ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester

Size: px
Start display at page:

Download "ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester"

Transcription

1 ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester This report records the results of the design tests made on Type PVN Station Class surge arresters in accordance with IEEE Standard C IEEE Standard for Metal Oxide Surge Arresters for AC Power Circuits (> 1kV). To the best of our knowledge and within the usual limits of testing practices, tests performed on the Type PVN arresters demonstrate full compliance with the relevant clauses of the referenced standard. M.G. Comber Manager, Engineering Dennis W. Lenk P.E. Principal Engineer Date: July, 2001 Separate reports provide details of the tests, according to the following table: Report No. Description Clause Issue Date EU1295-H-01 Insulation Withstand 8.1 7/31/2001 EU1295-H-02 Discharge Voltage 8.3 7/31/2001 EU1295-H-03 Disc Accelerated Aging 8.5 7/31/2001 EU1295-H-04 Polymer Accelerated Aging 8.6 7/31/2001 EU1295-H-05 Contamination 8.7 7/31/2001 EU1295-H-06 Internal Ionization and RIV 8.9 7/31/2001 EU1295-H-07 High Current, Short Duration /31/2001 EU1295-H-08 Transmission Line Discharge /31/2001 EU1295-H-09 Duty Cycle /31/2001 EU1295-H-10 Temporary Overvoltage /31/2001 EU1295-H-11 Pressure Relief /31/2001 EU1295-H-12 Maximum Design Cantilever Load-Static /31/2001 EU1295-H-13 Thermal Equivalency Test /31/2001

2 TYPE TEST REPORT No. EU1295-H-01 Insulation Withstand Tests on PVN Arrester Housing CERTIFICATION This is to certify that insulation withstand design tests have been successfully performed on Ohio Brass Type PVN Station Class surge arresters. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W. Lenk P.E. Principal Engineer July, 2001 Attachments

3 DESIGN TEST REPORT Type PVN Station Class Surge Arrester TITLE: Arrester Insulation Withstand Tests: INTRODUCTION: The following table lists the Type PVN arresters minimum strike distance, 1.2/50 required and actual impulse withstand levels, and 60 HZ required and actual dry and wet withstand levels as defined in Section of IEEE C Standard.. CONCLUSION: All housings meet or exceed these levels of voltage. 60 HZ 60 HZ 60 HZ 60 HZ Strike Imp w/s Imp w/s Dry w/s Dry w/s Wet w/s Wet w/s Arrester Distance Req d Actual Req d Actual Req d Actual MCOV (in) (KVc) (KVc) (kvrms) (kvrms) (kvrms) (kvrms)

4 TYPE TEST REPORT No. EU1295-H-02 Discharge Voltage Characteristic CERTIFICATION This is to certify that the discharge voltage characteristic design tests have been successfully performed on Ohio Brass Type PVN Station Class surge arresters. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W. Lenk P.E. Principal Engineer July, 2001 Attachments

5 TITLE: Discharge-voltage characteristic DESIGN TEST REPORT Type PVN Station Class Surge Arrester TEST OBJECTIVE: These measurements are used to obtain the maximum discharge voltages at various current magnitudes and waveshapes. TEST PROCEDURE: Discharge voltage tests were performed on three prorated test samples consisting of two MOV disks, an aluminum end terminal, solid steel spacer, and contact spring plate. The material selection and configuration facilitated an accurate proratio of inductive and resistive effects of all components in the impulse path of a full arrester. Tests were conducted in accordance with clause 8.3 of ANSI/IEEE Standard C IEEE Standard for Metal-Oxide Surge Arresters for AC Power Circuits (>1kV). Prorated test sections were subjected to 8/20 current waves with magnitudes ranging from 1.5 ka through 20 ka. In addition, Front-of-wave and switching surge discharge voltage tests were performed. TEST SAMPLES: Arresters are assembled from discs accumulated within 10 ka IR ranges as specified for each arrester rating. To verify catalog maximum IR levels were not exceeded, a discharge voltage ratio was established at each current level based on the test sections 10 ka IR (Table 2). That ratio was multiplied by the maximum 10 ka IR accumulation specified for each rating. As summarized on Table 3, the IR calculated based on the prorated test sections were under the maximum declared catalog levels. TEST RESULTS: The following oscillograms show the results of the individual discharge voltage tests. At the end of this section, a summary table compares the catalog protective characteristics versus the measured values extrapolated from the test data. The test specimen with a 10 Ka 8/20 IR of Kv represents the maximum discharge voltage for a 3.85 Kv rms Type PVN arrester. A. 8/20 Discharge Voltage Oscillograms: Tests were performed per Section for nominal 8/20 discharge current waveshapes Ka, 9.46 Kv, 8.4/18.0 2

6 3.14 Ka, Kv, 8.0/ Ka, Kv, 8.6/ Ka, Kv, 8.6/18.8 3

7 19.94 Ka, Kv, 8.8/ Ka, Kv, 8.8/20.3 B. FOW Oscillograms: Tests were performed per Section for nominal 10 Ka current surges with times to voltage crest approaching.5 microseconds Ka 3.0 us Kv 2.7 us 3.0/6.8 waveshape 4

8 10.03 Ka 1.5 us Kv 1.3 us 1.5/3.3 wavashape Ka us Kv us.85/1.9 waveshape C. Switching Surge Oscillograms: Tests were performed per Section for switching surge current magnitudes of 500 and 1000 amps. 5

9 514 Amps, 8.74 Kv, 49.3/ Amps, 9.11 Kv, 41.2/89.6 6

10 Arrester MCOV PROTECTIVE CHARACTERISTICS COMPARISON TABLE 10 ka FOW IR Catalog Max. (kv) 10 ka FOW IR Prorated Measured (kv) (1) Amp SS IR Catalog Max. (kv) (1) Amp SS IR Prorated Measured (kv) 10 ka 8/20 IR Catalog Max. (kv) 10 ka 8/20 IR Prorated Measured (kv) 40 ka 8/20 IR Catalog Max. (kv) 40 ka 8/20 IR Prorated Measured (kv) (*) Measured prorated discharge voltage at specified waveshapes equals (arrester MCOV/3.85) times disc measured IR at the specified waveshape. (1) 500 amp IR for kv MCOV; 1kA IR for kv MCOV. 7

11 TYPE TEST REPORT No. EU1295-H-03 Disc Accelerated Aging CERTIFICATION This is to certify that the disc accelerated aging design tests have been successfully performed on Ohio Brass Type PVN Station Class Surge arresters. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W. Lenk P.E. Principal Engineer July, 2001 Attachments

