and Visible Smoke Release for Discrete Products and their Accessories Installed in Air-Handling Spaces. (9) Smoke detectors. (10) Duct insulation, coverings, and linings and other supplementary materials complying with Section (11) Materials in a Group H, Division 6, fabrication area including the areas above and below the fabrication area sharing a common air recirculation path with the fabrication area Factory-Made Air Ducts. Factory-made air ducts shall be approved for the use intended or shall conform to the requirements of the referenced standard for air ducts in Chapter 17. Each portion of a factory-made air duct system shall be identified by the manufacturer with a label or other suitable identification indicating compliance with the referenced standard for air ducts in Chapter 17 and its class designation. These ducts shall be listed and shall be installed in accordance with the terms of their listing. Flexible air connectors are not permitted Flexible Ducts. [OSHPD 1, 2, 3 & 4] In hospital building projects and all other health-care facilities, including clinics and correctional treatment centers, flexible ducts of not more than 10 feet (3048 mm) in length may be used to connect supply, return or exhaust-air terminal devices to rigid duct systems. Where constant volume, variable volume or mixing boxes are utilized, flexible duct of not more than 10 feet (3048 mm), may be used on the inlet side for alignment. An internal impervious liner shall be provided to isolate insulation material from conditioned air Joints and Seams of Ducts. Joints of duct systems shall be made substantially air-tight by means of tapes, mastics, gasketing, or other means. Crimp joints for round ducts shall have a contact lap of at least inch (38 mm) and shall be mechanically fastened by means of at least three (3) sheet-metal screws equally spaced around the joint, or an equivalent fastening method. Joints and seams for inch (0.41 mm) (No. 28 gauge) and inch (0.33 mm) (No. 30 gauge) residential rectangular ducts shall be as specified in the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible or another approved duct construction standard for inch (0.48 mm) (No. 26 gauge) material. Joints and seams for rectangular duct systems shall be as specified in the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible or another approved duct construction standard. Joints and seams for flat oval ducts and round ducts in other than single-dwelling units shall be as specified in the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible or another approved duct construction standard. Joints and seams and all reinforcements for factory-made air ducts and plenums shall meet with the conditions of prior approval in accordance with the installation instructions that shall accompany the product. Closure systems for rigid air ducts and plenums shall be listed in accordance with UL 181A, Standard for Closure Systems for Use with Rigid Air Ducts and Air Connectors. Closure systems for flexible air ducts shall be listed in accordance with UL 181B, Standard for Closure Systems for Use with Flexible Air Ducts and Air Connectors Metal. Every duct, plenum, or fitting of metal shall comply with the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible or duct systems complying with UL 181 for Factory Made Air Ducts and Air Connectors Tin. Existing tin ducts may be used when cooling coils are added to a heating system, provided the first ten (10) feet (3,048 mm) of the duct or plenum measured from the cooling coil discharge are constructed of metal of the gauge thickness set forth in the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible or another approved duct construction standard or are of approved material and construction. Tin ducts completely enclosed in inaccessible concealed areas need not be replaced. All accessible ducts shall be insulated to comply with the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible or another approved duct construction standard. For the purpose of this subsection, ducts shall be considered accessible where the access space is thirty (30) inches (762 mm) or greater in height Vibration Isolators. Vibration isolators installed between mechanical equipment and metal ducts (or casings) shall be made of an approved material and shall not exceed ten (10) inches (254 mm) in length Quality of Material. Galvanized steel shall be of lockforming quality with a minimum coating of 1.25 ounces of zinc per square foot (0.04 kg/m 3 ) conforming to the requirements of ASTM A653/A653M-07 Standard Specification for Steel Sheet, Zinc-Coat (Galvanized) or Zinc-Iron Alloy-Coat (Galvannealed) by the Hot Dip Process Installation of Ducts General Ducts Under Floor or Crawl Space. Air ducts installed under a floor in a crawl space shall be installed as follows: CALIFORNIA MECHANICAL CODE

5 (1) Shall not prevent access to any area of the crawl space. (2) Where it is required to move under ducts for access to areas of the crawl space a minimum vertical clearance of eighteen (18) inches (457 mm) shall be provided Metal Ducts. Ducts shall be securely fastened in place at each change of direction and as set forth in the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible or another approved duct construction standard. Vertical rectangular ducts and vertical round ducts shall be supported as set forth in the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible or another approved duct construction standard. Riser ducts shall be held in place by means of metal straps or angles and channels to secure the riser to the structure. Metal ducts shall be installed with at least four (4) inches (102 mm) separation from earth. Metal ducts when installed in or under a concrete slab shall be encased in at least two (2) inches (51 mm) of concrete. Ducts shall be installed in a building with adequate clearance so as to permit retaining the full thickness of fireproofing on structural members. Supports for rectangular ducts as set forth in the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible or another approved duct construction standard, when suspended from above, shall be installed on two opposite sides of each duct and shall be riveted, bolted, or metal screwed to each side of the duct at not more than the intervals specified. Horizontal round ducts forty (40) inches (1,016 mm) or less in diameter, when suspended from above shall be supported at intervals not more than as set forth in the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible or another approved duct construction standard with one hanger installed to comply with the requirements listed below: Ducts shall be equipped with tight-fitting circular bands extending around the entire perimeter of the duct at each specified support interval Circular bands shall be not less than one (1) inch (25 mm) wide nor less than equivalent to the gauge of the duct material it supports. Exception: Ducts ten (10) inches (254 mm) and less in diameter may be supported by No. 18 gauge galvanized steel wire Each circular band shall be provided with a suitable means of connecting to the suspending support Ducts shall be braced and guyed to prevent lateral or horizontal swing Factory-Made Air Ducts. Listed Class 0 or Class 1 factory-made air ducts may be installed in any occupancy covered by this code. Factory-made air ducts shall not be used for vertical risers in air-duct systems serving more than two stories. Such ducts shall not penetrate construction where fire dampers are required. Factory-made air ducts shall be installed with at least four (4) inches (102 mm) of separation from earth, except when installed as a liner inside of concrete, tile, or metal pipe; they shall be protected from physical damage. The temperature of the air to be conveyed in any of these classes of ducts shall not exceed 250 F (122 C) Protection of Ducts. Ducts installed in locations where they are exposed to mechanical damage by vehicles or from other causes shall be protected by approved barriers Support of Ducts. Installers shall provide the manufacturer s field fabrication and installation instructions. In the absence of specific supporting materials and spacing, approved factory-made air ducts may be installed as set forth in the ANSI/SMACNA HVAC Duct Construction Standards - Metal and Flexible or another approved duct construction standard Protection Against Flood Damage. In flood hazard areas, ducts shall be located above the design flood elevation or shall be designed and constructed to prevent water from entering or accumulating within the ducts during floods up to the design flood elevation. If the ducts are located below the design flood elevation, the ducts shall be capable of resisting hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding to the design flood elevation Insulation of Ducts. Supply-, return-air ducts and plenums of a heating or cooling system shall be insulated to achieve the minimum thermal (R) value as set forth in Tables 6-6A and B. [OSHPD 1, 2, 3 & 4] Cold air ducts shall be insulated wherever necessary or to prevent condensation problems. Exceptions: (1) Factory-installed plenums, casings, or ductwork furnished as a part of HVAC equipment tested and rated in accordance with approved energy efficiency standards. (2) Ducts or plenums located in conditioned spaces. (3) For runouts less than ten (10) feet (3,048 mm) in length to air terminals or air outlets, the rated R value of insulation need not exceed R-3.5 (R-0.6). (4) Backs of air outlets and outlet plenums exposed to unconditioned or indirectly conditioned spaces with face areas exceeding five (5) square feet (0.5 m ) need not exceed R-2 (R-0.4); those five (5) square feet (0.5 m 2 ) or smaller need not be insulated. 5) Ducts and plenums used exclusively for evaporative cooling systems. Approved materials shall be installed within ducts and plenums for insulating, sound deadening, or other purposes. Materials shall have a mold, humidity, and erosion-resistant surface that meets the requirements of the referenced standard for air ducts in Chapter 17. Duct liners in systems operating with air velocities exceeding 2,000 feet per minute (10.16 m/s) shall be fastened with both adhesive and mechanical fasteners, and exposed edges shall have adequate treatment to withstand the operating velocity CALIFORNIA MECHANICAL CODE 107

