1 Presents Harmonics
2
3
4
5
6
7 What is a Harmonic? A harmonic is the term used for current flow on your facilities power system at frequencies other than 60Hertz.
8 Harmonic Problems Include:
9 Harmonic Problems Over heating and failure of: Transformers Computers Motors Lights & Ballast's Switchgear etc... Motor Control Centers
10 Harmonic Problems Electrical and Electronic damage. Control System errors due to Electrical noise caused by harmonics. Blown Fuses for no APPARENT reason. Nuisance tripping of Circuit Breakers.
11 What exactly is a Harmonic?
12 Linear use of power 680V Volts 0V 680V 200A 0A Amps 200A
13 Equipment: Power in a Linear fashion
14 Non-Linear use of power 680V Volts 0V 680V 200A 0A Amps 200A
15 Equipment: Power in a NON-linear fashion Computers Modern Lights and Ballast's Copiers & Other Office Equipment Variable Frequency Drives All equipment that uses an AC to DC power supply
16 Typical Non-Linear frequencies that cause problems: 3 x 60 = 180HZ 5 x 60 = 300HZ 7 x 60 = 420HZ 11 x 60 = 660HZ 13 x 60 = 780HZ
17 Why does Non-Linear current flow cause problems in my facility?
18 Magnetic field produced around wire 200A 0A 200A Section of Wire
19 Combination of Linear & Non-Linear power 200A 0A 200A Section of Wire
20 Harmonic currents flow on your power system neutral Why?
21 Normal 3 Phase Balanced System (Linear Load) A Phase +60A B Phase C Phase Regular Lighting Motors 0A -60A
22 Normal 3 Phase Balanced System (Linear Load) A Phase B Phase Freeze Time C Phase +60A 0A -60A
23 Normal 3 Phase Balanced System (Linear Load) -60A +20A +40A =0Amps
24
25 Balanced Linear loads A Phase B Phase C Phase
26 01-Harmonics Video
27 Unbalanced Linear Loads
28 02-Harmonics Video
29 Harmonics occur when equipment uses current in a Non-Linear fashion. Equipment that commonly does this: Personal Computers Various Office Equipment Copiers, Printers etc Electronic and Magnetic Ballast's Modern Welders Variable Frequency Drives Any device that uses Switched-Mode Power Supplies
30 Harmonic 3 Phase Un-Balanced System B Phase Copier or other Office equipment Freeze Time +60A +70A 0A +20A -60A +20A +70A
31 Harmonic 3 Phase Un-Balanced System
32 These Harmonic current flows on the neutral may be 1.73 times larger than the supply current. IEEE 519 is the standard used to determine maximum Harmonic distortion levels. They are different between voltage and current.
33
34 Non linear loads A Phase B Phase C Phase
35 Non Linear Loads B Phase A Phase C Phase
36 03-Harmonics Video
37 A Phase 14.1 Amps B Phase 14.2 Amps C Phase 13.9 Amps Neutral 22.5 Amps
38 A Phase 100Amp B Phase 100Amp C Phase 100Amp Neutral? Amp 50 Amp 173 Amps
39 5 th, 7 th, 13 th Harmonics Harmonic Profile th 7th 13th High Harmonic Current -100
40 IEEE Current Maximum Harmonic Current Distortion ISC / IL TDD % % % % % ISC=Maximum short circuit current IL= Maximum demand load TDD= Total Demand Distortion
41 Current Harmonics Example: Typical Office Building 1200A 208Y/120 service 30K AIC The Maximum IEEE Harmonic distortion is: 30,000 AIC / 960 = on the IEEE chart is 8%
42 IEEE 519-Voltage Maximum Harmonic Voltage Distortion Voltage TVD 69kV and below 5% TVD=Total Voltage Distortion
43 Harmonics: Low Harmonic Waveform
44 Highly Distorted Waveform
45
46 Since current flow induces voltage, you may see very large voltage spikes with large Harmonic systems. 180HZ 3rd Harmonic
47 Large ground currents can induce voltage into systems that are damaged by grounds that are not at zero potential.
48 Harmonic currents travel throughout your power system. Since they are not at 60HZ they can damage capacitors and transformers that are designed to operate only at 60HZ Harmonics can cause damage and unexpected shutdown of Computers, Variable Frequency Drives, UPS Systems and other electronic equipment.
