1 Series PM30 PLUS Powermeters PM30PPM30EPM30EH DNP3 Communications Protocol Reference Guide BG048 Rev. A4

2 Every effort has been made to ensure that the material herein is complete and accurate. However, the manufacturer is not responsible for any mistakes in printing or faulty instructions contained in this book. Notification of any errors or misprints will be received with appreciation. For further information regarding a particular installation, operation or maintenance of equipment, contact the manufacturer or your local representative or distributor. REVISION HISTORY A A A3 A4 Nov 007 Mar 008 Jun 00 Oct 05 Release F versions..6 or higher. Added functions 7 Immediate Freeze and 8 Immediate Freeze No Acknowledgement. Added DNP 6-bit and 3-bit frozen binary counter and analog input objects. Added DNP Object 50 Time and Date to the Class 0 point list. F versions.3.3 or higher. Added kvah importexport and 4-quadrant kvarh registers. Added support for the LL wiring mode.

3 Table of Contents GENERAL... 5 DNP 3.0 PROTOCOL IMPLEMENTATION DEVIATIONS FROM STANDARD DNP IMPLEMENTATION DEVICE ADDRESS TRANSACTION TIMING CLASS 0 RESPONSE FROZEN COUNTERS FROZEN ANALOG INPUTS SCALING 6-BIT ANALOG INPUTS SCALING 6-BIT BINARY COUNTERS PASSORD PROTECTION DNP POINT MAP ANALOG INPUTS - BASIC SET BINARY INPUTS - BASIC SET BINARY COUNTERS - BASIC SET FROZEN COUNTERS...3 Total Energies Basic Set E... 3 Counters Extended Set... 3 Total Energies - Extended Set E... 4 Phase Energies - Extended Set E ANALOG INPUTS, BINARY INPUTS AND COUNTERS EXTENDED SET...5 Digital Inputs DI-DI Relay Outputs RO-RO... 5 Counters Cycle Phase Values Cycle Total Values Cycle Auxiliary Values Second Phase Values Second Total Values Second Auxiliary Values... 8 Present Volt, Ampere and Power Demands... 8 Total Energies E... 9 Phase Energies E... 0 VV Harmonic Distortion EH... 0 VV3 Harmonic Distortion EH... 0 V3V3 Harmonic Distortion EH... I Harmonic Distortion EH... I Harmonic Distortion EH... I3 Harmonic Distortion EH... Fundamental (H0 Phase Values EH... Fundamental (H0 Total Values EH... Minimum -Cycle Phase Values... Minimum -Cycle Total Values... Minimum -Cycle Auxiliary Values... Maximum -Cycle Phase Values... Maximum -Cycle Total Values... 3 Maximum -Cycle Auxiliary Values... 3 Maximum Demands FACTORY DEVICE SETTINGS AND IDENTIFICATION...5 Device Identification... 5 Factory Device Settings... 5 Device Identification (alias... 5 Port Identification

4 3.7 DEVICE CONTROL...7 Device Authorization Register... 7 Device ResetClear... 7 Alarm Notification... 8 Remote Relay Control DEVICE SETUP...3 Basic Setup... 3 Communication Ports Setup... 3 Device Options Setup DNP PROTOCOL SETUP...35 DNP Options Setup DNP Class 0 Point Assignments DATA SCALES AND UNITS Data Scales Data Units Low Resolution Option Data Units High Resolution Option DATA FORMATS iring Mode Instrument Options DNP Object Variations DNP Class 0 Objects APPENDIX A DNP APPLICATION MESSAGES... 4 APPENDIX B DNP DEVICE PROFILE

5 General This document specifies a subset of the DNP3 communications protocol used to transfer data between a master computer station and the PM30. The document provides the complete information necessary to develop third-party communications software capable of communication with the Series PM30 instruments. Additional information concerning operating the device, configuring the communication parameters, and communication connections may be found in the "PM30 PLUS Installation and Operation Manual". Refer to Configuring DNP in the PM30 PLUS Installation and Operation Manual for information on how to configure Class 0 responses via the supplemental PAS software. The document is applicable to the PM30P, PM30E and PM30EH devices. IMPORTANT In 3-wire connection schemes, the unbalanced current and phase readings for power factor, active power, and reactive power will be zeros, because they have no meaning. Only the total three-phase power values will be shown. Most of the advanced features are configured using multiple setup parameters that can be accessed in a number of contiguous registers. hen writing the setup registers, it is recommended to write all the registers at once using a single request, or to clear (zero the setup before writing into separate registers. Designations used in the guide: E - available in the PM30E and PM30EH EH - available in the PM30EH 5

6 DNP 3.0 Protocol Implementation DNP3 (Distributed Network Protocol is an open standard designed by Harris Control Division. DNP defines a command-response method of communicating digital information between a master and slave device. Detailed information regarding DNP3 is available in the Basic 4 Document Set which can be obtained from the DNP User Group.. Deviations from Standard The PM30 implements Level of the DNP3 communication protocol. The device does not support unsolicited responses or hardware collision avoidance. The data link layer differs from the Basic 4 specifications because of the master-slave relationship between devices. hen the device receives a request, no further requests can be sent until after the device makes the appropriate response.. DNP Implementation The PM30, like most devices, allows retrieving regular analog and binary data from the device by executing directed (non-broadcast Read requests. Binary-Output-Status objects and Analog-Output-Status objects are sent with flags that always indicate ONLINE. A Binary-Output-Status object that indicates the current state of a control digital point (relay uses remote forced data as well as local forced data bits. The value of a state bit indicates the current state of the digital output point. The PM30 executes the parameter clear function and demands resets using the Direct- Operate, SBOOperate or Direct-Operate-No-Acknowledge command to specified points of the Control-Relay-Output-Block object. Issuing the Direct-Operate, SBOOperate or Direct-Operate-No-Acknowledge command to appropriative points of the Analog-Output-Block object can change the setup parameters. The device also supports the DNP functions rite, Cold-Restart and Delay Measurement. Refer to Appendix A for information on specific requests and responses. Appendix B contains the standard DNP Device Profile Document. The device attempts to respond with the same object variation and qualifier as those in the request. Exceptions to this rule include changing variation 0 to a specific variation and changing qualifier code 6 to. If the device receives an invalid request, it sets the internal indication to the error code. The following internal indication bits are supported: Octet Posit ion Bit Posi tion Description 0 0 Set when a request received with a broadcast destination address. Cleared after next response. 0 7 Device restart - set when the device powers up or after executing Cold Restart, cleared by writing zero to object Time-synchronization required from the master. Cleared when master sets the time. 0 5 Set when the device is in the Local state. Cleared when the device in the Remote state. 5 Set when the current configuration in the device is corrupted. May also be set as a result of the legal changes in the setup configuration whenever another setup is affected by the changes made. Cleared by writing zero to points using object... Device Address Each device on a DNP link must have a unique address. The PM30 allows a device address in the range of 0 to 6553 to be selected. The DNP master can use addresses 6

7 65533 to for broadcast requests. A broadcast request never generates a DNP response... Transaction Timing The PM30 response time to master requests is indicated in Table -. Table - Response Time Baud Rate, bps Response Time, ms Min Max Typical The Direct-Operate, SBOOperate or Direct-Operate-No-Acknowledge requests for resetclear registers and setpoint changing are immediately confirmed...3 Class 0 Response The PM30 DNP implementation supports a wide variety of messages. The most common method of getting static object information from the meter via DNP is to issue a read Class 0 request. The PM30 allows you to configure the Class 0 response by assigning ranges of points to be polled via Class 0 requests (see Section 3.9, DNP Protocol setup. The Class 0 point list may contain up to 3 ranges of points. The total number of points that can be reported in the Class 0 response is limited by the one application fragment size, or 048 bytes. Refer to Configuring DNP in the PM30 PLUS installation and Operation Manual for information on how to configure Class 0 responses via PAS...4 Frozen Counters The PM30 supports function codes 7 Immediate Freeze, 8 Immediate Freeze No Acknowledgment, 9 Freeze with Clear and 0 Freeze with Clear No Acknowledgment for Binary Counter object 0. The freeze command copies the Binary Counter points listed in Section 3.4 to a freeze buffer with the time of freeze. All Binary Counter points are frozen together. Since the freeze command may request clearing counters, the device uses a single freeze buffer that is shared among all communication ports and TCPIP connection sockets so that issuing a freeze command via a number of connections may cause unpredictable results. The objects that were frozen can be requested by asking for 6-bit or 3-bit Frozen Counter objects with any variation listed in the device profile (see Appendix D, with the time of freeze or without time. 6-bit Frozen Counter objects may be scaled to avoid over-range errors if this option is enabled in the device (see Section..7, Scaling 6-bit Binary Counters. The response contains the last frozen values of the corresponding Binary Counter points. Frozen Counters requested with variation 0 are responded with the default variation specified for the Frozen Counter object in the DNP Options Setup (see Section 3.9, DNP Protocol setup...5 Frozen Analog Inputs The PM30 supports function codes 7 Immediate Freeze and 8 Immediate Freeze No Acknowledgment for Analog Input object 30. Any of the Analog Input points listed in Sections 3. and 3.5 can be frozen. The points that are to be frozen must be listed in the Class 0 point list (see Section..3 using any Frozen Analog Input object type. The total number of points that can be frozen is limited 7

8 to 50. If Class 0 doesn t specify Frozen Analog Input points, the device responds to function 7 Immediate Freeze with the IIN. bit set - Outstation does not support requested operation for objects in the request. The freeze command copies the corresponding Analog Input points to a freeze buffer with the time of freeze. The device provides a local freeze buffer for every communication port and every TCPIP connection socket, so the Frozen Analog Input points must be requested via the same connection through which a freeze command was sent; otherwise the device may not guarantee that the frozen values are correlated with the corresponding freeze command. The objects that were frozen can be requested by asking for 6-bit or 3-bit Frozen Analog Input objects with variations 0 through 6, with the time of freeze or without time. 6-bit Frozen Analog Input objects may be scaled to avoid over-range errors if this option is enabled in the device (see Section..6, Scaling 6-bit Analog Inputs. The response contains the last frozen values of the corresponding Analog Input points if the freeze command was executed before, or immediate values of the corresponding Analog Input points in the event the freeze command has never been executed. Requesting Frozen Analog Input points with time of freeze without the freeze command can be used to get immediate values of the Analog Input points with timestamps. Frozen Analog Inputs requested with variation 0 are responded with the variation specified for the requested points in the Class 0 point list...6 Scaling 6-bit Analog Inputs Any of the variations through 4 can be used with the Analog Input objects. Variations specified in Sections 3. and 3.4 show those that can be used to read a full-range value without a possible over-range error when no scaling is used to accommodate the value to the requested object size. hen over-range occurs, a positive value is reported as 3767 and a negative value as -3768, with the over-range bit in the flag octet being set to if a variation is requested. To avoid over-range errors when a variation or 4 is required, a liner scaling may be used to scale 3-bit analog readings to 6-bit Analog Input objects (see DNP Options setup in Section 3.9. Scaling is enabled in the device by default. hen scaling is enabled, either analog input requested with variation or 4 will be scaled to the range of to 3767 for bi-directional parameters (such as power and power factor, and to the range of 0 to 3767 for single-ended positive parameters (voltage, current, frequency, etc.. To get a true reading, the reverse conversion should be done using the following formula: where: EXAMPLE Y = ((X DNP_LO (HI - LO (DNP_HI DNP_LO + LO Y - True reading in engineering units X - Raw input data in the range of DNP_LO DNP_HI LO, HI - Data low and high scales in engineering units (for device data scales, see Section 4 DNP_LO - DNP low conversion scale: DNP_LO = for a point with a negative LO scale DNP_LO = 0 for a point with a zero or positive LO scale DNP_HI - DNP high conversion scale: DNP_HI = 3767 If you have read a value of 0 for point AI:3 that shows the I current (see Section 3. and the CT primary current is 00A (the high current scale is 00 = 400A, then the current reading in engineering units is as follows: (0-0 (400-0( =.45A 8