6 Insulation applied to the surface of ducts, including duct coverings, linings, tapes, and adhesives, located in buildings shall have a flame-spread index not greater than twenty-five (25) and a smoke developed index not greater than fifty (50), when tested in accordance with NFPA 255, Method of Test of Burning Characteristics of Building Materials, or in accordance with ASTM E 84, Surface Burning Characteristics of Building Materials, or in accordance with the provisions of UL 723, Test for Surface Burning Characteristics of Building Materials. The specimen preparation and mounting procedures of ASTM E 2231, Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess Surface Burning Characteristics, shall be used. Air duct coverings and linings shall not flame, glow, smolder, or smoke when tested in accordance with ASTM C 411, Hot-Surface Performance of High-Temperature Thermal Insulation, at the temperature to which they are exposed in service. In no case shall the test temperature be below 250 F (121 C). Factory-made air ducts and faced insulations intended for installation on the exterior of ducts shall be legibly printed with the name of the manufacturer, the thermal resistance (R) value at installed thickness, and the flame-spread index and smoke developed index of the composite material [OSHPD 1, 2, 3 (surgical clinics) & 4] Thermal acoustical lining materials shall not be installed within ducts, terminal boxes, sound traps, and other in-duct systems serving areas such as operating, cesarean operating rooms, delivery rooms, post anesthesia care units, cystoscopy, cardiac cath labs, nurseries, intensive care units, newborn intensive care units, and airborne infection Isolation rooms unless terminal filters with 90 percent average efficiency based on ASHRAE Standard or minimum efficiency rating value (MERV) of 14 are installed downstream of the duct lining [OSHPD 1, 2 & 4] Thermal or acoustical lining materials shall not be installed within ducts which are downstream of the percent high-efficiency particulate air (HEPA) filter or with minimum efficiency rating value (MERV) of 17 required in Section for protective environment rooms Smoke Dampers, Fire Dampers, and Ceiling Dampers Smoke Dampers. Smoke dampers shall comply with the standards for leakage-rated dampers referenced in Chapter 17, and shall be installed in accordance with approved manufacturer s installation instructions when required by the Building Code. Smoke dampers shall be labeled by an approved agency Fire Dampers. Fire dampers shall comply with the standard for fire dampers referenced in Chapter 17, and shall be installed in accordance with the approved manufacturer s installation instructions when required by the Building Code. Fire dampers shall have been tested for closure under airflow conditions and shall be labeled for both maximum airflow permitted and direction of flow. When more than one damper is installed at a point in a single air path, the entire airflow shall be assumed to be passing through the smallest damper area. Fire dampers shall be labeled by an approved agency. Ductwork shall be connected to damper sleeves or assemblies in accordance with the fire damper manufacturer s installation instructions Ceiling Radiation Dampers. Ceiling radiation dampers shall comply with the standard for ceiling radiation dampers referenced in Chapter 17, and shall be installed in accordance with the manufacturer s approved installation instructions in the fire-resistive ceiling element of floor-ceiling and roofceiling assemblies when required by the Building Code. Fire dampers not meeting the temperature limitation of ceiling radiation dampers shall not be used as a substitute. Ceiling radiation dampers shall be labeled by an approved agency Multiple Arrangements. When size requires the use of multiple dampers, the installation shall be framed in an approved manner to ensure that the dampers remain in place Access and Identification. Dampers shall be provided with an approved means of access large enough to permit inspection and maintenance of the damper and its operating parts. The access shall not impair fire-resistive construction. Access shall not require the use of tools, keys, or special knowledge. Access points shall be permanently identified on the exterior by a label with letters not less than 1 2 inch (12.7 mm) in height reading: SMOKE DAMPER or FIRE DAMPER. Access doors in ducts shall be tight fitting and suitable for the required duct construction Freedom from Interference. Dampers shall be installed in a manner to ensure positive closing or opening as required by function. Interior liners or insulation shall be held back from portions of a damper, its sleeve, or adjoining duct that would interfere with the damper s proper operation. Exterior materials shall be installed so as to avoid interference with the operation or maintenance of external operating devices needed for proper function Temperature Classification of Operating Elements. Fusible links, thermal sensors, and pneumatic or electric operators shall have a temperature rating or classification as required by the Building Code When the automatic activation of a smoke damper or a combination smoke-fire damper occurs, the HVAC system serving such dampers shall immediately shut down. Exceptions: (1) HVAC systems that are part of an engineered smoke evacuation system. (2) Where the automatic activation causes all the smoke dampers and combination smoke-fire dampers to close in the enclosed space having a common atmosphere where openings are required to be protected. (3) Where analysis demonstrates shutoff would create a greater hazard. The HVAC system shall not be restarted again until all the dampers are reset and fully opened Ventilating Ceilings General. Perforated ceilings may be used for air supply within the limitations of this section. Exit corridors, when required to be of fire-resistive construction by the Building Code, shall not have ventilating ceilings CALIFORNIA MECHANICAL CODE