12 TITLE: Accelerated aging procedure DESIGN TEST REPORT PVN Station Class Surge Arrester INTRIODUCTION: This test is performed to measure the mov disc aging characteristic. The measured watts values are used to develop elevated voltage ratios kc and kr which are used in the duty cycle and discharge current withstand tests to simulate the performance of arresters that have a service life equivalent to 1000 hours at 115 o C. SAMPLE PREPARATION: Three 60 mm diameter x 23 mm long discs and three 60 mm diameter x 41 mm long discs were selected for testing. The three 23 mm long discs are designated as samples #1, 2, & 3 while the 41 mm long discs are designated as samples #4, 5, & 6. TEST RESULTS: The test was performed per Section 8.5 of ANSI/IEEE C Standard. The three test samples were placed inside a 115 plus/minus 2 o C. oven and energized at MCOV for 1000 hours. The watts loss of each sample was measured at MCOV and duty cycle rated voltage three hours after energization and at the completion of the 1000 test duration. The following table summarizes the results of the 1000 hour accelerated aging tests. All watts values were measured with the samples at 115 o C. INITIAL FINAL INITIAL FINAL SAMPLE WATTS WATTS WATTS CONCLUSION: For each test sample, the final watts loss at MCOV and rating is less than the initial watts measured. Therefore, the kc and kr factors equals 1.0 in the design tests requiring demonstration of thermal stability. 2

13 TYPE TEST REPORT No. EU1295-H-04 Polymer Accelerated Aging CERTIFICATION This is to certify that the polymer accelerated aging design tests have been successfully performed on Ohio Brass Type PVN Station Class surge arresters. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W. Lenk P.E. Principal Engineer July, 2001 Attachments

14 DESIGN TEST REPORT PVN Station Class Surge Arrester TITLE: Accelerated aging tests of external polymeric insulating systems : INTRODUCTION: This test was performed per Section 8.6 of IEEE Standard C TEST PROCEDURE: Accelerated aging tests by exposure to light were performed per Section 8.6.1, Test Method c). Tests were performed on polymer housing and insulating bracket material using the fluorescent UV technique described in ASTM G Test duration was 1000 hours on three samples of each material. Accelerated aging tests by exposure to electrical stress were performed per Section Three PVN arrester housing configurations were tested. Each housing configuration consisted of (2) 8.4 kv MCOV housings connected together with the insulating collar used to assemble higher rated arresters. The total MCOV rating of this housing configuration is 16.8 kv rms. The specification requires that the applied test voltage represent the highest gradient stress per mm of creepage distance. To achieve this required high gradient, the arrester internal mov disc elements were removed and replaced with an insulating core. This allowed the applied voltage of 30 kvrms to be applied without failing the test sample. This represents the highest MCOV stress based on leakage distance. Tests were performed by attaching arresters to a vertical ferris wheel. As the wheel rotates, each arrester is sequentially dipped into a 400 ohm-centimeter water bath. Each arrester is allowed to drip-off excessive contaminant and is then energized at MCOV to force the arrester housing into a dry banding condition. The arrester test is performed until each arrester has been subjected to 1000 hours on voltage. Results: Per Section 8.6.1, the polymer material passed the test requirement as there were no cracks greater than the allowed.1 mm depth. Per Section 8.6.2, the specimens passed this test as there was no evidence of external flashovers, punctures, or internal breakdowns during the described tests. There was no evidence of surface tracking on the arrester housings or the insulating collars after the 1000 hour on-voltage test. The required 10 ka IR measurements could not be performed on these arresters as the internal mov discs had been replaced by an insulating section so that the required high voltage stress could be applied to the arrester housings during the 1000 hour test. Conclusion: The PVN arrester housing design has met the accelerated aging requirements as specified in Section 8.6 of IEEE C Standard. 2

15 TYPE TEST REPORT No. EU1295-H-05 Contamination Test CERTIFICATION This is to certify that the contamination design test has been successfully performed on Ohio Brass Type PVN Station Class surge arresters. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W. Lenk P.E. Principal Engineer July, 2001 Attachments

16 TITLE: Contamination tests: DESIGN TEST REPORT PVN Station Class Surge Arrester INTRODUCTION: This test was performed per Section 8.7 of IEEE Standard C The tests were performed on a three unit (144 kv MCOV size) and a four unit (180 kv MCOV size) arrester. TEST PROCEDURE: The partial wetting test procedure was performed per Section of C Standard. Prior to the application of contaminant (455 ohm-cm resistivity), the arrester was energized at MCOV for 1 hour. After 1 hour of energization, the arrester was de-energized and slurry contaminant was applied over the entire porcelain surface of the bottom half of the arrester. After a 2-3 minute wait, the arrester was energized at MCOV for 15 minutes, at which time the voltage was turned off and the bottom half of the arrester resprayed with contaminant. Within 5 minutes of deenergization, the arrester was reenergized at MCOV. After 15 minutes, the arrester resistive component of current was recorded. After 30 additional minutes at MCOV, remeasurement of the resistive current confirmed thermal stability and the test was completed. TEST RESULTS: In both cases, the arresters demonstrated thermal stability after the second partial wetting test series. No unit or arrester flashover occurred during the above testing. Disassembly of the test arresters revealed no damage to the internal components as a result of the partial wetting contamination test. 2

17 TYPE TEST REPORT No. EU1295-H-06 INTERNAL IONIZATION and RIV CERTIFICATION This is to certify that the internal ionization and RIV design tests have been successfully performed on Ohio Brass Type PVN Station Class surge arrester. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W. Lenk P.E. Principal Engineer July, 2001 Attachments

18 DESIGN TEST REPORT PVN Station Class Surge Arrester TITLE: Internal-ionization voltage (IIV) and RIV tests: TEST PROCEDURE AND SAMPLE: Internal ionization and RIV testing was performed per clause 8.9 of IEEE Standard C The test was performed on a 180 kv MCOV PVN arrester. TEST EQUIPMENT: Equipment and test methods conformed to NEMA LA requirements. Prior to the test, the Stoddart Noise Meter NM-25T was calibrated using a General Radio Signal Generator Type 1001-A. TEST RESULTS: A background noise level of 5 µv was measured at an open circuit voltage of 189 kv (105%MCOV). With the 180 kv arrester placed in the circuit, a noise level of 7 µv was measured. CONCLUSION: The 180 kv MCOV PVN arrester passed test requirements per Section 8.9 of IEEE C Standard, as measured noise levels were within the 10 µv IIV test limit. 2

19 TYPE TEST REPORT No. EU1295-H-07 HIGH CURRENT, SHORT DURATION TEST CERTIFICATION This is to certify that the high current, short duration design test has been successfully performed on Ohio Brass Type PVN Station Class surge arrester. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W.Lenk P.E. Principal Engineer July, 2001 Attachments

