ASSESSMENT OF HARMONIC DISTORTION LEVELS IN LV NETWORKS WITH INCREASING PENETRATION LEVELS OF INVERTER CONNECTED EMBEDDED GENERATION

Size: px
Start display at page:

Download "ASSESSMENT OF HARMONIC DISTORTION LEVELS IN LV NETWORKS WITH INCREASING PENETRATION LEVELS OF INVERTER CONNECTED EMBEDDED GENERATION"

Transcription

1 ASSESSMENT OF HARMONIC DISTORTION LEVELS IN LV NETWORKS WITH INCREASING PENETRATION LEVELS OF INVERTER CONNECTED EMBEDDED GENERATION Adam DYŚKO, Graeme M. BRT, James R. McDONALD niversity of Strathclyde K a.dysko@strath.ac.uk, g.burt@eee.strath.ac.uk, j.mcdonald@eee.strath.ac.uk Ian B. B. HNTER SP PowerSystems Ltd K Ian.Hunter@SPPowerSystems.com SMMARY The paper presents a new simulation based method for harmonic distortion level evaluation at the point of common coupling in power system distribution networks. The proposed method aims to calculate the anticipated levels of voltage and current distortion by performing comparative simulation studies based on the information on the existing power quality profiles and the planned future network configuration including inverter connected embedded generation. Time domain simulation is used in order to calculate current and voltage waveforms which then can be analysed with FFT algorithm. The paper gives a detailed explanation of the method followed by the case study performed on a fragment of an actual LV distribution network. In order to provide a holistic assessment of harmonic distortion weekly profiles are analysed in 10 minute intervals which is consistent with the approach proposed in the European standard EN INTRODCTION With growing penetration levels of small-scale embedded generation utilities express an increasing concern about power quality in the MV and LV parts of the distribution networks. The notion of possible deterioration of power quality comes mainly from the fact that many small as well as some medium-scale generators are connected to the utility networks by means of the power electronic based interfaces. Sources of energy such as photovoltaics and fuel cells generate DC power and require 50Hz inverters in order to connect to the power grid which due to their non-linear characteristics introduce higher harmonics. Practical assessment of harmonic distortion levels is not a straightforward task because of the interconnectivity of the power system and the non-linear nature of the problem. The influence of the particular inverter connected generator may significantly differ depending on the location in the network. Moreover, distortion is never static and changes with load demand and generation output. All of these factors contribute to the complexity of the power quality harmonic analysis and therefore it is often not obvious which harmonic level should be treated as an index for the assessment of the distortion level. A number of approaches are presented in the engineering standards and recommendations. For example according to the European standard EN [1] 95% of the 10 minute mean rms values of each individual harmonic voltage should be less than or equal to the specified levels. Similarly, the British standard G5/4 [2] recommends measurements of one week of 3 second or 10 minute average values. On the other hand IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems [3] list harmonic distortion levels for the worst case for normal operation (conditions lasting longer than one hour). For shorter periods, during startups or unusual conditions, the limits may be exceeded by 50%. There are also some suggestions as to how to estimate future distortion levels. There are also a large number of technical publications referring to harmonic distortion assessment. Frequently appearing solution to this problem is a combination of the analytical methods with empirical data obtained from field measurements. In [4] the authors assess harmonic distortion levels caused by power factor correction capacitors using HARMFLO (Harmonic Power Flow Study Program) software. The results are compared with field tests. Similarly, in [5] and [6] the simulation results are compared with monitoring data. As to more general concepts of harmonic propagation in power networks including the models of different power system non-linear components, the work of the Task Force on Harmonics Modeling and Simulation is very relevant [7, 8]. The method proposed in this paper suggests a systematic simulation based approach which leads to the prediction of the harmonic distortion levels with future non-linear embedded generators and loads. It aims to be a network design supporting tool which will allow to estimate voltage distortion in a holistic manner utilising existing load and harmonic profiles in conjunction with the models and the profiles of the generators to be connected to the network. For the prototype case studies, the ATP simulation software was used for power system transient simulation and LabView software for harmonic analysis. METHODOLOGY Calibration of the network parameters The basis for the calibration procedure is the monitoring data collected in the substation supplying the distribution network for a period of at least one week. In most cases one week is sufficient to capture load and power quality characteristic of the network. Depending on the climatic changes during the year it may be necessary to collect the data in two or three different seasons. Calibration of loads. In most distribution systems the load levels fluctuate during the day within a wide range of values. This has a direct influence on current flows in the network as