49 Harmonic Problems- Transformers When harmonic currents flow through a transformer, the transformer will heat up more than one with 60Hz currents flowing through it. This is caused by eddy current loses in the core and coil windings of the transformer. What are eddy currents?
50 Harmonic Problems - Transformers When these magnetic lines of force cut through the wire they induce current flow. This current flow (internal to the wire) is called an eddy current. Eddy currents The higher frequency current (caused by harmonics) running through the transformer core and coils cause eddy currents to flow more readily in each of the core and coil winding conductors. These eddy currents cause excessive heat to build up in the transformer leading to damage and limiting the life of the transformer.
51 Harmonic Problems - Transformers This figure shows that the de-rating can reach 50% when the transformer supplies more than 70% of its load to single phase power supplies of electronic load equipment. Figure 8-5 shows an example of a de-rating curve (appearing in Zavadil et al. [B8]2 ) obtained by more accurate computations based on IEEE Std C Source: Based on Zavadil [B8]. Source-IEEE Std Copyright IEEE. All rights reserved.
52 Harmonic Problems Variable Frequency Drives, Computers, UPS Systems DC bus Voltage = 150 Volts DC bus Voltage with Clean Voltage
53 Harmonic Problems Variable Frequency Drives, Computers, UPS Systems DC bus Voltage = 135 Volts (10%) low DC bus Voltage with Distorted Voltage 10% lower
54 Detecting a Harmonic System Problem Use a Harmonic analyzer test meter ON 15% OFF VOLT AMP WAVE HARM THD% MODE ALL HARMONIC ANALYZER Use a Power Monitoring System D PowerLogic Use a True RMS Volt-Ohm-Ammeter COMPARED 100 AMP TO: VOLT AMP An Averaging Volt-Ohm-Ammeter 90 AMP VOLT AMP WATT OHM WATT OHM DIGITAL MULTIMETER MULTIMETER
55 True RMS amp meter Averaging amp meter
56 Solving a Harmonic System Problem Size Equipment to withstand the large Harmonic Neutral currents by using: 1. Oversize (K-factor) Transformers. 2. Oversize Neutrals in Switchboards Panelboards,Busway, and all Neutral wiring. Install Harmonic Filter Banks that trap and eliminate Harmonics. Use Harmonic cancellation transformers.
57 Install Harmonic Filter Banks that trap & eliminate Harmonics. The most popular filter is a series tuned L-C shunt filter. A phase B phase C phase Tuned L-C (Inductor-Capacitor) Filter (Trap) Tuned to the Harmonic level that is causing problems in the system.
58 Passive Harmonic Filter
59 Install Active Harmonic filters that repair the distorted voltage.
60 Example of Harmonic Correction
61 Use Harmonic Mitigating transformers.
62 Harmonic Mitigating Transformers Function N A B C N A B C Mitigation Standard and K rated Transformers Harmonic Mitigating Transformers
63 Non Linear load with Harmonic Mitigating transformer B Phase A Phase C Phase
64 04-Harmonics Video
65 Harmonic Mitigating Transformers Conventional Transformer Harmonic Mitigating Transformer
66 Harmonic Mitigating Transformers Harmonic Mitigating Transformer
67 5 th, 7 th, 13 th Harmonics Harmonic Profile th 7th 13th High Harmonic Current -100
68 5 th, 7 th, 13 th Harmonics 100 Harmonic Profile th 7th 13th High Harmonic Current GONE
69 Harmonic Mitigating Transformers Installation involving Harmonic Mitigating Transformers in a typical four-story office building 4th Floor Panel with regular transformer Total Harmonic Distortion 7.7% 3rd Floor Panel with regular transformer Total Harmonic Distortion 5.9% 2nd Floor Panel with regular transformer Total Harmonic Distortion 5.4% 1 st Floor Panel with regular transformer Total Harmonic Distortion 5.1% 480 Volt Main Switchgear Total Harmonic Distortion 2.8% Harmonic levels on each floor are above the IEEE 519 maximum allowed level of 5%. The 7.7% level on the forth floor resulted in a distorted voltage waveform.
