PQVO3Sd Short duration voltage variations
|
|
- Willa Heath
- 6 years ago
- Views:
Transcription
1 1MRS Issued: 6/2005 Version: A/ PQVO3Sd Short duration voltage variations Data subject to change without notice Contents 1. Introduction Features Short duration voltage variations Application Input description Output description Description of operation Configuration Voltage measurement Current measurement Input/output configuration Rated frequency Measuring mode Operation criteria Outputs of the function block Swell Sag Interruption Counters Indications and events Resetting Recorded Data Measurement accuracy Parameters and Events General Setting values Control Settings Measurement values Input Data Output Data Recorded data... 21
2 PQVO3Sd Distribution Automation Events Technical Data
3 Distribution Automation PQVO3Sd 1. Introduction 1.1 Features Single-phase, two-phase and three-phase voltage variation measurement. Voltage sag, swell and interruption measurement. Measurement according to IEC Recording of the 3 latest events, providing time stamps of event start and min/max measurement, duration and min/max voltage of each phase. Also measured currents preceding the event are recorded for each measured phase current. Counters for sag, swell and interruption events. 1.2 Short duration voltage variations Voltage variations are the most typical power quality events that have the largest impact on sensitive customers. Short-duration voltage variations are almost always caused by a fault condition. Depending on where the fault is located, the fault can cause either a temporary voltage rise (swell) or voltage drop (sag). A special case of a voltage drop is complete loss of voltage (interruption). The impact on the voltage during the actual fault condition is a short duration variation. The typical duration of a short duration voltage variation, as defined in most of the publications, is from 10 ms to 60 seconds. Sag A voltage sag is a sudden reduction of the supply voltage. In most publications, a voltage sag is characterized as a voltage drop to a value between 90 % and 1 % of the nominal voltage. Voltage sags are usually caused by system faults but can also be caused by the switching of large loads or the starting of motors. A typical voltage sag can also be associated with a single line-to-ground fault. A fault on a parallel feeder will result in a voltage drop at the substation bus. This fault affects all of the other feeders until the fault is cleared. Swell A voltage swell is defined as an increase in supply voltage. Typical magnitudes are between 110 % and 180 % of the nominal voltage. Swells are also usually associated with system faults, but not as frequently as voltage sags. A single line-to-ground fault in the system can result in a voltage swell on the healthy phases. Switching off large loads or switching on large capacitor banks can also cause voltage swells. 3
4 PQVO3Sd Distribution Automation Interruption A voltage interruption is defined as a decrease of the supply voltage to a value less than 1 % of the nominal voltage. Interruptions can be the result of power system faults, equipment failures, and control function failures. Utility protective devices and the particular event causing the fault determine the duration of an interruption. 1.3 Application The PQVO3Sd function block is used for measuring short duration voltage variations in distribution networks. Power quality is being evaluated in the voltage waveform by measuring voltage swells, sags and interruptions. Power quality measurements carried out by the function block PQVO3Sd follow the European Standard EN The measuring principles are taken from the International standard IEC Table 1. Protection diagram symbols as seen in the relay terminal ABB IEC ANSI PQVO3Sd PQ 3U<> PQ 3U<> For IEC symbols used in single line diagrams, refer to the manual Technical Descriptions of Functions, Introduction, 1MRS MUM Figure 1. PQVO3Sd function block symbol 4
5 Distribution Automation PQVO3Sd 1.4 Input description Name Type Description UL1_U12 Analog channel Input for measuring voltage UL1 or signal (SINT) U12 UL2_U23 UL3_U31 IL1 IL2 IL3 RESET Analog channel signal (SINT) Analog channel signal (SINT) Analog channel signal (SINT) Analog channel signal (SINT) Analog channel signal (SINT) Digital signal (BOOL, pos. edge) Input for measuring voltage UL2 or U23 Input for measuring voltage UL3 or U31 Input for measuring phase current IL1 Input for measuring phase current IL2 Input for measuring phase current IL3 Input signal for resetting the counters and registers of the function 1.5 Output description Name Type Description SWELL Digital signal Output indicating the start of a voltage (BOOL, active high) swell SAG INTERRUPTION SWELL_COUNTER SAG_COUNTER INT_COUNTER Digital signal (BOOL, active high) Digital signal (BOOL, active high) Unsigned integer (UINT) Unsigned integer (UINT) Unsigned integer (UINT) Output indicating the start of a voltage sag Output indicating the start of a voltage interruption Output indicating the amount of swells counted Output indicating the amount of sags counted Output indicating the amount of interruptions counted 5
6 PQVO3Sd Distribution Automation 2. Description of operation 2.1 Configuration Voltage measurement Voltage variation measurement (voltage sag/swell/interruption) can be done for phase-to-ground or phase-to-phase voltages. Voltages can be measured with conventional voltage transformers or voltage dividers (does not apply for phase-to-phase voltages). Virtual phase-to-phase voltage measurement channels can be used instead of the corresponding analog measurement channels. Voltage sag/swell/interruption measurement can be performed for one, two or three phases (at least one voltage measurement channel must be connected) Current measurement Currents can be measured with conventional current transformers or Rogowski coils. Current measurement can be performed for one, two or three phases (current measurement is optional). Measured currents are registered by the function block and can later be used e.g. in calculation of power loss caused by a voltage sag or an interruption Input/output configuration The measuring devices and signal types for the analog channels are selected and parameterized in a special dialog box of the graphic RECAP tool (IEC configuration tool). The binary inputs are parameterized in the same programming environment. The number of selectable analog inputs, binary inputs and binary outputs depends on the hardware used. When the analog channels and binary inputs have been selected and parameterized in the dialog box, the inputs and outputs of the function block can be configured in a graphic worksheet of the RECAP tool. The digital inputs 6