20 DESIGN TEST REPORT PVN Station Class Surge Arrester TITLE: High Current, Short Duration Discharge Withstand Test SAMPLE PREPARATION: This test was performed per Section of ANSI/IEEE Standard C The test was performed on a thermally prorated section of a full size arrester. The MCOV and duty cycle rating of the prorated section are assigned to represent the most severe condition; i.e., the minimum allowed discharge voltage level. TEST PROCEDURE: Before and after the high current, short duration test, the 10 KA 8/20 discharge voltage of the test sample was measured. The test sample was subjected to (2) 100 KA 4/10 discharges. Sufficient time was allowed between discharges for the sample to cool to ambient temperature (25oC.). Within 5 minutes after the second high current discharge, the sample remained energized at MCOV and the sample watts loss was monitored until thermal stability was demonstrated. TEST RESULTS: The prorated section was subjected to two nominal 100KA 6.2/13.2 high current discharges. The following traces show the actual current values. Discharge # 1 (108.1KA) Discharge # 2 (105.4KA) 2

21 Within 5 minutes of the second high current discharge, the sample was energized at times MCOV (12.25KV RMS). The sample remained energized until thermal stability was demonstrated. The following table summarizes the measured watts of the test sample during the recovery portion of the test. Applied Voltage Time Sample (KV RMS) (Minutes) Watts ======== ======== ====== The sample 10 KA 8/20 discharge voltage was measured before and after the high current test. The measured values are summarized below. 10 KA IR Before = KV 10 KA IR After = KV 3

22 TEST SUMMARY: The prorated test sample successfully completed the high current test and demonstrated thermal stability during the recovery test when energized at MCOV. The 10 KA 8/20 discharge voltage changed an acceptable +0.6%, within the allowable 10% acceptance limit. Disassembly revealed no evidence of physical damage to the test sample. Therefore, the test sample has successfully fulfilled the high current, short duration requirements of the Station Class arrester. 4

23 TYPE TEST REPORT No. EU1295-H-08 TRANSMISSION LINE DISCHARGE TEST CERTIFICATION This is to certify that the transmission line discharge design test has been successfully performed on Ohio Brass Type PVN Station Class surge arrester. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W. Lenk P.E. Principal Engineer July, 2001 Attachments

24 DESIGN TEST REPORT PVN Station Class Surge Arrester TITLE: Transmission Line Discharge Test: SAMPLE PREPARATION: This test was performed per Section of ANSI/IEEE Standard C The test was performed on a thermally prorated section of a full size arrester. The MCOV of the prorated section is assigned to represent the most severe condition; i.e., the minimum allowed discharge voltage level. TEST PARAMETERS: The test setup is intended to model a 140 kv MCOV arrester applied on a 230 kv system. The system parameters were derived from Table 5 of the C62.11 Standard. The system and prorated section parameters are defined as follows: System Surge Impedance System Charge System Capacitance Line Length Equivalent Duration (TD)* Prorated Test Sample MCOV 400 Ohm 513 kv 2.45 Microfarad 175 Miles 1890 Microseconds 8.97 kv RMS Proratio Factor (K) Required Generator Surge Impedance Required Generator Charge Required Generator Capacitance Measured Generator Impedance (Zg) Measured Line Discharge Duration Equivalent Generator Line Length Ohm kv 38.2 Microfarad 20.8 Ohm 1983 Microseconds 184 Miles Number of Generator Sections 16 *TD = miles times

25 Test Procedure Before and after the transmission line discharge test, the 10 ka 8/20 discharge voltage of the test sample was measured. The procedure was performed per Section of the C62.11 Standard. The procedure consisted of subjecting the test specimen to three groups of six consecutive operations followed by one group of two operations with a time interval between consecutive operations of one minute. The test specimen was allowed to cool to ambient between Shots No. 6 and No. 7 and between Shots No. 12 and No. 13. After the eighteenth shot, the test sample was placed inside an oven and heated to 66 o C. After the heated test sample was subjected to Shots No. 19 and No. 20, the sample was energized at 1.04 times mcov and thermal stability was demonstrated. TEST RESULTS: Figure No. 1 measures the surge impedance and confirms the duration of the transmission line generator. Figure 1 Zg = kv/808 Amps Zg = 20.8 Ohms Duration = 184 Miles Figure 2 is an oscillographic record of the first transmission line discharge through the test sample. 3

26 Figure 2 Shot 1 After successful completion of the (18) shot test, the sample was preheated to 60 o C. and subjected to two additional transmission line discharges spaced one minute. Figure No. 3 is an oscillographic record of the 20th shot. Figure 3 Shot 20 After the 20th shot, the sample was energized at 1.04 times MCOV ( 9.33 kv RMS ). The sample remained energized until thermal stability was demonstrated. The following table summarizes the measured watts of the test sample during the recovery portion of the test. 4

27 Applied Voltage Time Sample (kv RMS) (Minutes) Watts The sample 10 ka 8/20 discharge voltage was measured before and after the duty cycle test. The measured values are summarized below. 10 ka IR Before = kv 10 ka IR After = kv CONCLUSION: The prorated test sample successfully completed the transmission line discharge test and demonstrated thermal stability during the recovery test when energized at 1.04 times MCOV. The 10 ka 8/20 discharge voltage changed an acceptable +.7%, within the allowable 10% acceptance limit. Disassembly revealed no evidence of physical damage to the test sample. Therefore, the test sample has successfully fulfilled the transmission line discharge requirements of a PVN 140 kv MCOV Station Class arrester applied to a 230 kv system. 5

28 TYPE TEST REPORT No. EU1295-H-09 DUTY CYCLE TEST CERTIFICATION This is to certify that the duty cycle design test has been successfully performed on Ohio Brass Type PVN Station Class surge arrester. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W. Lenk P.E. Principal Engineer July, 2001 Attachments

29 TITLE: Duty Cycle Test: DESIGN TEST REPORT PVN Station Class Surge Arrester TEST OBJECTIVE: Section specifies that the 20-shot rated voltage and 2-shot recovery portion of the Duty Cycle test on Intermediate Class arresters be performed with 5 ka 8/20 lightning impulses. The actual Duty Cycle tests were performed per the more severe Heavy Duty Distribution arrester requirements, which subjects the test sample to 20-10kA impulses and then 2-40 ka impulses during the recovery portion of the Duty Cycle test. SAMPLE PREPARATION: This test was performed per Section 8.7 of ANSI/IEEE Standard C The test was performed on a thermally prorated section of a full size arrester. The MCOV and duty cycle rating of the prorated section are assigned to represent the most severe condition; i.e., the minimum allowed discharge voltage level. TEST PROCEDURE: Before and after the duty cycle test, the 10 KA 8/20 discharge voltage of the test sample was measured. The test sample was then energized at duty cycle rated voltage and subjected to (20) 10 KA 8/20 discharges spaced one minute apart. Per the standard, these 5 KA discharges were electrically timed to occur at approximately 60o before 60-Hz voltage crest. The test sample was next preheated to 60oC. and subjected to two additional 5 KA 8/20 duty cycle operations while energized at MCOV. After the second duty cycle operation, the sample remained energized at MCOV and the sample watts loss was monitored until thermal stability was demonstrated. TEST RESULTS: The prorated section was energized at duty cycle rated voltage ( KV RMS ) and subjected to (20) 10 KA surges spaced one minute apart. The sample watts was monitored throughout the test. The watts increased from 30 after the first discharge to 124 immediately after the twentieth discharge. Figure 1 illustrates a typical duty cycle discharge operation. Figure 1 2