70 Harmonic Mitigating Transformers After installation of only one Harmonic Mitigating Transformer on the 4th floor the following readings were logged: New Harmonic Mitigating Transformer 4th Floor Panel with new transformer Total Harmonic Distortion 3.2% 3rd Floor Panel with regular transformer Total Harmonic Distortion 4.8% 2nd Floor Panel with regular transformer Total Harmonic Distortion 4.3% 1 st Floor Panel with regular transformer Total Harmonic Distortion 4.0% 480 Volt Main Switchgear Total Harmonic Distortion 1.7% Total Harmonic Distortion on the 4th floor dropped from 7.7% to an acceptable IEEE519 level of 3.2%. This also had an effect on the rest of the building power lowering the Harmonic levels as shown.
71 Harmonic Mitigating Transformers Installation of Transformers that treat harmonics have many benefits, however the two largest benefits are: Elimination of harmonics that cause damage to or errors with your sensitive equipment. Energy savings from eliminating harmonics in your facility.
72 DOE 2016 Transformers The U.S. Department of Energy (DOE) adopted a new set of minimum efficiency standards for Dry-Type Transformers that are sold into the United States. This had a significant impact for distributors and end users. The new rule took effect on January 1st, The rule replaced the old minimum efficiency levels, which were known as the NEMA TP-1 or DOE 2010 efficiency levels. The new efficiency level is generally referred to as the DOE 2016 efficiency level.
73 Power Quality & Efficiency Matrix Delivers best voltage quality to connected equipment Improves voltage quality to connected equipment UL Listed to survive when feeding electronic equipment Not designed to feed load with load >10% current distortion (ANY mix of electronic equipment) K-Rated Old Standard Old TP-1 DOE 2016 Harmonic Canceling Energy Efficient EE/HMT (DOE2016) Better Power Quality Survival UL Issue Power Quality Efficiency
74 Energy savings with NON-LINEAR loads & Power Quality Cost Energy Savings Power Quality TP1 Manufacturing Stopped Jan, Unit 1 Unit None K-rated 2 Units 1.1 Units None DOE Units 0.99 Units None Harmonic Mitigating Energy Efficient DOE Units 0.75 Units Yes
75 Payback Calculator
76 Harmonics END Please fill out the evaluation form to receive attendance credit. An Address MUST be Provided to receive your attendance certificate. Thank you for attending PQU s Harmonics Seminar
Harmonics I Harmonics White Paper. Power Protection Products, Inc. by Dan Maxcy l 2018 Update
Power Protection Products, Inc. White Paper by Dan Maxcy l 2018 Update P3 is the industry s trusted and respected critical power, cooling and energy solutions provider. 877-393-1223 I www.p3-inc.com HARMONICS
More informationPower Factor & Harmonics
Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics
More informationHarmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions
Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE - 519 Solutions Harmonics Tutorial 1 Power Conversion Equipment can save energy and control motors, heaters,
More informationHarmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.
Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics
More informationAPQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)
APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute
More information3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.
MAIN TOPICS DISCUSSED Electric Rates Electrical system utilization ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K Power quality Harmonics Power factor (Cos phi) improvement Section K - 2 ELECTRIC
More information7/15/2002 PP.AFD.08 1 of 28
Power Quality Considerations When Applying Adjustable Frequency Drives Explanations and Various Countermeasures 7/15/2002 PP.AFD.08 1 of 28 Power Quality Why the Renewed Interest in Power Quality? Copy
More informationPower Quality. Answering Today s Power Challenges. Why Your Existing Transformer May Be Inadequate. How Harmonics Affect Transformers
Power Quality 13 Answering Today s Power Challenges Jefferson Electric is continually updating its product line to remain on the forefront of transformer technology. Electrical harmonics have become a
More information2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives
.0 Volume 6 Solid-State Control CA0800007E March 05 www.eaton.com V6-T-47 .0 Adjustable Frequency Drives Overview What Are Harmonics? Take a perfect wave with a fundamental frequency of 60 Hz, which is
More informationHarmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution
Harmonic Solutions in Electrical Systems Raed Odeh Application Specialist - Power Quality & Electrical Distribution Agenda I. Harmonic Basics II.Harmonic Mitigation Solutions III.Case Study 2 Harmonic
More information22.0 Harmonics in Industrial Power Systems
1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a
More informationElectrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018
Electrical Theory Power Principles and Phase Angle PJM State & Member Training Dept. PJM 2018 Objectives At the end of this presentation the learner will be able to: Identify the characteristics of Sine