7 Distribution Automation PQVO3Sd are connected to the Boolean inputs of the function block. In the same way, the outputs of the function block are connected to the output signals. The voltage measurement channels are connected to the UL1_U12, UL2_U23 and UL3_U31 inputs of the function block. The following voltages can be connected to each input: Table 2. Input name UL1_U12 UL2_U23 UL3_U31 Measured voltage channels Measured voltage UL1, UL1b, U12, U12b, U12s or U12bs UL2, UL2b, U23, U23b, U23s or U23bs UL3, UL3b, U31, U31b, U31s or U31bs Note 1. The function block setting Declared voltage is set to % when phase-to-phase voltages are connected, and to 57.7% in case that phase-toground voltages are connected. This means that if a voltage different from nominal voltage is connected to the terminal, the setting Declared voltage is set to this voltage. Note 2. If the LV side voltages (e.g. U12b) are connected to the function block, then the LV side measurement of the phase currents must be used as well. Otherwise it is not possible to use recorded data, provided by the function block, for calculation of lost power. Note 3. True RMS measurement must be selected for voltage and current channels. 2.2 Rated frequency The rated frequency of the device is set via a dialog box in the configuration tool. In addition, the global control parameter Rated frequency of the relay can be used to read the rated frequency. 2.3 Measuring mode The function block measures true RMS voltage (includes harmonics etc.). The results are compared to nominal voltage or declared voltage. 2.4 Operation criteria The PQVO3Sd function block measures short duration voltage variations, i.e. voltage sags, swells and interruptions longer than 1 cycle (for interruptions1½ 7
8 PQVO3Sd Distribution Automation cycle) of the fundamental frequency (20 ms for 50 Hz and 16 ms for 60 Hz) and shorter than 60 s in voltage waveform. The maximum magnitude (in case of voltage swell) or depth (in case of voltage sag or interruption) and the duration of the event can be obtained by measuring the RMS value of the voltage for each phase. The maximum magnitude and depth is defined as a percentage value calculated from the difference between the nominal (or declared) and the measured voltage (e.g. 70 % depth means that the minimum magnitude of a sag event is 70 % of the nominal amplitude). The duration of each phase corresponds to the period during which the RMS values measured remain above or below the corresponding limit. Figure 2 illustrates the duration and magnitude limits of the function block. PQVO3Sd measures RMS values for voltage. When this measured RMS value drops below the sag limit, and in the same time remains above the interruption limit, a sag is detected. If the voltage drops below the interruption limit, an interruption is detected. When the measured RMS value rises above the swell limit, a swell is detected. Note 4. The function block setting Interrupt. limit must be set below the setting Sag limit for correct and standardized operation of the function block. Figure 2. Duration and voltage magnitude limits for swell, sag and interruption measurement If a voltage swell, sag or interruption is detected, the corresponding output signal (SWELL, SAG or INT) is set to the Boolean value TRUE. The output signal is TRUE during the swell, sag or interruption event. The outputs SWELL 8
9 Distribution Automation PQVO3Sd and SAG can be active in the same time in case of e.g. a single-phase earth fault (see Figure 7). 2.5 Outputs of the function block Swell 1. The SWELL output is set to TRUE when the voltage level of any phase rises above the swell limit (IEC ). 2. The SWELL output is set to FALSE when the voltage levels of all phases are equal to or below the swell limit (minus the hysteresis) or when the swell is active longer than the maximum duration. Figure 3. Three-phase swell (this voltage variation is considered as a valid event and is being recorded) 9
10 PQVO3Sd Distribution Automation Sag 1. The SAG output is set to TRUE when the voltage level on any phase drops below the sag limit (IEC ). 2. The SAG output is set to FALSE when the voltage levels of all phases are equal to or above the sag limit (plus the hysteresis) or when the sag is active longer than the maximum duration. Figure 4. Three-phase sag. Phase U2 (green) starts and phase U3 (blue) ends the event 10
11 Distribution Automation PQVO3Sd Interruption 1. The INT output is set to TRUE when the voltage levels of all phases drop below the interruption limit (IEC ). 2. The INT output is set to FALSE when the voltage level of any phase is equal to or above the interruption limit (plus the hysteresis), or when the interruption is active longer than the maximum duration. Figure 5. Three-phase interruption When only one or two phases are below the interruption limit, the event is regarded as a sag, and the SAG output is set to TRUE during the event (see Figure 6). 11
12 PQVO3Sd Distribution Automation Figure 6. One-phase interruption (event is regarded as a sag) 12
