1000Vac distribution system for Signalling System applications

Size: px
Start display at page:

Download "1000Vac distribution system for Signalling System applications"

Transcription

1 1000Vac distribution system for Signalling System applications

2

3 System for Transforming, Carrying and Distributing 1000Vac electric energy for technological equipment and devices along the railway line. This system allows to implement a distribution system that can be supplied from either ends (without distinction), but with sources which can never be paralleled. The main components of the distribution system being dealt with are the following: Station A 400Vac/1000Vac step-up transformer; Station B 400Vac/1000Vac step-up transformer; Three-core cable for 1000Vac distribution backbones; 1000Vac/400Vac step-down transformers for serving IS/ Aut/TLC lineside systems with input-output configuration present in peripheral locations. Each step-up transformer in the stations is supplied by the essential switchboards set after the UPS unit (SIAP IS 732D or pre-existing power supply system). Below is shown a synoptic single line diagram of the 1000Vac distribution line between two generic stations A and B in the assumption that (for instance) between the two stations there exist N peripheral locations. The need for running the system with at least one sectioning point open results from the fact that it must not be possible to parallel the essential distributions (UPS) of the two stations (A and B) in which are fitted the step-up transformers. The input-output configuration on the step-down transformer allows to supply the transformer from either side (right or left). 1000Vac line reconfiguration after a failure can be performed via manual commands or via automatic procedures which restore the system by making use of the backup energy provided by the system auxiliary services. Such operations can be managed locally, as well as remotely in manual mode by personnel qualified to remote control. If load arrangement reconfiguration on the 1000Vac line can be planned and is not linked to the effects of automatic reconfigurations after a failure, then it will be possible to manage the shutdown (via terminal block contacts), on those pieces of equipment which require this operation before the powering off and restarting (bootstrap) procedures. 3

4 1000V distribution in Italian Signalling Systems (SS) 1000V distribution in SS systems in Italy has historically been managed via (not distributed) neutral connected to the ground. Based on overhead line electrification characteristics, the two cases described below there result. 1000Vac distribution with 3kVdc overhead line electrification In railway lines electrified with direct current (3kVdc), distribution is of TT type; consequently: step-up transformer secondary winding star centre is connected to station grounding system; step-down transformer ground points are connected to the centre of the inductive connections which are connected to rails; the screen of the distribution cable between two 1000V transformers (step-up - step-down transformer or stepdown - step-down transformer) is connected to ground from one end only in order to prevent current circulation inside transformers and most of all in the screen of the 1000Vac cable. In first earth fault conditions (on either the cable or transformers): voltage on ground points has a value which is very close to the nominal value of ground system voltage (1000Vac/1,73 = 580Vac) whereas fault currents feature an extremely low value that can only be identified by using a differential relay. 1000Vac distribution with 25kVdc overhead line electrification In railway lines electrified with alternate current (25kVac), distribution is of TN-S type; consequently: step-up transformer secondary winding star centre is connected to station grounding system which is connected to the buried linear ground plate laid along railway line; step-down transformer ground points are connected to the linear ground plate which is connected to the track via inductive connections; the screen of the distribution cable between two 1000V transformers (step-up - step-down transformer or stepdown - step-down transformer) is connected to ground at both ends. In first earth fault conditions (on either the cable or transformers): voltage on ground points has a value which is equal to a fraction of the ground system voltage whereas fault currents feature a high value which - although not sufficient to trigger the over-current relay of the circuit-breaker protecting the 1000Vac line - is however more than sufficient for safe triggering of a differential relay. 4