30 After successful completion of the (20) shot test, the sample was preheated to 60oC. and subjected to two additional 10 KA surges spaced one minute apart with the sample energized at 1.05 times MCOV ( 12.2 KV RMS ). The sample remained energized after the second 10 KA surge until thermal stability was demonstrated. The following table summarizes the measured watts of the test sample during the recovery portion of the test. Applied Voltage Time Sample (KV RMS) (Minutes) Watts ======== ======== ====== The sample 10 KA 8/20 discharge voltage was measured before and after the duty cycle test. The measured values are summarized below. 10 KA IR Before = KV 10 KA IR After = KV 3

31 TEST SUMMARY: The prorated test sample successfully completed the duty cycle test and demonstrated thermal stability during the recovery test when energized at 1.05 times MCOV. The 10 KA 8/20 discharge voltage changed an acceptable +.1%, within the allowable 10% acceptance limit. Disassembly revealed no evidence of physical damage to the test sample. Therefore, the test sample has successfully fulfilled the duty cycle requirements of the Station Class arrester. 4

32 TYPE TEST REPORT No. EU1295-H-10 TEMPORARY OVERVOLTAGE TEST CERTIFICATION This is to certify that the temporary overvoltage design test has been successfully performed on Ohio Brass Type PVN Station Class surge arrester. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W. Lenk P.E. Principal Engineer July, 2001 Attachments

33 DESIGN TEST REPORT PVN Station Class Surge Arrester TITLE: Temporary over-voltage tests (TOV): INTRODUCTION: This test was performed per Section 8.12 of IEEE Standard C The tests were performed on (5) prorated test samples, selected to represent the most severe design conditions, i.e., the minimum allowed discharge voltage level. TEST PROCEDURE: Per Section , each prorated sample is tested in (5) different time ranges ranging from ( seconds) to ( ,000 seconds). Per Section , the test is performed to demonstrate the temporary overvoltage capability of the design under "no prior duty" conditions. For each TOV voltage setting, the test circuit applies the voltage to the sample (preheated to 60oC) for a time duration sufficient to exceed that claimed on the "no prior duty" curve. Within 100 milliseconds after the TOV, a recovery voltage is applied for (30) minutes to demonstrate thermal stability. The recovery voltage level takes into account the maximum allowed watts loss for the sample. Prior to and after the TOV application, the 10 ka discharge voltage of each sample is measured. TEST RESULTS: Tests were successfully completed on (5) prorated samples in the required (5) time ranges. Each sample demonstrated thermally stability after TOV exposure. The 10 ka 8/20 discharge voltage of each sample changed less than 1.0 as a result of the TOV duty. There was no evidence of physical damage caused by the TOV testing. The following table summarizes the claimable TOV values for kv rated PVN arresters for "no prior" and "prior" duty conditions. TOV DURATION NO PRIOR DUTY TOV PRIOR DUTY TOV (SECONDS) (PER UNIT MCOV) (PER UNIT MCOV) ============= ================== ================ The following curve plots the individual "no prior duty" TOV data points on the claimed TOV capability curve. 2

34 PVN 60 HZ TEMPORARY OVERVOLTAGE CAPABILITY CURVE PER IEEE C62.11 STANDA Per Unit Times MCOV Time-Seconds Data Points No Prior Duty Curve Prior Duty Curve 3

35 TYPE TEST REPORT No. EU 1295-H-11 PRESSURE RELIEF TEST CERTIFICATION This is to certify that the pressure relief design test has been successfully performed on Ohio Brass Type PVN Station Class surge arrester. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W. Lenk P.E. Principal Engineer July, 2001 Attachments

36 DESIGN TEST REPORT PVN Station Class Surge Arrester TITLE: Pressure Relief Test For Polymer Housed Station Class Arrester: INTRODUCTION: The high current and low current pressure relief tests were performed per Section 8.13 of ANSI/IEEE C Standard. For the high current tests, an additional timed reclose was performed on each test specimen approximately 20 cycles after completion of the required 12 cycle test. The high current tests were performed in the IREQ High Power Laboratory in Montreal on March 2, SAMPLE PREPARATION: Per Section , fuse wire was used to short out the mov disc elements. Two shorting methods were used. The "shorted" mode of failure consisted of externally locating a fuse wire along the outside contour of the stack of mov disc elements between the mov discs and the fiberglass-epoxy wrap. The "puncture" mode of failure consisted of drilling a 4 mm diameter hole through the center of each mov disc and then running a wire through the center of the stack of discs. For the high current tests, the longest available single unit arrester ( 48 kv MCOV ) was tested. TEST PROCEDURE: To achieve the high levels of fault current, the high current pressure relief tests were performed per Section with a reduced voltage source of 11.1 kv rms. Since the arrester arc resistance can significantly affect the required asymmetry, the claimable symmetrical rms current for the high current test procedure is calculated by dividing the 1st loop peak current by 2.6. The low current pressure relief tests were performed per Section TEST RESULTS: The following table summarizes the results of the pressure relief testing. The low current sample successfully vented within.23 seconds after fault initiation. The high current tests were performed on the longest arrester units. In addition to the initial 12 cycle fault current duty required per the standard test procedure, both the "punctured" and the "shorted" test samples were immediately subjected to a fault current reclose condition. Both arresters successfully vented. The highest claimable symmetrical fault current of 83.4 ka rms for 12.5 cycles, followed in 20 cycles by a claimable 81.5 ka rms 3 cycle reclose was recorded on the "shorted" design. The lower peak ka values recorded on the "punctured" arrester configuration were the result of the high arc resistance of that design when subjected to the reduced voltage test procedure. Initial Fault Reclose Fault =========================== =========================== 1 st 1st Mode Test Loop Actual Claimable Fault Loop Act Fault Condition Sample of Voltage Peak Symm. Symm. Durat. Peak Sym Durat. Of Sample MCOV Failure (kvrms) (kac) (karms) (karms) (Cyc) (kac) (karms) (Cyc) After Test ===== ==== ===== === ===== ====== ==== === ===== ==== =========== 2.55 Shorted Module Intact Housing Split 48 Shorted Module Intact Hsg Separated 48 Punctured Module Intact Hsg Separated 2