13 Distribution Automation PQVO3Sd Figure 7. Single-phase earth fault Note 5. If the voltage variation event is active longer than the maximum duration, the corresponding outputs are set to FALSE, as in Figure 8. Furthermore, the function block is disabled as long as the event remains active in order to prevent unnecessary indications. 13
14 PQVO3Sd Distribution Automation Figure 8. One-phase sag which duration is longer than setting Duration max Counters The SAG_COUNTER output indicates the sum of the detected valid (the event duration is between min and max duration) voltage sags since the last reset of the function block. The same functionality correspondingly applies for the SWELL_COUNTER and INT_COUNTER outputs. 14
15 Distribution Automation PQVO3Sd 2.6 Indications and events When the voltage level of any phase is below or above the corresponding limit, a start event (E1) is generated. An end event (E0) indicates ending of the particular event in case. If the measured duration of the detected event is between the minimum and maximum durations, it is considered as a valid voltage variation event and then the measurement values are recorded. This recording is indicated by the generation of the event E2, which is sent at the same time as event E0 (see Figure 3). A voltage variation detection is also indicated with a HMI text indication. Event sending can be seen in Figures 3-8. For more information see section Recorded Data. Note 6. The function block PQVO3Sd measures the duration of each voltage channel separately, but the duration settings (Duration min and Duration max) of the function block are compared to the total duration of the variation event. The event duration can be seen in Figure 6. This event duration determines whether the measurement values of the variation event are recorded or not. 2.7 Resetting The registers can be reset, either via the RESET input, over the serial bus or via the local HMI. The operation indicators, the counters and the recorded data can be reset as follows: Operation indicators Registers Counters RESET input of the function block 1) X X Parameter F514V013 1) X X General parameter F001V011 2) General parameter F001V012 2) General parameter F001V013 2) X X Push-button C 2) Push-buttons C + E (2 s) 2) Push-buttons C + E (5 s) 2) X X 1) Resets counters and recorded data of the particular function block. 2) Affects all function blocks. X X X X 15
16 PQVO3Sd Distribution Automation 2.8 Recorded Data General The information required for later power quality analysis is recorded when the function block has detected a valid voltage variation. The data of the last three events are stored into the registers Recorded data 1...3, beginning from Recorded data 1. These registers are updated in a cyclical manner, where the values of the most recent event overwrite the oldest recorded data. If recorded data has been reset or the relay has been restarted, first event is again stored to Recorded data 1. Date and time of variation start The time stamp for each of the 3 phases indicates the time instant at which the voltage variation event was detected. Date and time of min/max voltage value The time stamp for each of the 3 phases indicates the time instant at which the measured voltage was at a minimum/maximum during the measured power quality event. Type of voltage variation The type of the detected voltage variation event (swell/sag/interruption/ sag&swell). Magnitude (% of declared voltage) The minimum/maximum voltage value during the swell/sag/interruption for each of the 3 phases. Duration The duration of the swell/sag/interruption for each of the 3 phases. The measuring principle for duration measurement can be seen in Figure 6. Currents The measured currents preceding the start of swell/sag/interruption for each of the 3 phases. 16
17 Distribution Automation PQVO3Sd 2.9 Measurement accuracy In normal operating conditions, the voltage variation measurement accuracy is in accordance with the international standard IEC Duration measurement Measurement accuracy for duration measurement in normal operating conditions is: ± 1 fundamental frequency cycle (IEC Class A) Voltage and current measurement Measurement accuracies for voltage and current measurement are at normal operating conditions (IEC Class B): ± 1.0% of In (for current measurement) ± 1.0% of Un (for voltage measurement) 17
18 PQVO3Sd Distribution Automation 3. Parameters and Events 3.1 General Each function block has a specific channel number for serial communication parameters and events. The channel for PQVO3Sd is 514. The data direction of the parameters defines the use of each parameter as follows: Data direction R, R/M W R/W Description Read only Write only Read and write The different event mask parameters (see section Control Settings ) affect the visibility of events on the HMI or on the serial communication (LON or SPA) as follows: Event mask 1 (F514V101/102) Event mask 2 (F514V103/104) Event mask 3 (F514V105/106) Event mask 4 (F514V107/108) SPA / MMI (LON) LON LON LON For example, if only the events E3, E4 and E5 are to be seen on the HMI of the relay terminal, the event mask value 56 ( ) is written to the Event mask 1 parameter (F514V101). 18
19 Distribution Automation PQVO3Sd 3.2 Setting values Control Settings Parameter Code Values Unit Default Data Explanation direction Declared voltage V % R/W Declared input voltage Duration min V ms 10 R/W Minimum voltage variation duration Duration max V ms R/W Maximum voltage variation duration Swell limit V % R/W Swell threshold Sag limit V % 90.0 R/W Sag threshold Interrupt. limit V % 1.0 R/W Interruption threshold Reset registers V ) - 0 W Resetting of outputs and registers Event mask 1 V R/W Event mask for event transmission (E0... E2) Event mask 2 V R/W Event mask for event transmission (E0... E2) Event mask 3 V R/W Event mask for event transmission (E0... E2) Event mask 4 V R/W Event mask for event transmission (E0... E2) 1) Reset registers 0 = 0; 1 = Reset 19