5 Characteristics of the proposed system: IT distribution system and 1000Vac transformers in Class II In conventional systems the use of differential relays leads to risks of untimely releases due to indirect overvoltages mainly from atmosphere; such overvoltages may generate unbalanced pulse capacitive currents; these cases are rather frequent when the line is geographically wide. Proposed solution redefines the neutral point connection and the protection system against indirect contacts: in particular, this solution removes the problems in the best way by means of distribution systems with insulated neutral (IT) for managing the 1000Vac cable line and provides also step-up and step-down transformers in Class II with SELV type auxiliaries. An IT system provides for: transformer secondary winding star centre to be insulated from the ground; no ground point for step-up or step-down transformer as defined for Class II; screen of the distribution cable between two 1000V transformers (step-up - step-down transformer or step-down - step-down transformer) to be connected to ground from one end in 3 kvdc environment, or at both ends if in 25 kvac environment. In first earth fault conditions (on the cable), armor voltage has a value which is extremely low due to the extent of both the stray capacities of ground wires and the ground resistance at the screen ground connection point. Apart from system coordination, the first earth fault can persist with no time limit since power supply cut off is not required. Timely fault removal is however recommended in order to prevent that the occurrence of a second fault will cause power supply cut off. As concerns safety, this system does not therefore require that differential relays are used; consequently, the hazard of untimely releases is totally removed. This solution, consisting of QD400/1000 station Step-up Transformers and corresponding QD1000/400 line Step-down transformers, is used to supply line peripheral locations dedicated to manage individual devices and/or equipment like BA, RSC, Bca/M, PLL and RTB/RTR; this choice allows to confirm in advance that results expected in terms of reliability and consequently of working continuity will be high; these results will be more significant in line sections geographically characterized in unfavourable electrical conditions. In connection with the technical specifications in force at the present date, and in connection with improvements requested by the various circular letters, a power supply system has been implemented for 1000Vac lines with insulated neutral point connection (IT) and Class II transformers suitable to implement, among other things, an adequate partitioning barrier suitable to supply the electrical loads set downstream under Protection by Electrical Separation. Particularly remarkable is the 1000Vac energy distribution system managed with insulated neutral point connection and Tx and Rx transformer, since it results to be extremely immune to any line overvoltages, thereby improving considerably required service stability, safety and continuity. Further, as it is easily understood, immunity to noise caused by the proximity to the overhead line electrification system results to be decisive for the quality of service performed by electronic equipment. Line management with TT system and/or 380Vac line management: the right module within a common structure solution It could be required to supply the technological lineside loads with ground and neutral point connection different from the standard IT one (described above), for instance: with TT system. A TT system provides for: transformer secondary winding star centre to be freeearthing connected. differential relay provided on step-up transformer output circuit breaker. screen of the distribution cable between two 1000V transformers (step-up - step-down transformer or step-down - step-down transformer) to be connected to ground from one end in 3 kvdc environment, or at both ends if in 25 kvac environment. In this case, implementing an electrical protection system, suitable for operating under the abovementioned wires and grounds operating conditions, will provide for the following: Circuit breaker module fitted with differential relay; Transformer module electrical connection between stepup transformer secondary winding star centre and earth These interventions are minimal and do not involve changes to the fixed transformer structure which has been designed for all of the case histories known at present, thereby enabling friendly upgrades on site. Should it be required to carry out interventions on obsolete operating lines characterised by non-high nominal voltage due to the limited geographical extension of the line then, it will be possible to manage line 380/400Vac voltage by simply providing a proper transformer module with a different ratio of transformation, with no intervention on the fixed transformer structure. Main components V circuit breakers for step-up transformer outlets; V circuit breakers for step-down transformers; 3. Low voltage / low voltage transformers; 4. Parameters for setting 1000 [Vac] lines protections (like for instance short circuit current at end of line, 1kV transformers connection data to line section switchgear, neutral point connection, etc.). 5

6 400/1000 Vac step-up transformer It is the transformer which is generally installed at the station; its task is to raise the voltage dedicated to the line. Step-up transformer is a unit: in Class II as to 400 Vac low voltage circuits; in Class II as to 1000 Vac low voltage circuits; in Class III as to 24 Vdc safety extra-low voltage (SELV) circuits. This allows to create a suitable separation barrier between electrical systems managed with different neutral point connections (before and after the transformer) and to safely supply the equipment (transformer input circuits) in IT, or with Electrical Separation if required. Therefore, implementing Class II for some transformer circuits in the presence of metal structural work, implies: that double or reinforced insulation is not assigned to an insulating chassis; that parts inside the transformer have solid insulation, in air and of reinforced surface type towards metal structural work and that consequently metal structural work does not result to be classified as a ground point; that interior parts are provided with suitable mechanical protections aimed at not thwarting, during time, above indicated increased insulation. General characteristics Product name : 400/1000 step-up transformer Power supply Nominal input voltage: 400Vac, three-phase Nominal output voltage: 1.000Vac, three-phase Output voltage regulation steps: Nominal sizes [kva]: 1, Impulse voltage: 400Vac side: kv, 1000Vac side: 20 kv Mechanical characteristics Dimensions [l, h, d] [mm]: 900, 2.170, 785 Materials used: aluzinc steel Environmental and climatic characteristics IP rating: 21 Working temperature [C] : Storage temperature [ C] : Height: max 2,000m above sea level Relative humidity: 90% without condensate Diagnostics PLC Standards Complying with: EN1439, EN0950, EN0529. Availability, reliability and maintainability Maximum MTTR [h]: 30 Safety SIL level : 0 Single line diagram