2 well as distortion levels because they are evaluated as relative values with respect to fundamental frequency amplitude. The monitoring equipment is usually installed at the substation level and therefore the load measurements can be collected for individual circuits supplying groups of loads only. The loads are calibrated at each interval according to the principle illustrated in Fig. 1. It is assumed that the total measured load of the circuit or a group of loads (P M, Q M ) is divided proportionally to the estimated initial values of the loads (P k, Q k ) using the formula (1) and new calibrated values of the loads (P Ck, Q Ck ) are assigned to the individual loads. The estimated proportions of the loads (P k, Q k ) may be resolved on the basis of the installed capacity of the individual customers. G Z s P M, Q M tr 1 cb 1 B 1 l 1 l 2 P 1, Q 1 l 3 l 4 P 2, Q 2 P 3, Q 3... Fig. 1. Calibration principle of the group of loads (single phase) P Ck Pk Qk = PM, QCk = Q N M N P Q i= 1 i i= 1 i l n P N, Q N Each circuit would typically consist of the three groups of loads belonging to individual phases. For reasons of clarity a single line diagram is only presented in Fig. 1. More accurate load calibration would be possible only if the profiles of individual loads were known. Calibration of the harmonic levels. The second aspect of network calibration is the representation of the existing distortion levels. As it is often not possible to calibrate harmonics accurately across the whole network the calibration is performed for the specific location in the network. sually, it is a point of common coupling e.g. 11/0.4 kv substation busbar. The sinusoidal voltage and current sources connected to the distribution network model as shown in Fig. 2 help to generate required harmonic distortion at the specific location. The element Z Sh represents the impedance of the supply system, Z Lh is the equivalent impedance of the loads, V Dh is the voltage at the point of common coupling, and V Sh, I Sh are the parameters of the voltage and current harmonic sources. The idea of the harmonic calibration consists in adjusting the parameters of the sources V Sh, I Sh so that the voltage waveform V Dh contains the required harmonic levels (extracted from the monitoring data). V Sh Z Sh Z Lh I Sh I Dh V Dh Fig. 2. Power network equivalent circuit for harmonic h (single phase). (1) The method uses preliminary simulation results of the two networks: (a) with voltage sources V Sh only and (b) with current sources I Sh only. The results of preliminary simulations are used in order to calculate the final amplitudes and phases of the individual harmonic sources which induce required harmonic profile V Dh. The three phases should be calibrated individually. More detailed description of this calibration method can be found in the earlier publication [9]. Voltage profile calibration. The third aspect of calibration is proper adjustment of the voltage profile. The voltage profile is a result of the interaction between the changing loads and the activity of the regulative equipment (reactive power compensators, tap changers, etc.). The voltage is captured at the substation level by the monitoring equipment. The measured values can be utilised to adjust the network model supply voltage amplitude in order to characterise the existing voltage profile. Representing inverter connected generators For the purposes of characterising inverter-connected generators mainly two approaches can be adopted depending on the availability of the information. When detailed information from the inverter manufacturer is available it is possible to develop an accurate model including the power electronics elements and switching algorithm. On the other hand, when information is limited, the inverter behaviour can be synthesised using current harmonic sources. This approach requires a number of laboratory tests to be undertaken in order to record generated waveforms under changing loading conditions. The recorded current waveforms are then the basis for the construction of the model which synthesises the current from the harmonic information obtained during the tests. The case study in section III demonstrates the use of both approaches. Principle of the comparative method based on profiles The main aim of the harmonic evaluation methodology presented in this paper is to provide the framework for comparative power quality studies. The comparison is performed in two stages: (1) calibration of the network parameters for accurate simulation of the existing distortion profile (as described in previous sections), and (2) simulation of the anticipated distortion profile using the calibrated network in conjunction with the models of the generators and non-linear loads to be connected to the network. Therefore, the distribution network model is prepared in two versions: network (a) representing the system with all existing generators and loads and network (b) with additional embedded sources of energy and possible loads. Network data prepared in this way acts as a template for systematic simulation of the distortion profile. The network is calibrated and the profile is evaluated in pre-defined time steps (e.g. every 10min) depending on the available load and monitoring data. Finally, the harmonic profiles (individual harmonics or THD) can be collected and presented in a report.