20 PQVO3Sd Distribution Automation 3.3 Measurement values Input Data Parameter Code Values Unit Default Data direction Explanation UL1_U12 I x Un 0.00 R/M Phase-to-earth voltage UL1 or phase-to-phase voltage U12 UL2_U23 I x Un 0.00 R/M Phase-to-earth voltage UL2 or phase-to-phase voltage U23 UL3_U31 I x Un 0.00 R/M Phase-to-earth voltage UL3 or phase-to-phase voltage U31 IL1 I x In R/M Phase current IL1 IL2 I x In R/M Phase current IL2 IL3 I x In R/M Phase current IL Output Data Parameter Code Values Unit Default Data direction Explanation SWELL O ) - 0 R/M Swell in progress SAG O ) - 0 R/M Sag in progress INT O ) - 0 R/M Interruption in progress SWELL_COUNT O R/M Output indicating the amount of swells counted SAG_COUNT O R/M Output indicating the amount of sags counted INT_COUNT O R/M Output indicating the amount of interruptions counted 1) Active 0 = Not Active; 1 = Active 20
21 Distribution Automation PQVO3Sd Recorded data Recorded data 1 Parameter Code Values Unit Default Data Explanation direction Type V ) - 0 R/M Type of detected voltage variation event Start date U1 V202 YYYY-MM-DD - - R/M Event start date of phase 1 Start time U1 V203 hh:mm:ss.mss - - R/M Event start time of phase 1 Start date U2 V204 YYYY-MM-DD - - R/M Event start date of phase 2 Start time U2 V205 hh:mm:ss.mss - - R/M Event start time of phase 2 Start date U3 V206 YYYY-MM-DD - - R/M Event start date of phase 3 Start time U3 V207 hh:mm:ss.mss - - R/M Event start time of phase 3 Min/max date U1 V208 YYYY-MM-DD - - R/M Date of phase 1 min/max value measurement Min/max time U1 V209 hh:mm:ss.mss - - R/M Time of phase 1 min/max value measurement Min/max date U2 V210 YYYY-MM-DD - - R/M Date of phase 2 min/max value measurement Min/max time U2 V211 hh:mm:ss.mss - - R/M Time of phase 2 min/max value measurement Min/max date U3 V212 YYYY-MM-DD - - R/M Date of phase 3 min/max value measurement Min/max time U3 V213 hh:mm:ss.mss - - R/M Time of phase 3 min/max value measurement Duration 1 V ms 0 R/M Duration for phase 1 Duration 2 V ms 0 R/M Duration for phase 2 Duration 3 V ms 0 R/M Duration for phase 3 Mag. UL1_U12 V % 0.0 R/M Magnitude for phase 1 Mag. UL2_U23 V % 0.0 R/M Magnitude for phase 2 Mag. UL3_U31 V % 0.0 R/M Magnitude for phase 3 Current IL1 V x In R/M Phase current IL1 Current IL2 V x In R/M Phase current IL2 Current IL3 V x In R/M Phase current IL3 1) EVENT_TYPE 0 = Swell; 1 = Sag; 2 = Interruption; 3 = Sag&Swell 21
22 PQVO3Sd Distribution Automation Recorded data 2 Parameter Code Values Unit Default Data Explanation direction Type V ) - 0 R/M Type of detected voltage variation event Start date U1 V302 YYYY-MM-DD - - R/M Event start date of phase 1 Start time U1 V303 hh:mm:ss.mss - - R/M Event start time of phase 1 Start date U2 V304 YYYY-MM-DD - - R/M Event start date of phase 2 Start time U2 V305 hh:mm:ss.mss - - R/M Event start time of phase 2 Start date U3 V306 YYYY-MM-DD - - R/M Event start date of phase 3 Start time U3 V307 hh:mm:ss.mss - - R/M Event start time of phase 3 Min/max date U1 V308 YYYY-MM-DD - - R/M Date of phase 1 min/max value measurement Min/max time U1 V309 hh:mm:ss.mss - - R/M Time of phase 1 min/max value measurement Min/max date U2 V310 YYYY-MM-DD - - R/M Date of phase 2 min/max value measurement Min/max time U2 V311 hh:mm:ss.mss - - R/M Time of phase 2 min/max value measurement Min/max date U3 V312 YYYY-MM-DD - - R/M Date of phase 3 min/max value measurement Min/max time U3 V313 hh:mm:ss.mss - - R/M Time of phase 3 min/max value measurement Duration 1 V ms 0 R/M Duration for phase 1 Duration 2 V ms 0 R/M Duration for phase 2 Duration 3 V ms 0 R/M Duration for phase 3 Mag. UL1_U12 V % 0.0 R/M Magnitude for phase 1 Mag. UL2_U23 V % 0.0 R/M Magnitude for phase 2 Mag. UL3_U31 V % 0.0 R/M Magnitude for phase 3 Current IL1 V x In R/M Phase current IL1 Current IL2 V x In R/M Phase current IL2 Current IL3 V x In R/M Phase current IL3 1) EVENT_TYPE 0 = Swell; 1 = Sag; 2 = Interruption; 3 = Sag&Swell 22
23 Distribution Automation PQVO3Sd Recorded data 3 Parameter Code Values Unit Default Data Explanation direction Type V ) - 0 R/M Type of detected voltage variation event Start date U1 V402 YYYY-MM-DD - - R/M Event start date of phase 1 Start time U1 V403 hh:mm:ss.mss - - R/M Event start time of phase 1 Start date U2 V404 YYYY-MM-DD - - R/M Event start date of phase 2 Start time U2 V405 hh:mm:ss.mss - - R/M Event start time of phase 2 Start date U3 V406 YYYY-MM-DD - - R/M Event start date of phase 3 Start time U3 V407 hh:mm:ss.mss - - R/M Event start time of phase 3 Min/max date U1 V408 YYYY-MM-DD - - R/M Date of phase 1 min/max value measurement Min/max time U1 V409 hh:mm:ss.mss - - R/M Time of phase 1 min/max value measurement Min/max date U2 V410 YYYY-MM-DD - - R/M Date of phase 2 min/max value measurement Min/max time U2 V411 hh:mm:ss.mss - - R/M Time of phase 2 min/max value measurement Min/max date U3 V412 YYYY-MM-DD - - R/M Date of phase 3 min/max value measurement Min/max time U3 V413 hh:mm:ss.mss - - R/M Time of phase 3 min/max value measurement Duration 1 V ms 0 R/M Duration for phase 1 Duration 2 V ms 0 R/M Duration for phase 2 Duration 3 V ms 0 R/M Duration for phase 3 Mag. UL1_U12 V % 0.0 R/M Magnitude for phase 1 Mag. UL2_U23 V % 0.0 R/M Magnitude for phase 2 Mag. UL3_U31 V % 0.0 R/M Magnitude for phase 3 Current IL1 V x In R/M Phase current IL1 Current IL2 V x In R/M Phase current IL2 Current IL3 V x In R/M Phase current IL3 1) EVENT_TYPE 0 = Swell; 1 = Sag; 2 = Interruption; 3 = Sag&Swell Events Code Weighting coefficient Default mask Event reason Event state E0 1 1 Voltage variation start Reset E1 2 1 Voltage variation start Activated E2 4 1 Meas. values registered Ready 23
24 PQVO3Sd Distribution Automation 4. Technical Data Reset ratio Typ Configuration data Task execution interval (Relay Configuration Tool): 10 ms at the rated frequency f n = 50 Hz 24
MotStart Three-phase Start-Up Supervision for Motors
1MRS752307-MUM Issued: 10/1998 Version: F/23.06.2005 Data subject to change without notice MotStart Three-phase Start-Up Supervision for Motors Contents 1. Introduction... 2 1.1 Features... 2 1.2 Application...