7 [OSHPD 1, 2, 3 & 4] Ventilating ceilings are not permitted in health facilities Requirements. Ventilating ceilings shall comply with the following provisions: Suspended ventilating ceiling material shall have a Class I flame-spread classification on both sides, determined in accordance with the Building Code. Suspended ventilating ceiling supports shall be of noncombustible materials Lighting fixtures recessed into ventilating ceilings shall be of a type approved for that purpose Use of Under-Floor Space as Supply Plenum for Dwelling Units. An under-floor space may be used as a supply plenum, provided: The use of under-floor space shall be limited to dwelling units not more than two stories in height. Except for the floor immediately above the under-floor plenum, supply ducts shall be provided extending from the plenum to registers on other floor levels. Exception: In flood hazard areas, under-floor spaces shall not be used as supply plenums unless the flood opening requirements in the Building Code are satisfied Such spaces shall be cleaned of all loose combustible scrap material and shall be tightly and substantially enclosed The enclosing material of the under-floor space, including the sidewall insulation, shall be not more flammable than one (1) inch (25 mm) (nominal) wood boards (flame-spread index of 200). Installation of foam plastics is regulated by the Building Code Access shall be through an opening in the floor and shall be not less than twenty-four (24) inches by twenty-four (24) inches (610 mm x 610 mm) A furnace supplying warm air to under-floor space shall be equipped with an automatic control that will start the aircirculating fan when the air in the furnace bonnet reaches a temperature not higher than 150 F (66 C). Such control shall be one that cannot be set higher than 150 F (66 C) A furnace supplying warm air to such space shall be equipped with an approved temperature limit control that will limit outlet air temperature to 200 F (93 C) A noncombustible receptacle shall be placed below each floor opening into the air chamber, and such receptacle shall conform to the following: The receptacle shall be securely suspended from the floor members and shall be not more than eighteen (18) inches (457 mm) below the floor opening The area of the receptacle shall extend three (3) inches (76 mm) beyond the opening on all sides The perimeter of the receptacle shall have a vertical lip at least one (1) inch (25.4 mm) high at the open sides if it is at the level of the bottom of the joists, or three (3) inches (76 mm) high if the receptacle is suspended Floor registers shall be designed for easy removal in order to give access for cleaning the receptacles Exterior walls and interior stud partitions shall be firestopped at the floor Each wall register shall be connected to the air chamber by a register box or boot A duct conforming with Section shall extend from the furnace supply outlet at least six (6) inches (152 mm) below combustible framing The entire ground surface of the under-floor space shall be covered with a vapor barrier having a minimum thickness of four (4) mils ( mm) and a flame-spread index of 200 or less Fuel-gas lines and plumbing waste cleanouts are not located within the space Automatic Shutoffs. Air-moving systems supplying air in excess of 2000 cubic feet per minute (944 L/s) to enclosed spaces within buildings shall be equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the airmoving equipment upon detection of smoke in the main supplyair duct served by such equipment. Smoke detectors shall be labeled by an approved agency, approved and listed by California State Fire Marshal for air duct installation and shall be installed in accordance with the manufacturer s approved installation instructions. Such devices shall be compatible, with the operating velocities, pressures, temperatures, and humidities of the system. Where fire detection or alarm systems are provided for the building, the smoke detectors required by this section shall be supervised by such systems, and installed in accordance with NFPA 72, National Fire Alarm and Signaling, and the California Building and Fire Codes. Exceptions: (1) When the space supplied by the air-moving equipment is served by a total coverage smoke-detection system complying with the California Fire Code, interconnection to such system may be used to accomplish the required shutoff. (2) Automatic shutoff is not required when all occupied rooms served by the air-handling equipment have direct exit to the exterior and the travel distance does not exceed 100 feet (30,480 mm). (3) Automatic shutoff is not required for Group R, Division 3 and Group U Occupancies. (4) Automatic shutoff is not required for approved smokecontrol systems or where analysis demonstrates shutoff would create a greater hazard such as may be encountered in air-moving equipment supplying specialized portions of Group H Occupancies. Such equipment shall be required to have smoke detection with remote indication and manual shutoff capability at an approved location. (5) Smoke detectors that are factory installed in listed airmoving equipment may be used in lieu of smoke detectors installed in the main supply-air duct served by such equipment CALIFORNIA MECHANICAL CODE 109

8 TAbLE 6-6 A (I-P Units) Minimum Duct Insulation R Value a Cooling and Heating Only Supply Ducts and Return Ducts d, e Climate Zone Duct Location Envelope HDD65 CDD50 Exterior Ventilated Unvented Unvented Uncon- Indirectly buried Criteria Table Attic Attic w/ Attic w/ ditioned Conbackloaded Roof Space b ditioned Ceiling Insulation a Space c Heating-Only Ducts 5-1 to ,800 all none none none none none none none 5-8 to ,801 3,600 all R-3.5 none none none none none none 5-13 to ,601 5,400 all R-3.5 none none none none none none 5-16 to ,401 7,200 all R-6 R-3.5 none none none none R to ,201 9,000 all R-6 R-6 R-3.5 none none none R to ,001 10,800 all R-8 R-6 R-6 none R-3.5 none R ,801 12,600 all R-8 R-6 R-6 none R-6 none R ,601 16,200 all R-8 R-8 R-6 none R-6 none R ,201 19,800 all R-10 R-8 R-8 none R-6 none R ,801+ all R-10 R-10 R-8 none R-8 none R-6 Cooling-Only Ducts 5-15, 18, 20, all 0 1,800 R-1.9 R-1.9 R-1.9 R-1.9 R-1.9 none none 22 to , 14, 17, all 1,801 3,600 R-3.5 R-1.9 R-3.5 R-1.9 R-1.9 none none 19, , 9, 11, 13, all 3,601 5,400 R-3.5 R-3.5 R-6 R-1.9 R-1.9 none none , 6, 8, 10 all 5,401 7,200 R-6 R-6 R-6 R-3.5 R-1.9 none none 5-3, 5-5 all 7,201 9,000 R-6 R-6 R-6 R-3.5 R-3.5 none R all 9,001 10,800 R-6 R-6 R-8 R-3.5 R-3.5 none R all 10,801+ R-8 R-8 R-8 R-3.5 R-3.5 none R-3.5 Return Ducts 5-15 to 5-26 all climates R-3.5 R-3.5 R-3.5 none none none none none Notes: a b c d e Insulation R-values, measured in (h ft 2 ºF)/Btu, are for the insulation as installed and do not include film resistance. The required minimum thicknesses do not consider water vapor transmission and possible surface condensation. Where exterior walls are used as plenum walls, wall insulation shall be as required by the most restrictive condition. Insulation resistance measured on a horizontal plane in accordance with ASTM C518 at a mean temperature of 75ºF (24ºC) at the installed thickness. Includes crawl spaces, both ventilated and nonventilated. Includes return-air plenums with or without exposed roofs above. Vapor retarders shall be installed on supply ducts in spaces vented to the outside in geographic areas where the average summer dewpoint temperature based on the 2-1/2 percent column of dry-bulb and mean coincident wet-bulb temperature exceeds 60ºF (16ºC). Insulation shall have an approved weatherproof barrier CALIFORNIA MECHANICAL CODE