3 Problem of the phase shift of individual harmonics 50Hz sources One of the challenges in assessing the changes in distortion levels is the relative phase shift of the existing harmonics with respect to those generated by the inverters. For example, if the harmonics generated by the additional sources are in phase with the existing ones then the increase in distortion level is to be expected. Otherwise the distortion may become smaller than the original level. In order to represent properly the phases of individual harmonics it is essential that the monitoring equipment store the FFT analysis results as amplitude and phase. This way the simulated existing distortion level can be adequately calibrated in terms of the phase shift of individual harmonics and will be always set correctly with respect to the harmonics generated by the connected inverters. Interpretation of the results Voltage harmonic sources V Sh Circuit 1 Circuit 2 Circuit 3 Cable impedance PV 6 PV 1 PV 2 PV 3 PV 4 The results should be presented as daily (or weekly) harmonic distortion profiles of THD and perhaps of some most significant individual harmonics. Additionally, it is proposed to present the distortion profiles in the form of duration curves, which allow for convenient comparison with standard limits, with other studies and with other parts of the utility network. Furthermore this data can then be used for further statistical analyses in support of targeting associated network reinforcement. This format will be demonstrated during the case study. Current harmonic sources I Sh Circuit 4 Load Fig. 3. ATP Model of the distribution network THD Wednesday PV 5 CASE STDY Network model and data In order to illustrate the methodology a case study was performed on a fragment of the actual distribution network as presented in Fig. 3. The network consists of four LV circuits supplying various types of customers. Circuit 1 supplies an industrial estate, circuits 2 and 3 provide electricity to the residential area and circuit 4 supplies a commercial street. The monitoring equipment was installed on the LV side of the 11/0.4 kv substation in order to capture the load demand and current distortion profiles in all the circuits and the voltage distortion level on the LV busbar. The aim of the study was to investigate the impact of inverter connected PV generation installations in the residential area on the substation voltage distortion profile. Three different penetration levels were considered: 25kW, 50kW and 75kW of installed PV generation capacity. The maximum installed generation was represented by six lumped units connected across the residential circuits as indicated in Fig. 3 each one representing 12.5kW. For 25kW and 50kW two and four units were used respectively. Fig. 4 presents a weekly profile of voltage odd harmonics up to the 9 th. Even harmonics are not presented, as their level was negligible in this case. A midweek day (Wednesday) was selected from the weekly profile (ref. Fig. 4). Voltage H5 H3 0.2 H7 H9 0.0 Time [h] Fig. 4. Existing Voltage Harmonic Levels PV generator modelling Two different dynamic models of the inverter connected PV panels were utilised in order to characterise the distortion introduced by the sources. The first model illustrated in Fig. 5 was built using ATP controlled switches forming a single phase four valve bridge driven by the standard PWM algorithm with sinusoidal reference signal. The magnitude of the DC voltage and the phase of the PWM reference signal were controlled by the PI controller measuring active and reactive power. This allowed adjusting the generated active power according to the profile of the sun radiation by changing DC source magnitude and maintaining the unity power factor by the phase of the PWM reference signal. More detailed description of the PV generator modelling can be found in the publication [10].

4 Output kW PV PWM controller MODELS controlled DC Source Inverter Fig. 5. ATP model of the inverter connected PV panel Second model is presented in Fig. 6. It contains a MODELS controlled current source connected to the algorithm which synthesises the current waveform from individual harmonics. This way it was possible to reproduce accurately the current waveform which in this case was obtained from the laboratory testing of the commercially available 800W inverter designed for PV systems. Output No PV THD Measured Time [h] 50kW PV 25kW PV Fig. 7. Comparison of the daily voltage THD profiles with and without PV generation (PWM PV model) kW PV 50kW PV Current Controlling Algorithm I MODELS Controlled Current Source Fig. 6. Model of the inverter connected DC source based on harmonic synthesis of the empirical data Profile simulation results Each calculated harmonic profile included 144 simulations performed in 10-min time intervals. At each interval the necessary network load and distortion calibrations were performed. The final result for the PWM generator model is presented in Fig s 7-8. Five curves are presented in each figure indicating gradual changes in harmonic distortion with increasing levels of EG penetration compared with the measured levels. It is important to note that the THD duration curves give an immediate indication as to the level of distortion consistent with power quality standards. Taking the intersect with the dotted vertical line at the 5% mark (refer Fig. 8) gives a direct reading of the maximum distortion level which is not exceeded during 95% of the time. On the other hand, the daily profiles indicate the time relation between the new PV generation distortion and the existing distortion giving insight into potential power quality problems caused by the lack of diversity between existing and introduced distortion profiles. For example in Fig. 7 it can be observed for 25kW generation level that, although, the distortion is increased during the day it has practically no impact on the normative distortion level (refer to 5% mark on duration curve in Fig. 8). With 50kW PV penetration the distortion level rises approx. from THD=1.93% to THD=6%) and further 25kW causes the increase to THD=2.71%. This indicates that the relationship between the penetration level and harmonic distortion is not linear. Fig. 8. (read from THD duration curves at 5%) No PV 25kW PV THD Measured Fig. 9. Time [%] Comparison of the daily voltage THD duration curves with and without PV generation (PWM PV model) PWM Inverter Model Synthesised Inverter Model PV generation [kw] Influence of the PV penetration level on voltage harmonic distortion The influence of the PV penetration on the normative THD level for two inverter models is presented in Fig. 9 which shows that for both inverters above certain penetration threshold distortion starts to increase more rapidly and almost proportionally to the EG generation. For PWM inverter model this threshold appears around 25kW and for the synthesised model it is closer to 50kW. These characteristics are dependent on the inverter model as well as the daily profile