More informationInrush3 Three-Phase Transformer Inrush and Motor Start-Up Current Detector
1MRS752306-MUM Issued: 10/1997 Version: G/23.6.2005 Data subject to change without notice Three-Phase Transformer Inrush and Motor Start-Up Current Detector Contents 1. Introduction... 2 1.1 Features...
More informationUV3 _ Three-Phase Undervoltage Protection Low-Set Stage (UV3Low) High-Set Stage (UV3High)
1MRS752333-MUM Issued 10/1997 Version: H/23.06.2005 Data subject to change without notice Three-Phase Undervoltage Protection Low-Set Stage (UV3Low) High-Set Stage (UV3High) Contents 1. Introduction...
More informationPQVO3H Voltage Waveform Distortion Measurement
1MRS752336-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice Voltage Waveform Distortion Measurement Contents 1 Introduction... 3 1.1 Features... 3 1.2 Harmonic distortion...
More informationPSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)
1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1
More informationReducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems
Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant
More informationInstruction manual. art Installation manual
Instruction manual art. 01521 Installation manual Contents GENERAL FEATURES AND FUNCTIONALITY from page 4 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 6 COMMUNICATION OBJECTS GENERAL FEATURES AND
More informationOVERVIEW OF IEEE STD GUIDE FOR VOLTAGE SAG INDICES
OVERVIEW OF IEEE STD 1564-2014 GUIDE FOR VOLTAGE SAG INDICES ABSTRACT Daniel SABIN Electrotek Concepts USA d.sabin@ieee.org IEEE Std 1564-2014 Guide for Voltage Sag Indices is a new standard that identifies
More informationPower Quality Basics. Presented by. Scott Peele PE
Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement
More informationPOWER QUALITY AND SAFETY
POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION
More informationEIB/KNX Switch Actuators. User manual
EIB/KNX Switch Actuators User manual IT KNT 004 IT KNT 012 Tel.: +34943627988 E-mail: knx@dinuy.com Web: www.dinuy.com Contents 1. Introduction --------------------------------------------------------------------------------------------------------------
More informationCapacitor overvoltage protection function
Budapest, May 2018. User s manual version information Version Date Modification Compiled by 1.0 2012-10-10 First edition Gyula Poka Kornel Petri 1.1 2018-05-30 Minor corrections Erdős VERSION 1.1 2/5 Capacitor
More informationPower Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron
Power Quality and Circuit Imbalances 2015 Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Summary of IEEE 1159 Terms Category Types Typical Duration
More informationHigh-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime
Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with
More informationHigh speed bus transfer function block description Operation Manual
Operation anual FDE Rev.A Page 2 sur 27 User s manual version information Version Date odification Compiled by Version 1.0 30.06.2016. First edition Kiss - Petri A 15/06/2017 Change cover and diffusion
More informationFundamentals of Power Quality
NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»
More informationReliable Power Meters Multipoint Power Recorder
Reliable Power Meters Multipoint Power Recorder High-speed capability for permanent installation Technical Data What is Full Disclosure Technology? Full Disclosure Technology is built into all Fluke and
More informationULTRA RAPID POWER QUALITY ANALYZER
ULTRA RAPID POWER QUALITY ANALYZER Ultra rapid (cycle by cycle) advanced electrical network analysis Complete network harmonics analysis, up to 63 rd harmonic High visibility, 5 graphic LCD screen with
More informationEEE508 GÜÇ SİSTEMLERİNDE SİNYAL İŞLEME
EEE508 GÜÇ SİSTEMLERİNDE SİNYAL İŞLEME Signal Processing for Power System Applications Triggering, Segmentation and Characterization of the Events (Week-12) Gazi Üniversitesi, Elektrik ve Elektronik Müh.
More informationAn Introduction to Power Quality
1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger
More informationMultifunction Protection and Switchgear Control Unit REF 542plus Protection Manual
Multifunction Protection and Switchgear Control Unit REF 542plus Document ID: 1MRS755860 Issued: 2016-06-27 Revision: F Product version: 3.0 Copyright 2016 ABB. All rights reserved Copyright This document
More informationCentralized busbar differential and breaker failure protection function
Centralized busbar differential and breaker failure protection function Budapest, December 2015 Centralized busbar differential and breaker failure protection function Protecta provides two different types
More informationMultimeter 500CVD21 RTU500 series
Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase
More informationSPTO 1D2. Control module SPAC 3 C. User s manual and Technical description. U aux V _ V _. f n SPTO 1D2. I n = 1 / 5 A( I o)
SPTO 1D2 Control module User s manual and Technical description f n = 50 60 Hz I n = 1 / 5 A ( I ) I n = 1 / 5 A( I o) SPAC 3 C 2 5 IRF O I TEST INTERLOCK GAS PRESSURE MOTOR VOLTAGE STEP R L U aux 80...