7 Vdc auxiliary circuit-breaker module 2. Diagnostic (PLC), control and HMI module Vac circuit-breaker (after transformer) Vac circuit-breaker (at transformer input) 5. Ground switch disconnector. Voltage transformer and polling contactor /1000Vac three-phase step-up transformer 8. Terminal block compartment for line cable connection 7

8 1000/400 Vac step-down transformer It is the transformer which is generally installed on the line; its task is to adapt voltage coming from the line to industrial use parameters (230/400Vac, three-phase). Step-down transformer is a unit: in Class II as to 400 Vac low voltage circuits; in Class II as to 1000 Vac low voltage circuits; in Class III as to 24 Vdc safety extra-low voltage (SELV) circuits. This allows to create a suitable separation barrier between electrical systems managed with different neutral point connections (before and after the transformer) and to safely supply the equipment located after the transformer in Electrical Separation. Therefore, implementing Class II for the transformer circuits in the presence of metal structural work, implies: that double or reinforced insulation is not assigned to an insulating chassis; that parts inside the transformer have solid insulation, in air and of reinforced surface type towards metal structural work and that consequently metal structural work does not result to be classified as a ground point; that interior parts are provided with suitable mechanical protections aimed at not thwarting, during time, above indicated increased insulation. General characteristics Product name : 1000/400 Vac step-down transformer Power supply Nominal input voltage: 1000Vac, three-phase Nominal output voltage: 400Vac, three-phase Output voltage regulation steps: Nominal sizes [kva]: 1, Impulse voltage: 400Vac side: kv, 1000Vac side: 20 kv Mechanical characteristics Dimensions [l, h, d] [mm]: 900, 2.170, 785 Materials used: aluzinc steel Environmental and climatic characteristics IP rating: 21 Working temperature [C] : Storage temperature [ C] : Height: max 2,000m above sea level Relative humidity: 90% without condensate Diagnostics PLC Standards Complying with: EN1439, EN0950, EN0529. Availability, reliability and maintainability Maximum MTTR [h]: 30 Safety SIL level : 0 Single line diagram

9 Vdc auxiliary circuit-breaker module 2. Diagnostic (PLC) and control module Vac circuit-breaker (before transformer) Vac circuit-breaker (input/output) Vac circuit-breaker (output/input). Ground switch disconnector module 7. Battery charger module /400Vac three-phase step-down transformer 9. Terminal block compartment for line cable and battery connections 9

10 1000Vac line drive and control system The implemented 1000Vac line drive and control technological system is a real added value for this system of electrical energy distribution to technological lineside equipment and devices. The PLC installed in step-down transformers acts as concentrator of the relevant diagnostic info and data and controls the local logic functions. The same function is run also by the PLCs installed in step-up transformers which in addition are charged with the following roles: line manager, data concentrator of all the relevant transformers, diagnostic front-end to remote supervision system (Scada D&M). Communication architecture between PLCs provides TCP-IP (Modbus) network connection to be implemented in optical fibre(preferably) according to overvoltage protection matters issued by the latest RFI directions. The drive and control system implements several functions among which the main ones are the following: displaying the 1000Vac line energization state and diagnostic details of each transformer connected to it, on the HMI terminal provided on step-up transformers; executing single remote commands; managing insulation control between active wires and ground of the 1000Vac line (if the line is managed with neutral point connection and IT type grounds); option to run troubleshooting on 1000Vac line via remote control manual procedure or, via automatic procedure managed autonomously by the step-up transformer PLC which will identify the line section in failure and will provide to run automatic line reconfiguration isolating the failing section and supplying the step-down tran- sformers from line sections not involved in the failure. The identification procedure of the section in failure and the consequent reconfiguration of the circuit will be performed after Operator s confirmation if the 1000Vac line is managed with neutral point connection and IT type grounds or, immediately after the failure which has caused its powering-off in case the line is managed with neutral point connection and TT type grounds; automatic line reconfiguration when a live step-up transformer is powered off by its power supply system (set upstream) in order to allow prompt supplying to the technological lineside equipment and devices by the other step-up transformer, thereby restoring all the relevant functions; smart line management suitable to avoid unrequired circuit closing via interlocks on motorized commands and preventing undue manual commands directly on circuit breakers in order to safeguard power supply continuity; Integrated Energy Management (GEI) of line loads suitable to control supplying of non priority electrical loads (like for instance HVAC) in time-sharing thereby reducing the electrical load over the line in case of need; management of the power-off control of those technological equipment and devices that allow for this possibility for a correct shut-down before the intentional reconfiguration of the line, and management of the power-on control of the abovementioned equipment and devices once the reconfiguration procedure is over; management of the insulation control after the stepdown transformer, also in discontinuous control mode, and monitoring of main electrical parameters if choosing power supply of downstream loads with wires and grounds in Electrical Separation operation. 10

11 Property of Ansaldo STS SpA, 2013, all rights reserved. The copying, reproduction and use of this work in any form whatsoever is forbidden without the written authorization of Ansaldo STS SpA.