9 ..7 Scaling 6-bit Binary Counters Binary counters are stored in the device in 3-bit integer format. Using 6-bit Binary Counter objects can cause over-range errors if the counter value exceeds Scaling binary counters (see DNP Options setup in Section 3.9 allows changing a binary counter unit from to 000 in powers of 0 to accommodate a 3-bit counter value to 6-bit object format. If the scaling unit is greater than, the counter value is reported being divided by the scaling unit. To get the actual value, multiply the counter reading by the selected scaling unit..3 Password Protection The PM30 has a password protection option allowing you to protect your setups, cumulative registers and logs from being changed or cleared through communications. You can disable or enable password protection through communications or via the front display. For details, refer to your instrument Installation and Operation Manual. hen password protection is enabled, the user password you set in your instrument should be written into the device authorization register (point AO:9 before another write request is issued. If the correct password is not supplied while password protection is enabled, the instrument will respond to all write requests with the exception response Control operation not supported for this point. It is recommended to clear the password register after you have completed your changes in order to activate password protection. 9

10 3 DNP Point Map 3. Analog Inputs - Basic Set Var. 3 Point Description OptionsRange Units 30:3 AI:0 VV Voltage 0-Vmax U UINT3 R 30:3 AI: VV3 Voltage 0-Vmax U UINT3 R 30:3 AI: V3V3 Voltage 0-Vmax U UINT3 R 30:3 AI:3 I Current 0-Imax U UINT3 R 30:3 AI:4 I Current 0-Imax U UINT3 R 30:3 AI:5 I3 Current 0-Imax U UINT3 R 30:3 AI:6 k L -Pmax-Pmax U3 INT3 R 30:3 AI:7 k L -Pmax-Pmax U3 INT3 R 30:3 AI:8 k L3 -Pmax-Pmax U3 INT3 R 30:3 AI:9 kvar L -Pmax-Pmax U3 INT3 R 30:3 AI:0 kvar L -Pmax-Pmax U3 INT3 R 30:3 AI: kvar L3 -Pmax-Pmax U3 INT3 R 30:3 AI: kva L 0-Pmax U3 UINT3 R 30:3 AI:3 kva L 0-Pmax U3 UINT3 R 30:3 AI:4 kva L3 0-Pmax U3 UINT3 R 30:4 AI:5 Power factor L INT6 R 30:4 AI:6 Power factor L INT6 R 30:4 AI:7 Power factor L INT6 R 30:4 AI:8 Total PF INT6 R 30:3 AI:9 Total k -Pmax-Pmax U3 INT3 R 30:3 AI:0 Total kvar -Pmax-Pmax U3 INT3 R 30:3 AI: Total kva 0-Pmax U3 UINT3 R 30:3 AI: In (neutral Current 0-Imax U UINT3 R 30:4 AI:3 Frequency 0-Fmax 0.0 UINT6 R Hz 30:3 AI:4 Maximum k import sliding window 0-Pmax U3 UINT3 R demand 30:3 AI:5 k import accumulated demand 0-Pmax U3 UINT3 R 30:3 AI:6 Maximum kva sliding window demand 0-Pmax U3 UINT3 R 30:3 AI:7 kva accumulated demand 0-Pmax U3 UINT3 R 30:3 AI:8 I Maximum ampere demand 0-Imax U UINT3 R 30:3 AI:9 I Maximum ampere demand 0-Imax U UINT3 R Type R 0

11 Var. 3 Point Description OptionsRange Units 30:3 AI:30 I3 Maximum ampere demand 0-Imax U UINT3 R 30:3 AI:3 Present k import sliding window demand 0-Pmax U3 UINT3 R 30:3 AI:3 Present kva sliding window demand 0-Pmax U3 UINT3 R 30:4 AI:33 PF (import at Max. kva sliding window UINT6 R demand 30:4 AI:34 VV Voltage THD UINT6 R, 4 3-sec value 30:4 AI:35 VV3 Voltage THD UINT6 R, 4 3-sec value 30:4 AI:36 V3V3 Voltage THD UINT6 R, 4 3-sec value 30:4 AI:37 I Current THD UINT6 R 4 3-sec value 30:4 AI:38 I Current THD UINT6 R 4 3-sec value 30:4 AI:39 I3 Current THD UINT6 R 4 3-sec value 30:4 AI:40 I Current TDD UINT6 R 4 3-sec value 30:4 AI:4 I Current TDD UINT6 R 4 3-sec value 30:4 AI:4 I3 Current TDD UINT6 R 4 3-sec value NOTES: Energy and power demand readings and total harmonics are only available in the PM30EH meters. Voltage and voltage harmonics readings: when the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. All analog input points except of harmonics are -second average values. For volts, amps and power scales and units, refer to Section 4 Data Scales and Units. For analog input scaling formulas and examples, see Section..6, Scaling Analog Input Objects. 3 Any of the analog input points listed in the table can be frozen using functions 7 or 8 with object 30 and variation 0. See Section..5 for details. 4 In LL wiring mode the Harmonics calculations are not supported. Type R

12 3. Binary Inputs - Basic Set Var. Point Description Range Units Type R 0: BI:0 Relay # status 0- R 0: BI: Relay # status 0- R 0: BI:6 Status input # 0- R 0: BI:7 Status input # 0- R 0: BI:8 Status input #3 0- R 0: BI:9 Status input #4 0- R

13 3.3 Binary Counters - Basic Set Var. Point Description Range Units Type R 0:5 BC:0 kh import 0-999,999,999 kh UINT3 R 0:5 BC: kh export 0-999,999,999 kh UINT3 R 0:5 BC: kvarh net 0-999,999,999 kvarh UINT3 R 0:5 BC:3 kvah 0-999,999,999 kvah UINT3 R 0:5 BC:4 kvarh import 0-999,999,999 kvarh UINT3 R 0:5 BC:5 kvarh export 0-999,999,999 kvarh UINT3 R 0:5 BC:6 kvah import 0-999,999,999 kvah UINT3 R 0:5 BC:7 kvah export 0-999,999,999 kvah UINT3 R 0:5 BC:8 kvarh Q 0-999,999,999 kvarh UINT3 R 0:5 BC:9 kvarh Q 0-999,999,999 kvarh UINT3 R 0:5 BC:0 kvarh Q ,999,999 kvarh UINT3 R 0:5 BC: kvarh Q ,999,999 kvarh UINT3 R 3.4 Frozen Counters Var. Point Description Range Units Type R Total Energies Basic Set E :var FBC:0 kh import 0-999,999,999 kh UINT3 R :var FBC: kh export 0-999,999,999 kh UINT3 R :var FBC: kvarh net 0-999,999,999 kvarh UINT3 R :var FBC:3 kvah 0-999,999,999 kvah UINT3 R :var FBC:4 kvarh import 0-999,999,999 kvarh UINT3 R :var FBC:5 kvarh export 0-999,999,999 kvarh UINT3 R :var FBC:6 kvah import 0-999,999,999 kvah UINT3 R :var FBC:7 kvah export 0-999,999,999 kvah UINT3 R :var FBC:8 kvarh Q 0-999,999,999 kvarh UINT3 R :var FBC:9 kvarh Q 0-999,999,999 kvarh UINT3 R :var FBC:0 kvarh Q ,999,999 kvarh UINT3 R :var FBC: kvarh Q ,999,999 kvarh UINT3 R Counters Extended Set :var FBC:3538 Counter # 0-99,999 UINT3 R :var FBC:3539 Counter # 0-99,999 UINT3 R :var FBC:35330 Counter #3 0-99,999 UINT3 R :var FBC:3533 Counter #4 0-99,999 UINT3 R 3

14 Var. Point Description Range Units Type R Total Energies - Extended Set E :var FBC:38656 kh import 0-999,999,999 kh UINT3 R :var FBC:38657 kh export 0-999,999,999 kh UINT3 R :var FBC:38658 Not used UINT3 R :var FBC:38659 Not used UINT3 R :var FBC:38660 kvarh import 0-999,999,999 kvarh UINT3 R :var FBC:3866 kvarh export 0-999,999,999 kvarh UINT3 R :var FBC:3866 Not used UINT3 R :var FBC:38663 Not used UINT3 R :var FBC:38664 kvah total 0-999,999,999 kvah UINT3 R :var FBC:38665 Not used UINT3 R :var FBC:38666 Not used UINT3 R :var FBC:38667 kvah import 0-999,999,999 kvah UINT3 R :var FBC:38668 kvah export 0-999,999,999 kvah UINT3 R :var FBC:38669 Not used UINT3 R :var FBC:38670 Not used UINT3 R :var FBC:3867 Not used UINT3 R :var FBC:3867 Not used UINT3 R :var FBC:38673 Not used UINT3 R :var FBC:38674 kvarh Q 0-999,999,999 kvarh UINT3 R :var FBC:38675 kvarh Q 0-999,999,999 kvarh UINT3 R :var FBC:38676 kvarh Q ,999,999 kvarh UINT3 R :var FBC:38677 kvarh Q ,999,999 kvarh UINT3 R Phase Energies - Extended Set E :var FBC:389 kh import L 0-999,999,999 kh UINT3 R :var FBC:3893 kh import L 0-999,999,999 kh UINT3 R :var FBC:3894 kh import L ,999,999 kh UINT3 R :var FBC:3895 kvarh import L 0-999,999,999 kvarh UINT3 R :var FBC:3896 kvarh import L 0-999,999,999 kvarh UINT3 R :var FBC:3897 kvarh import L ,999,999 kvarh UINT3 R :var FBC:3898 kvah total L 0-999,999,999 kvah UINT3 R :var FBC:3899 kvah total L 0-999,999,999 kvah UINT3 R :var FBC:3890 kvah total L ,999,999 kvah UINT3 R NOTE For object variation, see DNP Options setup (see Section

15 3.5 Analog Inputs, Binary Inputs and Counters Extended Set Var. 3 Point Description OptionsRange Units 30:4 AI:3768 None 0 UINT6 R Digital Inputs DI-DI4 R 0: BI:34304 DI 0- R 0: BI:34305 DI 0- R 0: BI:34306 DI3 0- R 0: BI:34307 DI4 0- R Relay Outputs RO-RO R 0: BI:3486 Relay # 0- R 0: BI:3487 Relay # 0- R Counters 0:5 BC:3538 Counter # 0-99,999 UINT3 R 0:5 BC:3539 Counter # 0-99,999 UINT3 R 0:5 BC:35330 Counter #3 0-99,999 UINT3 R 0:5 BC:3533 Counter #4 0-99,999 UINT3 R -Cycle Phase Values 30:3 AI:35840 VV Voltage 0-Vmax U UINT3 R 30:3 AI:3584 VV3 Voltage 0-Vmax U UINT3 R 30:3 AI:3584 V3V3 Voltage 0-Vmax U UINT3 R 30:3 AI:35843 I Current 0-Imax U UINT3 R 30:3 AI:35844 I Current 0-Imax U UINT3 R 30:3 AI:35845 I3 Current 0-Imax U UINT3 R 30:3 AI:35846 k L -Pmax-Pmax U3 INT3 R 30:3 AI:35847 k L -Pmax-Pmax U3 INT3 R 30:3 AI:35848 k L3 -Pmax-Pmax U3 INT3 R 30:3 AI:35849 kvar L -Pmax-Pmax U3 INT3 R 30:3 AI:35850 kvar L -Pmax-Pmax U3 INT3 R 30:3 AI:3585 kvar L3 -Pmax-Pmax U3 INT3 R 30:3 AI:3585 kva L 0-Pmax U3 UINT3 R 30:3 AI:35853 kva L 0-Pmax U3 UINT3 R 30:3 AI:35854 kva L3 0-Pmax U3 UINT3 R 30:4 AI:35855 Power factor L INT6 R 30:4 AI:35856 Power factor L INT6 R 30:4 AI:35857 Power factor L INT6 R 30:4 AI:35858 VV Voltage THD UINT6 R, 4 -cycle value Type R 5

