1 Metasys Connectivity Technical Manual Metasys Integrator Section Application Note Issue Date January 19, 2006 APPLICATION NOTE Metasys Integrator Power Measurement Ltd. Application lntroduction Page 3 Application Details 3 Component Requirements 5 Vendor Contact Information 6 Design Considerations 7 Cable Connections 8 Cable Pinouts 8 Connecting the Cable 9 Metasys Integrator Setup 11 Point Mapping Tables 12 Power Measurement Ltd Power Meter for ACM Network 12 Power Measurement Ltd Power Meter, MODBUS Network for 16-Bit and 32-Bit Mode 13 Power Measurement Ltd Power Meter for ACM Network 14 Power Measurement Ltd Power Meter, MODBUS Network for 16-Bit Mode 16 Power Measurement Ltd Power Meter, MODBUS Network for 32-Bit Mode 18 Power Measurement Ltd Power Meter, MODBUS Network for 16- and 32-Bit Modes 21 Power Measurement Ltd Power Meter, MODBUS Network Johnson Controls, Inc. 1 Code No. LIT

2 Metasys Network Setup Page 26 Mapping to a CS Object 26 Custom Integration 27 2 Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

3 lntroduction This document explains Metasys Integrator Power Measurement Ltd. (PML) applications. Use this document with the Metasys Integrator Technical Bulletin (LIT ) in the Metasys Connectivity Technical Manual (FAN 629.5), which provides information on installing and commissioning Metasys Integrator. For information on Power Measurement Ltd. equipment, see Power Measurement Ltd. documentation (obtainable from a Power Measurement Ltd. representative). Application Details Metasys Integrator allows the following Power Measurement Ltd. equipment to become an integral part of the Metasys and Metasys Companion Networks: Model 3300 Power Meters Model 3710 Power Meters Model 3720 Power Meters Model 7300 Power Meters Use the Power Measurement Ltd. COM 32 converter, or the Power Measurement Ltd. COM 128 port replicator/converter as an RS-232 to RS-485 converter to connect to a Metasys or Companion Network via the Metasys Integrator. Each of the Power Measurement Ltd. devices listed above can be accessed by the full complement of Metasys Facility Management System (FMS) features, including Change-of-State (COS) monitoring, alarm notification, scheduling, trend, and totalization. The RS-232 to RS-485 converter connects to Metasys Integrator through the RS-232 port. Once connected, it is the interface between Power Measurement Ltd. equipment and non-power Measurement Ltd. devices (such as Metasys Integrator). Each Metasys Integrator vendor port can connect to one converter. The Power Measurement Ltd. COM 32 converter can connect to up to 32 devices in a daisy chain configuration. The Power Measurement Ltd. COM 128 converter has four ports, each of which can connect up to 32 Power Measurement Ltd. devices in a daisy chain configuration for a total of 128 devices per converter. Each Power Measurement Ltd. device must be fitted with the proper communications hardware. Figure 1 shows Power Measurement Ltd. and Metasys integration using the COM 32, and Figure 2 shows Power Measurement Ltd. and Metasys Companion integration using the COM 128. Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 3

4 Figure 1: Power Measurement Ltd. and Metasys Integration 4 Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

5 Figure 2: Power Measurement Ltd. and Metasys Companion Integration Component To integrate Power Measurement Ltd. equipment, you need: Requirements Power Measurement Ltd. COM 32, or Power Measurement Ltd. COM 128 RS-232 to RS-485 converter proper Power Measurement Ltd. devices and communication hardware RS-232 cable for connecting the converter to Metasys Integrator RS-485 two wire, shielded cable (for connecting the converter to Power Measurement Ltd. devices) Metasys Integrator N2 Bus (for connecting Metasys Integrator to the Metasys or Companion Network) portable PC for downloading vendor communication tables (.VCT files) and network setup information into Metasys Integrator, and for running diagnostics cable for connecting portable PC to Metasys Integrator the correct vendor communication table (.VCT file) to download into Metasys Integrator (supplied on Metasys Integrator diskette) Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 5

6 This document describes the RS-232 cable and the vendor communication tables. Power Measurement Ltd. documentation describes their equipment. The remaining components are described in the Metasys Integrator Technical Bulletin. (LIT ) in the Metasys Connectivity Technical Manual (FAN 629.5). Metasys Release Requirements To integrate Power Measurement Ltd. equipment into the Metasys Network, you need the following: Metasys Operator Workstation (OWS) software Release 6.0 or higher Metasys Integrator software/firmware Release 8.0 or higher Metasys To integrate Power Measurement Ltd. equipment into the Metasys Companion Companion Network, you need the following: Release Requirements Metasys Companion Release 4.0 or higher Metasys Integrator software/firmware Release 8.0 or higher Vendor Component Requirements Integration between Metasys Integrator and Power Measurement Ltd. has been tested with the equipment listed in Table 1. Changes to this equipment or integration of Power Measurement Ltd. products not discussed in this document will require additional software development and testing by Systems Products. For information on integrating other products, refer to the Custom Integration section in this technical bulletin. Table 1: Power Measurement Ltd. Part and Software Version Numbers Power Measurement Ltd. Product Firmware Version Model Number Model 3300 Power Meter Model 3710 Power Meter Model 3720 Power Meter (MODBUS) Model 7300 Power Meter (MODBUS) Model 3300 Power Meter (MODBUS) Model 3710 Power Meter (MODBUS) Power Measurement Ltd. COM 32 Converter Power Measurement Ltd. COM 128 Converter ACM B 3710 ACM ACM V ION MOD N/A COM 32 N/A COM 128 Vendor Contact Information Power Measurement Ltd. C/O Paul Doig, Marketing Engineer 2195 Keating Cross Road, Saanichton British Columbia, Canada V8M 2A5 Phone: (250) FAX: (250) Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

7 Design Considerations When integrating Power Measurement Ltd. equipment, consider the following: Make sure all Power Measurement Ltd. equipment is set up and running properly before attempting to integrate with the Metasys or Companion Network. (The Power Measurement Ltd. representative is responsible for operation of Power Measurement Ltd. equipment.) Make sure all Power Measurement Ltd. devices, including the converter, are set to the same baud rate, and that each has a unique communication address. (The Power Measurement Ltd. representative is responsible for setting the power meter baud rate.) RS-232 cable distance between Metasys Integrator and the RS-232 to RS-485 converter can be a maximum of 50 feet. Cable distance between the converter and the last power meter can be a maximum of 4000 feet. The passwords for all power meters must be set to 0. (The Power Measurement Ltd. representative is responsible for setting the power meter password.) The relays for the 3710 Power Meter must be under setpoint control (configured in the meter) for ACM networks. The invalid objects setting must be set to Yes for the 3720 Power Meter. The 3300, 3710, 3720, and 7300 Power Meters can all reside on a MODBUS network. The 3300 and 3710 can also exist on an ACM network. When configured for the ACM network, the 3300 or 3710 cannot be connected to the MODBUS RS-485 network. The 3720, 3710, and 3300 Power Meter interfaces support register sizes of 16- and 32-bits. If gigawatt hours are needed, configure the meter for 32-bit mode and use the 32-bit.vct file. Otherwise, configure the meter for 16-bit register size and use the 16-bit.vct file. Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 7

8 Cable Connections Cable Pinouts Use the following cable pinouts for the RS-232 connection between Metasys Integrator and the RS-232 to RS-485 converter. Vendor Port A or B on Integrator DB-9 Female Signal Pin RS-232 RS-232 Port On Converter DB-25 Male Pin Signal RD TD GND (50 ft. maximum) RD TD GND pml3 Figure 3: Cable Pinouts for COM 32 Converter Figure 4: Cable Pinouts for COM128 Converter 8 Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