9 TAbLE 6-6 b (I-P Units) Minimum Duct Insulation R Value a Combined Heating and Cooling Ducts d, e Climate Zone Duct Location Envelope HDD65 CDD50 Exterior Ventilated Unvented Unvented Uncon- Indirectly buried Criteria Attic Attic w/ Attic w/ Roof ditioned Conditioned Table backloaded Insulation a Space b Space c Ceiling ,801+ R-8 R-6 R-8 R-3.5 R-3.5 none R ,001 10,800 R-6 R-6 R-8 R-3.5 R-3.5 none R ,201 9,000 R-6 R-6 R-6 R-3.5 R-3.5 none R ,200 R-6 R-3.5 R-6 R-3.5 R-1.9 none R ,800 7,201+ R-6 R-6 R-6 R-3.5 R-3.5 none R ,800 5,401 7,200 R-6 R-6 R-6 R-3.5 R-3.5 none R , ,400 R-3.5 R-3.5 R-6 R-1.9 R-1.9 none R ,801 2,700 5,401+ R-6 R-6 R-6 R-3.5 R-3.5 none R ,801 2, ,400 R-6 R-3.5 R-6 R-1.9 R-1.9 none R ,701 3,600 5,401+ R-6 R-6 R-6 R-3.5 R-3.5 none R ,701 3,600 3,601 5,400 R-6 R-6 R-6 R-3.5 R-3.5 none R ,701 3, ,600 R-3.5 R-3.5 R-3.5 R-1.9 R-1.9 none R ,601 5,400 3,601+ R-6 R-6 R-6 R-3.5 R-3.5 none R ,601 5,400 1,801 3,600 R-6 R-3.5 R-6 R-1.9 R-3.5 none R ,601 5, ,800 R-3.5 R-3.5 R-3.5 R-1.9 R-1.9 none R ,401 7,200 3,601+ R-6 R-6 R-6 R-3.5 R-3.5 none R ,401 7,200 1,801 3,600 R-6 R-6 R-6 R-1.9 R-3.5 none R ,401 7, ,800 R-6 R-3.5 R-3.5 R-1.9 R-3.5 none R ,201 9,000 1,801+ R-8 R-6 R-6 R-1.9 R-3.5 none R ,201 9, ,800 R-6 R-6 R-6 R-1.9 R-3.5 none R ,001 10,800 1,801+ R-8 R-6 R-6 R-1.9 R-6 none R ,001 10, ,800 R-8 R-6 R-6 R-1.9 R-3.5 none R ,801 12,600 all R-8 R-6 R-6 R-1.9 R-6 none R ,601 16,200 all R-8 R-8 R-8 R-1.9 R-6 none R ,201 19,800 all R-10 R-8 R-8 R-3.5 R-6 none R ,801+ all R-10 R-10 R-8 R-3.5 R-8 R-3.5 R-6 Notes: a Insulation R-values, measured in (h ft 2 F)/Btu, are for the insulation as installed and do not include film resistance. The required minimum thicknesses do not consider water vapor transmission and possible surface condensation. Where exterior walls are used as plenum walls, wall insulation shall be as required by the most restrictive condition. Insulation resistance measured on a horizontal plane in accordance with ASTM C518 at a mean temperature of 75 F (24ºC) at the installed thickness. b Includes crawl spaces, both ventilated and nonventilated. c Includes return air plenums with or without exposed roofs above. d Vapor retarders shall be installed on cooling supply ducts in spaces vented to the outside in geographic areas where the average summer dewpoint temperature based on the 2-1/2 percent column of dry-bulb and mean coincident wet-bulb temperature exceeds 60 F (16 C). e Insulation shall have an approved weatherproof barrier CALIFORNIA MECHANICAL CODE 109.2

10 CALIFORNIA MECHANICAL CODE

CHAPTER 6 DUCT SYSTEMS

CHAPTER 6 DUCT SYSTEMS CHAPTER 6 DUCT SYSTEMS 601.0 Scope General. 601.1 General Applicability. Ducts and plenums that are portions of a heating, cooling, absorption or evaporative cooling, or product-conveying system shall

More information

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700 SECTION 23 3113 - LOW PRESSURE DUCTWORK PART 1 - GENERAL 1.1 SCOPE OF WORK: A. The work required under this section includes all work necessary for a complete installation of ductwork and accessories.

More information

SECTION LOW PRESSURE DUCTWORK

SECTION LOW PRESSURE DUCTWORK SECTION 15841 LOW PRESSURE DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07270 - Firestopping and Fire and Smoke Barrier Caulking. 2. 15260 - Vibration Isolation. 3. 15280 - Thermal Insulation

More information

A. Radius elbows with a construction radius of 1.5 the duct width are preferred to square elbows.

A. Radius elbows with a construction radius of 1.5 the duct width are preferred to square elbows. SECTION 233100 DUCTWORK 1.0 Acoustical duct lining in any part of the duct system is prohibited. All ductwork requiring insulation shall be externally insulated (Refer to the Sheet Metal Ductwork Insulation

More information

Never fill any required clearance space with insulation or any other building materials surrounding the chimney.

Never fill any required clearance space with insulation or any other building materials surrounding the chimney. INSTALLATION AND MAINTENANCE INSTRUCTIONS 1700ºF Air-Cooled Temp/Guard Chimney Sizes 8-16 Listing No. MH8251 Tested to UL103/ULC-S604 A MAJOR CAUSE OF RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCE

More information

SECTION MECHANICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Specification Sections, apply to this Section. B. Related Sections:

More information

*************************************************************************************************************

************************************************************************************************************* 15890 DUCTWORK ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 23 33 13 *************************************************************************************************************

More information

SECTION MECHANICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION Buebtel/Perlcins Community Learning Center GPD - 2001271.15 SECTION 15075 MECHANICAL IDENTIFICATION PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

2012 IMC Performing Commercial Mechanical Inspections

2012 IMC Performing Commercial Mechanical Inspections 2012 IMC Performing Commercial Mechanical Inspections Based Primarily on the 2012 International Mechanical Code (IMC ) and the 2012 International Fuel Gas Code (IFGC ) as applicable. ` Welcome I am You

More information

LOW PRESSURE STEEL DUCTWORK Mechanical Systems Insulation Outlets (HVAC) Testing and Balancing.