37 TYPE TEST REPORT No. EU1295-H-12 MAXIMUM DESIGN CANTILEVER LOAD-STATIC TEST CERTIFICATION This is to certify that the maximum design cantilever load-static design test has been successfully performed on Ohio Brass Type PVN Station Class surge arrester. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W. Lenk P.E. Principal Engineer July, 2001 Attachments

38 DESIGN TEST REPORT PVN Station Class Surge Arrester TITLE: Maximum Design Cantilever Load-Static Test TEST SAMPLES: The maximum design cantilever load (static) test was performed on a PVN 19.5 kv MCOV arrester. Tests were performed to validate the claimed 10,000 inch-pound continuous cantilever rating. TEST PROCEDURE: Testing was performed per the procedures specified in Section of IEEE Std C The test arrester was rigidly mounted at its base and top end loading applied to develop 10,000 inch-pound cantilever load. With the arrester under load, the arrester was energized at 1,05 times MCOV and internal ionization was measured. Successive testing was performed at 0 o, 90 o, 180 o, and 270 o. Per paragraph d), the arrester was placed inside a thermal cycling oven for 96 hours and subjected to a combination of 10,000 inch-pound load rotations and temperature excursions as specified in Figure 3 of C Standard. After completion of the thermal cycling test, the IIV was remeasured in the four quadrants with the arrester energized at 1.05 times MCOV. TEST RESULTS: The following table summarizes the results of the IIV tests with.6 microvolts of circuit background noise. Arrester # Direction of Applied 1200 in-lb Load (Degrees) IIV Testing Prior to and After Thermal Cycling 1.05 Times MCOV before Thermal Cycling (Microvolts) 1.05 Times MCOV after Thermal Cycling (Microvolts) CONCLUSION: Per Section , the internal ionization levels measured with the arrester loaded to 10,000 inch-pounds were unchanged as a result of the thermal cycling test. Visual examination revealed no evidence of mechanical damage. The above tests validated the electrical integrity of the PVN arrester assembled with a 3-lug base end casting when loaded to the 10,000 inch-pound continuous cantilever rating 2

39 TYPE TEST REPORT No. EU 1295-H-13 VERIFICATION OF THERMALLY PRORATED SECTION CERTIFICATION This is to certify that verification tests demonstrating thermal equivalency were successfully performed on Ohio Brass Type PVN Station Class surge arrester. Michael G. Comber Manager Engineering Ohio Brass & Chardon Products Dennis W. Lenk P.E. Principal Engineer July, 2001 Attachments

40 DESIGN TEST REPORT PVN Station Class Surge Arrester TITLE: Verification of thermally prorated arrester section: OBJECTIVE: Tests were performed per IEEE Standard C62.11 to validate the thermally prorated arrester section used on specified durability tests. TEST SAMPLES: The longest PVN module was assembled with thermocouples located in the bottom quarter, center, and upper quarter locations. The average temperature of the three thermocouples was compared with the temperature of the thermally prorated section. In both cases, thermocouples were located between two adjacent MOV disks. The longest module was chosen to represent the highest percent MOV mass per unit arrester length. TEST PROCEDURE: The full size arrester and the prorated section were heated up by applying a temporary overvoltage to the test samples. The full size arrester unit was instrumented with three (3) internal thermocouples, located at 1/4, 1/2, and 3/4 locations in the mov disc stack. The average temperature of the three arrester thermocouples was calculated for each 5 minute interval to develop the arrester unit cooling curve. The prorated section was instrumented with a single thermocouple and its cooling rated monitored at 5 minute intervals. CONCLUSION: Upon achieving the desired target temperature, the thermocouples were attached to a data logger and temperature was monitored continuously for 120 minutes. Figure 1 contains cooling curves verifying the longest PVN module arrester cooling rate was always greater than the prorated thermal test section. 120 Figure 1 TYPE PVN ARRESTER THERMAL COOLING CURVES FOR ARRESTER VERSUS PRORATED SECTION TEMPERATURE-DEG C COOLING TIME-MINUTES PRORATED SECTION TEMP AVERAGE ARRESTER TEM 2

UltraSIL Polymer-Housed VariSTAR Normal-Duty, Heavy-Duty and Riser Pole Distribution-Class Arresters

UltraSIL Polymer-Housed VariSTAR Normal-Duty, Heavy-Duty and Riser Pole Distribution-Class Arresters File Ref: Cat. Sec. 235-35 UltraSIL Polymer-Housed VariSTAR Normal-Duty, Heavy-Duty and Riser Pole Distribution-Class Arresters Bulletin 95062 September 2012 Supersedes 04/09 2012 Cooper Industries. All

More information

Effective February 2017 Supersedes January 2012 (CP1122)

Effective February 2017 Supersedes January 2012 (CP1122) File Ref: Cat. Sec. CA235013EN CT235003EN Supersedes January 2012 (CP1122) COOPER POWER SERIES UltraSIL Polymer-Housed VariSTAR Type US, UH, and UX Station Class Surge Arresters Certified Test Report Certification

More information

UltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report

UltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report CP No.: CP0804 Page: 1 of 20 UltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report October 2014 Supersedes 09/11 2014 Eaton CP No.: CP0804 Page: 2 of 20 UltraSIL Polymer-Housed

More information

IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4

IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 This report records the results of type tests made on H4 series 20 ka Line Discharge Class

More information

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER Analysis of Major Changes to Arrester Standards IEC 60099-4 STEVE BREWER Analysis of Major Changes to Arrester Standard IEC 60099-4 Steve Brewer- Senior Product Manager - HPS Arrester Business Unit Agenda

More information

Eaton s Cooper Power Series DEADFRONT ARRESTERS

Eaton s Cooper Power Series DEADFRONT ARRESTERS File Ref: 235-65, 235-68, 235-97, 235-101 Effective June 2015 CT235001EN Supersedes CP9314 May 2011 CERTIFIED TEST REPORT Eaton s Cooper Power Series DEADFRONT ARRESTERS CT235001EN Supersedes CP9314 May

More information

CLU Arrester. Certified Test Report. IEEE Standard C

CLU Arrester. Certified Test Report. IEEE Standard C CP No.: CP0605 Page 1 of 8 CLU Arrester Certified Test Report IEEE Standard C62.11-1999 CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the

More information

COOPER POWER. UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge Class 2 SERIES

COOPER POWER. UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge Class 2 SERIES Surge Arresters CA235033EN Supersedes February 2012 (I235-92) COOPER POWER SERIES UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge General Eaton