More informationVariable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation
Variable Frequency Drive Packages with Harmonic Mitigation Low Harmonic Drive Packages Engineered by Rockwell Automation What Do I Need to know About Harmonics? What are Harmonics? Harmonics are deviations
More informationLoad Isolation Transformers
4 Non-Linear Load Isolation Transformers Section Special winding techniques minimize eddy current losses. A double sized neutral handles excessive neutral currents. UL Listed for K Factor Loads 4, 13 &
More informationHarmonic mitigating transformers. Energy savings through harmonic mitigation
Harmonic mitigating transformers Energy savings through harmonic mitigation Harmonic mitigating transformers Today s issues and needs Eaton s Harmonic Mitigating Transformer (HMT) As our world becomes
More informationE S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --
D.,.,.,. E S C R I P T I V E B U L L E T I N Bulletin DB-106 Square D Company October, 1990 ---1 I SQU ARED COMPANY -- Electrical Power Distribution System - The Heart of the Business From small commercial
More informationEconomical Solutions to Meet Harmonic Distortion Limits[4]
Economical Solutions to Meet Harmonic Distortion Limits[4] Abstract: The widespread adoption of variable frequency drive technology is allowing electricity to be utilized more efficiently throughout most
More informationEffects of Harmonic Distortion I
Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,
More informationHarmonic control devices. ECE 528 Understanding Power Quality
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)
More informationHarmonics, its Mitigation & Result of Case study of Spinning Mill
International Journal of Innovative Research in Engineering & Management (IJIREM) ISSN: 2350-0557, Volume-2, Issue-4, July 2015, its Mitigation & of Case of Spinning Mill Yogesh Subhash Shimpi M. Tech
More informationPOWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.
POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products
More informationENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM
ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM Abstract Efficient operation of the electrical system of any facility is essential to controlling operational costs while maximizing
More informationHarmonic Mitigating Transformer - Technical Guide
Harmonic Mitigating - Technical Guide HARMONY Series s HARMONY-1 www.mirusinternational.com Benefits: Prevent voltage flat-topping while reducing energy costs. Reduce voltage distortion caused by harmonic
More informationHarmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017
Harmonics and Their Impact on Power Quality Wayne Walcott Application Engineering Manager June, 2017 Presentation Overview A little about harmonics What are harmonics What are NOT harmonics What creates
More informationGuide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics
Reactive Power and Harmonic Compensation Guide to Harmonics POWER QUALITY The Basics of Harmonics All business types, commercial, industrial, government and energy/utility have a concern with power quality.
More informationThyristorised Automatic Power Factor
Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor
More informationHarmonic mitigating transformers. Energy savings through harmonic mitigation
Harmonic mitigating transformers Energy savings through harmonic mitigation Harmonic mitigating transformers Today s issues and needs Eaton s harmonic mitigating transformer (HMT) As our world becomes
More informationUnderstanding Harmonic Suppression Systems
Slot Tech Feature Article Understanding Harmonic Suppression Systems Get a Handle on Wasted Energy and Excess Heat A typical casino will have thousands of switched-mode power supplies on-line, twenty-four
More informationElectromagnetic Harmonic Filters Technical Guide
Eliminator Series Electromagnetic Harmonic Filters Technical Guide Neutral Eliminator TM (NCE TM ) Parallel connected, 3-phase, 4-wire passive electromagnetic device that diverts 3rd and other triplen
More informationLow Pass Harmonic Filters
Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power
More informationSingle-Phase Transformation Review
Single-Phase Transformation Review S T U D E N T M A N U A L March 2, 2005 2 STUDENT TRAINING MANUAL Prerequisites: None Objectives: Given the Construction Standards manual and a formula sheet, you will
More informationR. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder
R. W. Erickson Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder 16.4. Power phasors in sinusoidal systems Apparent power is the product of the rms voltage and
More informationGeneral Description & Features Selection Charts Definition of Terms... 42
SECTION NON-LINEAR LOAD ISOLATION TRANSFORMERS Special winding techniques minimize eddy current losses. A double sized neutral handles excessive neutral currents. UL Listed for K Factor Loads 4, 1 & 20.