LOW PRESSURE STEEL DUCTWORK Mechanical Systems Insulation Outlets (HVAC) Testing and Balancing. SECTION 15841 LOW PRESSURE STEEL DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15180 - Mechanical Systems Insulation. 2. 15940 - Outlets (HVAC). 3. 15991 - Testing and Balancing. 1.02 SUBMITTALS

More information

SECTION BULLET- RESISTANT DOORS

SECTION BULLET- RESISTANT DOORS 1 SECTION 08 3950 BULLET- RESISTANT DOORS PART 1- GENERAL 1.01 SUMMARY A. This Section Includes: 1. Bullet- resistant steel door and frame systems. 2. Door hardware for bullet- resistant steel door and

More information

BUILDING PLAN REVIEW REQUIREMENTS

BUILDING PLAN REVIEW REQUIREMENTS TOWNSHIP OF NORTH FAYETTE BUILDING DEPARTMENT COMMERCIAL PLAN REVIEW REQUIREMENTS BUILDING PLAN REVIEW REQUIREMENTS In order to perform a thorough Building Plan Review, the following specifications, drawings

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 SUBMITTALS A.

More information

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details. SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.

More information

Technical Development Program

Technical Development Program Technical Development Program COMMERCIAL DISTRIBUTION SYSTEMS PRESENTED BY: Ray Chow Duct Design Level 1 Fundamentals Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Introduction

More information

Industrial Pipe Marking

Industrial Pipe Marking Industrial Pipe Marking Pipe and Valve Identification Specialists SPECIFICATIONS ASME (ANSI) Standard A13.1-2007 The ASME (ANSI) Standard for pipe identification is a widely used guideline in determining

More information

SECTION MECHANICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION SECTION 15190 MECHANICAL IDENTIFICATION PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Identification of mechanical products installed under Division 15. B. Related Sections: 1.02 REFERENCES 1.

More information

Travis County ESD #1. Building Plan Submittals. Information Bulletin. Fire Marshal Hancock

Travis County ESD #1. Building Plan Submittals. Information Bulletin. Fire Marshal Hancock Travis County ESD #1 Information Bulletin Building Plan Submittals Fire Marshal Hancock Effective Date 12/12/2018 Table of Contents INTRODUCTION 3 SECTION I. SUPPORTING DOCUMENTATION 4 SECTION II. GENERAL

More information

DIVISION 6 WOOD AND PLASTICS

DIVISION 6 WOOD AND PLASTICS DIVISION 6 WOOD AND PLASTICS PART 1 - GENERAL 1.01 SUMMARY A. This Section includes the following: 1. Wood framing. 2. Wood supports. 3. Wood blocking. 4. Wood cants. 5. Wood nailers. 6. Wood furring.

More information

CSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

CSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe Markers. 2. Valve Tags. 3. Equipment Nameplates. 4. Underground Marking Tape. 5. Duct

More information

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate requirements that are optional depending

More information

Ductwork Controls and Instrumentation Outlets (HVAC) HVAC Control System.

Ductwork Controls and Instrumentation Outlets (HVAC) HVAC Control System. SECTION 15910 DUCT ACCESSORIES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15890 - Ductwork. 2. 15900 - Controls and Instrumentation. 3. 15940 - Outlets (HVAC). 4. 15970 - HVAC Control System.

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017 SECTION 23 0553 - MECHANICAL SYSTEMS IDENTIFICATION GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

ROOFING City of Grand Rapids Building Safety Division

ROOFING City of Grand Rapids Building Safety Division ROOFING City of Grand Rapids Building Safety Division 218-326-7601 www.cityofgrandrapidsmn.com This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Grand

More information

Address: South Elgin, IL Phone: ( ) - Fax: ( ) - Cell: ( ) - Contractor Type: Phone: ( ) - Fax: ( ) - Cell: ( ) - Contact Type:

Address: South Elgin, IL Phone: ( ) - Fax: ( ) - Cell: ( ) - Contractor Type: Phone: ( ) - Fax: ( ) - Cell: ( ) - Contact Type: Community Development Department 10 N. Water Street Monday Friday 847 741 3894 8:30 a.m. 5:00 p.m. 847 741 3959 FAX www.southelgin.com BASEMENT REMODEL APPLICATION PROPERTY INFORMATION South Elgin, IL

More information

University of Houston Master Construction Specifications Insert Project Name SECTION MECHANICAL SCOPE OF WORK PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION MECHANICAL SCOPE OF WORK PART 1 - GENERAL SECTION 23 00 10 - MECHANICAL SCOPE OF WORK PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01

More information

SECTION AIR DISTRIBUTION SYSTEM

SECTION AIR DISTRIBUTION SYSTEM SECTION 23 30 00 AIR DISTRIBUTION SYSTEM PART 1 - GENERAL 1.1 Scope of Work: The work covered by this section consists of providing all labor, equipment and materials and performing all operations necessary

More information

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section.

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section. SECTION 23 31 13 METAL HVAC DUCTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in

More information

A. Product Data: For each electrical identification product indicated.

A. Product Data: For each electrical identification product indicated. SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION MECHANICAL IDENTIFICATION. 1. Identification of mechanical products installed under Division 15.