More informationUNIT-4 POWER QUALITY MONITORING
UNIT-4 POWER QUALITY MONITORING Terms and Definitions Spectrum analyzer Swept heterodyne technique FFT (or) digital technique tracking generator harmonic analyzer An instrument used for the analysis and
More informationVoltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment
s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering
More informationIntroduction to Harmonics and Power Quality
NWEMS Introduction to Harmonics and Power Quality August 20 24, 2018 Seattle, WA Track B Anaisha Jaykumar (SEL) Class Content» Definition of power quality (PQ)» Impact of PQ problems» Sources of poor PQ»
More informationGeneral specifications and features
General specifications and features General specifications and features Table 1 General AC/DC/Relay DC/DC/Relay DC/DC/DC Order number 6ES7 212-1BE31-0XB0 6ES7 212-1HE31-0XB0 6ES7 212-1AE31-0XB0 Dimensions
More informationReliability and Power Quality Indices for Premium Power Contracts
Mark McGranaghan Daniel Brooks Electrotek Concepts, Inc. Phone 423-470-9222, Fax 423-470-9223, email markm@electrotek.com 408 North Cedar Bluff Road, Suite 500 Knoxville, Tennessee 37923 Abstract Deregulation
More informationPQ Monitoring Standards
Characterization of Power Quality Events Charles Perry, EPRI Chair, Task Force for PQ Characterization E. R. Randy Collins, Clemson University Chair, Working Group for Monitoring Electric Power Quality
More informationcrio Resolver Simulation crio RVDT Simulation Manual V3.0
crio Resolver Simulation crio RVDT Simulation Manual V3.0 Page 1 / 25 Content 1. General... 3 1.1 Revision history... 3 1.2 Abbreviations... 3 1.3 Purpose... 3 1.4 Annexes... 4 1.5 List of tables... 4
More informationPOWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO
POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO Krasimir Marinov Ivanov, Technical University of Gabrovo, Gabrovo, BULGARIA Georgi Tsonev
More informationISSN Vol.07,Issue.21, December-2015, Pages:
ISSN 2348 2370 Vol.07,Issue.21, December-2015, Pages:4128-4132 www.ijatir.org Mitigation of Multi Sag/Swell using DVR with Hysteresis Voltage Control DAKOJU H V V S S N MURTHY 1, V. KAMARAJU 2 1 PG Scholar,
More informationK-BUS Switch Actuator
K-BUS Switch Actuator User manual-ver. 2 KA/R0416.1 KA/R0816.1 KA/R1216.1 Contents Contents... 2 1. Introduction... 3 1.1 Product and function overview... 3 2. Technical Properties... 3 3. Commissioning...
More informationFan Coil Actuator FCA 2
Fan Coil Actuator FCA 2 FCA 2 4920210 Updated: Feb-16 (subject to changes) Page 1 of 89 Contents 1 Function description... 4 1.1 Operation and display... 5 1.2 Advantages of the FCA 2... 6 1.2.1 Special
More informationPOWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION
POWER QUALITY A N D Y O U R B U S I N E S S A SUMMARY OF THE POWER QUALITY REPORT PUBLISHED BY THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION H YDRO ONE NETWORKS INC SEPTEMBER 2014
More informationPowerMonitor 5000 Family Advanced Metering Functionality
PowerMonitor 5000 Family Advanced Metering Functionality Steve Lombardi, Rockwell Automation The PowerMonitor 5000 is the new generation of high-end electrical power metering products from Rockwell Automation.
More informationSIPROTEC 5 Application Note
www.siemens.com/protection SIPROTEC 5 Application Note SIP5-APN-015: Answers for infrastructure and cities. SIPROTEC 5 - Application: SIP5-APN-015 Content 1 Application 3 1.1 Introduction 3 1.2 Overview
More informationRelion 605 series Self-Powered Feeder Protection REJ603 Product Guide
Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4
More informationUse of the application program. Contents. instabus EIB Application program description. September S2 Room temperature controller
Use of the application program Product family: Product type: Manufacturer: Heating, Air conditioning, Ventilation Thermostat Siemens Name: Room temperature controller IKE 250 DELTA millennium Order no.:
More informationwww. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay
Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:
More informationPower Analysis Summary
Power Analysis Summary Introduction This is a summary of the power conditions measured with these setup parameters: Measurement File: C:\Users\fhealy\Documents\Fluke\Power Analyze\Core 2 Recording.odn
More informationSection 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services
Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality
More informationPower quality report. A Manufacturing Plant
Power quality report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION... 5 2.1 SITE MONITORED...
More informationIn the event of a failure, the inverter switches off and a fault code appears on the display.
Issue 03/05 Faults and Alarms 5 Faults and Alarms 5.1 Fault messages In the event of a failure, the inverter switches off and a fault code appears on the display. NOTE To reset the fault code, one of three
More informationMRF3 Frequency Relay. Manual MRF3 (Revision A)
MRF3 Frequency Relay Manual MRF3 (Revision A) Woodward Manual MRF3 BG Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward
More informationPOWER QUALITY THAILAND LTD SINCE 1986
POWER QUALITY THAILAND LTD SINCE 1986 PQ TEST EQUIPMENT (198 S TO 215) BMI Power Quality recorders ($2,) BMI Energy recorders ($8,) BMI Line viewers (with oscilloscope) ($2) Dranetz 66 (1975) 626 (198
More informationRoadmap For Power Quality Standards Development
Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel
More informationRISH Master 3440i/3440iDL 0.2S
Operating Manual RISH Master 3440i/3440iDL 0.2S as per IEC62053-22 Touch Screen Digital Multi-Function Meter Installation & Operating Instructions Section Contents 1. Introduction INDEX 2. Measurement
More informationMetering Devices, Protective Relays, Software and Connectivity
, Protective Relays, Software and Connectivity.3 IQ Analyzer 6400/6600 Series IQ Analyzer Comprehensive Electrical Distribution Monitoring IQ Analyzer 6400/6600 Series Product Description Eaton s IQ Analyzer
More informationEN50160 Individual Report Summary
EN50160 Individual Report Summary Power Frequency (x.1) Supply Voltage Variations (x.3.x) Rapid Voltage Changes (x.4.1) Flicker (x.4.2) Supply Voltage Dips (x.5) Short Interruption of Supply Voltage (x.6)
More informationPower Quality Report. A Manufacturing Plant
Power Quality Report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant CHK Power Quality Pty Ltd Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION...