16 Var. 3 Point Description OptionsRange Units Type R UINT6 R, 4 -cycle value 30:4 AI:35859 VV3 Voltage THD :4 AI:35860 V3V3 Voltage THD UINT6 R, 4 -cycle value 30:4 AI:3586 I Current THD UINT6 R 4 -cycle value 30:4 AI:3586 I Current THD UINT6 R 4 -cycle value 30:4 AI:35863 I3 Current THD UINT6 R 4 -cycle value 30:4 AI:35864 I K-Factor UINT6 R 4 -cycle value 30:4 AI:35865 I K-Factor UINT6 R 4 -cycle value 30:4 AI:35866 I3 K-Factor UINT6 R 4 -cycle value 30:4 AI:35867 I Current TDD UINT6 R 4 -cycle value 30:4 AI:35868 I Current TDD UINT6 R 4 -cycle value 30:4 AI:35869 I3 Current TDD UINT6 R 4 -cycle value 30:3 AI:35870 V Voltage 0-Vmax U UINT3 R 30:3 AI:3587 V3 Voltage 0-Vmax U UINT3 R 30:3 AI:3587 V3 Voltage 0-Vmax U UINT3 R -Cycle Total Values 30:3 AI:36608 Total k -Pmax-Pmax U3 INT3 R 30:3 AI:36609 Total kvar -Pmax-Pmax U3 INT3 R 30:3 AI:3660 Total kva 0-Pmax U3 UINT3 R 30:4 AI:366 Total PF INT6 R 30:4 AI:366 Total PF lag UINT6 R 3 30:4 AI:3663 Total PF lead UINT6 R 3 30:3 AI:3664 Total k import 0-Pmax U3 UINT3 R 3 30:3 AI:3665 Total k export 0-Pmax U3 UINT3 R 3 30:3 AI:3666 Total kvar import 0-Pmax U3 UINT3 R 3 30:3 AI:3667 Total kvar export 0-Pmax U3 UINT3 R 3 30:3 AI: phase average L-NL-L voltage 0-Vmax U UINT3 R, 3 30:3 AI: phase average L-L voltage 0-Vmax U UINT3 R 3 30:3 AI: phase average current 0-Imax U UINT3 R 3 -Cycle Auxiliary Values 30:3 AI:36864 Not used UINT3 R 30:3 AI:36865 In (neutral Current 0-Imax U UINT3 R 6

17 Var. 3 Point Description OptionsRange Units 30:4 AI:36866 Frequency 0-Fmax 0.0 Hz UINT6 30:4 AI:36867 Voltage unbalance UINT6 R 30:4 AI:36868 Current unbalance UINT6 R -Second Phase Values 30:3 AI:370 VV Voltage 0-Vmax U UINT3 R 30:3 AI:37 VV3 Voltage 0-Vmax U UINT3 R 30:3 AI:37 V3V3 Voltage 0-Vmax U UINT3 R 30:3 AI:373 I Current 0-Imax U UINT3 R 30:3 AI:374 I Current 0-Imax U UINT3 R 30:3 AI:375 I3 Current 0-Imax U UINT3 R 30:3 AI:376 k L -Pmax-Pmax U3 INT3 R 30:3 AI:377 k L -Pmax-Pmax U3 INT3 R 30:3 AI:378 k L3 -Pmax-Pmax U3 INT3 R 30:3 AI:379 kvar L -Pmax-Pmax U3 INT3 R 30:3 AI:3730 kvar L -Pmax-Pmax U3 INT3 R 30:3 AI:373 kvar L3 -Pmax-Pmax U3 INT3 R 30:3 AI:373 kva L 0-Pmax U3 UINT3 R 30:3 AI:3733 kva L 0-Pmax U3 UINT3 R 30:3 AI:3734 kva L3 0-Pmax U3 UINT3 R 30:4 AI:3735 Power factor L INT6 R 30:4 AI:3736 Power factor L INT6 R 30:4 AI:3737 Power factor L INT6 R 30:4 AI:3738 VV Voltage THD UINT6 R, 4 3-sec value 30:4 AI:3739 VV3 Voltage THD UINT6 R, 4 3-sec value 30:4 AI:3740 V3V3 Voltage THD UINT6 R, 4 3-sec value 30:4 AI:374 I Current THD UINT6 R 4 3-sec value 30:4 AI:374 I Current THD UINT6 R 4 3-sec value 30:4 AI:3743 I3 Current THD UINT6 R 4 3-sec value 30:4 AI:3744 I K-Factor UINT6 R 4 3-sec value 30:4 AI:3745 I K-Factor UINT6 R 4 3-sec value Type R R 7

18 Var. 3 Point Description OptionsRange Units 30:4 AI:3746 I3 K-Factor UINT6 R 4 3-sec value 30:4 AI:3747 I Current TDD UINT6 R 4 3-sec value 30:4 AI:3748 I Current TDD UINT6 R 4 3-sec value 30:4 AI:3749 I3 Current TDD UINT6 R 4 3-sec value 30:3 AI:3750 V Voltage 0-Vmax U UINT3 R 30:3 AI:375 V3 Voltage 0-Vmax U UINT3 R 30:3 AI:375 V3 Voltage 0-Vmax U UINT3 R -Second Total Values 30:3 AI:37888 Total k -Pmax-Pmax U3 INT3 R 30:3 AI:37889 Total kvar -Pmax-Pmax U3 INT3 R 30:3 AI:37890 Total kva 0-Pmax U3 UINT3 R 30:4 AI:3789 Total PF INT6 R 30:4 AI:3789 Total PF lag UINT6 R 3 30:4 AI:37893 Total PF lead UINT6 R 3 30:3 AI:37894 Total k import 0-Pmax U3 UINT3 R 3 30:3 AI:37895 Total k export 0-Pmax U3 UINT3 R 3 30:3 AI:37896 Total kvar import 0-Pmax U3 UINT3 R 3 30:3 AI:37897 Total kvar export 0-Pmax U3 UINT3 R 3 30:3 AI: phase average L-NL-L voltage 0-Vmax U UINT3 R, 3 30:3 AI: phase average L-L voltage 0-Vmax U UINT3 R 3 30:3 AI: phase average current 0-Imax U UINT3 R 3 -Second Auxiliary Values 30:3 AI:3844 Not used UINT3 R 30:3 AI:3845 In (neutral Current 0-Imax U UINT3 R 30:4 AI:3846 Frequency 0-Fmax 0.0 UINT6 R Hz 30:4 AI:3847 Voltage unbalance UINT6 R 30:4 AI:3848 Current unbalance UINT6 R Present Volt, Ampere and Power Demands 30:3 AI:38400 VV Volt demand 0-Vmax U UINT3 R 30:3 AI:3840 VV3 Volt demand 0-Vmax U UINT3 R 30:3 AI:3840 V3V3 Volt demand 0-Vmax U UINT3 R 30:3 AI:38403 I Ampere demand 0-Imax U UINT3 R Type R 8

19 Var. 3 Point Description OptionsRange Units 30:3 AI:38404 I Ampere demand 0-Imax U UINT3 R 30:3 AI:38405 I3 Ampere demand 0-Imax U UINT3 R 30:3 AI:38406 k import block demand 0-Pmax U3 UINT3 R 30:3 AI:38407 kvar import block demand 0-Pmax U3 UINT3 R 30:3 AI:38408 kva block demand 0-Pmax U3 UINT3 R 30:3 AI:38409 k import sliding window demand 0-Pmax U3 UINT3 R 30:3 AI:3840 kvar import sliding window demand 0-Pmax U3 UINT3 R 30:3 AI:384 kva sliding window demand 0-Pmax U3 UINT3 R 30:3 AI:384 Not used UINT3 R 30:3 AI:3843 Not used UINT3 R 30:3 AI:3844 Not used UINT3 R 30:3 AI:3845 k import accumulated demand 0-Pmax U3 UINT3 R 30:3 AI:3846 kvar import accumulated demand 0-Pmax U3 UINT3 R 30:3 AI:3847 kva accumulated demand 0-Pmax U3 UINT3 R 30:3 AI:3848 k import predicted sliding window 0-Pmax U3 UINT3 R demand 30:3 AI:3849 kvar import predicted sliding window 0-Pmax U3 UINT3 R demand 30:3 AI:3840 kva predicted sliding window demand 0-Pmax U3 UINT3 R 30:4 AI:384 PF (import at Max. kva sliding window UINT6 R demand 30:3 AI:384 k export block demand 0-Pmax U3 UINT3 R 30:3 AI:3843 kvar export block demand 0-Pmax U3 UINT3 R 30:3 AI:3844 k export sliding window demand 0-Pmax U3 UINT3 R 30:3 AI:3845 kvar export sliding window demand 0-Pmax U3 UINT3 R 30:3 AI:3846 k export accumulated demand 0-Pmax U3 UINT3 R 30:3 AI:3847 kvar export accumulated demand 0-Pmax U3 UINT3 R 30:3 AI:3848 k export predicted sliding window 0-Pmax U3 UINT3 R demand 30:3 AI:3849 kvar export predicted sliding window 0-Pmax U3 UINT3 R demand 30:3 AI:38430 Not used UINT3 R 30:3 AI:3843 Not used UINT3 R 30:3 AI:3843 Not used UINT3 R 30:3 AI:38433 Not used UINT3 R 30:3 AI:38434 In Ampere demand 0-Imax U UINT3 R Total Energies E 0:5 BC:38656 kh import 0-999,999,999 kh UINT3 R 0:5 BC:38657 kh export 0-999,999,999 kh UINT3 R 0:5 BC:38658 Not used UINT3 R 0:5 BC:38659 Not used UINT3 R Type R 9