More information

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

VariSTAR Type AZL heavy-duty distribution-class MOV arrester Surge s Catalog Data CA235006EN Supersedes TD235007EN September 2014 COOPER POWER SERIES VariSTAR Type AZL heavy-duty distribution-class MOV arrester General Eaton incorporates the latest in metal oxide

More information

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv DMX-N gapless metal oxide surge arresters DMX-N surge arresters are used for the protection of switchgear, transformers and other equipment

More information

VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester

VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester Surge Arresters Catalog Data CA235016EN Supersedes TD235001EN September 2014 COOPER POWER SERIES VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester General Eaton's Cooper Power

More information

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester s Catalog Data CA3508EN Supersedes November 015 COOPER POWER SERIES POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) General Eaton s Cooper Power series POSI-BREAK M.O.V.E. surge arrester combines metal

More information

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester Surge Arresters Catalog Data CA235025EN Supersedes November 2015 COOPER POWER SERIES Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester General Eaton combines metal (zinc) oxide varistor technology in

More information

Surge Arresters. VariSTAR Type AZS Normal Duty Distribution Class MOV Arrester

Surge Arresters. VariSTAR Type AZS Normal Duty Distribution Class MOV Arrester Surge rresters VariSTR Type ZS Normal Duty Distribution Class MOV rrester Electrical pparatus 235-73 GENERL The Cooper Power Systems VariSTR Type ZS normal duty distribution class MOV arrester (Figure

More information

35 kv Class M.O.V.E. DirectConnect elbow arrester

35 kv Class M.O.V.E. DirectConnect elbow arrester Surge Arresters Catalog Data CA235026EN Supersedes November 2015 COOPER POWER SERIES 35 kv Class M.O.V.E. DirectConnect elbow arrester General Eaton's Cooper Power series M.O.V.E. DirectConnect elbow arrester

More information

Substation Design Volume VII

Substation Design Volume VII PDHonline Course E474 (5 PDH) Substation Design Volume VII Other Major Equipment Instructor: Lee Layton, P.E 2015 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088

More information

SURGE ARRESTERS AND TESTING. Keith Hill Doble Engineering Company

SURGE ARRESTERS AND TESTING. Keith Hill Doble Engineering Company SURGE ARRESTERS AND TESTING Keith Hill Doble Engineering Company Surge arresters are often overlooked when performing Power Factor tests on transformers, breakers and other apparatus in a substation. Often

More information

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS -1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification

More information

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS AMENDMENT NO. 1 SEPTEMBER 2011 TO IS 15086 (Part 1) : 2001/IEC 60099-1 (1991) SURGE ARRESTORS PART 1 NON-LINEAR RESISTOR TYPE GAPPED SURGE ARRESTORS FOR a.c. SYSTEMS (The Amendment was originally published

More information

Evaluating the Response of Surge Arresters

Evaluating the Response of Surge Arresters 1 Jens Schoene Chandra Pallem Tom McDermott Reigh Walling Evaluating the Response of Surge Arresters to Temporary Overvoltages Panel Session of the IEEE Wind and Solar Collector Design Working Group 2014

More information

Energy Division. Bowthorpe LV/MV Surge Arresters

Energy Division. Bowthorpe LV/MV Surge Arresters Energy Division Bowthorpe LV/MV Surge Arresters Bowthorpe EMP LV/MV surge arresters OCP, Open Cage Polymeric series Bowthorpe pioneered the development of polymeric housed surge arresters in the early

More information

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical

More information

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable: Reclosers NOVA Three-Phase Recloser Functional Specification Guide Functional specification for NOVA three-phase recloser 1. Scope This specification describes the features and ratings of the NOVA recloser.

More information

Tab 8 Surge Arresters

Tab 8 Surge Arresters s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION 1. SCOPE : TECHNICAL SPECIFICATION FOR LIGHTNING ARRESTORS 1.1. This Specification covers design, manufacture, testing at manufacturer's Works, packing, supply, delivery of 42 KV

More information

EE 1402 HIGH VOLTAGE ENGINEERING

EE 1402 HIGH VOLTAGE ENGINEERING EE 1402 HIGH VOLTAGE ENGINEERING Unit 5 TESTS OF INSULATORS Type Test To Check The Design Features Routine Test To Check The Quality Of The Individual Test Piece. High Voltage Tests Include (i) Power frequency

More information

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc. Surge Arresters Secondary Arresters and Protective Gaps Electrical Apparatus 235-10 GENERAL INFORMATION The necessity of providing surge arrester protection on low-voltage circuits is fundamentally the

More information

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s Designed for Partial Discharge Analyzers (PDA s) monitoring rotating machinery or other medium-voltage equipment from 1 to 35 kvac RMS at power-line frequencies of 10 Hz to 1 khz, Mica Capacitor Type 297

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L. /9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

ArresterFacts-002. Field Testing Arresters ArresterWorks.com. ArresterFacts are information modules pertaining to the arrester world.

ArresterFacts-002. Field Testing Arresters ArresterWorks.com. ArresterFacts are information modules pertaining to the arrester world. ArresterFacts are information modules pertaining to the arrester world. This Field Testing of Arresters module will clarify the many questions about assessing the quality of an installed high voltage arrester

More information

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED LIGHTNING ARRESTOR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, SectorII, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;

More information

PRODUCT SPECIFICATION. This specification defines the performance, test, quality and reliability requirements of the PwrBlade ULTRA product.

PRODUCT SPECIFICATION. This specification defines the performance, test, quality and reliability requirements of the PwrBlade ULTRA product. 1 of 10 B 1.0 Objective This specification defines the performance, test, quality and reliability requirements of the PwrBlade ULTRA product. 2.0 Scope This specification is applicable to the termination

More information

Great Northern Transmission Line: Behind the (Electrical) Design

Great Northern Transmission Line: Behind the (Electrical) Design Great Northern Transmission Line: Behind the (Electrical) Design November 8, 2017 Christian Winter, P.E. Minnesota Power Sivasis Panigrahi, P.E. POWER Engineers, Inc. What is the Great Northern Transmission

More information

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation

More information

Howard Smart Transformer Specification Guide

Howard Smart Transformer Specification Guide Howard Smart Transformer Specification Guide General Requirements Overhead pole-type smart distribution transformers shall be single phase, 60 Hz, mineral-oil filled and self-cooled and shall conform as

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

Metal-Oxide Varistors (MOVs) Thermally Protected Varistors > SMOV 25S Varistor Series

Metal-Oxide Varistors (MOVs) Thermally Protected Varistors > SMOV 25S Varistor Series S25S Varistor Series RoHS Description The Littelfuse S 25S thermally protected varistor is a self-protected device. It consists of a 25mm square varistor with an integral thermal designed to open in the