5 and that is why the simulation studies including detailed profile analysis such as the one presented in this paper are necessary in order to assess realistically the future power quality parameters. Harmonic phase shift considerations In order to investigate how the phase shift between the existing harmonics and the ones introduced by new generators can influence the resulting distortion level, a series of profile simulations were performed changing the angle of all existing harmonics with respect to the ones of the synthesised generator. Fig. 10 presents the results of phase shift scan for the penetration level of 25kW (midday) using the synthesised inverter model. The existing distortion level is marked by the dotted line at about %. It can be observed that the resulting THD index can change from minimum to maximum with an angular difference of merely 45 (e.g. minimum at approx. 210 and then following maximum at approx. 255 ). The result here confirms the measurements which indicated the predominance of the 5 th harmonic in the harmonic spectrum of the existing distortion (ref. to Fig. 4); the phase scan in Fig. 10 has five distinct peaks when the angle of the fundamental frequency changes by 360. This illustrates the potential for angular shift to be used for active compensation of dominant harmonics in the network when combined with on-line monitoring and programmable inverters. Voltage Phase [deg] Fig. 10. Influence of the phase shift on the resulting voltage distortion level (EG penetration 25kW) CONCLSIONS The paper presented a systematic simulation based methodology for the assessment of the harmonic distortion levels with the inclusion of the influence of the future inverter connected sources of renewable energy installed in LV networks. This methodology is aimed to assist the utilities in network development planning activities as it is anticipated that the levels of small generation penetration will continue to rise together with the participation of power electronics. An effort has been made to prepare an illustrative case study based on actual network and monitoring data. The results revealed also certain general characteristics of the harmonic distortion under varying EG penetration. It was demonstrated that distortion levels (as defined by the power quality standards) are not rising proportionally to the EG penetration levels. Although initially the harmonic distortion may not be noticeable (i.e. the distortion read from the THD duration curves at 5%), above a certain level a rapid deterioration of power quality can be expected in the network (ref. to Fig. 9). It is therefore essential that power utilities are equipped with appropriate simulation tools in order to anticipate the maximum permissible levels of small EG penetration which may vary in each case and is a function of existing network parameters and profiles as well as EG penetration level and the type of inverter. Moreover, as the sophistication of power electronic inverter increases and the microprocessor based controllers become increasingly more popular the method has a potential be used for the investigation of certain harmonic eliminating switching strategies and can therefore serve as a tool for investigating the methods of power quality improvement. ACKNOWLEDGEMENT The authors would like to express their gratitude to ScottishPower for providing network details and the monitoring data. REFERENCES [1] Voltage Characteristics of Electricity Supplied by Public Distribution Systems, 1994, EN 50160, E. [2] Engineering Recommendation G5/4, 1998, K. [3] IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, 1992, ANSI [4] S.M. Williams, G.T. Brownfield, and J.W. Duffus, 1993, Harmonic propagation on an electric distribution system: field measurements compared with computer simulation, IEEE Trans. on Pow. Del. vol. 8, [5] D. Tong, V.G. Nikolaenko, N. Ginbey, and I. Lau, 2000, Harmonic propagation in transmission system with multiple capacitor installations, presented at Int. Conf. on Power System Technology, vol. 2, [6] H. M. Beides and G. T. Heydt, 1992, Power system harmonics estimation and monitoring, Electric Machines and Power Systems. vol. 20, [7] Modeling and simulation of the propagation of harmonics in electric power networks. I. Concepts, models, and simulation techniques, 1996, IEEE Transactions on Power Delivery. vol. 11, [8] Modeling and simulation of the propagation of harmonics in electric power networks. II. Sample systems and examples, 1996, IEEE Trans. on Pow. Del. vol. 11, [9] A. Dyśko, G. M. Burt, J. R. McDonald, and J. Clark, 2001, Synthesis of harmonic distortion levels in an LV distribution network, IEEE Power Engineering Review, vol. 21, [10] G. M. Burt, A. Dyśko, J. R. McDonald, J. Clark, and I. Hunter, 2001, Power quality and the impact of building-integrated renewables, presented at ERA Technology Conference on Quality and Security of Electrical Supply, The Oxford Belfry, Thame, K.

Power Quality and Digital Protection Relays

Power Quality and Digital Protection Relays Power Quality and Digital Protection Relays I. Zamora 1, A.J. Mazón 2, V. Valverde, E. Torres, A. Dyśko (*) Department of Electrical Engineering - University of the Basque Country Alda. Urquijo s/n, 48013

More information

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits WREF 01 Paper # 048 Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits Ketut Dartawan Ricardo Austria, Le Hui and Mark Suehiro* Pterra Consulting Maui Electric Company*

More information

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS 66 CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS INTRODUCTION The use of electronic controllers in the electric power supply system has become very common. These electronic

More information

MODELING THE EFFECTIVENESS OF POWER ELECTRONICS BASED VOLTAGE REGULATORS ON DISTRIBUTION VOLTAGE DISTURBANCES

MODELING THE EFFECTIVENESS OF POWER ELECTRONICS BASED VOLTAGE REGULATORS ON DISTRIBUTION VOLTAGE DISTURBANCES MODELING THE EFFECTIVENESS OF POWER ELECTRONICS BASED VOLTAGE REGULATORS ON DISTRIBUTION VOLTAGE DISTURBANCES James SIMONELLI Olivia LEITERMANN Jing HUANG Gridco Systems USA Gridco Systems USA Gridco Systems