More informationHarmonic Filters for Single Phase Equipment
POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics
More informationBruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc.
Bruce L. Graves A Defining a Power System A power system is an assembly of generators, transformers, power lines, fuses, circuit breakers, protective devices, cables, and associated apparatus used to generate
More informationULTRA-K Series 600K - he
5 kva 500 kva ULTRA-K Series 600K - he High Efficiency K-Rated Power Conditioning Transformers Designed to be used with linear or non-linear loads. Applications: Audio / Video Recording Equipment IT Systems
More informationUnit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21
Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive
More informationARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services
ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion
More informationPreface...x Chapter 1 Electrical Fundamentals
Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5
More informationDry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION
NON-LINEAR TRANSFORMER PRESENTATION 1 PROBLEM: HARMONICS CAUSE EXCESSIVE TRANSFORMER HEATING Increased Losses Proximity Skin Effect Stray Losses Circulating Effect Triplen Harmonics Add in Neutral Increased
More informationUnderstanding Harmonics
Understanding Harmonics Terry Gaiser Sensus What Are Harmonics? 1 » What is Power Quality?» Power quality is the degree to which both the utilization and delivery of electric power affects the performance
More informationNon-Linear Load Transformers
Non-Linear Load Transformers Acme s Non-Linear Load and Harmonic Mitigating Transformers protect equipment on the line and prevent damage caused by harmonic currents. Many of today s electronic devices
More informationTech Byte 16: The Truths About Transformers Part 2
In The Truths About Transformers Part 1, the discussion focused on the reality that not all transformers are created equal. Today, more than ever, there is a need to look at every transformer application
More informationActive Harmonic Filter
Reactive Power and Harmonic Compensation Active Harmonic Filter The new StacoSine Plus active harmonic filter is available in 100, 150, 200 and 300 amp assemblies. Modules can be paralleled for a maximum
More informationMulti-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7
White Paper Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 Dr. Jun-koo Kang, Yaskawa Electric America Doc#: WP.AFD.02 Copyright Yaskawa Electric America,
More informationHarmonic control devices
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)
More informationSWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)
SWF DV/DT Solutions Sinewave Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Does your application use variable frequency drives for improved
More informationECET Modern Power
ECET 273000 Modern Power Course Instructors Course Philosophy This course is an introduction to a wide range of electrical energy systems technologies. Topics include fundamentals of energy conversion,
More informationASSOCIATION OF ENERGY ENGINEERS NORTHERN OHIO CHAPTER APRIL 21, 2005
ASSOCIATION OF ENERGY ENGINEERS NORTHERN OHIO CHAPTER APRIL 21, 2005 Two Types of Electrical Loads Linear Non-Linear INCANDESCENT LIGHTING COMPUTERS INDUCTION MOTORS VARIABLE FREQUENCY DRIVES FLUORESCENT
More informationCHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS
86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the
More informationTuningintobetter power quality
Technology Review Third harmonic filters Tuningintobetter power quality Jouko Jaakkola Your PC screen flickers, stops flickering, starts again... Irritating to be sure, and perhaps the first visible sign
More informationAn Introduction to Power Quality
1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger
More informationEffective Harmonic Mitigation with Active Filters
Advancing Power Quality White Paper Effective Harmonic Mitigation with Active Filters Written by: Ian Wallace Variable Speed Drive with no Harmonic Mitigation Industry standard variable speed drives, with
More informationHow adjustable speed drives affect power distribution
How adjustable speed drives affect power distribution Application Note Adjustable speed drives (ASDs) can be both a source and a victim of poor power quality. ASDs as victim loads Although ASDs are usually
More informationEmicon Engineering Consultants L.L.C.
Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com
More informationWelcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008
Welcome to the rd Annual Northern Ohio 3 rd Energy Management Conference September 30, 2008 Recover Lost Dollars Demand Side Electrical Energy Savings By Improving Distribution System Efficiency, Capacity
More informationTHE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY
by Cesar Chavez, Engineering Manager, Arteche / Inelap, and John Houdek, President, Allied Industrial Marketing, Inc. Abstract: Industrial facility harmonic distortion problems can surface in many different
More informationHARMONIC MITIGATIONCASE STUDY
HARMONIC MITIGATIONCASE STUDY CNCE AND NCE INSTALLATION AT BROADCASTING STUDIO Concerned about video noise detected on some of its studio equipment, E! Entertainment Television (ETV), commissioned a study
More informationPower Quality Solutions
Power Quality Solutions What is Power Quality? For electrical systems to function in their intended manner without significant loss of performance or life, they require a supply of electricity that is
More informationSection 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services
Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality
More informationReview of Electrical Noise on 120/240 volt Power Systems. Dec 12,
Review of Electrical Noise on 120/240 volt Power Systems Dec 12, 2006 cforster@phasorlabs.com 1 The electrical noise this investigation covers are the frequencies other than 60 Hertz that exist on a typical
More informationCASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant
CASE STUDY Implementation of Ford Motor Company SA Silverton Plant 1 SCENARIO Ford Motor Company is a global automotive and mobility company based in Dearborn, Michigan. Ford Motor Company of Southern
More informationFrequently Asked Questions (FAQs) MV1000 Drive
QUESTION 1. What is a conventional PWM Inverter? 2. What is a medium voltage inverter? 3. Are all MV inverters Voltage Source (VSI) design? 4. What is a Current Source Inverter (CSI)? 5. What output power
More informationNew power tools provide quality and efficiency By
Typical Delta-wye transformer New power tools provide quality and efficiency By Steve Terry For quite some time, it has been well understood that phase-control SCR dimming systems used in the entertainment
More informationVARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY
VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY Carrier Corporation Syracuse, New York October 2005 TABLE OF CONTENTS INTRODUCTION... 2 Common VFD Terms
More information1C.4.1 Harmonic Distortion
2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope This handbook section contains of PacifiCorp s standard for harmonic distortion (electrical pollution) control, as well
More informationGlossary 78 LIFETIME LIMITED WARRANTY. GREENLEE Phone: (International)
A AC alternating current, or current that reverses direction at regular rate. When graphed, alternating current can appear as a series of curves, squares, or triangles. The shape of the graph is referred
More informationAlternators Reactance for Nonlinear Loads
Alternators Reactance for Nonlinear Loads Allen Windhorn. P.E. 26 July, 2013 Introduction Widespread invocation of IEEE Std 519 on systems powered by generators, together with increased use of equipment
More informationABB n.v. Power Quality Products, October 2014
ABB n.v. Power Quality Products, October 2014 Power Quality Harmonic Basics Problems and solutions March 19, 2015 Slide 1 828m high 160 floors in total Total 113 PQF in this tower, 12000A PQFS 45M IP30
More informationTOSHIBA International Corp
TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification
More informationDrives 101 Lesson 5. Power Input Terminology for a VFD
Drives 101 Lesson 5 Power Input Terminology for a VFD This lesson covers the terminology associated with the incoming power to a Variable Frequency Drive (VFD) and the efforts to protect both the VFD and
More informationPQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement
PQ01 Harmonic Solutions for VFD s Review of Power Control Harmonics, Power Factor, Distortion & Displacement Related Content at the Expo PQ02 Power Quality and Monitoring.. PQ03 Using Test Eqipment to
More informationGenerator Advanced Concepts
Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves
More informationSECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012
SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM Unit Objectives Describe the structure of an atom. Identify atoms with a positive charge and atoms with a negative charge. Explain
More informationPower Factor. Power Factor Correction.
Power Factor. Power factor is the ratio between the KW and the KVA drawn by an electrical load where the KW is the actual load power and the KVA is the apparent load power. It is a measure of how effectively
More information1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.
PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02
More informationTechnical Paper. Harmonic Distortion in Data Centers
Technical Paper Harmonic in Data Centers Written By: Ian Wallace Summary Power quality and power reliability are critical to data center operation. As strides have been made to improve energy efficiency
More information+ 24V 3.3K - 1.5M. figure 01
ELECTRICITY ASSESSMENT 35 questions Revised: 08 Jul 2013 1. Which of the wire sizes listed below results in the least voltage drop in a circuit carrying 10 amps: a. 16 AWG b. 14 AWG c. 18 AWG d. 250 kcmil
More informationHarmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez
Harmonic Power A VFDs.com Whitepaper Written by Ernesto Jimenez Table of Contents 1. Need for Clean Electricity 2. What Are Harmonics? 3. Lower Order Harmonics 4. Causes of Harmonics 5. Effects of Harmonics
More informationPOWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics
POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1 Control of Harmonics
More informationCapstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:
Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation
More informationDo You Have a Harmonic Problem?