More information

Specifications. S&C BankGuard Plus Controls. For Substation Capacitor Banks and Shunt Reactors. Conditions of Sale

Specifications. S&C BankGuard Plus Controls. For Substation Capacitor Banks and Shunt Reactors. Conditions of Sale For Substation Capacitor Banks and Shunt Reactors Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified by the SPE CIAL

More information

Mar11 Rev J

Mar11 Rev J Product Specification 108-1051 11Mar11 Rev J System, Connector/Header, MTA 156 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for the TE Connectivity (TE) MTA

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

3EK8 distribution class surge arresters. Catalogue HP-AR Version siemens.com/arresters

3EK8 distribution class surge arresters. Catalogue HP-AR Version siemens.com/arresters Catalogue HP-AR 28.2 Version 2017 3EK8 distribution class surge arresters siemens.com/arresters Siemens surge arresters for any requirement Experience is most essential when it comes to reliability in

More information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral

More information

Qualification Test Report SlimSeal SSL Connector

Qualification Test Report SlimSeal SSL Connector Qualification Test Report SlimSeal SSL Connector 501-134042 6/26/15 Rev A 1. INTRODUCTION 1.1 Purpose Testing was performed on the TE Connectivity SlimSeal SSL Connector to determine its conformance to

More information

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric

More information

Appendix B to Working on Exposed Energized Parts

Appendix B to Working on Exposed Energized Parts Working on Exposed Energized Parts. - 1910.269 App B Regulations (Standards - 29 CFR) - Table of Contents Part Number: 1910 Part Title: Occupational Safety and Health Standards Subpart: R Subpart Title:

More information

Distribution/Substation Transformer

Distribution/Substation Transformer Distribution/Substation Transformer Type VFI, Vacuum Fault Interrupter Transformer Option Functional Specification Guide Functional specification for 15 kv, 25 kv, or 35 kv vacuum fault interrupter distribution/substation

More information

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Analysis of lightning performance of 132KV transmission line by application of surge arresters Analysis of lightning performance of 132KV transmission line by application of surge arresters S. Mohajer yami *, A. Shayegani akmal, A.Mohseni, A.Majzoobi High Voltage Institute,Tehran University,Iran

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60099-4 Edition 2.1 2006-07 Edition 2:2004 consolidated with amendment 1:2006 Surge arresters Part 4: Metal-oxide surge arresters without gaps for a.c. systems IEC 2006 Copyright

More information

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS 1. Introduction 2. Classification of High Voltage Tests 3. Test Voltages 4. High Voltage Testing of Electrical Apparatus 1. INTRODUCTION Purpose

More information

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV

More information

Insulation Co-ordination For HVDC Station

Insulation Co-ordination For HVDC Station Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating

More information

SOLARLOK PV BAR Junction Box

SOLARLOK PV BAR Junction Box SOLARLOK PV BAR Junction Box Table of contents 1. SCOPE... 2 1.1. Content... 2 1.2. Qualification... 3 2. APPLICABLE DOCUMENTS... 3 2.1. TE Connectivity Documents... 3 2.2. Commercial Standard... 3 3.

More information

Selection of MO surge arresters Overvoltage protection

Selection of MO surge arresters Overvoltage protection A P P L I C AT I O N N OT E 1. 1 Selection of MO surge arresters Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage protection

More information

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet ArresterWorks Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet 6/23/2012 Jonathan Woodworth Transient overvoltages are a fact of life on power systems. Arresters can

More information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING YEAR / SEM : IV / VII UNIT I OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS 1. What

More information

REPORT OF PERFORMANCE TIC

REPORT OF PERFORMANCE TIC REPORT OF PERFORMANCE TIC 1580-13 OBJECT TYPE Three-core power cable 18/30(36) kv, 3x500 mm2, 2XWY(P)-FR XLPE Rated voltage, U 0/U (U m) 18/30 (36) kv Conductor material Cu Conductor cross-section 3x500

More information

In-Service Testing and Diagnosis of Gapless Metal Oxide Surge Arresters According to IEC

In-Service Testing and Diagnosis of Gapless Metal Oxide Surge Arresters According to IEC In-Service Testing and Diagnosis of Gapless Metal Oxide Surge Arresters According to IEC60099-5 Overview of presentation Motivation for condition monitoring of metal oxide surge arresters (MOSA) The Surge

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR 621 212 DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING EE1003 HIGH VOLTAGE ENGINEERING QUESTION BANK UNIT-I OVER VOLTAGES IN ELECTRICAL POWER SYSTEM

More information

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994

More information

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems PPLICATION GUIDELINES OVERVOLTAGE PROTECTION Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems Foreword Up until 1998 no international standards

More information

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power

More information

Type Test of a 145 kv Termination Type TS 145-II

Type Test of a 145 kv Termination Type TS 145-II Test Report No 2009-125/2 Type Test of a 145 kv Termination Type TS 145-II Client: 3 M Deutschland GmbH Carl-Schurz-Str.1 41453 Neuss Reporter: Dr.-Ing. R. Badent Dr.-Ing. B. Hoferer This report includes

More information

Type MLSH 125 C Hermetic Slimpack, Aluminum Electrolytic Capacitor

Type MLSH 125 C Hermetic Slimpack, Aluminum Electrolytic Capacitor The world s only hermetically sealed aluminum electrolytic capacitor with glass-to-metal seal, type MLSH has extraordinary long life and rugged construction for the most demanding power electronics applications.

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid 1 Arpan K. Rathod, 2 Chaitanya H. Madhekar Students Electrical Engineering, VJTI, Mumbai, India

More information

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage Swati Agrawal Assistant Professor, MATS University, Raipur (C.G) Abstract: This paper describes the usage of surge

More information

7P Series - Surge Protection Device (SPD) Features 7P P P

7P Series - Surge Protection Device (SPD) Features 7P P P Features 7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025 SPD Type 1+2 Surge arrester range - single phase system / three phase system Surge arresters suitable in low-voltage applications in order to

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating

More information

New Modeling of Metal Oxide Surge Arresters

New Modeling of Metal Oxide Surge Arresters Signal Processing and Renewable Energy September 2017, (pp.27-37) ISSN: 2588-7327 New Modeling of Metal Oxide Surge Arresters Seyed Mohammad Hassan Hosseini 1 *, Younes Gharadaghi 1 1 Electrical Engineering

More information

Our experience. Our products

Our experience. Our products Our experience With 20 years know-how in the field of Medium Voltage network protection, DERVASIL designs and manufactures lightning arresters with zinc oxide varistors and synthetic housings. Our products

More information

Feb 13 Rev F

Feb 13 Rev F Product Specification IMPACT 100 Ohm Interconnect Systems 108-2351 14 Feb 13 Rev F 1. SCOPE 1.1. Content This specification defines the performance, tests and quality requirements for the TE Connectivity

More information

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018 Transformer Testing & Maintenance Fundamentals 1 AVO Training Institute, Inc. 2018 Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the

More information

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual. Manual Title: 550A Getting Started Supplement Issue: Part Number: 415509 Issue Date: 9/18 Print Date: November 01 Page Count: 19 Revision/Date: This supplement contains information necessary to ensure

More information

Earthing of Electrical Devices and Safety

Earthing of Electrical Devices and Safety Earthing of Electrical Devices and Safety JOŽE PIHLER Faculty of Electrical Engineering and Computer Sciences University of Maribor Smetanova 17, 2000 Maribor SLOVENIA joze.pihler@um.si Abstract: - This

More information

Reactor and inductor are names used interchangeably for this circuit device.