SECTION MECHANICAL IDENTIFICATION. 1. Identification of mechanical products installed under Division 15. SECTION 15190 MECHANICAL IDENTIFICATION PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Identification of mechanical products installed under Division 15. B. Related Sections: 1. Section 09900 -

More information

COMMERCIAL KITCHEN HOOD WORKSHEET/ CHECKLIST

COMMERCIAL KITCHEN HOOD WORKSHEET/ CHECKLIST COMMERCIAL KITCHEN HOOD WORKSHEET/ CHECKLIST Two copies of this worksheet/checklist must accompany plans sets submitted with commercial kitchen application. The applicant is responsible for assuring the

More information

Residential Construction Checklist Single and Two Family Construction

Residential Construction Checklist Single and Two Family Construction DATE: _ Building Inspection Submittal Requirements Residential Construction Checklist Single and Two Family Construction Submit a City of Big Spring Permit Application, checklist, and 3 complete hard copy

More information

SECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

SECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT SECTION 220553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT Henderson Engineers, Inc. PART 1 - GENERAL REQUIREMENTS 1.1 SUMMARY A. Extent of Plumbing work to be identified as required by this Section

More information

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS PART 1 GENERAL 1.01 Scope of Work A. Provide material, accessories, tools, equipment and labor as required for the complete fabrication

More information

PROJECT INSTRUCTIONS Roofing

PROJECT INSTRUCTIONS Roofing PROJECT INSTRUCTIONS Roofing This handout outlines some basic regulations contained within the 2015 Minnesota State Building Code, as well as other good building practices. However, this handout is not

More information

Installation Guide. Model #400. Corporate Office: 349 Highland Road East Macedonia, Ohio

Installation Guide. Model #400. Corporate Office: 349 Highland Road East Macedonia, Ohio Installation Guide Model #400 Corporate Office: 349 Highland Road East Macedonia, Ohio 44056 1.866.822.7328 www.ezbreathe.com Copyright 2006, EZ Breathe, LLC WHAT S INSIDE Before installing your EZ Breathe

More information

Piping & Equipment Identification

Piping & Equipment Identification Piping & Equipment Identification Part 1 General 1.01 Description of Work A. Work in this section includes: Identification materials, including necessary accessories indicated on Contract Documents and

More information

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available.

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available. SECTION 105113 - METAL LOCKERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION CABLE TRAYS

SECTION CABLE TRAYS SECTION 16139 CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section.

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section. SECTION 15800! AIR DISTRIBUTION PART 1! GENERAL 1.01 RELATED DOCUMENTS The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this

More information

A. Rough carpentry includes but is not limited to the following:

A. Rough carpentry includes but is not limited to the following: SECTION 06100 ROUGH CARPENTRY PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification Sections,

More information

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details. SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.

More information

APPENDIX A, UMC STANDARD 6-5 STANDARD FOR INSTALLATION OF FACTORY-MADE AIR DUCTS

APPENDIX A, UMC STANDARD 6-5 STANDARD FOR INSTALLATION OF FACTORY-MADE AIR DUCTS STANDARD FOR INSTALLATION OF FACTORY-MADE AIR DUCTS Sealing of fibrous glass duct board to the sheet metal sleeve must be made with glass fabric and mastic, except where operating pressure is less than

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-08 33 13 (May 2009) Change 2-11/12 --------------------------- Preparing Activity: USACE Nontechnical Title Revision (August 2015) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Design and Construction Standards SECTION ATHLETIC LOCKERS

Design and Construction Standards SECTION ATHLETIC LOCKERS SECTION 10505 ATHLETIC LOCKERS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The provisions of the General Conditions, Supplementary Conditions, and the Sections included under Division 1, General Requirements,

More information

Single-Family Dwelling Submittal Requirements

Single-Family Dwelling Submittal Requirements Single-Family Dwelling Submittal Requirements The purpose of this guideline is to assist our customers in preparing for plan submittal. The items listed must be included before your plans can be accepted

More information

Installation Instructions for Standard Lap and Self-Aligning Lap Siding

Installation Instructions for Standard Lap and Self-Aligning Lap Siding Installation Instructions for Standard Lap and Self-Aligning Lap Siding 7/16 in. Standard Laps Include: All Old Mill Widths, Cedar Shake Lap and Smooth Lap 1/2 in. Self-Aligning Include: 8 in. and 12 in.

More information

FIRE STATION NO TH STREET NORTH ST. PETERSBURG, FL M-1 SCOPE OF WORK SYMBOL DESCRIPTION SYMBOL DESCRIPTION HVAC SYMBOL LEGEND

FIRE STATION NO TH STREET NORTH ST. PETERSBURG, FL M-1 SCOPE OF WORK SYMBOL DESCRIPTION SYMBOL DESCRIPTION HVAC SYMBOL LEGEND HVAC SYMBOL LEGEND HVAC PIPING AND VALVES LEGEND HVAC GENERAL NOTES SCOPE OF WORK SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION PHASING OF WORK HVAC ABBREVIATIONS ABBREVIATION

More information

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations.

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations. General Conditions: 1. Deliver all food service equipment as specified herein, including that which is reasonably inferred, with all related items necessary to complete work shown on contract drawings

More information

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details. SECTION 081113 - HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section includes standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: For each type of product indicated.

More information

SECTION IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT

SECTION IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT SECTION 21 05 53 IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2015-2015 ARCAT, Inc. - All rights reserved PART 1 GENERAL

More information

SECTION COMMON WORK RESULTS FOR HVAC

SECTION COMMON WORK RESULTS FOR HVAC SECTION 23 05 00 COMMON WORK RESULTS FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Ball Valve. 2. Hangers and Supports. 3. Identification Tags and Sleeves. 1.2 INCLUDED SECTIONS A. Section

More information

PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES

PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Assign unit identification numbers to operating units of equipment within a class or subclass during the design phase of new buildings, additions,

More information

Collins Engineers Palmetto Islands County Park Boardwalk Repairs 03/28/2014 SECTION ROUGH CARPENTRY

Collins Engineers Palmetto Islands County Park Boardwalk Repairs 03/28/2014 SECTION ROUGH CARPENTRY PART 1 GENERAL 1.1 RELATED SECTIONS SECTION 061000 ROUGH CARPENTRY A. Drawings and general provisions of the Construction Contract, including General Conditions and Division 1 Specification Sections, apply

More information

PROGRAMMING SCHEMATIC DESIGN DESIGN DEVELOPMENT CONSTRUCTION DOCUMENTS. room) Scalable bubble diagrams schedules describing programmatic

PROGRAMMING SCHEMATIC DESIGN DESIGN DEVELOPMENT CONSTRUCTION DOCUMENTS. room) Scalable bubble diagrams schedules describing programmatic GENERAL SITE PROGRAMMING SCHEMATIC DESIGN DESIGN DEVELOPMENT CONSTRUCTION DOCUMENTS Scope of work narrative Building code review Description of construction Documentation on drawings as List of applicable

More information

Contemporary Collection

Contemporary Collection HZ5E Gas Fireplace Model HZ5E-NG1 HZ5E-LP1 Fuel Type Natural Gas Propane Gas Minimum Supply Pressure 5 W.C.(1.5 kpa) 1 W.C. (.98 kpa) Manifold Pressure - High 3.5 W.C. (.87 kpa) 1 W.C. (.9 kpa) Manifold