9 Connecting the Cable Connect the female end of the RS-232 cable to either Vendor Port A or Vendor Port B on Metasys Integrator. Connect the male end of the cable to the RS-232 port on the RS-232 to RS-485 converter. Metasys Integrator Vendor Port A or B RS-232 Cable COM 32 or COM 128 Converter RS-232 Port pml4 Figure 5: Port to Port Connection Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 9

10 Metasys Integrator Setup To set up Metasys Integrator, use a portable PC connected to the Metasys Integrator Terminal Port. Metasys Integrator setup involves: downloading the correct vendor communication table (.VCT file) setting up the ports assigning network addresses to the controllers Table 2 provides setup information specific to Power Measurement Ltd. applications. For detailed procedures, see the Metasys Integrator Technical Bulletin (LIT ) in the Metasys Connectivity Technical Manual (FAN 629.5). 10 Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

11 Table 2: Metasys Integrator Setup for Power Measurement Ltd. Applications Vendor Communication Table (.VCT) Power Measurement Ltd Power Meter-ACM Protocol Power Measurement Ltd Power Meter-ACM Protocol Power Measurement Ltd Power Meter - MODBUS 16-bit Power Measurement Ltd Power Meter - MODBUS 32-bit Power Measurement Ltd Power Meter - MODBUS 16-bit Power Measurement Ltd Power Meter - MODBUS 32-bit Power Measurement Ltd Power Meter - MODBUS 16-bit Power Measurement Ltd Power Meter - MODBUS 32-bit Power Measurement Ltd Power Meter - MODBUS Port Setup ACM Protocol Power Meter Baud Rate Word Length Stop Bits pml_3300.vct pml_3710.vct p3300m16.vct p3300m32.vct p3710m16.vct p3710m32.vct p3720m16.vct p3720m32.vct p7300mod.vct MODBUS Protocol Power Meter Parity None Interface RS-485 Network Configuration Vendor Address Model 3300/3710 (ACM) Model 3300, 3710, 3720, 7300 (MODBUS) Timeout Value Model 3300/3710 (ACM) Model 3300, 3710, 3720, 7300 (MODBUS) Poll Delay 3300/3720/7300 Meters 3710 Meter Performance Guide Approximate Scan Time (for a single MIG device) Model 3300 Power Meter Model 3710 Power Meter Model 3720 Power Meter Model 7300 Power Meter None RS ms 1000 ms 110 ms 220 ms 1 second 3 seconds 1 second 1 second Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 11

12 Point Mapping Tables Power Measurement Ltd Power Meter for ACM Network To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the L-N Average Phase Voltage is AI3. Table 3 shows the points available for mapping in the Power Measurement Ltd. Model 3300 Power Meter. Table 3: Power Measurement Ltd Power Meter for ACM Network NPT 1 NPA 2 Unit Description AI 1 Amp Average Phase Current AI 2 kw Total kw (Power) AI 3 Volt L-N Average Phase Voltage AI 4 Volt L-L Average Phase Voltage AI 5 Code Voltage Mode Code AI 6 GWh Total GW Hours AI 7 kwh Total kw Hours BO 1 Reset all Hour Counters* 1 Volt L-N Volts Phase A 2 Volt L-N Volts Phase B 3 Volt L-N Volts Phase C 4 Volt L-L Volts Phase AB 5 Volt L-L Volts Phase BC 6 Volt L-L Volts Phase CA 7 Amp Current Phase A 8 Amp Current Phase B 9 Amp Current Phase C 1 Network Point Type 2 Network Point Address * Do not map this point to Companion BO points. If you map this point to Metasys BO objects, make sure Auto Restore in the BO object s Definition/Focus window is disabled. 12 Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

13 Power Measurement Ltd Power Meter, MODBUS Network for 16-Bit and 32-Bit Mode Table 4: Power Measurement Ltd Power Meter, MODBUS Network for 16-Bit and 32-Bit Mode NPT 1 NPA 2 Unit Description AI 1 Amp Average Phase Current AI 2 kw Total kw (Power) AI 3 Volt L-N Average Phase Voltage AI 4 Volt L-L Average Phase Voltage AI 5 Code Voltage Mode Code AI 6 mwh Total mw Hours AI 7 kwh Total kw Hours 3 BO 1 Reset all Hour Counters* 1 Volt L-N Volts Phase A 2 Volt L-N Volts Phase B 3 Volt L-N Volts Phase C 4 Volt L-L Volts Phase AB 5 Volt L-L Volts Phase BC 6 Volt L-L Volts Phase CA 7 Amp Current Phase A 8 Amp Current Phase B 9 Amp Current Phase C 1 Network Point Type 2 Network Point Address 3 Use only for 16-bit mode * Do not map this point to Companion BO points. If you map this point to Metasys BO objects, make sure Auto Restore in the BO object s Definition/Focus window is disabled. Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 13

14 Power Measurement Ltd Power Meter for ACM Network To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Average Phase Current is AI1. Table 5 shows the points available for mapping in the Power Measurement Ltd. Model 3710 Power Meter. Table 5: Power Measurement Ltd Power Meter for ACM Network NPT 1 NPA 2 Unit Description AI 1 Amp Average Phase Current AI 2 kw Total kw (Power) AI 3 Total AI 4 R Total R AI 5 kw kw Demand AI 6 # Power Factor negative=lag, positive=lead AI 7 Hz Frequency AI 8 Code Voltage Mode Code AI 9 Volt Average Phase Voltage 3 AI 10 Amp Amp Demand AI 11 gwh gw Hours AI 12 kwh kw Hours AI 13 kwh-r Reverse kw Hours AI 14 kqh R Hours AI 15 Volt Auxiliary Voltage Input AI 16 kw Minimum kw Demand AI 17 kw Maximum kw Demand BI 1 Status Input S1 BI 2 Status Input S2 BI 3 Status Input S3 BI 4 Status Input S4 BI 5 Diagnostic Failure 0 = normal, 1 = alarm BO 1 Clear kw Hours* 0 = N/A, 1 = clear BO 2 Clear R Hours* 0 = N/A, 1 = clear BO 3 Reset Minimum/Maximum Logs* 0 = N/A, 1 = clear BO 4 Relay 1 Status 4 0 = released, 1 = operated BO 5 Relay 2 Status 4 0 = released. 1 = operated BO 6 Relay 3 Status 4 0 = released, 1 = operated 1 Network Point Type 2 Network Point Address 3 If the 3710/3720 Power Meter is operated in 4-wire wye, single or 3-wire wye mode, the Average Phase Voltage (AI9) is the average L-N phase voltage. If the Power Meter is operated in 3-wire delta mode, the Average Phase Voltage is the average L-L phase voltage. 4 When the relay is released, it is returned to normal setpoint control. The 3710 must be configured so that relays are under setpoint control. * Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure Auto Restore in the BO object s Definition/Focus window is disabled. Continued on next page Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

15 NPT 1 NPA 2 Unit Description (Cont.) Volt Volt Volt Volt Volt Volt Amps Amps Amps kw kw kw R R R # # 1 Network Point Type 2 Network Point Address Setpoint 1 Status Setpoint 2 Status Setpoint 3 Status Setpoint 4 Status Setpoint 5 Status Setpoint 6 Status Setpoint 7 Status Setpoint 8 Status Setpoint 9 Status Setpoint 10 Status Setpoint 11 Status Setpoint 12 Status Setpoint 13 Status Setpoint 14 Status Setpoint 15 Status Setpoint 16 Status Setpoint 17 Status L-N Voltage Phase A L-N Voltage Phase B L-N Voltage Phase C L-L Voltage Phase AB L-L Voltage Phase BC L-L Voltage Phase CA Amperage Phase A Amperage Phase B Amperage Phase C kw Phase A kw Phase B kw Phase C Phase A Phase B Phase C R Phase A R Phase B R Phase C Minimum Power Factor Minimum Power Factor negative = lag, positive = lead negative = lag, positive = lead Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 15