12 Ansaldo STS SpA Via Paolo Mantovani Genoa Italy

Components Track circuits UM71

Components Track circuits UM71 Components Track circuits UM71 Track circuits UM71 An essential element of railway safety, the track circuit detects the presence or absence of any vehicle on a given stretch of track. Jointless track

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Communication by power line carrier technology. For medium voltage networks

Communication by power line carrier technology. For medium voltage networks CELLULES STEP II CEP14/15 Communication by power line carrier technology For medium voltage networks STEP II - System Presentation Developped for networks 120 V 6,600 Volts including French standards 950

More information

ISOLATING TRANSFORMERS FOR TLC PLANTS

ISOLATING TRANSFORMERS FOR TLC PLANTS ISOLATING TRANSFORMERS FOR TLC PLANTS Isolating transformers for TLC plants The power supply of telecommunication plants and FM/TV relay stations has always entailed numerous problems and specific needs

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

e 2 TANGO-50 Short-Circuit Detector K Data Sheet

e 2 TANGO-50 Short-Circuit Detector K Data Sheet e 2 TANGO-50 Short-Circuit Detector K-31.2.1 Data Sheet We Create Ideas With Power! e 2 TANGO-50 short-circuit detector is a product of ELEKTROMETAL ENERGETYKA SA developed by our engineers with extensive

More information

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and

More information

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information

BAT-Series Grid Inverter. Battery Charger.

BAT-Series Grid Inverter. Battery Charger. BAT-Series Grid Inverter. Battery Charger. With the BAT-series, WSTECH offers a wide range of power converters for small to large energy storage applications. The BAT-series inverters offer a power range

More information

Transformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications

Transformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications Electrical Power Systems PSL2 Investigates the principles and operating characteristics of single-phase and three-phase power and distribution transformers Key Features Educational transformers with fully

More information

Series P. Applications

Series P. Applications Ratings 25 800 VA Voltage Primary 230 / 400 / 460 V range Secondary 6 / 12 V 12 / 24 V 24 / 48 V 115 / 230 V Voltage selection by means of metal connection bridges, offering the full rated power at any

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds

More information

Original operating instructions Fail-safe inductive sensor GM504S / / 2010

Original operating instructions Fail-safe inductive sensor GM504S / / 2010 Original operating instructions Fail-safe inductive sensor GM504S 704070 / 01 06 / 2010 Contents 1 Preliminary note 3 1.1 Explanation of symbols 3 2 Safety instructions 4 2.1 Safety-related requirements

More information

QUINT-PS/ 3AC/24DC/40

QUINT-PS/ 3AC/24DC/40 Primary-switched power supply unit with SFB technology, 3 AC, output current 40 A INTERFACE Data sheet 103133_en_00 1 Description PHOENIX CONTACT - 07/2009 Features QUINT POWER power supply units Maximum

More information

SPAD 346 C Stabilized differential relay

SPAD 346 C Stabilized differential relay SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

PACSystems* RX3i IC695MDL765

PACSystems* RX3i IC695MDL765 March 2011 PACSystems* RX3i IC695MDL765 Digital Output Module with Diagnostics 16-Channel The 24/125 volt DC 2A Smart Digital Output module, IC695MDL765, provides 16 discrete outputs in two isolated groups

More information

SPECIFICATION, CONTROLS AND ACCESSORIES

SPECIFICATION, CONTROLS AND ACCESSORIES AS440 Automatic Voltage Regulator (AVR) SPECIFICATION, CONTROLS AND ACCESSORIES English Original Instructions A043Y697 (Issue 2) Table of Contents 1. DESCRIPTION... 1 2. SPECIFICATION... 3 3. CONTROLS...