More information

SECTION HOLLOW METAL DOORS AND FRAMES

SECTION HOLLOW METAL DOORS AND FRAMES SECTION 081113 HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standard hollow metal doors and frames. 1.2 SUBMITTALS A. Product Data: Include construction details, material

More information

GE Monogram. Installation. Instructions. 36" Vent Hood. Model ZV750. Call anywhere in the US and Canada -

GE Monogram. Installation. Instructions. 36 Vent Hood. Model ZV750. Call anywhere in the US and Canada - at :: rangehoods. com GE Monogram Instructions Model ZV750 GE Monogram at:: rangehoods. com is a division of CAUTION WARNING Before you begin Read these instructions completely and carefully. IMPORTANT:

More information

4. Metal roof jacks at penetrations and attachments

4. Metal roof jacks at penetrations and attachments - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - SECTION 07 61 00 METAL SHINGLE ROOFING - - - - - - - - - - -

More information

FT DIX ELEMENTARY SCHOOL PHASE VII, CLASSROOM ADDITION PEMBERTON TOWNSHIP REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5349A

FT DIX ELEMENTARY SCHOOL PHASE VII, CLASSROOM ADDITION PEMBERTON TOWNSHIP REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5349A SECTION 061050 - MISCELLANEOUS CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Sheet Metal Worker Level 2

Sheet Metal Worker Level 2 Level 2 Unit: B1 Welding 2 (GMAW and SMAW) Level: Two Duration: 25 hours Theory: Practical: 5 hours 20 hours Overview: Upon completion of this unit of instruction the apprentice will demonstrate knowledge

More information

SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Symphony II Adaptable Table System

Symphony II Adaptable Table System Symphony II Adaptable Table System 1.00 General 1.01 Conditions 1.02 Scope of work 1. This section covers all materials, equipment, tools and labor for the supply and installation of the laboratory Symphony

More information

FUEL GAS PIPING SECTION A. The provisions of SECTION 15010, MECHANICAL GENERAL REQUIREMENTS, apply to this section.

FUEL GAS PIPING SECTION A. The provisions of SECTION 15010, MECHANICAL GENERAL REQUIREMENTS, apply to this section. FUEL GAS PIPING SECTION 15355 PART 1 GENERAL 1.1 DESCRIPTION A. The provisions of SECTION 15010, MECHANICAL GENERAL REQUIREMENTS, apply to this section. B. This specification covers both interior and exterior

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 06 1053 - MISCELLANEOUS ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Division 01 Specification

More information

SHEET METAL FLASHING AND TRIM Christ on the Mountain

SHEET METAL FLASHING AND TRIM Christ on the Mountain SECTION 076200 - SHEET METAL FLASHING AND TRIM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Compatibly with the bumping of flashings and trim as identified in the Membrane Roofing Section 075000.

More information

ROOF-CEILING CONSTRUCTION

ROOF-CEILING CONSTRUCTION CHAPTER 8 ROOF-CEILING CONSTRUCTION SECTION R801 GENERAL R801.1 Application. The provisions of this chapter shall control the design and construction of the roof-ceiling system for all buildings. R801.2

More information

WoodWORKS Channeled Plank

WoodWORKS Channeled Plank CEILING&WALL SYSTEMS Between us, ideas become reality WoodWORKS Channeled Plank Assembly and Installation Instructions 1. General 1.1 Product Description WoodWorks Channeled acoustical ceiling and wall

More information

MATERIAL COMBINATION NUMBER 2: Corrosive environment requiring harder, wear-resistant seating faces and resistance to dezincification.

MATERIAL COMBINATION NUMBER 2: Corrosive environment requiring harder, wear-resistant seating faces and resistance to dezincification. Cast Iron Slide Gates Spec Sheet General The contractor shall furnish and install the following cast iron slide gate assemblies as listed on the Gate Schedule and detailed on the manufacturer s drawings.

More information

City of Long Beach Department of Development Services Building and Safety Bureau. Wood Frame Prescriptive Provisions For Residential Construction

City of Long Beach Department of Development Services Building and Safety Bureau. Wood Frame Prescriptive Provisions For Residential Construction City of Long Beach Department of Development Services Building and Safety Bureau Wood Frame Prescriptive Provisions For Residential Construction Information Bulletin BU-010 Eff: 01-01-2011 Rev: 07-05-2017

More information

ECOVENT USA CHIMNEY MODEL EV-SHT 5"-8" DIAMETER INSTALLATION INSTRUCTIONS

ECOVENT USA CHIMNEY MODEL EV-SHT 5-8 DIAMETER INSTALLATION INSTRUCTIONS ECOVENT USA CHIMNEY MODEL EV-SHT 5"-8" DIAMETER INSTALLATION INSTRUCTIONS A MAJOR CAUSE OF CHIMNEY RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. IT IS

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

1. Section : Rough Carpentry 2. Section : Exterior Insulation and Finishing Systems 3. Section : Metal Roof Panels

1. Section : Rough Carpentry 2. Section : Exterior Insulation and Finishing Systems 3. Section : Metal Roof Panels SECTION 06 16 00 SHEATHING PART 1 GENERAL 1.1 SUMMARY A. Section includes: 1. Roof and Wall Sheathing. B. Related Sections: Documents relating to the work of this section include, but are not limited to,

More information

B. Samples: For color, letter style, and graphic representation required for each identification material and device.

B. Samples: For color, letter style, and graphic representation required for each identification material and device. PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1.

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. PAGE 1 PART 1 GENERAL 1.1 REFERENCE.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1. 1.2 RELATED WORK SPECIFIED ELSEWHERE.1 Installation

More information

Installation Instructions for Old Mill Shingle and Designer Shake Lap Siding

Installation Instructions for Old Mill Shingle and Designer Shake Lap Siding Installation Instructions for Old Mill Shingle and Designer Shake Lap Siding Includes: Cove, Craftsmen Staggered, Diamond, Fish Scale, Octagon, Round and Old Mill Shingle Lap Important: Read and understand

More information

A/E REVIEW CHECKLIST HVAC

A/E REVIEW CHECKLIST HVAC A/E CHECKLIST HVAC Reviewers should - Use Checklists when reviewing any type of VA construction project for the following disciplines: Site and Landscape, Architectural, Structural, Plumbing, Fire Protection,

More information

Product Guide Specification

Product Guide Specification Extrutech Plastics, Inc. September 2012 5902 West Custer Street Manitowoc, Wisconsin 54220 Toll Free 888-818-0118 Phone 920-684-9650 Fax 920-684-4344 Website www.epiplastics.com E-mail info@epiplastics.com

More information

TENANT IMPROVEMENT 16 FEBRUARY WEST 27TH STREET, 4TH FLOOR 100% CD OWNER/BID ADD 1-03/08/2018

TENANT IMPROVEMENT 16 FEBRUARY WEST 27TH STREET, 4TH FLOOR 100% CD OWNER/BID ADD 1-03/08/2018 SECTION 055000 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

HOLLOW METAL DOORS AND FRAMES

HOLLOW METAL DOORS AND FRAMES SECTION 081113 HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty HOT AISLE CONTAINMENT SYSTEM (HACS) REVISION #1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. C. Drawings and general provisions of the Contract, including General and Supplementary. Conditions apply to

More information

A. Product Data: For each type of process and factory-fabricated product indicated.

A. Product Data: For each type of process and factory-fabricated product indicated. SECTION 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Wood framing. 2. Wood supports. 3. Wood blocking. 4. Wood cants. 5. Wood nailers. 6. Wood furring.