16 Power Measurement Ltd Power Meter, MODBUS Network for 16-Bit Mode To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Average Current is AI1 Table 6: Power Measurement Ltd Power Meter, MODBUS Network for 16-Bit Mode NPT 1 NPA 2 Unit Description AI 1 Amp AI 2 kw AI 3 AI 4 R AI 5 Volt AI 6 Amp AI 7 Volt AI 8 Volt AI 9 # AI 10 Hz AI 11 KW AI 12 # 1 kwh 2 mwh 3 kwh 4 mwh 5 kwh 6 mwh 7 Rh 8 mvarh 9 Rh 10 mvarh 11 Rh 12 mvarh 13 kw 14 kvar 15 # Hz 18 KW 19 KVAR 20 # 1 Network Point Type 2 Network Point Address Average Current Total Kilowatts Total R Total Voltage Auxiliary I4 Neutral Current Average LN Voltage 3 Voltage LL Average 3 Power Factor Total Frequency at V1 kw Total Demand Real Time Polarity kwh Import mwh Import kwh Export mwh Export kwh Total mwh Total Rh Import mvarh Import Rh Export mvarh Export Rh Total mvarh Total Minimum kw Total Minimum kvar Total Minimum Power Factor Total Minimum Total Minimum Frequency Maximum kw Total Maximum R Total Maximum Power Factor Total 3 If the 3710/3720 Power Meter is operated in 4-wire wye, single or 3-wire wye mode, the Average Phase Voltage(AI7) is the average L-N phase voltage. If the Power Meter is operated in 3-wire delta mode, the Average Phase Voltage (AI8) is the average L-L phase voltage. Continued on next page Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

17 NPT 1 NPA 2 Unit Description (Cont.) BO BO BO BO BO KVA Hz Volt Volt Volt Volt Volt Volt Amp Amp Amp KW KW KW KVAR KVAR KVAR KVAR KVA 1 Network Point Type 2 Network Point Address Maximum Total Maximum Frequency Voltage at Phase A Voltage at Phase B Voltage at Phase C Voltage at Phase AB Voltage at Phase BC Voltage at Phase CA Current at Phase A Current at Phase B Current at Phase C Kilowatts at Phase A Kilowatts at Phase B Kilowatts at Phase C R at Phase A R at Phase B R at Phase C at Phase A at Phase B at Phase C Reset All Minimum/ Maximum Values* Reset Hour Counters* Relay 1 3 Relay 2 3 Relay = N/A, 1 = Clear 0 = N/A, 1 = Clear 0 = Released, 1 = Operated 0 = Released, 1 = Operated 0 = Released, 1 = Operated 3 When the relay is released, it is returned to normal setpoint control. The 3710 must be configured so that relays are under setpoint control. * Do not map this point to Companion BO points. If you map this point to Metasys BO objects, make sure Auto Restore in the BO object s Definition/Focus window is disabled. Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 17

18 Power Measurement Ltd Power Meter, MODBUS Network for 32-Bit Mode To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Average Current is AI1 Table 7: Power Measurement Ltd Power Meter, MODBUS Network for 32-Bit Mode NPT 1 NPA 2 Unit Description AI 1 Amp AI 2 KW AI 3 KVA AI 4 KVAR AI 5 Volts AI 6 Amp AI 7 Volts AI 8 Volts AI 9 # AI 10 Hz AI 11 kw AI 12 # 1 mwh 2 mwh 3 mwh 4 mvarh 5 mvarh 6 mvarh 7 kw 8 R 9 # Hz 12 kw 13 R 14 # 1 Network Point Type 2 Network Point Address Average Current Total Kilowatts Total R Total Voltage Auxiliary I4 Neutral Current Average LN Voltage 3 Voltage LL Average 3 Power Factor Total Frequency at V1 kw Total Demand Real Time Polarity mwh Import mwh Export mwh Total mvarh Import mvarh Export mvarh Total Minimum kw Total Minimum kvar Total Minimum Power Factor Total Minimum Total Minimum Frequency Maximum kw Total Maximum R Total Maximum Power Factor Total 3 If the 3710/3720 Power Meter is operated in 4-wire wye, single or 3-wire wye mode, the Average Phase Voltage (AI7) is the average L-N phase voltage. If the Power Meter is operated in 3-wire delta mode, the Average Phase Voltage (AI8) is the average L-L phase voltage. Continued on next page Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

19 NPT 1 NPA 2 Unit Description (Cont.) BO BO BO BO BO Hz Volts Volts Volts Volts Volts Volts Amp Amp Amp kw kw kw R R R 1 Network Point Type 2 Network Point Address Maximum Total Maximum Frequency Voltage at Phase A Voltage at Phase B Voltage at Phase C Voltage at Phase AB Voltage at Phase BC Voltage at Phase CA Current at Phase A Current at Phase B Current at Phase C Kilowatts at Phase A Kilowatts at Phase B Kilowatts at Phase C R at Phase A R at Phase B R at Phase C at Phase A at Phase B at Phase C Reset all minimum/ maximum values* Reset hour counters* Relay 1 3 Relay 2 3 Relay = N/A, 1 = Clear 0 = N/A, 1 = Clear 0 = Released, 1 = Operated 0 = Released, 1 = Operated 0 = Released, 1 = Operated 3 When the relay is released, it is returned to normal setpoint control. The 3710 must be configured so that relays are under setpoint control. * Do not map this point to Companion BO points. If you map this point to Metasys BO objects, make sure Auto Restore in the BO object s Definition/Focus window is disabled. Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 19

20 Power Measurement Ltd Power Meter, MODBUS Network for 16- and 32-Bit Modes To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Average Current is AI1. Table 8 shows the points available for mapping in the Power Measurement Ltd. Model 3720 Power Meter. Table 8: Power Measurement Ltd Power Meter, MODBUS Network for 16-Bit and 32-Bit Mode NPT 1 NPA 2 Unit Description AI 1 Arms Average Current AI AI AI AI AI AI AI AI AI AI AI kwrms kvrms VAux Arms Vrms Vrms Hz Total Kilowatts Total R Total Voltage Auxiliary Neutral Current (I4) Voltage Imbalance Current Imbalance Average LN Voltage Voltage LL average Power Factor Total Frequency at Va BO 1 Reset All Minimum/Maximum Values* 0=n/a 1=reset BO 2 Reset All k/mw, k/mvar, k/mva Hours* 0=n/a 1=reset 1 kwh kwh Import 2 MWh M/GWh Import 3 3 kwh kwh Export 4 MWh M/GWh Export 3 5 kwh kwh Total 6 MWh M/GWh Total 3 7 kwh kwh Net 8 MWh M/GWh Net 3 9 Rh Rh Import 10 MVARh M/GVARh Import 3 11 Rh Rh Export 12 MVARh M/VARh Export 3 13 Rh Rh Total 14 MVARh M/GVARh Total 3 15 Rh Rh Net 16 MVARh M/GVARh Net 3 1 Network Point Type 2 Network Point Address 3 For 32-bit mode, the value is G (Giga) and for 16-bit mode, the value is M (Mega). * Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure Auto Restore in the BO object s Definition/Focus window is disabled. Continued on next page Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