20 Var. 3 Point Description OptionsRange Units 0:5 BC:38660 kvarh import 0-999,999,999 kvarh UINT3 R 0:5 BC:3866 kvarh export 0-999,999,999 kvarh UINT3 R 0:5 BC:3866 Not used UINT3 R 0:5 BC:38663 Not used UINT3 R 0:5 BC:38664 kvah total 0-999,999,999 kvah UINT3 R 0:5 BC:38665 Not used UINT3 R 0:5 BC:38666 Not used UINT3 R 0:5 BC:38667 kvah import 0-999,999,999 kvah UINT3 R 0:5 BC:38668 kvah export 0-999,999,999 kvah UINT3 R 0:5 BC:38669 Not used UINT3 R 0:5 BC:38670 Not used UINT3 R 0:5 BC:3867 Not used UINT3 R 0:5 BC:3867 Not used UINT3 R 0:5 BC:38673 Not used UINT3 R 0:5 BC:38674 kvarh Q 0-999,999,999 kvarh UINT3 R 0:5 BC:38675 kvarh Q 0-999,999,999 kvarh UINT3 R 0:5 BC:38676 kvarh Q ,999,999 kvarh UINT3 R 0:5 BC:38677 kvarh Q ,999,999 kvarh UINT3 R Phase Energies E 0:5 BC:389 kh import L 0-999,999,999 kh UINT3 R 0:5 BC:3893 kh import L 0-999,999,999 kh UINT3 R 0:5 BC:3894 kh import L ,999,999 kh UINT3 R 0:5 BC:3895 kvarh import L 0-999,999,999 kvarh UINT3 R 0:5 BC:3896 kvarh import L 0-999,999,999 kvarh UINT3 R 0:5 BC:3897 kvarh import L ,999,999 kvarh UINT3 R 0:5 BC:3898 kvah total L 0-999,999,999 kvah UINT3 R 0:5 BC:3899 kvah total L 0-999,999,999 kvah UINT3 R 0:5 BC:3890 kvah total L ,999,999 kvah UINT3 R VV Harmonic Distortion EH, 4 30:4 AI:3968 H0 Harmonic distortion UINT6 R 30:4 AI:3969 H0 Harmonic distortion UINT6 R 30: :4 AI:3907 H40 Harmonic distortion UINT6 R VV3 Harmonic Distortion EH, 4 30:4 AI:3944 H0 Harmonic distortion UINT6 R 30:4 AI:3945 H0 Harmonic distortion UINT6 R Type R 0

21 Var. 3 Point Description OptionsRange Units 30: :4 AI:39463 H40 Harmonic distortion UINT6 R V3V3 Harmonic Distortion EH, 4 30:4 AI:39680 H0 Harmonic distortion UINT6 R 30:4 AI:3968 H0 Harmonic distortion UINT6 R 30: :4 AI:3979 H40 Harmonic distortion UINT6 R I Harmonic Distortion EH 4 30:4 AI:39936 H0 Harmonic distortion UINT6 R 30:4 AI:39937 H0 Harmonic distortion UINT6 R 30: :4 AI:39975 H40 Harmonic distortion UINT6 R I Harmonic Distortion EH 4 30:4 AI:409 H0 Harmonic distortion UINT6 R 30:4 AI:4093 H0 Harmonic distortion UINT6 R 30: :4 AI:403 H40 Harmonic distortion UINT6 R I3 Harmonic Distortion EH 4 30:4 AI:40448 H0 Harmonic distortion UINT6 R 30:4 AI:40449 H0 Harmonic distortion UINT6 R 30: :4 AI:40487 H40 Harmonic distortion UINT6 R Fundamental (H0 Phase Values EH -cycle values 30:3 AI:4364 VV Voltage 0-Vmax U UINT3 R 30:3 AI:4365 VV3 Voltage 0-Vmax U UINT3 R 30:3 AI:4366 V3V3 Voltage 0-Vmax U UINT3 R 30:3 AI:4367 I Current 0-Imax U UINT3 R 30:3 AI:4368 I Current 0-Imax U UINT3 R 30:3 AI:4369 I3 Current 0-Imax U UINT3 R Type R

22 Var. 3 Point Description OptionsRange Units 30:3 AI:4370 k L -Pmax-Pmax U3 INT3 R 30:3 AI:437 k L -Pmax-Pmax U3 INT3 R 30:3 AI:437 k L3 -Pmax-Pmax U3 INT3 R 30:3 AI:4373 kvar L -Pmax-Pmax U3 INT3 R 30:3 AI:4374 kvar L -Pmax-Pmax U3 INT3 R 30:3 AI:4375 kvar L3 -Pmax-Pmax U3 INT3 R 30:3 AI:4376 kva L 0-Pmax U3 UINT3 R 30:3 AI:4377 kva L 0-Pmax U3 UINT3 R 30:3 AI:4378 kva L3 0-Pmax U3 UINT3 R 30:4 AI:4379 Power factor L INT6 R 30:4 AI:4380 Power factor L INT6 R 30:4 AI:438 Power factor L INT6 R Fundamental (H0 Total Values EH -cycle values 30:3 AI:4350 Total fundamental k -Pmax-Pmax U3 INT3 R 30:3 AI:435 Total fundamental kvar -Pmax-Pmax U3 INT3 R 30:3 AI:435 Total fundamental kva 0-Pmax U3 UINT3 R 30:4 AI:4353 Total fundamental PF INT6 R Minimum -Cycle Phase Values 30:3 AI:4403 VV Voltage 0-Vmax U UINT3 R 30:3 AI:44033 VV3 Voltage 0-Vmax U UINT3 R 30:3 AI:44034 V3V3 Voltage 0-Vmax U UINT3 R 30:3 AI:44035 I Current 0-Imax U UINT3 R 30:3 AI:44036 I Current 0-Imax U UINT3 R 30:3 AI:44037 I3 Current 0-Imax U UINT3 R Minimum -Cycle Total Values 30:3 AI:4488 Total k -Pmax-Pmax U3 INT3 R 30:3 AI:4489 Total kvar -Pmax-Pmax U3 INT3 R 30:3 AI:4490 Total kva 0-Pmax U3 UINT3 R 30:4 AI:449 Total PF UINT6 R Absolute value Minimum -Cycle Auxiliary Values 30:3 AI:44544 Not used UINT3 R 30:3 AI:44545 In Current 0-Imax U UINT3 R 30:4 AI:44546 Frequency 0-Fmax 0.0 UINT6 R Hz Maximum -Cycle Phase Values 30:3 AI:46080 VV Voltage 0-Vmax U UINT3 R Type R

23 Var. 3 Point Description OptionsRange Units 30:3 AI:4608 VV3 Voltage 0-Vmax U UINT3 R 30:3 AI:4608 V3V3 Voltage 0-Vmax U UINT3 R 30:3 AI:46083 I Current 0-Imax U UINT3 R 30:3 AI:46084 I Current 0-Imax U UINT3 R 30:3 AI:46085 I3 Current 0-Imax U UINT3 R Maximum -Cycle Total Values 30:3 AI:46336 Total k -Pmax-Pmax U3 INT3 R 30:3 AI:46337 Total kvar -Pmax-Pmax U3 INT3 R 30:3 AI:46338 Total kva 0-Pmax U3 UINT3 R 30:4 AI:46339 Total PF UINT6 R Absolute value Maximum -Cycle Auxiliary Values 30:3 AI:4659 Not used UINT3 R 30:3 AI:46593 In Current 0-Imax U UINT3 R 30:4 AI:46594 Frequency 0-Fmax 0.0 UINT6 R Hz Maximum Demands 30:3 AI:46848 VV Maximum volt demand 0-Vmax U UINT3 R 30:3 AI:46849 VV3 Maximum volt demand 0-Vmax U UINT3 R 30:3 AI:46850 V3V3 Maximum volt demand 0-Vmax U UINT3 R 30:3 AI:4685 I Maximum ampere demand 0-Imax U UINT3 R 30:3 AI:4685 I Maximum ampere demand 0-Imax U UINT3 R 30:3 AI:46853 I3 Maximum ampere demand 0-Imax U UINT3 R 30:3 AI:46854 Not used UINT3 R 30:3 AI:46855 Not used UINT3 R 30:3 AI:46856 Not used UINT3 R 30:3 AI:46857 Maximum k import sliding window 0-Pmax U3 UINT3 R demand 30:3 AI:46858 Maximum kvar import sliding window 0-Pmax U3 UINT3 R demand 30:3 AI:46859 Maximum kva sliding window demand 0-Pmax U3 UINT3 R 30:3 AI:46860 Not used UINT3 R 30:3 AI:4686 Not used UINT3 R 30:3 AI:4686 Not used UINT3 R 30:3 AI:46863 Maximum k export sliding window 0-Pmax U3 UINT3 R demand 30:3 AI:46864 Maximum kvar export sliding window 0-Pmax U3 UINT3 R demand 30:3 AI:46865 Not used UINT3 R 30:3 AI:46866 Not used UINT3 R 30:3 AI:46867 Not used UINT3 R Type R 3

24 Var. 3 Point Description OptionsRange Units 30:3 AI:46868 Not used UINT3 R 30:3 AI:46869 In Maximum ampere demand 0-Imax U UINT3 R Type R NOTES: Energy and power demand readings are only available in the PM30E and PM30EH meters. Total harmonics readings are only available in the PM30EH meters. Voltage and voltage harmonics readings: when the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. For volts, amps, power and frequency scales and units: refer to Section 4 Data Scales and Units. For analog input scaling formulas and examples, see Section..6, Scaling Analog Input Objects. 3 Any of the analog input points listed in the table can be frozen using functions 7 or 8 with object 30 and variation 0. See Section..5 for details. 4 In LL wiring mode the Harmonics calculations are not supported. 4

25 3.6 Factory Device Settings and Identification Object:V ar. Object:P oint Description OptionsRange Units Type R Device Identification 30:3 AI:56 Device serial number UINT3 R 30:4 AI:57 Device model ID 300=PM30P, UINT6 R 30=PM30A, 300=PM30E, =PM30EH 30:4 AI:58- AI:6 Device model name PM30P, PM30A, PM30E, PM30EH UINT3 R Null-terminated string. Each four characters are packed into a 3-bit word. 30:3 AI:6- Reserved UINT3 R AI:65 30:4 AI:66 Device firmware version number UINT6 R Two higher decimal digits = major version number, two lower decimal digits = minor version number 30:4 AI:67 Device firmware build number -99 UINT6 R 30:3 AI:68- Reserved UINT3 R AI:69 30:4 AI:70 Boot loader version number UINT6 R Two higher decimal digits = major version number, two lower decimal digits = minor version number 30:4 AI:7 Boot loader build number -99 UINT6 R 30:3 AI:7- AI:74 Reserved UINT3 R Factory Device Settings 30:4 AI:75 V-V3 input range 690, 0 (option U V UINT6 R 30:4 AI:76 V-V3 input overload 0 UINT6 R 30:3 AI:77- Reserved UINT3 R AI:78 30:4 AI:79 I-I3 input range, 5 A UINT6 R 30:4 AI:80 I-I3 input overload 00 UINT6 R 30:4 AI:8- AI:88 Reserved UINT6 R Device Identification (alias 30:4 AI:03 Firmware build number -99 UINT6 R 30:4 AI:04 Firmware version number UINT6 R Two higher decimal digits = major version number, two lower decimal digits = minor 5

26 Object:V ar. Object:P oint Description OptionsRange Units Type R 30:3 30:3 AI:05 AI:06 Instrument options F UINT3 R Port Identification 30:4 AI:07 Current serial port number 0=COM, =COM UINT6 R version number 6