More information

TYPE "B" GAS VENT. Do not connect gas vent to a solid or liquid fuelled appliance or any appliance requiring a chimney.

TYPE B GAS VENT. Do not connect gas vent to a solid or liquid fuelled appliance or any appliance requiring a chimney. TYPE "B" GAS VENT SD (sizes 3", 4", 5", 6", 7") INSTALLATION INSTRUCTIONS Type "B" Gas Vents are strictly for interior or enclosed exterior use or exterior use above a roof line. Read vent and appliance

More information

ICC-ES Evaluation Report Reissued September 1, 2012 This report is subject to renewal September 1, 2013.

ICC-ES Evaluation Report Reissued September 1, 2012 This report is subject to renewal September 1, 2013. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1790 Reissued September 1, 2012 This report is subject to renewal September 1, 2013. A Subsidiary of the International Code Council

More information

Testing. Material testing will be according to applicable AASHTO, ASTM or Department methods as specified.

Testing. Material testing will be according to applicable AASHTO, ASTM or Department methods as specified. 907.01 Section 907. FENCING MATERIALS 907.01 General Requirements. Materials for use in fencing property, right-of-way and other installations must comply with this section. 907.02 Testing. Material testing

More information

SECTION MECHANICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION SECTION 15190 MECHANICAL IDENTIFICATION PART 1 GENERAL 1.01 SECTION INCLUDES A. Section Includes: 1. Nameplates. 2. Tags. 3. Stencils. 4. Pipe Markers. 1.02 SUBMITTALS A. Submit valve chart and schedule,

More information

SECTION CARPENTRY

SECTION CARPENTRY SECTION 06100 CARPENTRY PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Carpentry work including grounds, nailers, blocking, miscellaneous framing, plywood backing panels, plywood sheathing, preservative

More information

Design Deliverables. Summary. A. Expectations for Design Deliverables:

Design Deliverables. Summary. A. Expectations for Design Deliverables: Design Deliverables Summary A. Expectations for Design Deliverables: The Design Team is obligated to advance and deliver the project with a professional manner and standard of care that meets the expectations

More information

A. All trim that has been damages, broken, or missing shall be repaired or replaced with material of the same size, shape, and type.

A. All trim that has been damages, broken, or missing shall be repaired or replaced with material of the same size, shape, and type. SECTION 062000 - FINISH CARPENTRY PART 1 - GENERAL 1.1 SECTION REQUIREMENTS A. All trim that has been damages, broken, or missing shall be repaired or replaced with material of the same size, shape, and

More information

U1500E Gas Fireplace

U1500E Gas Fireplace Model U1500E-NG U1500E-LP Fuel Type Natural Gas Propane Minimum Supply Pressure 5 W.C. (1.25 kpa) 11 W.C. (2.73 kpa) Manifold Pressure - High 3.5 W.C. (0.87 kpa) 10 W.C. (2.48 kpa) Manifold Pressure -

More information

TRIBAL BUILDING AND DEVELOPMENT Plan Check Submittal

TRIBAL BUILDING AND DEVELOPMENT Plan Check Submittal TRIBAL BUILDING AND DEVELOPMENT Plan Check Submittal Complete sets of plans are required. Plans shall be stamped and wet signed by the architect or engineer. (signed and accompanied with letter from Homeowners

More information

Excavating, Backfilling, and Compaction for Utilities Piping (Plumbing).

Excavating, Backfilling, and Compaction for Utilities Piping (Plumbing). SECTION 15047 - IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Identification including necessary accessories indicated on Construction Documents and specified in this section or as required

More information

Facility Services Subgroup Preface for Divisions 21` through 28

Facility Services Subgroup Preface for Divisions 21` through 28 Facility Services Subgroup Preface for Divisions 21` through 28 1.1 EXECUTIVE SUMMARY A. This document provides standards for the Consultants and Contractors producing mechanical and electrical design

More information

SECTION MANHOLES

SECTION MANHOLES SECTION 02601 MANHOLES PART 1 GENERAL 1.01 SCOPE OF WORK A. WORK required under this section consists of all materials, accessories, equipment, tools, and labor required to install precast concrete standard

More information

IMPORTANT! READ BEFORE PROCEEDING! SV Weather Caps

IMPORTANT! READ BEFORE PROCEEDING! SV Weather Caps SV Weather Caps OPERATION & MAINTENANCE Revised: 08/24/15 IMPORTANT! READ BEFORE PROCEEDING! The information contained herein is, to the best of our knowledge, accurate and applicable for proper operation

More information

City of Thousand Oaks

City of Thousand Oaks TENANT IMPROVEMENT SUBMITTAL CHECKLIST SUBMIT THREE SETS OF SCALED DRAWINGS (ONE TO BE A BLACKLINE SET) WITH THE FOLLOWING INFORMATION: 1. 2. 3. 4. 5. 6. 7. 8. 9. SITE PLAN: Show building location (vicinity

More information

METALWORKS TARTAN PANELS General Installation Instructions

METALWORKS TARTAN PANELS General Installation Instructions CEILING SYSTEMS METALWORKS TARTAN PANELS General Installation Instructions 1. GENERAL 1.1. Product Description MetalWorks Tartan system is a combination of metal ceiling panels available in a range of

More information

NK / NL series. Rectangular VAV and CAV air volume control terminals

NK / NL series. Rectangular VAV and CAV air volume control terminals NK / NL series Table of contents Description Page Type designation 1 Technical data - General 2 - Specification 3 - Installation instruction 3 Model overview / dimensions 4-5 Sound data NKOAOOB / NLOAOOB

More information

SECTION ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK:

SECTION ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK: SECTION 061000 - ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK: A. Definition: Rough carpentry includes carpent~y work not specified as part of other sections and which is generally not exposed, except as otherwise

More information