21 NPT 1 NPA 2 Unit Description (Cont.) h MVAh h MVAh h MVAh h MVAh kw kw kw kw R R R R Hz 1 Network Point Type 2 Network Point Address h Import M/GVAh Import 3 h Export M/GVAh Export 3 h Total M/GVAh Total 3 h Net M/GVAh Net 3 Minimum Kilowatts Phase A Minimum Kilowatts Phase B Minimum Kilowatts Phase C Minimum Kilowatts Total Minimum R Phase A Minimum R Phase B Minimum R Phase C Minimum R Total Minimum Power Factor Phase A Minimum Power Factor Phase B Minimum Power Factor Phase C Minimum Power Factor Total Minimum Phase A Minimum Phase B Minimum Phase C Minimum Total Minimum Frequency Minimum Phase A Voltage K-Factor Minimum Phase B Voltage K-Factor Minimum Phase C Voltage K-Factor Minimum Auxiliary Voltage K-Factor Minimum Phase A Current K-Factor Minimum Phase B Current K-Factor Minimum Phase C Current K-Factor Minimum Neutral Current K-Factor Minimum Phase A Voltage Total Harmonic Distortion Minimum Phase B Voltage Total Harmonic Distortion Minimum Phase C Voltage Total Harmonic Distortion 3 For 32-bit mode, the value is G (Giga) and for 16-bit mode, the value is M (Mega). Continued on next page... Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 21

22 NPT 1 NPA 2 Unit Description (Cont.) kw kw kw kw R R R R Hz 1 Network Point Type 2 Network Point Address Continued on next page... Minimum Auxiliary Voltage Total Harmonic Distortion Minimum Phase A Current Total Harmonic Distortion Minimum Phase B Current Total Harmonic Distortion Minimum Phase C Current Total Harmonic Distortion Minimum Neutral Current Total Harmonic Distortion Maximum Kilowatts Phase A Maximum Kilowatts Phase B Maximum Kilowatts Phase C Maximum Kilowatts Total Maximum R Phase A Maximum R Phase B Maximum R Phase C Maximum R Total Maximum Power Factor Phase A Maximum Power Factor Phase B Maximum Power Factor Phase C Maximum Power Factor Total Maximum Phase A Maximum Phase B Maximum Phase C Maximum Total Maximum Frequency Maximum Phase A Voltage K Factor Maximum Phase B Voltage K Factor Maximum Phase C Voltage K Factor Maximum Auxiliary Voltage K Factor Maximum Phase A Current K Factor Maximum Phase B Current K Factor Maximum Phase C Current K Factor Maximum Neutral Current K Factor Maximum Phase A Voltage Total Harmonic Distortion Maximum Phase B Voltage Total Harmonic Distortion Maximum Phase C Voltage Total Harmonic Distortion Maximum Auxiliary Voltage Total Harmonic Distortion Maximum Phase A Current Total Harmonic Distortion Maximum Phase B Current Total Harmonic Distortion Maximum Phase C Current Total Harmonic Distortion Maximum Neutral Current Total Harmonic Distortion 22 Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

23 NPT 1 NPA 2 Unit Description (Cont.) Vrms Vrms Vrms Vrms Vrms Vrms Arms Arms Arms kwrms kwrms kwrms kvrrms kvrrms kvrrms 1 Network Point Type 2 Network Point Address Voltage at Phase A Voltage at Phase B Voltage at Phase C Voltage at Phase AB Voltage at Phase BC Voltage at Phase CA Current at Phase A Current at Phase B Current at Phase C Kilowatts at Phase A Kilowatts at Phase B Kilowatts at Phase C KVAR at Phase A KVAR at Phase B KVAR at Phase C Power Factor at Phase A Power Factor at Phase B Power Factor at Phase C KVA at Phase A KVA at Phase B KVA at Phase C Phase A Voltage K-Factor Phase B Voltage K-Factor Phase C Voltage K-Factor Aux Voltage K-Factor Phase A Current K-Factor Phase B Current K-Factor Phase C Current K-Factor Neutral Current K-Factor Phase A Voltage Total Harmonic Distortion Phase B Voltage Total Harmonic Distortion Phase C Voltage Total Harmonic Distortion Aux Voltage Total Harmonic Distortion Phase A Current Total Harmonic Distortion Phase B Current Total Harmonic Distortion Phase C Current Total Harmonic Distortion Neutral Current Total Harmonic Distortion Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 23

24 Power Measurement Ltd Power Meter, MODBUS Network Table 9 shows the points available for mapping in the Power Measurement Ltd. Model 7300 Power Meter: Table 9: Power Measurement Ltd Power Meter, MODBUS Network NPT 1 NPA 2 Unit Description AI 1 Vrms Voltage LN Average To get the hardware AI 2 Vrms Voltage LL Average reference for AI 3 Average Current mapping points to AI 4 Voltage Unbalance CS object attributes AI 5 Current Unbalance (via the software model), combine the AI 6 Hz Frequency NPT (Network Point AI 7 Real Time Polarity Type) and NPA AI 8 kw kw Total Demand (Network Point AI 9 R R Total Address). For AI 10 Total example, the AI 11 Power Factor Signed Average hardware reference AI 12 kwh kwh Total for the Average Current is AI3. BO 1 Reset Minimum/Maximum Values 0 = n/a, 1 = reset* BO 2 Energy 0 = n/a, 1 = reset* 1 Volts Voltage at Phase A 2 Volts Voltage at Phase B 3 Volts Voltage at Phase C 4 Volts Voltage at Phase AB 5 Volts Voltage at Phase BC 6 Volts Voltage at Phase CA 7 Amps Current at Phase A 8 Amps Current at Phase B 9 Amps Current at Phase C 10 kw kw at Phase A 11 kw kw at Phase B 12 kw kw at Phase C 13 R R at Phase A 14 R R at Phase B 15 R R at Phase C 1 Network Point Type 2 Network Point Address * Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure Auto Restore in the BO object s Definition/Focus window is disabled. Continued on next page Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

25 NPT 1 (Cont.) NPA 2 Unit Description /- 20 +/- 21 +/- 22 kwh 23 R kw 26 R Volts 29 Amps 30 kw 31 R Hz Hz 37 kwh 38 kwh 39 kwh 40 Rh 41 Rh 42 Rh 43 Rh 44 h 1 Network Point Type 2 Network Point Address at Phase A at Phase B at Phase C Power Factor Signed A Power Factor Signed B Power Factor Signed C kw Total to Date R Total to Date Total to Date kw Total to Date Maximum R Total to Date Maximum Total to Date Maximum Voltage LN Average Maximum Current Average Maximum kw Total Maximum R Total Maximum Total Maximum Frequency Maximum Voltage LN Average Minimum Current Average Minimum Frequency Minimum kwh Import kwh Export kwh Net Rh Import Rh Export Rh Total KVARh Net HVah Total Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 25

26 Metasys Network Setup Metasys Network Setup is described in the Metasys Integrator Technical Bulletin (LIT ) in the Metasys Connectivity Technical Manual (FAN 629.5). This section contains details specific to Power Measurement Ltd. applications. Mapping to a Table 10: Software Model and CS Object Definition CS Object Application Software Model Display Attribute NT Command (on Models diskette) (recommended) Attribute (recommended) Model 3300 Power Meter Model 3710 Power Meter Model 3720 Power Meter Model 7300 PML_3300.DDL PML_3710.DDL PML_3720.DDL AI1 Average Phase Current AI1 Average Phase Current AI1 Average Phase Current BO1 Reset All Hours BO1 Clear kw Hours BO2 Clear kw Hours PML_7300.DDL AI1 BO2 Power Meter Average Voltage LN Clear kw hours 26 Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