More information

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory Emílio F. Couto, Júlio S. Martins, João L. Afonso Department of Industrial Electronic University of Minho Campus de Azurém

More information

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants 4th International Conference on Machinery, Materials and Information Technology Applications (ICMMITA 2016) Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants Chen-Xin

More information

INVESTIGATING THE BENEFITS OF MESHING REAL UK LV NETWORKS

INVESTIGATING THE BENEFITS OF MESHING REAL UK LV NETWORKS INVESTIGATING THE BENEFITS OF MESHING REAL UK LV NETWORKS Muhammed S. AYDIN Alejandro NAVARRO Espinosa Luis F. OCHOA The University of Manchester UK The University of Manchester UK The University of Manchester

More information

Determination of Smart Inverter Power Factor Control Settings for Distributed Energy Resources

Determination of Smart Inverter Power Factor Control Settings for Distributed Energy Resources 21, rue d Artois, F-758 PARIS CIGRE US National Committee http : //www.cigre.org 216 Grid of the Future Symposium Determination of Smart Inverter Power Factor Control Settings for Distributed Energy Resources

More information

HARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE

HARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE HARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE Ibrahim ABDULHADI Federico COFFELE Power Networks Demonstration Centre - UK ibrahim.f.abdulhadi@strath.ac.uk federico.coffele@strath.ac.uk

More information

Harmonics Elimination Using Shunt Active Filter

Harmonics Elimination Using Shunt Active Filter Harmonics Elimination Using Shunt Active Filter Satyendra Gupta Assistant Professor, Department of Electrical Engineering, Shri Ramswaroop Memorial College of Engineering and Management, Lucknow, India.

More information

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment s Evaluating Methods, Power Quality and s Assessment regarding Voltage Dip Immunity of Equipment ANTON BELÁŇ, MARTIN LIŠKA, BORIS CINTULA, ŽANETA ELESCHOVÁ Institute of Power and Applied Electrical Engineering

More information

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES C.E.T. Foote*, G.W. Ault*, J.R. McDonald*, A.J. Beddoes *University of Strathclyde, UK EA Technology Limited, UK c.foote@eee.strath.ac.uk

More information

A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions

A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 16, NO. 5, SEPTEMBER 2001 603 A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions

More information

A Single Phase Multistring Seven Level Inverter for Grid Connected PV System

A Single Phase Multistring Seven Level Inverter for Grid Connected PV System A Single Phase Multistring Seven Level Inverter for Grid Connected PV System T.Sripal Reddy, M.Tech, (Ph.D) Associate professor & HoD K. Raja Rao, M.Tech Assistat Professor Padrthi Anjaneyulu M.Tech Student

More information

A Three Phase Seven Level Inverter for Grid Connected Photovoltaic System by Employing PID Controller

A Three Phase Seven Level Inverter for Grid Connected Photovoltaic System by Employing PID Controller A Three Phase Seven Level Inverter for Grid Connected Photovoltaic System by Employing PID Controller S. Ragavan, Swaminathan 1, R.Anand 2, N. Ranganathan 3 PG Scholar, Dept of EEE, Sri Krishna College

More information

IMPROVING KWH-METER PERFORMANCE AT PV ON GRID SYSTEM BY MULTIPLYING THE NUMBER OF SAMPLING SIGNAL

IMPROVING KWH-METER PERFORMANCE AT PV ON GRID SYSTEM BY MULTIPLYING THE NUMBER OF SAMPLING SIGNAL IMPROVING KWH-METER PERFORMANCE AT PV ON GRID SYSTEM BY MULTIPLYING THE NUMBER OF SAMPLING SIGNAL 1 ISDAWIMAH, 2 RUDY SETIABUDY, 3 RIDWAN GUNAWAN 123 Department of Electrical Engineering, Universitas Indonesia,

More information

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions Fernando Bastião and Humberto Jorge Department of Electrical Engineering and Computers

More information

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2 IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online): 2321-0613 Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive

More information

Design of Single Phase Pure Sine Wave Inverter for Photovoltaic Application

Design of Single Phase Pure Sine Wave Inverter for Photovoltaic Application Design of Single Phase Pure Sine Wave Inverter for Photovoltaic Application Yash Kikani School of Technology, Pandit Deendayal Petroleum University, India yashkikani004@gmail.com Abstract:- This paper

More information

Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks

Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks André Braga Instituto Superior Técnico Av. Rovisco Pais, 1049-001 Lisbon, Portugal

More information

Some European experiences with renewable installations

Some European experiences with renewable installations Some European experiences with renewable Waveform distortion Ana Maria Blanco, Jan Meyer, Sascha Müller, Anantaram Varatharajan 08.08.2017 Content 1. Introduction 2. Distributed PV inverters (

More information

Power quality emission assessment of photovoltaic inverters based on IEC technical report :2011