27 3.7 Device Control Var. Point Description OptionsRange Units Type R Device Authorization Register 40:(read 4:(write AO:9 hen write: 8-digit password. hen read: 0 = access permitted, - = authorization required. Device ResetClear 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write BO:0 CROB:0 BO: CROB: BO: CROB: BO:3 CROB:3 BO:4- CROB:4- BO: CROB: BO:3 CROB:3 BO:4 CROB:4 BO:5 CROB:5 BO:6 CROB:6 BO:7-0 CROB: (Read (rite Clear total energy registers 0 = state OFFON R Clear total maximum demand registers (all demands 0 = state OFFON R Clear power demands 0 = state OFFON R Clear voltampere demands 0 = state OFFON R Reserved 0 = state OFFON R Clear pulse counters (all counters 0 = state OFFON R Clear pulse counter# 0 = state OFFON R Clear pulse counter# 0 = state OFFON R Clear pulse counter#3 0 = state OFFON R Clear pulse counter#4 0 = state OFFON R Reserved 0 = state OFFON R R Returns zero PULSE ON Returns zero PULSE ON Returns zero PULSE ON Returns zero PULSE ON Returns zero PULSE ON Returns zero PULSE ON Returns zero PULSE ON Returns zero PULSE ON Returns zero PULSE ON Returns zero PULSE ON Returns zero PULSE ON 0:(read BO: Clear MinMax log 0 = state OFFON R Returns zero 7

28 Var. Point Description OptionsRange Units Type R :(write CROB: PULSE ON Alarm Notification 0:(read :(write B0:64 CROB:64 Reserved 0 = state OFFON R 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write 0:(read :(write B0:65 CROB:65 B0:66 CROB:66 B0:67 CROB:67 B0:68 CROB:68 B0 :69 CROB:69 BI :70 CROB:70 B0 :7 CROB:7 B0:7 CROB:7 B0:73 CROB:73 B0:74 CROB:74 B0:75 CROB:75 B0:76 CROB:76 Reserved 0 = state OFFON R RAMData error 0 = state OFFON R CPU watchdog reset 0 = state OFFON R Sampling fault 0 = state OFFON R CPU exception 0 = state OFFON R Reserved 0 = state OFFON R Software watchdog reset 0 = state OFFON R Loss of power (power down 0 = state OFFON R Device reset (cold restart 3 0 = state OFFON R Configuration reset 3 0 = state OFFON R RTC fault (time synchronization required 3 0 = state OFFON R Reserved 0 = state OFFON R 0:(read B0:77 Reserved 0 = state OFFON R 8

29 Var. Point :(write CROB:77 0:(read B0:78 :(write CROB:78 0:(read B0:79 :(write CROB:79 Remote Relay Control 0:(read BO:80 :(write CROB:80 0:(read :(write NOTES: BO:8 CROB:8 Description OptionsRange Units Type R Reserved 0 = state OFFON R EEPROM fault 0 = state OFFON R Relay # Force operateforce releasenormal Relay # Force operateforce release Normal 0 = state OFFON R 0 = state OFFON R 4 4 The following restriction should be noted when using object to control the listed points. The Count byte is ignored. The Control Code byte is checked: - Pulse On ( is valid for all points; other codes are invalid and will be rejected. The On Time and Off Time fields are ignored. The status byte in the response will reflect the success or failure of the control operation: - Request Accepted (0 will be returned if the command was accepted; - Request not Accepted due to Formatting Errors (3 is returned if the Control Code byte was incorrectly formatted or if an invalid code was present in the command; - Control Operation not Supported for this Point (4 is returned if the Control Point was out of control. The alarm indication points indicate possible problems with the device hardware or setup configuration. The hardware problems are indicated by the appropriate points, which are set whenever the instrument fails self-test diagnostics, or in the event of loss of power. The dedicated binary point indicates the setup configuration problems, which is set when either configuration register is corrupted. In this event, the instrument will use the default configuration. The configuration corrupt bit may also be set as a result of the legal changes in the setup configuration since the instrument might implicitly change or clear other setups if they are affected by the changes made. Issuing the Direct-Operate, SBOOperate or Direct-Operate-No-Acknowledge command using the Control-Relay-Output-Block object (with the code operation Latch-Off to points can reset hardware fault points. The configuration corrupt status point is also reset automatically when you change setup either via the front panel or through communications. The following restrictions should be noted when using Object to control the listed points: The Count byte is ignored. The Control Code byte is checked: - Latch Off is valid for all points; other codes are invalid and will be rejected. 9

30 The On Time and Off Time fields are ignored. The status byte in the response will reflect the success or failure of the control operation: - Request Accepted (0 is returned if the command was accepted; - Request not Accepted due to Formatting Errors (3 is returned if the Control Code byte was incorrectly formatted or if an invalid Code was present in the command. 3 These self-check alarms are doubled with the corresponding internal indication bits. 4 To manually operate a relay, use the Direct-Operate, SBOOperate or Direct-Operate-No-Acknowledge command to point 80 or 8 of the Control-Relay-Output-Block object with the Control Code value Latch On. To manually release Relay #, use the Direct-Operate, SBOOperate or Direct-Operate-No-Acknowledge command to point 80 or 8 of the Control-Relay- Output-Block object with the Control Code value Latch Off. The following restrictions should be noted when using object to control the listed points: The Count byte is ignored. The Control Code byte is checked: - Pulse On, Pulse Off, Latch On (Pulse OnClose and Latch Off (Pulse OnTrip are valid for all points; other codes are invalid and will be rejected; - Clear sub-field is valid; other sub-fields are ignored. The On Time specifies in ms the amount of time the digital point is to be turned on. The minimal value of the On Time is 500 ms and the actual value may differ from the specified value by up to 50 ms. The Off Time specifies in ms the amount of time the digital point is to be turned off. The minimal value of the Off Time is 500 ms and the actual value may differ from the specified value by up to 50 ms. The Status byte in the response reflects the success or failure of the control operation: - Request Accepted (0 will be return if the command was accepted; - Request not Accepted due to Formatting Errors (3 will be returned if the Control Code byte was incorrectly formatted or an invalid Code was present in the command; - Control Operation not Supported for this Point (4 will be returned if the Control Point was out of control. 30

31 3.8 Device Setup Object:V ar. Basic Setup 40: (read 4: (write 40: (read 4: (write 40: (read 4: (write 40: (read 4: (write 40: (read 4: (write 40: (read 40: (read 40: (read 40: (read 4: (write 40: (read 40: (read 4: (write Object:P oint Description OptionsRange Units Type R AO:0 iring mode F UINT6 R AO: PT ratio 0 to UINT3 R AO: CT primary current to 50,000 A UINT6 R AO:3 Power block demand period E,,3,5,0,5,0,30,60 min, 55 = external synchronization min UINT6 R AO:4 Voltampere demand period 0 to 800 sec UINT6 R AO:5 Reserved UINT3 R AO:6 Reserved UINT3 R AO:7 Reserved UINT3 R AO:8 Number of blocks in a sliding window E to 5 UINT6 R AO:9- AO:0 Reserved UINT3 R AO: Nominal line frequency 5, 50, 60, 400 Hz UINT6 R If the external synchronization is selected, the DI input is considered a pulse or KYZ input. The pulse edge restarts the power demand block accumulation interval. Read as Read as Read as Read as

32 Object:V ar. 40: (read 4: (write 40: (read 40: (read 4: (write Object:P oint Description OptionsRange Units Type R AO: Maximum demand load current 0 to 50,000 (0 = CT primary current A UINT6 R AO:3- AO:9 Reserved UINT3 R AO:0 PT ratio multiplication factor, 0 UINT6 R Communication Ports Setup COM Setup 40: (read 4: (write 40: (read 4: (write 40: (read 4: (write 40: (read 4: (write 40: (read 4: (write 40: (read 4: (write 40: (read 4: (write AO:64 Communication protocol 0=SATEC ASCII, =Modbus RTU, =DNP3.0 UINT6 R AO:65 Interface =RS-485 UINT6 R AO:66 Device address SATEC ASCII: 0-99 Modbus RTU: -47 DNP3.0: AO:67 Baud rate =300 bps, =600 bps, 3=00 bps, 4=400 bps, 5=4800 bps, 6=9600 bps, 7=900 bps, 8=38400 bps, 9=57600 bps, 0=500 bps AO:68 Data format 0=7 bitseven parity, =8 bitsno parity, =8 bitseven parity UINT3 R UINT6 R UINT6 R AO:69 Flow control UINT6 R AO:70 RTS mode UINT6 R 40: AO:7 ASCII compatibility mode 0=disabled, =enabled UINT6 R Read as Format 0 is not allowed in DNP3.0 NA for COM (read as NA for COM (read as

33 Object:V ar. (read 4: (write 40: (read 4: (write 40: (read 4: (write 40: (read 4: (write 40: (read 4: (write 40: (read 4: (write 40: (read 40: (read 40: (read 4: (write Object:P oint Description OptionsRange Units Type R COM Setup AO:80 Communication protocol 0=SATEC ASCII, = Modbus RTU, =DNP3.0, 5=Profibus DP AO:8 Interface 0=RS-3, =RS-4, =RS- 485, 6=Ethernet, 7=Profibus AO:8 Device address SATEC ASCII: 0-99 Modbus RTU: -47 DNP3.0: Profibus DP: 0-6 AO:83 Baud rate =300 bps, =600 bps, 3=00 bps, 4=400 bps, 5=4800 bps, 6=9600 bps, 7=900 bps, 8=38400 bps, 9=57600 bps, 0=500 bps AO:84 Data format 0=7 bitseven parity, =8 bitsno parity, =8 bitseven parity UINT6 R UINT6 R UINT6 R UINT6 R UINT6 R AO:85 Flow control 0=no flow control =software (XONXOFF =hardware (CTS UINT6 R AO:86 RTS mode 0=not used, UINT6 R =RTS is permanently asserted =RTS is asserted during the transmission AO:87 ASCII compatibility mode 0=disabled, =enabled UINT6 R Format 0 is not allowed in DNP3.0 33

34 Object:V ar. Object:P oint Description OptionsRange Units Type R Device Options Setup 40: (read 4: (write AO:9 Power calculation mode 0=using reactive power: S=f(P,Q, =using non-active power: Q=f(S,P 40: (read 4: (write 40: (read 4: (write 40: (read 40: (read 4: (write 40: (read 4: (write 40: (read 40: (read 4: (write AO:93 Energy roll value E 0= 0 4, = 0 5, = 0 6, 3= 0 7, 4= 0 8, 5=x0 9 UINT6 R UINT6 R AO:94 Phase energy calculation mode E 0=disabled, =enabled UINT6 R AO:03 Starting voltage, percent of FS voltage UINT6 R Default.5 AO:95- AO:0 Reserved UINT6 R Read as AO:0 Energy LED test mode E 0=disabled, =h test, =varh UINT6 R LED pulse rate is 0,000 test pulseskh AO:04- AO:05 Reserved UINT6 R Read as AO:06 Device resolution (see Section 4 for details 0 = Low resolution, = High UINT6 R Default 0 resolution 34

35 3.9 DNP Protocol Setup Object:V ar. Object:Point Description OptionsRange Units Type R DNP Options Setup 40: (read 4: (write AO:3 Default Binary Input Static object variation F3 (default=0 UINT6 R 40: AO:33 Reserved Read as UINT3 R (read 40: AO:34 Default Binary Counter object variation F3 (default=3 UINT6 R (read 4: (write 40: (read 4: (write 40: (read 40: (read 4: (write 40: (read 40: (read 4: (write 40: (read 4: (write 40: (read 40: (read 4: (write AO:35 Default Frozen Binary Counter object variation F3 (default=4 UINT6 R AO:36:37 Reserved Read as UINT3 R AO:38 Default Analog Input object variation F3 (default=3 UINT6 R AO:39-AO:4 Reserved Read as UINT3 R AO:43 6-bit BC scaling 0= (default, = 0, UINT6 R = 00, 3= 000 AO:44 6-bit AI scaling 0=disabled, =enabled (default UINT6 R AO:45-AO:47 Reserved Read as UINT6 R AO:48 SelectOperate Timeout to 30 (default=0 sec sec UINT6 R 40: AO:49 Multi Fragment Interval 5 to 500 (default=0 ms ms UINT6 R