??????? Do You Have a Harmonic Problem? Forster Electrical Engineering, Inc. 550 N. Burr Oak Ave, Oregon, WI 53575 (608) 835-9009 (608) 835-9039 fax 1 March 1999 What is THD? Total Harmonic Distortion
More informationFundamentals of Power Quality
NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»
More informationCHAPTER 4 HARMONICS AND POWER FACTOR
4.1 Harmonics CHAPTER 4 HARMONICS AND POWER FACTOR In this research a comparative study of practical aspects of mixed use of diode and Thyristor converter technologies in Aluminium Smelters has been carried
More informationAlternative Designs to Support Electronic Loads in Extensive UPS Distribution Systems
Alternative Designs to Support Electronic Loads in Extensive UPS Distribution Systems Philip J.A. Ling, P.Eng. Powersmiths International Corp. Toronto, Canada M1H 2X1 philip.ling@powersmiths.com Cyril
More informationHARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N
HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N Harmonic Basics 3 rd Harmonic Fundamental 5 t1h Harmonic 7 th Harmonic Harmonic
More informationDo Capacitor Switching Transients Still Cause Problems?
Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution
More informationHarmonic Analysis and Its Mitigation Using Different Passive Filters
Harmonic Analysis and Its Mitigation Using Different Passive Filters Ashlin Gloria Reginald 1, K J Thomas 2 1 PG Scholar, Amal Jyothi College of Engineering, Kanjirapally Kottayam, India ashlingloriar@gmail.com
More informationTECHNICAL BULLETIN 004a Ferroresonance
May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques
More informationPRODUCT FEATURES TYPICAL APPLICATIONS
The AVR voltage regulator and PLC power conditioner product lines consists of over 250 standard units arranged in 29 different voltage families to provide 95% coverage of day-to-day application needs.
More informationHarmonic Filters and Reactors
Harmonic Filters and Reactors Harmonics are invisible but costly If one looks up the meaning of harmonics in any one of several technical dictionaries, it is normally defined as being A sinusoidal component
More informationA. Harmonics. non-linear loads. are. required)
Harmonic Comparison between Fluorescent and WOLED (White Organic LED) Lamps Hari Maghfiroh, Fadhila Tresna Nugraha, and Harry Prabowo Abstract Fluorescent and WOLED are widely used because it consumes
More informationGrounding for Power Quality
Presents Grounding for Power Quality Grounding for Power Quality NEC 250.53 states that ground resistance should be less than 25 ohms. Is this true? Grounding for Power Quality No! NEC 250.53 states
More informationFluke 40/41 Power Harmonics Analysers
Data Pack A Issued March 2002 232-4752 Fluke 40/41 Power Harmonics Analysers This data sheet refers to the Fluke 40 and Fluke 41 Power Harmonics Analysers. RS stock no. Description 215-9621 Fluke 41B power
More informationSECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED
SECTION 16280 LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED PART 1 - GENERAL 1.1 SUMMARY This specification defines the requirements for active harmonic filter systems in order to meet IEEE-519-2014
More informationClamp Meter ABCs. Application Note. The transformer action
Clamp Meter ABCs What is a clamp meter and what can it do? What measurements can be made with a clamp meter? How do you get the most out of a clamp meter? Which clamp meter is best suited to the environment
More informationAlternator winding pitch and power system design
Our energy working for you. TM Power topic #5981 Technical information from Cummins Power Generation Alternator winding pitch and power system design White Paper Rich Scoggins Applications Engineering
More informationSHARDA Make Harmonics Filter
SHARDA Make Harmonics Filter SHARDA offers perfect solution to minimize Harmonics level of industries where non-linear load like, VFD, Electronics load, Convertors, Voltage booster equipment s are present.
More informationINTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs
INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection
More informationFluke Clamp Meters Solutions for every need
Fluke Clamp Meters Solutions for every need 381 355 773 more solutions inside Clamp Meter selection chart Job functions Applications Recommended clamp Process Technician/ Automation Specialist Multiple
More information