Power quality emission assessment of photovoltaic inverters based on IEC technical report :2011 University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part A Faculty of Engineering and Information Sciences 23 Power quality emission assessment of photovoltaic

More information

VOLTAGE QUALITY PROVISION IN LOW VOLTAGE NETWORKS WITH HIGH PENETRATION OF RENEWABLE PRODUCTION

VOLTAGE QUALITY PROVISION IN LOW VOLTAGE NETWORKS WITH HIGH PENETRATION OF RENEWABLE PRODUCTION VOLTAGE QUALITY PROVISION IN LOW VOLTAGE NETWORKS WITH HIGH PENETRATION OF RENEWABLE PRODUCTION ABSTRACT Anže VILMAN Elektro Gorenjska, d.d. Slovenia anze.vilman@elektro-gorenjska.si Distribution system

More information

Hybrid Power Quality Compensator for Traction Power System with Photovoltaic Array

Hybrid Power Quality Compensator for Traction Power System with Photovoltaic Array IJMTST Volume: 2 Issue: 07 July 2016 ISSN: 2455-3778 Hybrid Power Quality Compensator for Traction Power System with Photovoltaic Array M. Kalidas 1 B. Lavanya 2 1PG Scholar, Department of Electrical &

More information

Power Quality Improvement in Distribution System Using D-STATCOM

Power Quality Improvement in Distribution System Using D-STATCOM Power Quality Improvement in Distribution System Using D-STATCOM 1 K.L.Sireesha, 2 K.Bhushana Kumar 1 K L University, AP, India 2 Sasi Institute of Technology, Tadepalligudem, AP, India Abstract This paper

More information

Harmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems

Harmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems University of Wollongong Research Online University of Wollongong Thesis Collection 1954-2016 University of Wollongong Thesis Collections 2006 Harmonic impact of photovoltaic inverter systems on low and

More information

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM 64 CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM 4.1 INTRODUCTION Power electronic devices contribute an important part of harmonics in all kind of applications, such as power rectifiers, thyristor converters

More information

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) PATTI.RANADHEER Assistant Professor, E.E.E., PACE Institute

More information

UNIT-4 POWER QUALITY MONITORING

UNIT-4 POWER QUALITY MONITORING UNIT-4 POWER QUALITY MONITORING Terms and Definitions Spectrum analyzer Swept heterodyne technique FFT (or) digital technique tracking generator harmonic analyzer An instrument used for the analysis and

More information

A Practical Application of Low Voltage DC Distribution Network Within Buildings

A Practical Application of Low Voltage DC Distribution Network Within Buildings A Practical Application of Low Voltage DC Distribution Network Within Buildings B Marah 1 Hoare Lea LLP. London, UK bmarah@theiet.org Y R Bhavanam 2, G A Taylor 2, M K Darwish 2 Brunel University London.

More information

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Phanikumar.Ch, M.Tech Dept of Electrical and Electronics Engineering Bapatla Engineering College, Bapatla,

More information

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads Ponananthi.V, Rajesh Kumar. B Final year PG student, Department of Power Systems Engineering, M.Kumarasamy College of

More information

Reduced PWM Harmonic Distortion for a New Topology of Multilevel Inverters

Reduced PWM Harmonic Distortion for a New Topology of Multilevel Inverters Asian Power Electronics Journal, Vol. 1, No. 1, Aug 7 Reduced PWM Harmonic Distortion for a New Topology of Multi Inverters Tamer H. Abdelhamid Abstract Harmonic elimination problem using iterative methods

More information

LOW ORDER HARMONICS IMPROVEMENT OF A SINGLE GRID CONNECTED INVERTER SYSTEM UNDER PR CONTROL TECHNIQUE

LOW ORDER HARMONICS IMPROVEMENT OF A SINGLE GRID CONNECTED INVERTER SYSTEM UNDER PR CONTROL TECHNIQUE LOW ORDER HARMONICS IMPROVEMENT OF A SINGLE GRID CONNECTED INVERTER SYSTEM UNDER PR CONTROL TECHNIQUE S. Salimin 1, A. A Bakar 1 and M. Armstrong 2 1 Department of Electrical Power, Faculty of Electrical

More information

Analysis of Utility Interactive Photovoltaic Generation System using a Single Power Static Inverter

Analysis of Utility Interactive Photovoltaic Generation System using a Single Power Static Inverter Asian J. Energy Environ., Vol. 5, Issue 2, (2004), pp. 115-137 Analysis of Utility Interactive Photovoltaic Generation System using a Single Power Static Inverter D. C. Martins*, R. Demonti, A. S. Andrade

More information

Improving Passive Filter Compensation Performance With Active Techniques

Improving Passive Filter Compensation Performance With Active Techniques IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 50, NO. 1, FEBRUARY 2003 161 Improving Passive Filter Compensation Performance With Active Techniques Darwin Rivas, Luis Morán, Senior Member, IEEE, Juan