36 Object:V ar. (read 4: (write 40: (read 40: (read 4: (write 40: (read 4: (write 40: (read 4: (write Object:Point Description OptionsRange Units Type R AO:50-AO:5 Reserved Read as UINT3 R AO:53 Time Sync Period 0 to (default=86400 sec sec UINT3 R AO:54 Voltage scale, secondary volts 60 to 88V (default=44v V UINT6 R AO:55 Current scale, secondary amps 0 to 00 (default CT secondary DNP Class 0 Point Assignments 40:(read 4:(write 40:(read 4:(write 40:(read 4:(write AO:5- AO:54 AO:55- AO:57 AO:45- AO:47 0.A UINT6 R DNP object and variation F4 UINT3 R Start point number Start point number for the selected object UINT3 R Number of points in a range 0-8 UINT6 R DNP Class 0 Point Range DNP Class 0 Point Range DNP Class 0 Point Range 3 4 NOTES: The default variation indicates the variation that is used for requests with qualifier code 06 (variation 0 when no specific variation is requested by a master station. Scaling 6-bit AI objects (see Section..6 lets accommodate 3-bit analog input readings to 6-bit object format. Scaling is enabled by default. It is not applied to 3-bit AI objects (object 30, variations and 3. 3 The Select Before Operate command causes the device to start a timer. The following Operate command must be sent before the value specified by the SelectOperate Timeout expires. 36

SERIES PM172 POWERMETERS COMMUNICATIONS. DNP Communications Protocol REFERENCE GUIDE

SERIES PM172 POWERMETERS COMMUNICATIONS. DNP Communications Protocol REFERENCE GUIDE SERIES PM172 POWERMETERS COMMUNICATIONS DNP3-2000 Communications Protocol REFERENCE GUIDE Every effort has been made to ensure that the material herein is complete and accurate. However, the manufacturer

More information

C191HM POWERMETER AND HARMONIC MANAGER COMMUNICATIONS REFERENCE GUIDE

C191HM POWERMETER AND HARMONIC MANAGER COMMUNICATIONS REFERENCE GUIDE C191HM POWERMETER AND HARMONIC MANAGER COMMUNICATIONS ASCII Communications Protocol REFERENCE GUIDE Every effort has been made to ensure that the material herein is complete and accurate. However, the

More information

Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH

Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH Series PM PLUS Powermeters PMPPMEPMEH SATEC ASCII Communications Protocol eference Guide BG46 ev. A4 Every effort has been made to ensure that the material herein is complete and accurate. However, the

More information

PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH

PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH Installation and Operation Manual BG0425 Rev. A18 LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument

More information

PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH

PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH Installation and Operation Manual BG0425 Rev. A15 LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument

More information

EIG DNP V3.0 Protocol Assignments

EIG DNP V3.0 Protocol Assignments E Electro Industries/G augetech "The Leader in Web Accessed Power Monitoring" EIG DNP V3.0 Protocol Assignments For Futura+ and DM Series Power Monitors Version 1.14 July 15, 2003 Doc # E100-7-03 V1.14

More information

Data Sheet. RISH Master Record %THD

Data Sheet. RISH Master Record %THD Data Sheet %THD Application : measures important electrical parameters & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, active energy

More information

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2 PART 1 PART 2 PRODUCTS 2.01 MANUFACTURERS A. Eaton products B.. C.. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features

More information

Installation and Operating Instructions

Installation and Operating Instructions Energy Division Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems Our commitment. Your advantage. Contents Page 1 Introduction 4 1.1 Measurement Capabilities 5 1.2

More information

EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1. Three phase multifunction din rail energy meter

EASTRON SDM630MCT-RJV / SDM630MCT-RJA User Manual V1.1. Three phase multifunction din rail energy meter SDM630MCT-RJV-333mV SDM630MCT-RJA-00mA Three phase multifunction din rail energy meter Plug-in solution; labor saving; wiring mistake free Measures kwh KVarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, THD,etc.

More information

E50 MODBUS POINT MAP

E50 MODBUS POINT MAP E50 MODBUS POINT MAP The E50C2 Full Data Set (FDS) features data outputs such as demand calculations, per phase VA and VAR, and VAh VARh accumulators. The E50C3 Data Logging model adds configuration registers

More information

Installation Instructions and Reference Handbook. Installation instructions

Installation Instructions and Reference Handbook. Installation instructions Installation Instructions and Reference Handbook Multi-instrument MIB 7000/7000C/7020 4189320016B (UK) DEIF A/S Product information Installation instructions Basic operation DEIF A/S, Frisenborgvej 33

More information

See notes for calculations 4110 Usage Hours 1 Integer RO Y - Hours YP Usage Minutes 1 Integer RO Y - Minutes 0-59 YP

See notes for calculations 4110 Usage Hours 1 Integer RO Y - Hours YP Usage Minutes 1 Integer RO Y - Minutes 0-59 YP Table of Contents 2 FW Release summary Y Y Y Y Y Y PM RS FW History Y Y Y PM_2 OS FW History Y Y Y PM_2 RS FW History Y Y Y Setup & Status Metering Min Max Demand IO Alarms N N Reset Commands DL System

More information

Metasys Integrator Power Measurement Ltd. Application

Metasys Integrator Power Measurement Ltd. Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date January 19, 2006 APPLICATION NOTE Metasys Integrator Power Measurement Ltd. Application lntroduction Page

More information

ULTRA RAPID POWER QUALITY ANALYZER

ULTRA RAPID POWER QUALITY ANALYZER ULTRA RAPID POWER QUALITY ANALYZER Ultra rapid (cycle by cycle) advanced electrical network analysis Complete network harmonics analysis, up to 63 rd harmonic High visibility, 5 graphic LCD screen with

More information

Contents. Introduction and description Package contents Device identification PM Options... 80

Contents. Introduction and description Package contents Device identification PM Options... 80 Contents 1 Introduction and description Package contents... 77 Device identification... 77 2 Characteristics PM500... 78 Options... 80 3 Installation Front-panel cut-out... 82 Mounting... 82 4 Connections

More information

PowerPlex PowerPlex. DNP3 Interface Option Manual. June 15, 2010 ML0009 Document Revision C 2010 by Bitronics, LLC

PowerPlex PowerPlex. DNP3 Interface Option Manual. June 15, 2010 ML0009 Document Revision C 2010 by Bitronics, LLC PowerPlex PowerPlex DNP3 Interface Option Manual June 15, 2010 ML000 Document Revision C 2010 by ronics, LLC -S530 (formerly DOS53) RS-232C DNP3 Protocol -S540 (formerly DOS54) RS-45 DNP3 Protocol Firmware

More information

Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems

Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems Tyco Electronics UK Limited Crompton Instruments Freebournes Road, Witham, Essex, CM8 3AH, UK Tel: +44 1376 509 509

More information

DNP V3.00 LEVEL 2 Protocol Assignments

DNP V3.00 LEVEL 2 Protocol Assignments Electro Industries / GaugeTech "The Leader in Power Monitoring and " DNP V3.00 LEVEL 2 Protocol Assignments For Nexus 1252, 1262, 1272 and 1500 Power Monitors Doc # E107709 Revision 1.1, 20 Electro Industries/GaugeTech

More information

Soluciones! Para el ahorro y control de la energía eléctrica. Distribuidor autorizado:

Soluciones! Para el ahorro y control de la energía eléctrica. Distribuidor autorizado: Soluciones! Para el ahorro y control de la energía eléctrica Distribuidor autorizado: Series PM174 Powermeter and Power Quality Analyzer Installation and Operation Manual BG0411 Rev. A2 LIMITED WARRANTY

More information

TAS APFC Controller / Load Managers with MOD-BUS Interface

TAS APFC Controller / Load Managers with MOD-BUS Interface TAS APFC Controller / Load Managers with MOD-BUS Interface Designed & Prepared by TAS PowerTek Pvt. Ltd., W-61, MIDC Ambad, Nasik-422010, India. Updated on: 4th June 2017, Sunday. Data Parameter Field

More information

ELECTRICAL VARIABLE ANALYZER RELAY EVAR

ELECTRICAL VARIABLE ANALYZER RELAY EVAR ELECTRICAL VARIABLE ANALYZER RELAY EVAR 1 ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this

More information

ezpac Operation Manual

ezpac Operation Manual ezpac SA300 Series SUBSTATION AUTOMATION UNIT SA310/SA320/SA330 Operation Manual BG0346 Rev. A5 Chapter 1 Introduction Controls and Indicators LIMITED WARRANTY The manufacturer offers the customer a 24-month

More information

ENGLISH 3 Phase Multi-function Power Meter 1/5A MID MID

ENGLISH 3 Phase Multi-function Power Meter 1/5A MID MID Professionally approved products. Datasheet Stock Number: 144-0527 3 Phase Multi-function Power Meter 1/5A MID 96mm² Panel Mounted Power Meter. MID UK Specifications The 144-0527 is a new generation modern

More information

Digital Multifunction Instrument - Rish Master 3440

Digital Multifunction Instrument - Rish Master 3440 Application Rish Master 3440 measures important electrical parameters in 3 phase and single phase etwork & replaces the multiple analog panel meters. It measures electrical parameters like AC current,

More information

MultiComm. DNP3 Protocol Option Manual. June 15, 2010 ML0005 Document Revision C 2010 by Bitronics, LLC

MultiComm. DNP3 Protocol Option Manual. June 15, 2010 ML0005 Document Revision C 2010 by Bitronics, LLC MultiComm DNP3 Protocol Option Manual June 15, 2010 ML0005 Document Revision C 2010 by Bitronics, LLC -S113 (Formerly DOS11.3) RS-232C DNP3 Protocol -S123 (Formerly DOS12.3) RS-45 DNP3 Protocol Firmware

More information

Modular Metering System ModbusTCP Communications Manual

Modular Metering System ModbusTCP Communications Manual Modular Metering System Manual Revision 7 Published October 2016 Northern Design Metering Solutions Modular Metering System ModbusTCP 1 Description The multicube modular electricity metering system simultaneously

More information

Centrale de mesure Power Meter PM500 Merlin Gerin

Centrale de mesure Power Meter PM500 Merlin Gerin Notice d'installation et d'utilisation Installation and user manual Centrale de mesure Power Meter PM500 Merlin Gerin 059473_D Introduction and description Package contents c one PM500 power meter with

More information

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics Power Quality Monitor Individual Harmonics measurement upto 56th Harmonics True representation of Voltage & Current waveforms. Phasor Representation of All 3 phases for system analysis Real Time Clock

More information

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49 TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument True RMS measurement User-friendly programing Four different types for optimal specification RS485 interface For 3- or 4-wire connection Compact

More information

Technical Data Sheet AMIK 300 / 301

Technical Data Sheet AMIK 300 / 301 USA SINCE 1936 RELIABILITY BEYOND MEASURE Technical Data Sheet AMIK 300 / 301 LISTED File No. E471457 AMIK AMIK 300 is a compact multifunction instrument with touch screen LCD utility which measures important

More information

745 Transformer Protection System Communications Guide

745 Transformer Protection System Communications Guide Digital Energy Multilin 745 Transformer Protection System Communications Guide 745 revision: 5.20 GE publication code: GEK-106636E GE Multilin part number: 1601-0162-A6 Copyright 2010 GE Multilin GE Multilin

More information

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features:

RISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features: Application : RISH Master 3430 measures important electrical parameters in 3 phase and single phase Network & replaces the multiple analog panel meters. It measures electrical parameters like AC current,

More information

H8238/MCM MODBUS POINT MAP

H8238/MCM MODBUS POINT MAP H8238/MCM MODBUS POINT MAP F O R M A T Int Float R/W NV Description 1 257/258 R/W NV Energy Consumption, kwh, Low-word integer 2 259/260 R/W NV Energy Consumption, kwh, High-word integer Both 257/258 and

More information

4111 Usage Minutes 1 Integer RO Y - Minutes 0-59 Y Y YP

4111 Usage Minutes 1 Integer RO Y - Minutes 0-59 Y Y YP Table of Contents 2 Setup & Status Y Y Y Metering Y Y Y Min Max Y Y Y Demand Y Y Y IO Y Y Y Alarms N N Y Reset Commands Y Y Y DL System Y Y Y Notes Y Y Y 5 Setup & Status 24 Usage Hours 2 Float RO Y -

More information

PM296/RPM096 Power Quality Analyzers. Installation and Operation Manual

PM296/RPM096 Power Quality Analyzers. Installation and Operation Manual PM296/RPM096 Power Quality Analyzers Installation and Operation Manual LIMITED WARRANTY The manufacturer offers the customer an 24-month functional warranty on the instrument for faulty workmanship or

More information

USER S MANUAL EMPOWER POWER METER TRINITY. Empower Operational Manual

USER S MANUAL EMPOWER POWER METER TRINITY. Empower Operational Manual USER S MANUAL EMPOWER POWER METER This document contains the latest technical information about Empower which is a micro-controller based Power meter. The product Empower is sophisticated electronic equipment,

More information

DIRIS A40/A41 RS485 PROFIBUS DP. Operating instructions F GB D I NL E P. SOCOMEC GROUP switching PROTECTION & ups

DIRIS A40/A41 RS485 PROFIBUS DP. Operating instructions F GB D I NL E P. SOCOMEC GROUP switching PROTECTION & ups DIRIS A40/A41 RS485 PROFIBUS DP Operating instructions F GB D I NL E P SOCOMEC GROUP switching PROTECTION & ups 2 DIRIS A20 - Réf. : 536 182 A GB 876_786_A_gb.indd 2 3/04/09 10:50:47 GB Contents PRELIMINARY

More information

MODBUS RS485 SERIAL PROTOCOL

MODBUS RS485 SERIAL PROTOCOL MODBUS RS485 SERIAL PROTOCOL ED39DIN DMM3 VIP39DIN VIP396 SIRIO STAR3 STAR3din VERSION 09 JULY 2004 Modbus SIRIO.doc 09 JULY 2004 Pag.1/22 The STAR3, STAR3 din, VIP396, VIP39din, DMM3, SIRIO and ED39din

More information

Know your energy. Modbus Register Map EM etactica Power Meter

Know your energy. Modbus Register Map EM etactica Power Meter Know your energy Modbus Register Map EM etactica Power Meter Revision history Version Action Author Date 1.0 Initial document KP 25.08.2013 1.1 Document review, description and register update GP 26.08.2013

More information

RISH Master 3440i/3440iDL 0.2S

RISH Master 3440i/3440iDL 0.2S Operating Manual RISH Master 3440i/3440iDL 0.2S as per IEC62053-22 Touch Screen Digital Multi-Function Meter Installation & Operating Instructions Section Contents 1. Introduction INDEX 2. Measurement

More information

PMAC770 Multifunction Power Meter. Installation & Operation Manual V2.0 ZHUHAI PILOT TECHNOLOGY CO., LTD.

PMAC770 Multifunction Power Meter. Installation & Operation Manual V2.0 ZHUHAI PILOT TECHNOLOGY CO., LTD. PMAC770 Multifunction Power Meter Installation & Operation Manual V2.0 ZHUHAI PILOT TECHNOLOGY CO., LTD. Danger and warning! This device can be installed only by professionals. The manufacturer shall not

More information

PEM353. Universal measuring device

PEM353. Universal measuring device 353 Universal measuring device 353_D00335_00_D_XXEN/06.2018 353 Universal measuring device Product description The digital universal measuring device 353 is used to record and display measured quantities

More information

Integra 1560 and 1580 Digital Transducer Systems

Integra 1560 and 1580 Digital Transducer Systems Integra 1560 and 1580 multi function transducers provide high accuracy

More information

815LT Submersible Smart Level Transmitter

815LT Submersible Smart Level Transmitter These instructions provide information for installation, process connection, electrical connection, configuration, operation and maintenance of the 815LT Submersible Smart Level Transmitter. The 815LT

More information

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES) Alpha Series www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters Shunts ALPHA

More information

DIRIS Ap RS485 JBUS/MODBUS COM. Systèmes de Coupure et de Protection Industrial Switching and Protection Systems ON 1

DIRIS Ap RS485 JBUS/MODBUS COM. Systèmes de Coupure et de Protection Industrial Switching and Protection Systems ON 1 DIRIS Ap RS485 JBUS/MODBUS F GB ON 1 D COM I NL E P Systèmes de Coupure et de Protection Industrial Switching and Protection Systems PRELIMINARY OPERATIONS NB: For personnel and product safety please read

More information

PM-PA/PM-PAC POWER ANALYZER

PM-PA/PM-PAC POWER ANALYZER PM-PA/PM-PAC POWER ANALYZER 1. INTRODUCTION Power Analyzer is an ideal device to control measure and monitor all electrical parameters of a system. Thanks to its four display rows, all parameters can be

More information

DIRIS A40/A41 RS485 PROFIBUS DP COM. Operating instructions. PROFIBUS Certification

DIRIS A40/A41 RS485 PROFIBUS DP COM. Operating instructions. PROFIBUS Certification DIRIS A40/A41 RS485 PROFIBUS DP Operating instructions F GB D I NL E P ON 1 COM PROFIBUS Certification SOCOMEC GROUP SWITCHING PROTECTION & UPS Systèmes de Coupure et de Protection Industrial Switching

More information

Know your energy. Modbus Register Map EB etactica Power Bar

Know your energy. Modbus Register Map EB etactica Power Bar Know your energy Modbus Register Map EB etactica Power Bar Revision history Version Action Author Date 1.0 Initial document KP 25.08.2013 1.1 Document review, description and register update GP 26.08.2013

More information

Operating Guide October 2006

Operating Guide October 2006 Operating Guide October 2006 Safety 1 Safety This manual represents your meter as manufactured at the time of publication. It assumes standard software. Special versions of software may be fitted, in which

More information

Line-to-line RMS Volts, 3 phases 4 digits (XXX.X) Volts

Line-to-line RMS Volts, 3 phases 4 digits (XXX.X) Volts digital ac POWER MONITOR DESCRIPTION The DSP is a three-phase, three-element multifunction digital transducer with outputs for voltage, current, and power via serial communication. Applications include

More information

DNP V3.00 Protocol Assignments

DNP V3.00 Protocol Assignments Electro Industries / GaugeTech "The Leader in Web Accessed Power Monitoring and Control" DNP V3.00 Protocol Assignments For Nexus 1250, 1260 and 1270 Power Monitors Revision 1.7 November 14, 2007 Doc #

More information

Energy Division

Energy Division Energy Division http://energy.tycoelectronics.com Installation and Operating Manual Integra 1560 and 1580 Digital Metering and Transducer Systems Tyco Electronics UK Limited Crompton Instruments Freebournes

More information

COMMUNICATION MODBUS PROTOCOL MFD44 NEMO-D4Le

COMMUNICATION MODBUS PROTOCOL MFD44 NEMO-D4Le COMMUNICATION MODBUS PROTOCOL MFD44 NEMO-D4Le PR129 20/10/2016 Pag. 1/21 CONTENTS 1.0 ABSTRACT... 2 2.0 DATA MESSAGE DESCRIPTION... 3 2.1 Parameters description... 3 2.2 Data format... 4 2.3 Description

More information

Bulletin 1403 Ethernet Communications Card

Bulletin 1403 Ethernet Communications Card Installation Instructions Bulletin 1403 Ethernet Communications Card (Catalog Number 1403-NENET) 1 Bulletin 1403 Ethernet Communications Card Important User Information Because of the variety of uses for

More information

POWER QUALITY AND REVENUE METER EM920. Operation Manual. BG0482 Rev. A4

POWER QUALITY AND REVENUE METER EM920. Operation Manual. BG0482 Rev. A4 POWER QUALITY AND REVENUE METER EM920 Operation Manual BG0482 Rev. A4 LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship or parts

More information

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters RI-F200 Series Single and Three Phase Multifunction Energy Meter DIN 96 panel mounted -/1A or -/5A current transformer input Single phase or three phase network compatible Programmable voltage and current

More information

DEIF A/S. Description of options. Option H3 Serial communication Profibus DP Multi-line 2 version 2. Description of option. Functional description

DEIF A/S. Description of options. Option H3 Serial communication Profibus DP Multi-line 2 version 2. Description of option. Functional description Description of options Option H3 Serial communication Profibus DP Multi-line 2 version 2 4189340279I SW 2.42.X Description of option Functional description DEIF A/S Parameter table Data tables DEIF A/S,

More information

ASCO 5210 Digital Power Meter. Operator s Manual DANGER

ASCO 5210 Digital Power Meter. Operator s Manual DANGER Operator s Manual ASCO 5210 Digital Power Meter TABLE OF CONTENTS section-page INTRODUCTION General Information... 1-1 Measurements... 1-2 Specifications... 1-3 Device Ratings... 1-4 INSTALLATION Mounting...

More information

Modbus communication module for TCX2: AEX-MOD

Modbus communication module for TCX2: AEX-MOD Modbus communication module for TCX2: Communication Specification TCX2 is factory installed in TCX2 series controllers with -MOD suffix, and is also available separately upon request for customer installation

More information

PM 305 Operating Guide

PM 305 Operating Guide PM 305 Operating Guide Northern Design PREFACE PM305 Operating Guide Revision 2.05 October 2000 This manual represents your meter as manufactured at the time of publication. It assumes standard software.

More information

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

CHAPTER AC DRIVE PARAMETERS. In This Chapter... CHAPTER AC DRIVE 4 PARAMETERS In This Chapter... GS2 Parameter Summary....................4 2 Detailed Parameter Listings.................4 11 Motor Parameters........................4 11 Ramp Parameters.........................4

More information

InfraStruXure Manager v4.x Addendum: Building Management System Integration

InfraStruXure Manager v4.x Addendum: Building Management System Integration InfraStruXure Manager v4.x Addendum: Building Management System Integration Introduction This addendum explains the integration of the APC InfraStruXure Manager Appliance with a Building Management System

More information

PMC-53A. Intelligent Multifunction Meter User Manual Version: V1.0A

PMC-53A. Intelligent Multifunction Meter User Manual Version: V1.0A PMC-53A Intelligent Multifunction Meter User Manual Version: V1.0A January 16, 2017 This manual may not be reproduced in whole or in part by any means without the express written permission from CET Inc.