More informationSPAD 346 C Stabilized differential relay
SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault
More informationMinimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners
Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners IEEE Canada Webinar Presentation May 21, 2008 Bob Hanna, FIEEE, P.Eng. RPM Engineering Ltd. www.rpm-eng.com David
More informationE50 MODBUS POINT MAP
E50 MODBUS POINT MAP The E50C2 Full Data Set (FDS) features data outputs such as demand calculations, per phase VA and VAR, and VAh VARh accumulators. The E50C3 Data Logging model adds configuration registers
More informationProtection & Control Terminals REF 54_, REM 54_, RET 54_, REC 523. Configuration Guideline
1MRS750745-MUM Issued: 20.10.1998 Version: L/08.07.2005 Contents 1. About this manual...7 1.1. Copyrights...7 1.2. Trademarks...7 1.3. General...7 1.4. Use of symbols...8 1.5. Document conventions...9
More informationEN 50160:2010 IMPROVEMENTS OF THE REVISED VERSION. TC8X System Aspects of Electricity Supply
Joint Workshop CEER/ECRB EURELECTRIC on Voltage Quality Monitoring Brussels, 1 st October 2012 EN 50160:2010 IMPROVEMENTS OF THE REVISED VERSION Maurizio Delfanti Politecnico di Milano Dipartimento di
More informationBenchmarking Distribution Power Quality at BGE
Benchmarking Distribution Power Quality at BGE Dewane Daley Engineer Baltimore Gas & Electric Company 410-291-3198 dewane.a.daley@bge.com Large Scale Benchmarking Projects at BGE Distribution System Power
More informationA Guide to Power Quality Testing
A Guide to Power Quality Testing Table of Contents What is power quality?... 3 Power quality phenomenon... 3 Under-voltage... 3 Over-voltage... 3 Voltage dips (sags) and swells... 4 Voltage dips (sags)...
More informationinstabus EIB product documentation
Page: 1 of 39 Push button interface 4-gang Sensor Product name: Push button interface 4-gang Design: UP (flush-mounting type) Item no.: 2076-4T-01 ETS search path: Input / Binary Input, 4-gang / Push button
More informationPOWER QUALITY MONITORING - PLANT INVESTIGATIONS
Technical Note No. 5 January 2002 POWER QUALITY MONITORING - PLANT INVESTIGATIONS This Technical Note discusses power quality monitoring, what features are required in a power quality monitor and how it
More informationDesign and Development of DVR model Using Fuzzy Logic Controller for Voltage Sag Mitigation
Design and Development of DVR model Using Fuzzy Logic Controller for Voltage Sag Mitigation 1 Hitesh Kumar Yadav, 2 Mr.S.M. Deshmukh 1 M.Tech Research Scholar, EEE Department, DIMAT Raipur (Chhattisgarh)
More informationPower Quality Analysers
Power Quality Analysers Review of Power Quality Indicators and Introduction to Power Analysers ZEDFLO Australia 6-Mar-2011 www.zedflo.com.au Power Quality Indicators Review of main indicators of electrical
More informationPower Quality - 1. Introduction to Power Quality. Content. Course. Ljubljana, Slovenia 2013/14. Prof. dr. Igor Papič
Course Power Quality - 1 Ljubljana, Slovenia 2013/14 Prof. dr. Igor Papič igor.papic@fe.uni-lj.si Introduction to Power Quality Content Session 1 Session 2 Session 3 Session 4 1st day 2nd day 3rd day 4th
More informationRISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics
Power Quality Monitor Individual Harmonics measurement upto 56th Harmonics True representation of Voltage & Current waveforms. Phasor Representation of All 3 phases for system analysis Real Time Clock
More informationThe universal input/output device is a DIN rail mounted device. It is connected to the EIB via a bus connecting terminal.
, GH Q631 0026 R0111 SK 0097 B97 The universal input/output device is a DIN rail mounted device. It is connected to the EIB via a bus connecting terminal. The device has 32 freely programmable inputs/outputs,
More informationINSTRUCTION MANUAL. AQ F3x0 Feeder protection IED
INSTRUCTION MANUAL AQ F3x0 Feeder protection IED Instruction manual AQ F3x0 Feeder protection IED 2 (173) Revision 1.00 Date November 2010 Changes - The first revision. Revision 1.01 Date January 2011
More informationVoltage Compensation of AC Transmission Lines Using a STATCOM
Exercise 1 Voltage Compensation of AC Transmission Lines Using a STATCOM EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the operating principles of STATCOMs used for
More informationThree Phase Power Calibrator and Tester of Power Engineering Devices
C300B Data Sheet Three Phase Power Calibrator and Tester of Power Engineering Devices C300B Power Calibrator and Tester 3-phase voltage source up to 560V 3-phase current source up to 120A and 1-phase up
More informationMitigation of voltage sags/swells unbalanced in low voltage distribution systems
International Journal of Science and Advanced Technology (ISSN 2221-8386) Volume 1 No 6 August 211 Mitigation of voltage sags/swells unbalanced in low voltage distribution systems M. N. Tandjaoui, C. Benachaiba,
More informationSimulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System
Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System G. Laxminarayana 1, S. Raja Shekhar 2 1, 2 Aurora s Engineering College, Bhongir, India Abstract: In this
More informationPQM3000RGW Class A rack 19 power quality analyzer with Rogowski coils
Class A rack 19 power quality analyzer with Rogowski coils Rack 19 mounting Current inputs for direct connection of Rogowski coils Harmonics and interharmonics measurement Data recording for further EN
More informationtheben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77
Fan Coil Actuator FCA 1 FCA 1 492 0 200 Version: Jan-08 (Subject to change) Page 1 of 77 Contents 1 Functional characteristics...4 1.1 Operation and display...5 1.2 Advantages of the FCA 1...5 1.2.1 Special
More informationA POWER QUALITY INSTRUMENT FOR HARMONICS INTERHARMONICS AND AMPLITUDE DISTURBANCES MEASUREMENTS
Proceedings, XVII IMEKO World Congress, June 7, 003, Dubrovnik, Croatia Proceedings, XVII IMEKO World Congress, June 7, 003, Dubrovnik, Croatia XVII IMEKO World Congress Metrology in the 3rd Millennium
More informationPower Quality Disturbaces Clasification And Automatic Detection Using Wavelet And ANN Techniques