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This

More information

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR). RETROFITTING Motor Protection Relay NPM800R (R2 case) and NPM800RE (R3 case) are dedicated to the refurbishment of 7000 series (R2 and R3 cases) of CEE relays providing the protection of medium voltage

More information

Types VIS and CRE. A e. Compliance with Standards. Uses. Features

Types VIS and CRE. A e. Compliance with Standards. Uses. Features Fig. 1 Pure Sine Wave IGBT Controlled CCRs Types VIS and CRE Compliance with Standards FAA: AC 150/5345-10 (current edition), L-828, L-829 except for input voltage ICAO: Aerodrome Design Manual Part 5,

More information

MINI-PS AC/24DC/1.3

MINI-PS AC/24DC/1.3 Power supply unit INTERFACE Data sheet 102894_en_03 1 Description PHOENIX CONTACT 2015-11-17 Features MINI POWER power supplies for MCR technology In measurement and control technology (MCR), modular electronics

More information

MV protection relay. Installation assistance guide. Sepam ranges

MV protection relay. Installation assistance guide. Sepam ranges MV protection relay Installation assistance guide Sepam ranges Series 20 Series 40 Series 80 Sepam 2000 51312779F0 A2 1/60 Contents Aims of the guide... 3 Reference documents... 3 Part I: Generic installation

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing. 1.0 Scope This document describes the specification for Toshiba 1000 Series On-Line Uninterruptible Power System (UPS). The UPS will supply a computer grade AC output sine wave which is unaffected by the

More information

QUINT-PS AC/24DC/40

QUINT-PS AC/24DC/40 Power supply unit INTERFACE Data sheet 102315_en_02 1 Description PHOENIX CONTACT 2010-04-23 Features QUINT POWER power supply units for plant and special engineering reliably start heavy loads with high

More information

Technical catalogue. Emax Low voltage air circuit-breakers. Hotline:

Technical catalogue. Emax Low voltage air circuit-breakers.   Hotline: Technical catalogue Emax Low voltage air circuit-breakers www.alobitanbd.com Hotline: 01711548558 PAGE : 02 The new Emax have received innumerable international certifications and approval by the major

More information

Webinar: An Effective Arc Flash Safety Program

Webinar: An Effective Arc Flash Safety Program Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of

More information

Upgrading Your Electrical Distribution System To Resistance Grounding

Upgrading Your Electrical Distribution System To Resistance Grounding Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding

More information

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units BETA Switching Transformers, Bells and Socket Outlets /2 Product overview /3 4AC3 0, 4AC3 1 bell transformers /5 4AC3 4... 4AC3 transformers for permanent loads /8 4AC2 4 power supply units / 7LQ2 2 bells

More information

MELPRO TM -D Mitsubishi ELectric corporation's PROtection relay for Distribution.

MELPRO TM -D Mitsubishi ELectric corporation's PROtection relay for Distribution. MITSUBISHI Numerical Protection Relay MELPRO TM -D Series MELPRO TM -D Mitsubishi ELectric corporation's PROtection relay for Distribution. Relays suitable for advanced network systems and strongly support

More information

Industrial PSU with universal input voltage range ( VAC line to line) and configurable output voltage. North America

Industrial PSU with universal input voltage range ( VAC line to line) and configurable output voltage. North America World-Wide 3-phase Input Voltage Range (nom. 200 Vrms to 480 Vrms), PF > 0.94 High Power Density 16 W/in 3 94% Typical Efficiency Parallel Operation up to 16 Units (50.4 kw) Cold-Plate Cooling System -25

More information

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web: Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation

More information

SM2000 TECHNICAL DESCRIPTION

SM2000 TECHNICAL DESCRIPTION SM2000 TECHNICAL DESCRIPTION 1 GENERAL DESCRIPTION The SM2000 module is a high frequency switch mode rectifier. It converts the single phase AC line voltage into an isolated DC voltage. It can be used

More information

Complex Solution for the Distribution Substation REF 542plus. Application and Setting Guide

Complex Solution for the Distribution Substation REF 542plus. Application and Setting Guide Complex Solution for the Distribution Substation REF 542plus 1MRS756412 Complex Solution for the Distribution Substation REF 542plus Copyrights The information in this document is subject to change without

More information

SISNet Distance Extenders

SISNet Distance Extenders April 2011 Page 1 Extend the DeltaV SIS remote peer ring with Dedicated safety communications Full communications redundancy Flexibility to meets project needs Consistent update rate Introduction The DeltaV

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

AC/DC Power Supply Series APPLICATION NOTE

AC/DC Power Supply Series APPLICATION NOTE ZMS100 AC/DC Power Supply Series APPLICATION NOTE ZMS100 Application Notes Issue 3 Document Number 260160 Page 1 of 15 Contents Contents... 2 1. INPUT... 3 AC INPUT LINE REQUIREMENTS... 3 2. DC OUTPUT...