27 Custom Integration For information on integrating products that are not discussed in this document, first refer to the Metasys Compatible Products, an online list of released connectivity products. If this list does not provide the information you require, consider using the System Integration Services (SIS) Request Custom Engineered Solutions process to request a custom contract from the System Integration Team. Access both the Metasys Compatible Products and the Request Custom Engineered Solutions process from The Portal by performing the following steps: 1. From The Portal, select Products and Services > Delivery. 2. Under the Service Delivery Support column, select Systems Integration Services. The System Integration Services homepage appears. 3. Under Popular Links, select Metasys Compatible Products Listing for a searchable database. 4. After you complete your search, return to the SIS homepage. 5. Select Request a Custom Engineered Solution to view the process used for requesting all types of SIS engineered solutions and services. 6. Click Online Request Page to enter a custom engineered request online. If you need further assistance, contact the Johnson Controls Field Support Center. Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 27

28 Notes 28 Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

29 Notes Metasys Integrator Metasys Integrator Power Measurement Ltd. Application 29

30 Notes Controls Group FAN E. Michigan Street Metasys Connectivity Technical Manual P.O. Box 423 Metasys Integrator Release 8.0 Milwaukee, WI Printed in U.S.A Metasys Integrator Metasys Integrator Power Measurement Ltd. Application

Metasys Integrator ESAM E as VND device Application

Metasys Integrator ESAM E as VND device Application Systems Integration Services Europe Application Note Issue Date 0203 APPLICATION NOTE Metasys Integrator ESAM E742002 as VND device Application Introduction 2 Systems Integration Services Europe Contacts

More information

SERIES PM172 POWERMETERS COMMUNICATIONS. DNP Communications Protocol REFERENCE GUIDE

SERIES PM172 POWERMETERS COMMUNICATIONS. DNP Communications Protocol REFERENCE GUIDE SERIES PM172 POWERMETERS COMMUNICATIONS DNP3-2000 Communications Protocol REFERENCE GUIDE Every effort has been made to ensure that the material herein is complete and accurate. However, the manufacturer

More information

C191HM POWERMETER AND HARMONIC MANAGER COMMUNICATIONS REFERENCE GUIDE

C191HM POWERMETER AND HARMONIC MANAGER COMMUNICATIONS REFERENCE GUIDE C191HM POWERMETER AND HARMONIC MANAGER COMMUNICATIONS ASCII Communications Protocol REFERENCE GUIDE Every effort has been made to ensure that the material herein is complete and accurate. However, the

More information

Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH

Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH Series PM30 PLUS Powermeters PM30PPM30EPM30EH DNP3 Communications Protocol Reference Guide BG048 Rev. A4 Every effort has been made to ensure that the material herein is complete and accurate. However,

More information

Data Sheet. RISH Master Record %THD

Data Sheet. RISH Master Record %THD Data Sheet %THD Application : measures important electrical parameters & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, active energy

More information

Contents. Introduction and description Package contents Device identification PM Options... 80

Contents. Introduction and description Package contents Device identification PM Options... 80 Contents 1 Introduction and description Package contents... 77 Device identification... 77 2 Characteristics PM500... 78 Options... 80 3 Installation Front-panel cut-out... 82 Mounting... 82 4 Connections

More information

Installation Instructions and Reference Handbook. Installation instructions

Installation Instructions and Reference Handbook. Installation instructions Installation Instructions and Reference Handbook Multi-instrument MIB 7000/7000C/7020 4189320016B (UK) DEIF A/S Product information Installation instructions Basic operation DEIF A/S, Frisenborgvej 33

More information

EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1. Three phase multifunction din rail energy meter

EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1. Three phase multifunction din rail energy meter SDM630MCT-RJV-333mV SDM630MCT-RJA-00mA Three phase multifunction din rail energy meter Plug-in solution; labor saving; wiring mistake free Measures kwh KVarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, THD,etc.

More information

EIG DNP V3.0 Protocol Assignments

EIG DNP V3.0 Protocol Assignments E Electro Industries/G augetech "The Leader in Web Accessed Power Monitoring" EIG DNP V3.0 Protocol Assignments For Futura+ and DM Series Power Monitors Version 1.14 July 15, 2003 Doc # E100-7-03 V1.14

More information

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features:

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features: Application : RISH Master 3430 measures important electrical parameters in 3 phase and single phase Network & replaces the multiple analog panel meters. It measures electrical parameters like AC current,

More information

PEM353. Universal measuring device

PEM353. Universal measuring device 353 Universal measuring device 353_D00335_00_D_XXEN/06.2018 353 Universal measuring device Product description The digital universal measuring device 353 is used to record and display measured quantities

More information

Centrale de mesure Power Meter PM500 Merlin Gerin

Centrale de mesure Power Meter PM500 Merlin Gerin Notice d'installation et d'utilisation Installation and user manual Centrale de mesure Power Meter PM500 Merlin Gerin 059473_D Introduction and description Package contents c one PM500 power meter with

More information

Digital Multifunction Instrument - Rish Master 3440

Digital Multifunction Instrument - Rish Master 3440 Application Rish Master 3440 measures important electrical parameters in 3 phase and single phase etwork & replaces the multiple analog panel meters. It measures electrical parameters like AC current,

More information

Metasys Zoning Package Commissioning

Metasys Zoning Package Commissioning Technical Bulletin Issue Date 11/01/01 TECHNICAL BULLETIN Metasys Zoning Package Commissioning Metasys Zoning Package Commissioning...2 Introduction... 2 Key Concepts... 3 HVAC PRO Software...3 Configuration

More information

RISH Master 3440i/3440iDL 0.2S

RISH Master 3440i/3440iDL 0.2S Operating Manual RISH Master 3440i/3440iDL 0.2S as per IEC62053-22 Touch Screen Digital Multi-Function Meter Installation & Operating Instructions Section Contents 1. Introduction INDEX 2. Measurement

More information

Installation Instructions Hawkeye 8025/8026 Networked (N2 Bus) Power Meter Compatible with Johnson Controls, Inc. Metasys & Companion Systems

Installation Instructions Hawkeye 8025/8026 Networked (N2 Bus) Power Meter Compatible with Johnson Controls, Inc. Metasys & Companion Systems Installation Instructions Hawkeye 805/806 Networked (N Bus) Power Meter Compatible with Johnson Controls, Inc. Metasys & Companion Systems Applications Tenant submetering Energy management & performance

More information

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters Technical Data Sheet Alpha 20 Alpha 20 is a compact multifunction instrument which Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel

More information

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES) Alpha Series www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters Shunts ALPHA

More information

Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems

Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems Tyco Electronics UK Limited Crompton Instruments Freebournes Road, Witham, Essex, CM8 3AH, UK Tel: +44 1376 509 509

More information

RISH Master 3430 DIGITAL MULTI-FUNCTION TRANSDUCER. Electro-Meters

RISH Master 3430 DIGITAL MULTI-FUNCTION TRANSDUCER. Electro-Meters measures important electrical parameters in phase and single phase etwork & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, Power, Energy

More information

Installation and Operating Instructions

Installation and Operating Instructions Energy Division Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems Our commitment. Your advantage. Contents Page 1 Introduction 4 1.1 Measurement Capabilities 5 1.2

More information

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2 PART 1 PART 2 PRODUCTS 2.01 MANUFACTURERS A. Eaton products B.. C.. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features

More information

Power Quality and Energy Measurement PEM533

Power Quality and Energy Measurement PEM533 Power Quality and Energy Measurement _D00013_02_D_XXEN/11.2014 Power Quality and Energy Measurement 0.5 S Product description The digital universal measuring device is suited for measuring and displaying