More information

Energy Management. Type WM14 DIN Advanced version. Product Description 3-phase advanced power analyzer with integrated programming

Energy Management. Type WM14 DIN Advanced version. Product Description 3-phase advanced power analyzer with integrated programming Energy Management Type WM14 DI version Protection degree (front): IP40 2 digital outputs 16 freely configurable alarms with OR/AD logic linkable with up to 2 digital outputs RS422/485 serial output (MODBUS-RTU),

More information

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT. MODBUS/BECO2200-M3425A Communication Data Base for M-3425A Integrated Protection System Device I.D. = 150 Specifications presented herein are thought to be accurate at the time of publication but are subject

More information

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features: (With All Display Parameters) Application : RISH EM 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network

More information

INTELLIGENT DIGITAL MULTI POWER METER [DIC-MPM]

INTELLIGENT DIGITAL MULTI POWER METER [DIC-MPM] Feature Suit for LV/ HV voltage system Compact design with all real-time measurement Consist of basic unit and optional modules 10 years back-up of integrated energy data Large LCD, high brightness High

More information

53U MULTI POWER MONITOR OPERATING MANUAL MODEL 53U CONTENTS. (4 digital displays)

53U MULTI POWER MONITOR OPERATING MANUAL MODEL 53U CONTENTS. (4 digital displays) OPERATING MANUAL MULTI POWER MONITOR (4 digital displays) MODEL 53U 53U CONTENTS BEFORE USE... 2 POINTS OF CAUTION... 2 LIGHTNING SURGE PROTECTION... 2 COMPONENT IDENTIFICATION... 3 INSTALLATION... 4 TERMINAL

More information

Technical Data Sheet

Technical Data Sheet Technical Data Sheet parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters. Special Features Pulse/Limit Switch output (optional) Number of interruption Application

More information

Multi-functional Power Meter DPM-C530A User Manual.

Multi-functional Power Meter DPM-C530A User Manual. Multi-functional Power Meter DPM-C530A User Manual www.deltaww.com Table of Contents 1. Preface 2 2. Notes 3 2.1 Safety Notes 3 2.2 Installation Environment 4 3. Descriptions of Parts 5 3.1 Operating Interface

More information

RISH Master 3430 DIGITAL MULTI-FUNCTION TRANSDUCER. Electro-Meters

RISH Master 3430 DIGITAL MULTI-FUNCTION TRANSDUCER. Electro-Meters measures important electrical parameters in phase and single phase etwork & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, Power, Energy

More information

Ceiec Electric Technology

Ceiec Electric Technology PMC-630 E Advanced Multifunction Ethernet Meter User Manual Version: V1.0A 07/03/2013 Ceiec Electric Technology This manual may not be reproduced in whole or in part by any means without the express written

More information

TNM96-ETL Energy Meter & Electrical Powermeter

TNM96-ETL Energy Meter & Electrical Powermeter TNM96-ETL Energy Meter & Electrical Powermeter Celsa Messgeräte GmbH Barthelsmühlring 16, 76870 Kande - Germany Telefon: +49 7275 9883-0; Telefax: +49 7275 9883-33 Web: www.celsagermany.com; E-Mail: info@celsagermany.com

More information

Multifunction network analyzer Q15U Q96U2L - Q96U4... Q15E Q96E MCU - MCUH Programmable transducer MCUU

Multifunction network analyzer Q15U Q96U2L - Q96U4... Q15E Q96E MCU - MCUH Programmable transducer MCUU Multifunction network analyzer Q15U2... - Q96U2L - Q96U4... Q15E2... - Q96E2... - MCU - MCUH Programmable transducer MCUU OPERATING MANUAL Ipm0163.8 - Edition 06.09 Langer Messtechnik GmbH Soyerhofstrasse

More information

POWER QUALITY AND REVENUE METER EM720/EM720T. Operation Manual. BG0451 Rev. A1

POWER QUALITY AND REVENUE METER EM720/EM720T. Operation Manual. BG0451 Rev. A1 POWER QUALITY AND REVENUE METER EM720/EM720T Operation Manual BG0451 Rev. A1 LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship

More information

AMIK 200 / 201 Technical Data Sheet

AMIK 200 / 201 Technical Data Sheet AMIK 200 / 201 Technical Data Sheet AMIK Special Features MODBUS (RS-485) Communication available only on Amik 201 On site Programmable CT/PT Ratios User selectable CT Secondary 1A/5A User selectable PT

More information

Monitoring Electric Network Via Internet

Monitoring Electric Network Via Internet Monitoring Electric Network Via Internet NETWORK ANALYSER let "it" analyse! MPR63 Real time monitoring via internet / intranet Measurement of all electrical parameters Including Harmonics Automatic recording

More information

Conzerv EM6400NG series

Conzerv EM6400NG series Conzerv EM6400NG series Multi-function power & energy meters Technical datasheet PB115131 Introducing EM6400NG, next generation power meters of iconic EM6400 series with innovative Accurate measurements

More information

Application Note Assigning and Reducing the DNP V3.0 Points List on the ABB PCD Timothy S. Fahey, PE

Application Note Assigning and Reducing the DNP V3.0 Points List on the ABB PCD Timothy S. Fahey, PE Application Note Assigning and Reducing the DNP V3.0 s List on the ABB PCD Timothy S. Fahey, PE Introduction This document defines a subset of the full points list given in the DNP 3.0 Implementation Details

More information

OHIO SEMITRONICS, INC. DIGITAL AC POWER MONITOR OSI SPECIFICATIONS

OHIO SEMITRONICS, INC. DIGITAL AC POWER MONITOR OSI SPECIFICATIONS DIGITAL AC POWER MONITOR DESCRIPTION The DSP is a three-phase, three-element multifunction digital transducer with outputs for voltage, current, and power via serial communication. Applications include

More information

Micro Motion Model 1700 Transmitters with Analog Outputs 1700***A. Configuration and Use Manual Supplement. Configuration Operation Maintenance

Micro Motion Model 1700 Transmitters with Analog Outputs 1700***A. Configuration and Use Manual Supplement. Configuration Operation Maintenance P/N MMI-20015780, Rev. AA September 2009 Micro Motion Model 1700 Transmitters with Analog Outputs Configuration and Use Manual Supplement 1700***A Configuration Operation Maintenance Micro Motion customer

More information

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters Technical Data Sheet Alpha 20 Alpha 20 is a compact multifunction instrument which Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel

More information

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613 Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613 Data Bulletin 0613IB1201 06/2012 Retain for future use. 0613IB1201 Modbus Communications System for Micrologic A, P, and H

More information

SERIAL COMMUNICATION PROTOCOL WM24-96 V1 R0 WM Vers. 1 Rev. 0. January 3 rd, 2006

SERIAL COMMUNICATION PROTOCOL WM24-96 V1 R0 WM Vers. 1 Rev. 0. January 3 rd, 2006 Page 1 Vers. 1 Rev. 0 January 3 rd, 2006 Page 2 Index INDEX...2 1...3 1.1 INTRODUCTION...3 1.2 FUNCTIONS...3 1.3 MEMORY AREA...5 1.4 IDENTIFICATION CODE...5 2 RAM VARIABLES MAP...6 2.1 INSTANTANEOUS VARIABLES

More information

Instruction Sheet UPS SERIES. Serial Control Protocol. I Rev E

Instruction Sheet UPS SERIES. Serial Control Protocol. I Rev E Instruction Sheet UPS SERIES Serial Control Protocol I-00341 Rev E (THIS PAGE INTENTIONALLY LEFT BLANK) Page 1 TABLE OF CONTENTS 1 Protocol Overview...3 1.1 Signal characteristics...3 1.2 Primary DB9 Pin

More information

Ziegler EM 1320/30/40

Ziegler EM 1320/30/40 Ziegler EM 1320/30/40 Operating Manual Ziegler EM 1340 2-60-006-00-00483_Rev. C - 9/2014 www.ziegler-instruments.com 1 36 DIGITAL MULTIFUNCTION INSTRUMENT Programmable Multi-function Energy Meter Installation

More information

Delta Din-rail Power Meter DPM-D520I User Manual.

Delta Din-rail Power Meter DPM-D520I User Manual. Delta Din-rail Power Meter DPM-D520I User Manual www.deltaww.com Table of Content 1. Preface 4 2. Notes 5 2.1 Safety Notes 5 2.2 Installation Environment 6 3. Descriptions of Parts 7 3.1 Operating Interface

More information

Interface Description A2000. Multifunctional Power Meter Communications Protocol per DIN Draft /2.15

Interface Description A2000. Multifunctional Power Meter Communications Protocol per DIN Draft /2.15 Interface Description A2000 Multifunctional Power Meter Communications Protocol per DIN Draft 19244 3-349-125-03 14/2.15 1 Overview of Telegrams (Commands) to the A2000 per DIN Draft 19244...4 2 Telegram

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

Energy Management Three-phase energy meter with output modules Type EM4-DIN

Energy Management Three-phase energy meter with output modules Type EM4-DIN Energy Management Three-phase energy meter with output modules Type EM4-DIN Class 1 (active energy) Class 2 (reactive energy) Three-phase multi-function energy meter Back-lighted LCD display 3 1 / 2 DGT

More information

815PT Smart Pressure Transmitter

815PT Smart Pressure Transmitter 815PT Smart Pressure Transmitter General Instructions These instructions provide information for installation, process connection, electrical connection, configuration, operation and maintenance of the

More information

Energy Management Energy Meter Type EM21 72R Retro-Fit

Energy Management Energy Meter Type EM21 72R Retro-Fit Energy Management Energy Meter Type EM21 72R Retro-Fit Including 3 miniature split-core current sensors 10mm (90A), 16mm (150A) and 24mm (250A) diameter holes Class A (kwh) according to EN50470-3 Class

More information

Power analyzers and Energy Meters Power Analyzer Type WM14-DIN

Power analyzers and Energy Meters Power Analyzer Type WM14-DIN Power analyzers and Energy Meters Power Analyzer Type WM14-DIN Optional RS422/485 serial port Alarms (visual only) V LN, An Class 2 (active energy) Class 3 (reactive energy) Accuracy ±0.5 F.S. (current/voltage)

More information

Power analyzers and Energy Meters Power Analyzer Type WM14-96

Power analyzers and Energy Meters Power Analyzer Type WM14-96 Power analyzers and Energy Meters Power Analyzer Type WM14-96 Optional RS422/485 serial port Alarms (visual only) V LN, An Class 2 (active energy) Class 3 (reactive energy) Accuracy ±0.5 F.S. (current/voltage)

More information

Energy Management Energy Meter Type EM340

Energy Management Energy Meter Type EM340 Energy Management Energy Meter Type EM340 Digital input (for tariff management Easy connection or wrong current direction detection Certified according to MID Directive (option PF only: see how to order

More information

E.S.A.M. unicenter s.r.l.

E.S.A.M. unicenter s.r.l. RS485 serial interface ESAM protocol The Network Analyzers Exx00 can communicate with three protocols : - MODBUS RTU (see specific manual) - ESAM (proprietary protocol, described in this manual) - METASYS

More information

SUPPLY NETWORK ANALYZER CVM-96 SERIES

SUPPLY NETWORK ANALYZER CVM-96 SERIES SUPPLY NETWORK ANALYZER CVM-96 SERIES (Power Demand) INSTRUCTION MANUAL ( M 981 326 / 00B - GB) (c) CIRCUTOR S.A. ----- Supply network analyzer CVM-96 ------ User's manual --- Page No. 1 CVM-96 SUPPLY

More information

Commissioning Instructions Rev. 03

Commissioning Instructions Rev. 03 Power Factor regulator BLR-CM-T/RT L1 L2 L3 Einspeisung Supply Last Load BLR-CM-T + - Triggereingang/ Triggerinput BEL-TSXX N PE L1 L2 L3 Einspeisung Supply Last Load BLR-CM-RT + - Triggereingang/ Triggerinput

More information