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

Transformers, Power Supply Units and Socket Outlets

Transformers, Power Supply Units and Socket Outlets Transformers, Power Supply Units and Socket Outlets /2 Introduction /3 4AC3 bell transformers /4 4AC3 safety transformers /5 4AC2 power supply units /6 5TE6 REG socket outlets For further technical product

More information

Protection Relays. U-MLEs-PLv. Ultra Line. DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 32, 45, 49, 64, 76, 79, 80

Protection Relays. U-MLEs-PLv. Ultra Line. DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 32, 45, 49, 64, 76, 79, 80 Ultra Line DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 3, 45, 49, 64, 76, 79, 80 D.C. Feeder protection relay with setting parameters programmable locally or via serial communication. Suitable

More information

Earthing of Electrical Devices and Safety

Earthing of Electrical Devices and Safety Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This

More information

Protection Relays. U-MLEs-PLv-Ts. Ultra-Ts. DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 32, 45, 49, 64, 76, 79, 80

Protection Relays. U-MLEs-PLv-Ts. Ultra-Ts. DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 32, 45, 49, 64, 76, 79, 80 Ultra-Ts DC SUBSTATION PROTECTIVE RELAY (double voltage Line Test) 32, 45, 49, 64, 76, 79, 80 D.C. Feeder protection relay with setting parameters programmable locally or via serial communication. Suitable

More information

90 ReStart AUTOMATIC RECLOSING DEVICES

90 ReStart AUTOMATIC RECLOSING DEVICES RESTART WITH AUTOTEST Technical data TYPE ReStart with Autotest 2P ReStart with Autotest PRO 2P ReStart with Autotest PRO 4P Electrical characteristics Standards: EN 50557, EN 61008-1 Distribution system:

More information

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of:

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of: 1 PAPER 5 Sample Questions A- C&G 2382 17th Edition Paper A 1 o/c1 BS 7671 does not apply to a equipment of aircraft b photovoltaic systems c marinas d fairgrounds. 2 o/c1 Where protection for persons

More information

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED SECTION 16280 LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED PART 1 - GENERAL 1.1 SUMMARY This specification defines the requirements for active harmonic filter systems in order to meet IEEE-519-2014

More information

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability

More information

PROXIMITY SENSOR TERMINOLOGY

PROXIMITY SENSOR TERMINOLOGY Never use this desk reference for installation or operation of equipment. Refer to manual for installation and operation instructions. The following descriptions refer to the European standard EN 60947-5-2.

More information

Proximity Sensor Terminology

Proximity Sensor Terminology The following descriptions refer to the European standard EN 60947-5-2. of 2007. The specifications given here are intended to be minimum performance values described by the standard. Alignment must not

More information

EMI Installation Guidelines

EMI Installation Guidelines EMI Installation Guidelines Although Red Lion Controls Products are designed with a high degree of immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed

More information

Modbus Register Map: InfraStruXure Symmetra 3-Phase Absolute Starting Register Number, (Decimal)

Modbus Register Map: InfraStruXure Symmetra 3-Phase Absolute Starting Register Number, (Decimal) Modbus Map: InfraStruXure Symmetra 3-Phase 990-3249 // Status Word 0 40000 0 8 Reserved R = UPS ready to provide power to the load upon return of normal line voltage or upon user command = State == Enable

More information

DeltaV SIS Logic Solver

DeltaV SIS Logic Solver DeltaV SIS Process Safety System Product Data Sheet September 2017 DeltaV SIS Logic Solver World s first smart SIS Logic Solver Integrated, yet separate from the control system Easy compliance with IEC

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted

More information

QUINT-PS/ 1AC/24DC/20

QUINT-PS/ 1AC/24DC/20 Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data sheet 103129_en_04 1 Description PHOENIX CONTACT - 02/2010 Features QUINT POWER power supply units Maximum system

More information

02/11/2015

02/11/2015 Emergency stop and safety guard monitoring 1 channel KNAC3-YS Part number 85103035 "Emergency stop" & "Gate monitoring" functions Single channel operation Security with redundancy and feedback circuit

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

Distribution/Substation Transformer

Distribution/Substation Transformer Distribution/Substation Transformer Type VFI, Vacuum Fault Interrupter Transformer Option Functional Specification Guide Functional specification for 15 kv, 25 kv, or 35 kv vacuum fault interrupter distribution/substation