More information

Soluciones! Para el ahorro y control de la energía eléctrica. Distribuidor autorizado:

Soluciones! Para el ahorro y control de la energía eléctrica. Distribuidor autorizado: Soluciones! Para el ahorro y control de la energía eléctrica Distribuidor autorizado: Series PM174 Powermeter and Power Quality Analyzer Installation and Operation Manual BG0411 Rev. A2 LIMITED WARRANTY

More information

ENGLISH 3 Phase Multi-function Power Meter 1/5A MID MID

ENGLISH 3 Phase Multi-function Power Meter 1/5A MID MID Professionally approved products. Datasheet Stock Number: 144-0527 3 Phase Multi-function Power Meter 1/5A MID 96mm² Panel Mounted Power Meter. MID UK Specifications The 144-0527 is a new generation modern

More information

Monitoring Electric Network Via Internet

Monitoring Electric Network Via Internet Monitoring Electric Network Via Internet NETWORK ANALYSER let "it" analyse! MPR63 Real time monitoring via internet / intranet Measurement of all electrical parameters Including Harmonics Automatic recording

More information

ULTRA RAPID POWER QUALITY ANALYZER

ULTRA RAPID POWER QUALITY ANALYZER ULTRA RAPID POWER QUALITY ANALYZER Ultra rapid (cycle by cycle) advanced electrical network analysis Complete network harmonics analysis, up to 63 rd harmonic High visibility, 5 graphic LCD screen with

More information

DEIF A/S. Description of options. Option H3 Serial communication Profibus DP Multi-line 2 version 2. Description of option. Functional description

DEIF A/S. Description of options. Option H3 Serial communication Profibus DP Multi-line 2 version 2. Description of option. Functional description Description of options Option H3 Serial communication Profibus DP Multi-line 2 version 2 4189340279I SW 2.42.X Description of option Functional description DEIF A/S Parameter table Data tables DEIF A/S,

More information

AMIK 200 / 201 Technical Data Sheet

AMIK 200 / 201 Technical Data Sheet AMIK 200 / 201 Technical Data Sheet AMIK Special Features MODBUS (RS-485) Communication available only on Amik 201 On site Programmable CT/PT Ratios User selectable CT Secondary 1A/5A User selectable PT

More information

InfraStruXure Manager v4.x Addendum: Building Management System Integration

InfraStruXure Manager v4.x Addendum: Building Management System Integration InfraStruXure Manager v4.x Addendum: Building Management System Integration Introduction This addendum explains the integration of the APC InfraStruXure Manager Appliance with a Building Management System

More information

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features: (With All Display Parameters) Application : RISH EM 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network

More information

Energy Division

Energy Division Energy Division http://energy.tycoelectronics.com Installation and Operating Manual Integra 1560 and 1580 Digital Metering and Transducer Systems Tyco Electronics UK Limited Crompton Instruments Freebournes

More information

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49 TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument True RMS measurement User-friendly programing Four different types for optimal specification RS485 interface For 3- or 4-wire connection Compact

More information

Power Quality and Energy Measurement PEM575

Power Quality and Energy Measurement PEM575 Power Quality and Energy Measurement _D00016_03_D_XXEN/12.2015 Power Quality and Energy Measurement Product description The digital universal measuring device is suited for measuring and displaying electrical

More information

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics Power Quality Monitor Individual Harmonics measurement upto 56th Harmonics True representation of Voltage & Current waveforms. Phasor Representation of All 3 phases for system analysis Real Time Clock

More information

Bulletin 1403 Ethernet Communications Card

Bulletin 1403 Ethernet Communications Card Installation Instructions Bulletin 1403 Ethernet Communications Card (Catalog Number 1403-NENET) 1 Bulletin 1403 Ethernet Communications Card Important User Information Because of the variety of uses for

More information

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES)

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES) Alpha Series www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters Shunts ALPHA

More information

Technical Data Sheet AMIK 300 / 301

Technical Data Sheet AMIK 300 / 301 USA SINCE 1936 RELIABILITY BEYOND MEASURE Technical Data Sheet AMIK 300 / 301 LISTED File No. E471457 AMIK AMIK 300 is a compact multifunction instrument with touch screen LCD utility which measures important

More information

VIP Current & Power Multimeter

VIP Current & Power Multimeter VIP Current & Power Multimeter Rev 1.6 Table of Contents 1. Mechanical Installation... 3 2. Wiring diagram... 4 3. Specifications... 5 Technical Specifications... 5 3.2 Measuring Specifications... 5 4.

More information

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication: Application : RISH Master 3490 SS is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy having auto-resetting 8 digit seven segment LED counter. The unit

More information

HSIANG CHENG ELECTRIC CORP.

HSIANG CHENG ELECTRIC CORP. DWG NO. : 26298001 VER : 3.0 METER Introduction About ower Meter The is conceptualized and designed to revolutionize the approach to traditional power metering. Each is a compact, electronically advanced

More information

Installation & Operation Manual ELNet VIP

Installation & Operation Manual ELNet VIP Installation & Operation Manual ELNet VIP Electrical Measurements Table of Contents 1. Mechanical Installation... 1-3 2. Wiring diagram... 2-5 3. Specifications... 3-6 Technical Specifications... 3-6 Measuring

More information

Application Note Assigning and Reducing the DNP V3.0 Points List on the ABB PCD Timothy S. Fahey, PE

Application Note Assigning and Reducing the DNP V3.0 Points List on the ABB PCD Timothy S. Fahey, PE Application Note Assigning and Reducing the DNP V3.0 s List on the ABB PCD Timothy S. Fahey, PE Introduction This document defines a subset of the full points list given in the DNP 3.0 Implementation Details

More information

PowerLogic power-monitoring units. PM700 series power meter. Technical data sheet

PowerLogic power-monitoring units. PM700 series power meter. Technical data sheet PowerLogic power-monitoring units PM700 series power meter Technical data sheet 2009 Functions and characteristics The PowerLogic PM700 series power meter offers all the measurement capabilities required

More information

ASCO 5210 Digital Power Meter. Operator s Manual DANGER

ASCO 5210 Digital Power Meter. Operator s Manual DANGER Operator s Manual ASCO 5210 Digital Power Meter TABLE OF CONTENTS section-page INTRODUCTION General Information... 1-1 Measurements... 1-2 Specifications... 1-3 Device Ratings... 1-4 INSTALLATION Mounting...