International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 13, Issue 6 (June 2017), PP.61-67 Power Quality Disturbaces Clasification And Automatic
More informationThree-phase instantaneous overcurrent protection function block description
Three-phase instantaneous overcurrent protection block description Document ID: PRELIMINARY VERSION User s manual version information Version Date Modification Compiled by Preliminary 30.10.2009 Preliminary
More informationComplimentary Reference Material
Complimentary Reference Material This PDF has been made available as a complimentary service for you to assist in evaluating this model for your testing requirements. TMG offers a wide range of test equipment
More informationStabilized Differential Relay SPAD 346. Product Guide
Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault
More informationMultimeter 560CVD11 Data sheet
RTU500 series Multimeter 560CVD11 Data sheet The fault current is measured up to 20 times nominal current. The current inputs withstand 50 times nominal current for 1 s. The Multimeter is equipped with
More informationSPECIFICATION FOR OVERCURRENT RELAYS
SPECIFICATION FOR OVERCURRENT RELAYS 1/9 1. Procedure A manufacturer willing to classify an overcurrent relay according to this specification should provide: A complete file providing a clear, unambiguous
More informationADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION
23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB
More informationINSTRUCTION MANUAL. AQ F210 Feeder Protection IED
INSTRUCTION MANUAL AQ F210 Feeder Protection IED Instruction manual AQ F210 Feeder Protection IED 2 (298) Revision 1.00 Date 8.4.2013 Changes - The first revision for AQ-F210 IED. Revision 1.01 Date 22.11.2013
More informationNX Series Inverters. HVAC Pocket Programming Guide
NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product
More informationI2C Encoder. HW v1.2
I2C Encoder HW v1.2 Revision History Revision Date Author(s) Description 1.0 22.11.17 Simone Initial version 1 Contents 1 Device Overview 3 1.1 Electrical characteristics..........................................
More informationSolectria Renewables Modbus Level 5 For models PVI KW
Solectria Renewables Modbus Level 5 For models PVI 50 100KW Revision B 2014, Solectria Renewables, LLC DOCR 070381 B Table of Contents 1 Solectria Renewables Modbus Level 5... 3 1.1 Determine Modbus Level...
More informationData Compression of Power Quality Events Using the Slantlet Transform
662 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002 Data Compression of Power Quality Events Using the Slantlet Transform G. Panda, P. K. Dash, A. K. Pradhan, and S. K. Meher Abstract The
More informationFault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice
Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and
More informationDISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS
DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS Le Tang, Jeff Lamoree, Mark McGranaghan Members, IEEE Electrotek Concepts, Inc. Knoxville, Tennessee Abstract - Several papers have
More informationUMG 103 DIN Rail Measuring Device Modbus-Adressenliste and Formulary (Valid from firmware rel )
DIN Rail Measuring Device Modbus-Adressenliste and Formulary (Valid from firmware rel. 0.931) www.janitza.com Dok Nr. 1.036.020.6.f Janitza electronics GmbH Vor dem Polstück 1 D-35633 Lahnau Support Tel.
More information1. Introduction to Power Quality
1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and
More informationCOMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.
COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.Booma 2 Electrical and Electronics engineering, M.E., Power and
More informationAQ F201 Overcurrent and Earthfault
INSTRUCTION MANUAL AQ F201 Overcurrent and Earthfault Relay Instruction manual AQ F201 Overcurrent and Earth-fault Relay 2 (198) Revision 1.00 Date 8.1.2013 Changes - The first revision for AQ-F201 Revision
More informationDSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.
15 Watts xxx Series Ultra Slim Design 15% Peak Load for 3 seconds Ambient Operation from -1 C to +7 C High Efficiency Selectable Overload Characteristic Selectable Remote Inhibit or Enable 3 Year Warranty
More information6000 W, 2450 MHz Microwave Generator GMP 60K SM 56T400 FST 3 IR
6000 W, 2450 MHz Microwave Generator GMP 60K SM 56T400 FST 3 IR Power supply It is based upon the latest switch mode power supply technology, offering size reduction (smallest 6 kw available on the market,
More informationKNX manual High-performance switch actuators RM 4 H FIX1 RM 8 H FIX2
KNX manual High-performance switch actuators RM 4 H FIX1 RM 8 H FIX2 4940212 4940217 2018-10-17 Contents 1 Function description 3 2 Operation 4 3 Technical data 5 4 The FIX2 RM 8 H application programme
More informationRequirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH
Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 5th October 2010 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT
More informationCurrent Module, 3-channel, MDRC SM/S , GH Q R0111
, GH Q631 0034 R0111 SK 0086 B 99 Load and residual currents can be measured simultaneously using the current module. There are 3 isolated and independent measuring circuits available for this. The current
More informationKNX manual 1-channel flush-mounted switch actuator SU 1
KNX manual 1-channel flush-mounted switch actuator SU 1 4942520 2018-10-04 Contents 1 Function description 3 2 Operation 4 3 Technical data 5 4 The SU 1 application programme 7 4.1 Selection in the product
More informationHarmonic Distortion Levels Measured at The Enmax Substations
Harmonic Distortion Levels Measured at The Enmax Substations This report documents the findings on the harmonic voltage and current levels at ENMAX Power Corporation (EPC) substations. ENMAX is concerned
More informationDPX³ 250 Electronic 4P - ModbusTable LGR EN v1.01.xls
GENERAL MODBUS TABLE ORGANIZATION Starting of the Group s Starting of the Group s System Version (Release) System Version (Build) Group Name (Text) Group Code Group Complexity Group Version 1638 000 01
More information