More information

Uncompromising Quality: More Reliability for Single-Phase and Three-Phase Supply Networks

Uncompromising Quality: More Reliability for Single-Phase and Three-Phase Supply Networks Uncompromising Quality: More Reliability for Single-Phase and Three-Phase Supply Networks This is where quality counts twice as much. No wonder, since low-voltage miniature transformers are indispensable

More information

Reference Number PDS 07 (RIC Standard: EP SP)

Reference Number PDS 07 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Reference Number PDS 07 (RIC Standard: EP 12 10 00 20 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Jan 05 Standards

More information

AC/DC Power Supply Series APPLICATION NOTE

AC/DC Power Supply Series APPLICATION NOTE -175 AC/DC Power Supply Series APPLICATION NOTE NV175 Application notes 3.4.doc Document Number 69493 Page 1 of 16 1. INPUT...3 AC INPUT LINE REQUIREMENTS... 3 2. DC OUTPUT...3 OUTPUT VOLTAGES... 3 REMOTE

More information

Effective System Grounding

Effective System Grounding Effective System Grounding By Andrew Cochran of I-Gard and John DeDad of DeDad Consulting The costs associated with losses stemming from ground faults are staggering. For example, over a seven year period,

More information

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS) AC CURRENT GENERATOR PERFORMANCES Wide range of current 50 db dynamic range Signal-to-noise ratio: 80 db open loop protection Stability < 0,1% Very low THD distortion < 0,3% External synchronization Build-up

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

PLC-K506 Series FEATURES DESCRIPTION FEATURES

PLC-K506 Series FEATURES DESCRIPTION FEATURES FEATURES Two High Speed Counters Two Pulse Train Outputs Two Pulse Width Modulation Outputs Inputs 10 Outputs 1 RS232 Port 2 RS485 Ports Supports Modbus RTU Protocol Communicate With Up to 32 Devices DESCRIPTION

More information

VOLTAGE DETECTING SYSTEMS

VOLTAGE DETECTING SYSTEMS INTEGRATED OPTOELECTRIC SYSTEM OF VOLTAGE DETECTION WITH TOTAL SAFETY GUARANTEED BY GALVANIC INSULATION AND INTERNAL FAULT SUPERVISION pag.1 di 13 INDE 1.PREVIEW.. 3 2.GENERAL.. 3 3.STANDARD REFERENCES..

More information

PD300. Transformer, generator and motor protection Data sheet

PD300. Transformer, generator and motor protection Data sheet PD300 Transformer, generator and motor protection Data sheet DSE_PD300_eng_AO No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam T&D. One of

More information

DIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges)

DIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges) PERFORMANCES 12 ranges of AC current from 16 ma to 128 A peak AC permanent current up to 26 ARMS Nine ranges of DC permanent current from 16 ma to 12 A DC current ± 6mA or ± 10 ma stackable to AC current

More information

DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters

DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters Section [26 35 26][16280] Active Harmonic Filters (Low Voltage) Part 1 General 1.1 Summary A. Scope: Provide design and engineering, labor,

More information

Circuit breakers for direct current applications

Circuit breakers for direct current applications Circuit breakers for direct current applications Complementary technical information schneider-electric.com Complementary technical information Circuit breakers for direct current applications Contents

More information

Drive Safety integrated AC servo amplifier <MR-J3- S 0.1kW to 55kW> Safety logic unit <MR-J3-D05>

Drive Safety integrated AC servo amplifier <MR-J3- S 0.1kW to 55kW> Safety logic unit <MR-J3-D05> General-Purpose AC Servo MELSERVO-J3 Drive Safety integrated AC servo amplifier Safety logic unit The MR-J3- S Drive Safety integrated AC servo amplifier (SSCNET Ⅲ

More information

8V General information. 2 Order data 8V

8V General information. 2 Order data 8V 8V05.00-8V05.00- General information Modular mechanical design using plug-in modules Integrated line filter Integrated braking resistor All connections are made using plug-in connectors Integrated electronic

More information

SPECIFICATION, CONTROLS AND ACCESSORIES

SPECIFICATION, CONTROLS AND ACCESSORIES MX341 Automatic Voltage Regulator (AVR) SPECIFICATION, CONTROLS AND ACCESSORIES English Original Instructions A043Y699 (Issue 2) Table of Contents 1. DESCRIPTION... 1 2. SPECIFICATION... 3 3. CONTROLS...