More information

Energy Management Modular Smart Power Transducer Type SPT-90

Energy Management Modular Smart Power Transducer Type SPT-90 Energy Management Modular Smart Power Transducer Type SPT-90 Class 0.5 (current/voltage) 16-bit µp-based modular smart power transducer Measurements of: W, Wavg, VA, VAr, PF, Wh, VAh, VArh, Amax (among

More information

Conzerv EM6400NG series

Conzerv EM6400NG series Conzerv EM6400NG series Multi-function power & energy meters Technical datasheet PB115131 Introducing EM6400NG, next generation power meters of iconic EM6400 series with innovative Accurate measurements

More information

ELECTRICAL VARIABLE ANALYZER RELAY EVAR

ELECTRICAL VARIABLE ANALYZER RELAY EVAR ELECTRICAL VARIABLE ANALYZER RELAY EVAR 1 ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this

More information

Integra 1560 and 1580 Digital Transducer Systems

Integra 1560 and 1580 Digital Transducer Systems Integra 1560 and 1580 multi function transducers provide high accuracy

More information

EM-72 Electricity Meters for Current Transformers

EM-72 Electricity Meters for Current Transformers Product sheet MT8.18 Meter EM72 EM-72 Electricity Meters for Current Transformers EM72 electricty meters have been designed for panel mounting to monitor electricity consumption and the quality of the

More information

MID. Energy Management Energy Meter Type EM23 DIN. Product Description. Type Selection. How to order EM23 DIN AV9 3 X O1 PF A EM23 DIN

MID. Energy Management Energy Meter Type EM23 DIN. Product Description. Type Selection. How to order EM23 DIN AV9 3 X O1 PF A EM23 DIN Energy Management Energy Meter Type EM23 DIN Certified according to MID Directive (option PF only): see how to order below Other version available (not certified, option X): see how to order on the next

More information

Brushed DC Motor Control. Module with CAN (MDL-BDC24)

Brushed DC Motor Control. Module with CAN (MDL-BDC24) Stellaris Brushed DC Motor Control Module with CAN (MDL-BDC24) Ordering Information Product No. MDL-BDC24 RDK-BDC24 Description Stellaris Brushed DC Motor Control Module with CAN (MDL-BDC24) for Single-Unit

More information

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters RI-F200 Series Single and Three Phase Multifunction Energy Meter DIN 96 panel mounted -/1A or -/5A current transformer input Single phase or three phase network compatible Programmable voltage and current

More information

NETWORK ANALYZERS Analyzers

NETWORK ANALYZERS Analyzers CONTENTS PRODUCTS RANGE NA.03 NETWORK ANALYZER - LCC NETWORK ANALYZER - LCA NETWORK ANALYZER - LDA NETWORK ANALYZER - LAB96 NETWORK ANALYZER - LABM NA.04 NA.06 NA.09 NA.10 NA.13 NETWORK ANALYZER - LCCM

More information

Energy Division

Energy Division Energy Division http://energy.tycoelectronics.com Installation and Operating Manual Integra 1560 and 1580 Digital Metering and Transducer Systems Tyco Electronics UK Limited Crompton Instruments Freebournes

More information

Power Quality and Energy Measurement PEM575

Power Quality and Energy Measurement PEM575 Power Quality and Energy Measurement _D00016_00_D_XXEN/06.2013 Power Quality and Energy Measurement Product description The digital universal measuring device is suited for measuring and displaying electrical

More information

SUPPLY NETWORK ANALYZER CVM-96 SERIES

SUPPLY NETWORK ANALYZER CVM-96 SERIES SUPPLY NETWORK ANALYZER CVM-96 SERIES (Power Demand) INSTRUCTION MANUAL ( M 981 326 / 00B - GB) (c) CIRCUTOR S.A. ----- Supply network analyzer CVM-96 ------ User's manual --- Page No. 1 CVM-96 SUPPLY

More information

DPF-MAC Auto power factor controller

DPF-MAC Auto power factor controller Digital Electric& Electronics System DPF-MAC Auto power factor controller MULTI POWER FACTOR AUTOMATIC MULTI POWER FACTOR AUTOMATIC Introduction DPF-MAC increases usage efficiency by controlling the power

More information

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN)

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN) Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN) 217-3367 Ordering Information Product Number Description 217-3367 Stellaris Brushed DC Motor Control Module with CAN (217-3367)

More information

Modbus communication module for TCX2: AEX-MOD

Modbus communication module for TCX2: AEX-MOD Modbus communication module for TCX2: Communication Specification TCX2 is factory installed in TCX2 series controllers with -MOD suffix, and is also available separately upon request for customer installation

More information

Energy Management Energy Meter with plug-in Output Modules Type EM4-DIN

Energy Management Energy Meter with plug-in Output Modules Type EM4-DIN Energy Management Energy Meter with plug-in Output Modules Type EM4-DIN Degree of protection (front): IP 40 Front dimensions: 9 DIN modules RS 422/485 Serial port by means of optional module Dual pulse

More information

Energy Management Three-phase energy meter with output modules Type EM4-DIN

Energy Management Three-phase energy meter with output modules Type EM4-DIN Energy Management Three-phase energy meter with output modules Type EM4-DIN Class 1 (active energy) Class 2 (reactive energy) Three-phase multi-function energy meter Back-lighted LCD display 3 1 / 2 DGT

More information

Power Quality and Energy Measurement PEM330/PEM333

Power Quality and Energy Measurement PEM330/PEM333 Power Quality and Energy Measurement PEM330/PEM333 TDB310001en / 02.2013 Power Quality and Energy Measurement PEM330/PEM333 0.5S Product description The universal measuring device PEM330/333 is used to

More information

Energy Management Modular Power Analyzers Type WM2-96

Energy Management Modular Power Analyzers Type WM2-96 ISE, Inc. - 10100 Royalton Rd. - Cleveland, OH 44133 USA Energy Management Modular Power Analyzers Type WM2-96 - Tel: (440) 237-3200 - Fax: (440) 237-1744 - http://instserv.com Class 1 Modular power analyzer

More information

ZHUHAI PILOT TECHNOLOGY CO., LTD.

ZHUHAI PILOT TECHNOLOGY CO., LTD. SPM32 Multifunctional Power Meter SPM32 Multifunction Power Meter Installation & Operation Manual V1.0 ZHUHAI PILOT TECHNOLOGY CO., LTD. Danger and warning! This device can be installed only by professionals.

More information

MPS PROFIBUS-DP INTERFACE

MPS PROFIBUS-DP INTERFACE 3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.littelfuse.com/protectionrelays MPS PROFIBUS-DP INTERFACE PRELIMINARY SEPTEMBER 8, 2003 Publication: PROFIBUS-M

More information

BAS Integration Manual

BAS Integration Manual Snow Melting Control 680 Introduction BAS Integration Manual Snow Melting 680_B 10/15 Replaces: 04/15 The Snow Melting Control 680 can communicate with a Building Automation System (BAS) using either BACnet

More information

TAS APFC Controller / Load Managers with MOD-BUS Interface

TAS APFC Controller / Load Managers with MOD-BUS Interface TAS APFC Controller / Load Managers with MOD-BUS Interface Designed & Prepared by TAS PowerTek Pvt. Ltd., W-61, MIDC Ambad, Nasik-422010, India. Updated on: 4th June 2017, Sunday. Data Parameter Field

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 105U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 105U range of wireless I/O provides a low cost alternative

More information

C u t l e r- H a m m e r. IQ Analyzer START Q U I C KS TA RT G U I D E

C u t l e r- H a m m e r. IQ Analyzer START Q U I C KS TA RT G U I D E C u t l e r- H a m m e r IQ Analyzer START Q U I C KS TA RT G U I D E C O N T E N T S Introduction 4 Mounting 9 IMPORTANT NOTICE Use this Guide to begin performing basic metering functions quickly, without

More information

Home Automation, Inc. Omnistat2. RC-1000 and RC-2000 Communicating Thermostat. Serial Protocol Description

Home Automation, Inc. Omnistat2. RC-1000 and RC-2000 Communicating Thermostat. Serial Protocol Description Home Automation, Inc. Omnistat2 RC-1000 and RC-2000 Communicating Thermostat Serial Protocol Description This document contains the intellectual property of Home Automation, Inc. (HAI). HAI authorizes

More information

PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH

PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH Installation and Operation Manual BG0425 Rev. A15 LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of wireless I/O provides a low cost alternative

More information

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement Date: 2012-06-27 Vendor Name: Trane Product Name: Trane TR150 Product Model Number: TR150 Applications Software Version: 3.0 Firmware Revision: 3.0