Reactor and inductor are names used interchangeably for this circuit device. Recommended Design Criteria for Air-Cooled Reactor for Line and Track Circuits Revised 2015 (7 Pages) A. Purpose This Manual Part recommends design criteria for an air-cooled reactor for line and track

More information

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 2 August 216 ISSN (online): 2349-784X Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

More information

FACTORY AND FIELD VERIFICATION TESTS OF CONTROLLED SWITCHING SYSTEM

FACTORY AND FIELD VERIFICATION TESTS OF CONTROLLED SWITCHING SYSTEM FACTORY AND FIELD VERIFICATION TESTS OF CONTROLLED SWITCHING SYSTEM by H. Ito, H. Tsutada, H. Kohyama, H. Yamamoto Mitsubishi Electric Corp. H. Wilson, S. Billings Mitsubishi Electric Power Products, Inc.

More information

Regional Technical Seminar SHORT CIRCUIT FORCES

Regional Technical Seminar SHORT CIRCUIT FORCES Regional Technical Seminar SHORT CIRCUIT FORCES Short Circuit Forces Wallace Exum Electrical Design Engineer wallace.exum@spx.com Agenda 1. What is Short Circuit 2. Types of Faults 3. How to Calculate

More information

Mar11 Rev D

Mar11 Rev D Product Specification 108-1050-1 11Mar11 Rev D MTA-100 Wire-To-Wire Posted Connector System 1. SCOPE 1.1. Content This specification covers the performance, tests and quality requirements for the TE Connectivity

More information

This Certificate consists of 75 pages in total.

This Certificate consists of 75 pages in total. Object Heat shrinkable indoor termination 1086-16 Type MZDNK-3-15-C Rated voltage, U 0 /U (U m ) 8,7/15 (17,5) kv Conductor material Cu Conductor cross-section 3 x 185 mm 2 Insulation material XLPE Manufacturer

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

Metal Oxide Varistors

Metal Oxide Varistors Straight Lead Dimensions Table Series 5D 7D 10D 14D 20D D max 7 9.5 14 17.5 24 d* 0.6 0.6 0.8 0.8 1 W** 5 5 7.5 7.5 10 H max 12.5 14.5 20 22.5 29.5 H1 max 10 12 17 20.5 28 T max 4.9 4.9 8.5 8.5 9 P max

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

THREE-PHASE SHORT-CIRCUIT TESTING OF HIGH-VOLTAGE CIRCUIT-BREAKERS USING SYNTHETIC CIRCUITS

THREE-PHASE SHORT-CIRCUIT TESTING OF HIGH-VOLTAGE CIRCUIT-BREAKERS USING SYNTHETIC CIRCUITS Denis DUFOURNET Head of CERDA High Power and High Voltage Laboratories in Villeurbanne, France. Georges MONTILLET Dead Tank Circuit Breakers Product Manager Development, Charleroi, PA USA. Charleston,

More information

The Reflective Wave Phenomena

The Reflective Wave Phenomena Application Note The Reflective Wave Phenomena Rev2.doc The Reflective Wave Phenomena Note to Specifiers This application note contains Cutler-Hammer s recommendations for the application of filters for

More information

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual. Manual Title: 5502E Getting Started Supplement Issue: 3 Part Number: 4155211 Issue Date: 9/18 Print Date: November 2012 Page Count: 12 Revision/Date: This supplement contains information necessary to ensure

More information

3MElectrical Markets Division

3MElectrical Markets Division 3MElectrical Markets Division Contents Summary 3 Purpose... 3 Test Specimen 3 Test Deviations... 4 Test Results 5 Impulse Test Oscillograms... 10 Specimen Photographs.. 11 Equipment Documentation: Impulse

More information

StarSine Power Quality Products

StarSine Power Quality Products StarSine Power Quality Products Medium Voltage Static Voltage Regulator ( MV SVR ) MV SVR PROTECTS THE WHOLE FACILITY LOADS FROM VOLTAGE SAGS CAUSED BY UTILITY GRID FAULTS Voltage sags, whether due to

More information

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES Authors: Joe Perez, P.E.: SynchroGrid, College Station, Texas Hung Ming Chou, SynchroGrid, College Station, Texas Mike McMillan, Bryan

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

Outdoor Instrument Transformers. Application Guide

Outdoor Instrument Transformers. Application Guide Outdoor Instrument Transformers Application Guide Introduction Edited by Knut Sjövall, knut.sjovall@se.abb.com ABB Power Technologies AB Department: PTHV/HV/MT SE-771 80 LUDVIKA, Sweden 2 1HSE 9543 40-00en

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60071-2 Third edition 1996-12 Insulation co-ordination Part 2: Application guide This English-language version is derived from the original bilingual publication by leaving out

More information

Minimum Leakage Current for Dry Band Formation under Polluted Environment

Minimum Leakage Current for Dry Band Formation under Polluted Environment Minimum Leakage Current for Dry Band Formation under Polluted Environment Suresh A.G 1, Pradipkumar Dixit 2, 1(Research Scholar, Jain University, Associate Prof BTLIT College Bangalore, India) 2 ( Associate

More information

Qualification Test Report Mini-Universal MATE-N-LOK* Connector

Qualification Test Report Mini-Universal MATE-N-LOK* Connector Qualification Test Report Mini-Universal MATE-N-LOK* Connector 501-589 21 May 12 Rev B 1. INTRODUCTION 1.1. Purpose 1.2. Scope Testing was performed on the Tyco Electronics Mini-Universal MATE-N-LOK* Connectors

More information

This specification covers performance, tests and quality requirements for MINIPAK* HDL Board Mount Receptacle or Plug Connector System.

This specification covers performance, tests and quality requirements for MINIPAK* HDL Board Mount Receptacle or Plug Connector System. Product Specification 108-2325 25Jun09 Rev B MINIPAK* HDL Board Mount Receptacle or Plug Connector System 1. SCOPE 1.1. Content This specification covers performance, tests and quality requirements for

More information