More information

PHOENIX CONTACT

PHOENIX CONTACT Selective circuit breaker CLIPLINE Data sheet 100464_en_05 PHOENIX CONTACT 2009-11-17 1 Description The electronic circuit breaker, which has a design width of just 12.5 mm, selectively protects all 24

More information

TN, TT & IT Earthing Arrangements

TN, TT & IT Earthing Arrangements TN, TT & IT Earthing Arrangements In IT and TN-C networks, residual current devices are far less likely to detect an insulation fault. In a TN-C system, they would also be very vulnerable to unwanted triggering

More information

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS SAUDI STANDARD NO. SASO IEC 60669-2-2: 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS Part 2-2: Particular requirements Electromagnetic remote-control switches (RCS) SAUDI ARABIAN

More information

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges.

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges. APPLICATION: Basler Electric offers a New Line of digitally controlled brush (static) or brushless excitation systems designed for use with existing Hydro, Gas as well as Diesel driven generators requiring

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

Overvoltage and undervoltage. Dr Audih 1

Overvoltage and undervoltage. Dr Audih 1 Overvoltage and undervoltage Dr Audih 1 A Overvoltage is defined as an increase in the r.m.s. value of the voltage up to a level between 1.1 pu to 1.8 pu at power frequency for periods ranging from a half

More information

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009 Catalog 00 Contactors up to 5 A Motor Starters up to 55 kw 03/009 Kraus & Naimer The development of the Blue Line rotary switch, contactor and motor starter product ranges is based on more than hundred

More information

KNC-PLC-K506 Series FEATURES DESCRIPTION FEATURES

KNC-PLC-K506 Series FEATURES DESCRIPTION FEATURES FEATURES Two High Speed Counters Two Pulse Train Outputs Two Pulse Width Modulation Outputs Inputs 10 Outputs 1 RS232 Port 2 RS485 Ports Supports Modbus RTU Protocol Communicate with up to 32 devices DESCRIPTION

More information

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area. Primary-switched power supply with SFB technology, 1 AC, output current 20 A INTERFACE Data Sheet 103129_en_01 PHOENIX CONTACT - 05/2008 1 Description QUINT POWER power supply units highest system availability

More information

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of

More information

PHOENIX CONTACT

PHOENIX CONTACT Electronic circuit breaker CLIPLINE Data sheet 102898_en_03 PHOENIX CONTACT 2010-12-17 1 Description The electronic circuit breaker can be used in applications that cover all aspects of the switched-mode

More information

Integration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201

Integration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201 1SDC007402G0201 Index 1. Introduction... 2 2. Theoretical outline 2.1 Restricted earth fault... 3 2.2 Selectivity between medium and low voltage... 4 3. Application examples and wiring logic 3.1 Restricted

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

satech SynchroStar GPS 200 Series

satech SynchroStar GPS 200 Series satech SynchroStar GPS 200 Series KEY BENEFITS Designed with high quality oscillator OCXO the device is characterized by superior frequency stability and improved holdover performance that allows maintaining

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Est Static Frequency Converter. SFX 10kVA - 10MVA

Est Static Frequency Converter. SFX 10kVA - 10MVA Est.1968 Static Frequency Converter SFX 10kVA - 10MVA Static Frequency Converter SFX 10kVA - 10MVA A Concept Thycon Static Frequency Converters (SFX) convert supply frequency to load requirement frequency.

More information

AC/DC Power Supply Series APPLICATION NOTE

AC/DC Power Supply Series APPLICATION NOTE -175 AC/DC Power Supply Series APPLICATION NOTE 69493 NV175 App note 4.doc Document Number 69493 Page 1 of 17 1. INPUT...3 AC INPUT LINE REQUIREMENTS... 3 2. DC OUTPUT...3 OUTPUT VOLTAGES... 3 REMOTE SENSE...

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. The Importance of the Neutral-Grounding Resistor Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. Presentation Preview What is high-resistance grounding (HRG)? What is the purpose of HRG? Why

More information

02/11/2015

02/11/2015 Standstill monitoring KSW3-JS Part number 85102331 Function "Stillstand detection without sensors" Independent of rotation direction Security with redundancy and feedback circuit 3 forcibly guided "NO"

More information

Original operating instructions Fail-safe inductive sensor GG507S / / 2013

Original operating instructions Fail-safe inductive sensor GG507S / / 2013 Original operating instructions Fail-safe inductive sensor GG507S 80005283 / 00 05 / 2013 Contents 1 Preliminary note...3 1.1 Explanation of symbols...3 2 Safety instructions...4 2.1 Safety-related requirements

More information