More information

Portable Circuit Monitor Series 2000

Portable Circuit Monitor Series 2000 Instruction Bulletin Bulletin No. July 1997 LaVergne, TN, USA Portable Circuit Monitor Series 2000 1997Square D Company All Rights Reserved NOTICE Read these instructions carefully and look at the equipment

More information

P P S - M W S C A N 2 H

P P S - M W S C A N 2 H µ-controller-systems / HARD- & SOFTWARE-DESIGN POWER-SUPPLIES FROM MILLIWATTS TO KILOWATTS Device: PPS-MWS-2000-4000-CAN2H 04 / 2018 Page 1 / 6 S w i t c h i n g M o d e P o w e r S u p p l y f o r M a

More information

ME432 Three-phase Power Meter

ME432 Three-phase Power Meter ME432 Three-phase Power Meter Connectivity advantages MODEL ME432 Support Extra sensor Programmable digital output I/O function 333mV CT Rogowski coil Relay 1*digital output Power 85~265V AC/DC 1 Feature

More information

Power analyzers and Energy Meters Power Analyzer Type WM14-DIN

Power analyzers and Energy Meters Power Analyzer Type WM14-DIN Power analyzers and Energy Meters Power Analyzer Type WM14-DIN Optional RS422/485 serial port Alarms (visual only) V LN, An Class 2 (active energy) Class 3 (reactive energy) Accuracy ±0.5 F.S. (current/voltage)

More information

Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH

Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH Series PM PLUS Powermeters PMPPMEPMEH SATEC ASCII Communications Protocol eference Guide BG46 ev. A4 Every effort has been made to ensure that the material herein is complete and accurate. However, the

More information

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number:  Address: NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information

More information

Technical Data Sheet. x1000. kwh R Y B

Technical Data Sheet. x1000. kwh R Y B Technical Data Sheet x1000 Von kwh IRev 3600 imp /kwh R Y B is a compact multifunction instrument which is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy

More information

PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH

PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH Installation and Operation Manual BG0425 Rev. A18 LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument

More information

Circuit Monitor Series 2000

Circuit Monitor Series 2000 Instruction Bulletin Bulletin No. 3020IM9806 February 1999 LaVergne, TN, USA (Replaces 3020IM9301R10/97 dated January 1998) Circuit Monitor Series 2000 Reference Manual NOTICE Read these instructions carefully

More information

EVDP610 IXDP610 Digital PWM Controller IC Evaluation Board

EVDP610 IXDP610 Digital PWM Controller IC Evaluation Board IXDP610 Digital PWM Controller IC Evaluation Board General Description The IXDP610 Digital Pulse Width Modulator (DPWM) is a programmable CMOS LSI device, which accepts digital pulse width data from a

More information

Power analyzers and Energy Meters Power Analyzer Type WM14-96

Power analyzers and Energy Meters Power Analyzer Type WM14-96 Power analyzers and Energy Meters Power Analyzer Type WM14-96 Optional RS422/485 serial port Alarms (visual only) V LN, An Class 2 (active energy) Class 3 (reactive energy) Accuracy ±0.5 F.S. (current/voltage)

More information

Current Clamp. 210

Current Clamp. 210 Our range of devices includes clamp meters for measuring current leaks, AC and DC current, voltage, power, resistance, continuity, capacitance or frequency. Some clamp meters have a clearly arranged display

More information

mmint Modbus translator module installation and use

mmint Modbus translator module installation and use Instructional Leaflet IL66A7508H09 Supersedes July 2009 mmint Modbus translator module installation and use Contents Description Page List of figures... 2 List of tables.... 2 Section 1: General description...

More information

MID. Energy Management Energy Analyzer Type EM Product Description. How to order EM26 96 AV5 3 H O3 S1 PF A. Type Selection EM26 96

MID. Energy Management Energy Analyzer Type EM Product Description. How to order EM26 96 AV5 3 H O3 S1 PF A. Type Selection EM26 96 Energy Management Energy Analyzer Type EM26 96 M-bus communication by means of VMU-B adapter Application adaptable display and programming procedure (Easyprog function) Easy connections management Certified

More information

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL 1.01 SUMMARY: The following technical specification describes the requirements of the high accuracy standalone 3 phase Power

More information

PMAC770 Multifunction Power Meter. Installation & Operation Manual V2.0 ZHUHAI PILOT TECHNOLOGY CO., LTD.

PMAC770 Multifunction Power Meter. Installation & Operation Manual V2.0 ZHUHAI PILOT TECHNOLOGY CO., LTD. PMAC770 Multifunction Power Meter Installation & Operation Manual V2.0 ZHUHAI PILOT TECHNOLOGY CO., LTD. Danger and warning! This device can be installed only by professionals. The manufacturer shall not

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

Metering Devices, Protective Relays, Software and Connectivity

Metering Devices, Protective Relays, Software and Connectivity , Protective Relays, Software and Connectivity.3 IQ Analyzer 6400/6600 Series IQ Analyzer Comprehensive Electrical Distribution Monitoring IQ Analyzer 6400/6600 Series Product Description Eaton s IQ Analyzer

More information

INTELLIGENT DIGITAL MULTI POWER METER [DIC-MPM]

INTELLIGENT DIGITAL MULTI POWER METER [DIC-MPM] Feature Suit for LV/ HV voltage system Compact design with all real-time measurement Consist of basic unit and optional modules 10 years back-up of integrated energy data Large LCD, high brightness High

More information

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613 Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613 Data Bulletin 0613IB1201 06/2012 Retain for future use. 0613IB1201 Modbus Communications System for Micrologic A, P, and H

More information

Mate Serial Communications Guide This guide is only relevant to Mate Code Revs. of 4.00 and greater

Mate Serial Communications Guide This guide is only relevant to Mate Code Revs. of 4.00 and greater Mate Serial Communications Guide This guide is only relevant to Mate Code Revs. of 4.00 and greater For additional information contact matedev@outbackpower.com Page 1 of 20 Revision History Revision 2.0:

More information

Energy Management Energy Meter Type EM340

Energy Management Energy Meter Type EM340 Energy Management Energy Meter Type EM340 Digital input (for tariff management Easy connection or wrong current direction detection Certified according to MID Directive (option PF only: see how to order

More information

ELITE PRO. Automation Components, Inc.

ELITE PRO. Automation Components, Inc. ELITE PRO Automation Components, Inc. FEA TUR E S For single or 3-phase systems using 80-600V phase-to-phase (AC or DC) services when line powered or 0-600V (AC or DC) when externally powered. Measures

More information

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY WN U-60 Attachment C to Schedule 152, Page 1 SCHEDULE 152 APPLICATION FOR INTERCONNECTING A GENERATING FACILITY TIER 2 OR TIER 3 This Application is considered complete when it provides all applicable

More information

Energy Management. Type WM14-DIN Basic Version. How to order WM14-DIN AV5 3 D PGX. Type Selection. Input specifications. CptBSoft

Energy Management. Type WM14-DIN Basic Version. How to order WM14-DIN AV5 3 D PGX. Type Selection. Input specifications. CptBSoft Energy Management Power Analyzer ype WM-DI Basic Version Optional dual pulse output Alarms (visual only) V L, An Optional galvanically insulated measuring inputs Product Description ype Selection Range

More information

DEIF A/S. Description of options. Option H1 Serial communication CAN open. Description of options. Functional description. Tables.

DEIF A/S. Description of options. Option H1 Serial communication CAN open. Description of options. Functional description. Tables. Description of options Option H1 Serial communication CAN open 4189340277G SW version 2.42.X Description of options Functional description DEIF A/S Tables Parameter list Object dictionary DEIF A/S, Frisenborgvej

More information