More information

Tripping of circuit breakers in PV installations due to zero sequence field impedance

Tripping of circuit breakers in PV installations due to zero sequence field impedance Tripping of circuit breakers in PV installations due to zero sequence field impedance B. Verhelst 1,2, C. Debruyne 1,2, J. Desmet 1,2 1 dept. Electrical Engineering - Lemcko HoWest Kortrijk, Belgium bart.verhelst@howest.be

More information

Power quality measurements in a singlehouse

Power quality measurements in a singlehouse 24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 2: Power quality and electromagnetic compatibility Power quality measurements in a singlehouse microgrid

More information

A Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)

A Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104) International Journal of Electrical and Computer Engineering (IJECE) Vol. 4, No. 3, June 2014, pp. 322 328 ISSN: 2088-8708 322 A Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)

More information

Grid Converters for Photovoltaic

Grid Converters for Photovoltaic Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements

More information

29 Level H- Bridge VSC for HVDC Application

29 Level H- Bridge VSC for HVDC Application 29 Level H- Bridge VSC for HVDC Application Syamdev.C.S 1, Asha Anu Kurian 2 PG Scholar, SAINTGITS College of Engineering, Kottayam, Kerala, India 1 Assistant Professor, SAINTGITS College of Engineering,

More information

ANALYSING PERFORMANCE OF SUPER-CAPACITOR AND BATTERY IN LOW VOLTAGE ELECTRICAL DISTRIBUTION SYSTEMS

ANALYSING PERFORMANCE OF SUPER-CAPACITOR AND BATTERY IN LOW VOLTAGE ELECTRICAL DISTRIBUTION SYSTEMS th March 4. Vol. 6 No. 5-4 JATIT & LLS. All rights reserved. ISSN: 99-8645 www.jatit.org E-ISSN: 87-95 ANALYSING PERFORMANCE OF SUPER-CAPACITOR AND BATTERY IN LOW VOLTAGE ELECTRICAL DISTRIBUTION SYSTEMS

More information

EMERGING distributed generation technologies make it

EMERGING distributed generation technologies make it IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, NOVEMBER 2005 1757 Fault Analysis on Distribution Feeders With Distributed Generators Mesut E. Baran, Member, IEEE, and Ismail El-Markaby, Student Member,

More information

SIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS

SIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS SIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS Qin Jiang School of Communications & Informatics Victoria University P.O. Box 14428, Melbourne City MC 8001 Australia Email: jq@sci.vu.edu.au

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

II. RESEARCH METHODOLOGY

II. RESEARCH METHODOLOGY Comparison of thyristor controlled series capacitor and discrete PWM generator six pulses in the reduction of voltage sag Manisha Chadar Electrical Engineering Department, Jabalpur Engineering College

More information

TO LIMIT degradation in power quality caused by nonlinear

TO LIMIT degradation in power quality caused by nonlinear 1152 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 13, NO. 6, NOVEMBER 1998 Optimal Current Programming in Three-Phase High-Power-Factor Rectifier Based on Two Boost Converters Predrag Pejović, Member,

More information

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER International Journal of Electrical and Electronics Engineering Research (IJEEER) ISSN 2250-155X Vol. 3, Issue 2, Jun 2013, 309-318 TJPRC Pvt. Ltd. PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID

More information

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER Presented by Ric Austria, Principal at Pterra Consulting to the IEEE San Francisco Chapter Feb 17, 2016 California Public Utilities Commission,

More information

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Dr. Jagdish Kumar, PEC University of Technology, Chandigarh Abstract the proper selection of values of energy storing

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 BACKGROUND The increased use of non-linear loads and the occurrence of fault on the power system have resulted in deterioration in the quality of power supplied to the customers.

More information

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY POWER QUALITY IMPROVEMENT OF GRID CONNECTED WIND ENERGY SYSTEM BY USING STATCOM Mr.Mukund S. Mahagaonkar*, Prof.D.S.Chavan * M.Tech

More information

p. 1 p. 6 p. 22 p. 46 p. 58

p. 1 p. 6 p. 22 p. 46 p. 58 Comparing power factor and displacement power factor corrections based on IEEE Std. 18-2002 Harmonic problems produced from the use of adjustable speed drives in industrial plants : case study Theory for

More information

Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier

Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier Transactions on Electrical Engineering, Vol. 1 (2012), No. 1 30 Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier Jan Michalík1), Jan Molnár2) and Zdeněk Peroutka2)

More information

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults Enhancement of Power Quality in Distribution System Using D-Statcom for Different s Dr. B. Sure Kumar 1, B. Shravanya 2 1 Assistant Professor, CBIT, HYD 2 M.E (P.S & P.E), CBIT, HYD Abstract: The main

More information

Implementation Full Bridge Series Resonant Buck Boost Inverter

Implementation Full Bridge Series Resonant Buck Boost Inverter Implementation Full Bridge Series Resonant Buck Boost Inverter A.Srilatha Assoc.prof Joginpally College of engineering,hyderabad pradeep Rao.J Asst.prof Oxford college of Engineering,Bangalore Abstract:

More information

Control of Power Converters for Distributed Generation

Control of Power Converters for Distributed Generation Mechatronics Industrial Advisory Board 2004 Control of Power Converters for Distributed Generation Ph.D. Student: Min Dai Advisor: Prof. Ali Keyhani Department of Electrical and Computer Engineering The

More information

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD T PRAHLADA 1, P SUJATHA 2, P BHARATH KUMAR 3 1PG Scholar,

More information

Recent results on the Power Quality of Italian 2x25 kv 50 Hz railways

Recent results on the Power Quality of Italian 2x25 kv 50 Hz railways th IMEKO TC4 International Symposium and 18th International Workshop on ADC Modelling and Testing Research on Electric and Electronic Measurement for the Economic Upturn Benevento, Italy, September 15-17,

More information

Synchronization and Smooth Connection of Solar Photovoltaic Generation to Utility Grid

Synchronization and Smooth Connection of Solar Photovoltaic Generation to Utility Grid International Journal of Electrical Engineering. ISSN 0974-2158 Volume 9, Number 1 (2016), pp. 51-56 International Research Publication House http://www.irphouse.com Synchronization and Smooth Connection

More information

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing

More information

HARMONIC contamination, due to the increment of nonlinear

HARMONIC contamination, due to the increment of nonlinear 612 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 44, NO. 5, OCTOBER 1997 A Series Active Power Filter Based on a Sinusoidal Current-Controlled Voltage-Source Inverter Juan W. Dixon, Senior Member,

More information

SOLID-STATE TRANSFORMERS

SOLID-STATE TRANSFORMERS SOLID-STATE TRANSFORMERS Mrs. K. S. Gadgil 1 1 Asst Professor, Department of Electrical Engineering, AISSMS IOIT, Maharashtra, India ABSTRACT Solid State Transformer (SST) has been regarded as one of the

More information

CHAPTER 5 MODIFIED SINUSOIDAL PULSE WIDTH MODULATION (SPWM) TECHNIQUE BASED CONTROLLER

CHAPTER 5 MODIFIED SINUSOIDAL PULSE WIDTH MODULATION (SPWM) TECHNIQUE BASED CONTROLLER 74 CHAPTER 5 MODIFIED SINUSOIDAL PULSE WIDTH MODULATION (SPWM) TECHNIQUE BASED CONTROLLER 5.1 INTRODUCTION Pulse Width Modulation method is a fixed dc input voltage is given to the inverters and a controlled

More information

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

AC Sources for IEC 1000 Harmonics and Flicker Testing

AC Sources for IEC 1000 Harmonics and Flicker Testing APPLICATION NOTE #101 IEC 1000-3-2 and IEC 1000-3-3 The IEC 1000-3 standard is concerned with the quality of the utility line power. To ensure good power quality, this standard specifies limits for the

More information

Harmonic Analysis of 1.5 kw Photovoltaic System in the Utility Grid

Harmonic Analysis of 1.5 kw Photovoltaic System in the Utility Grid Harmonic Analysis of 1.5 kw Photovoltaic System in the Utility Grid V.Tamilselvan 1, V.Karthikeyan 2 Associate Professor, Dept. of EEE, Adhiyamaan College of Engineering, Hosur, Tamilnadu, India 1,2 ABSTRACT:

More information

A Reduction of harmonics at the Interface of Distribution and Transmission Systems by using Current Source active Power Filter

A Reduction of harmonics at the Interface of Distribution and Transmission Systems by using Current Source active Power Filter International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, Volume 8, Issue 6 (September 2013), PP.35-39 A Reduction of harmonics at the Interface of Distribution

More information

Experimental Implementation of a Low-Cost Single Phase Five-Level Inverter for Autonomous PV System Applications Without Batteries

Experimental Implementation of a Low-Cost Single Phase Five-Level Inverter for Autonomous PV System Applications Without Batteries Engineering, Technology & Applied Science Research Vol. 8, No. 1, 2018, 2452-2458 2452 Experimental Implementation of a Low-Cost Single Phase Five-Level Inverter for Autonomous PV System Applications Without

More information

Voltage Flicker Mitigation in Electric Arc Furnace using D-STATCOM

Voltage Flicker Mitigation in Electric Arc Furnace using D-STATCOM pp. 7-11 Krishi Sanskriti Publications http://www.krishisanskriti.org/areee.html Voltage Flicker Mitigation in Electric Arc Furnace using D-STATCOM Deepthisree M. 1, Illango K. 2, Kirthika Devi V. S. 3

More information

A New Control Method for the Power Interface in Power Hardware-in-the-Loop Simulation to Compensate for the Time Delay.

A New Control Method for the Power Interface in Power Hardware-in-the-Loop Simulation to Compensate for the Time Delay. A New Control Method for the Power Interface in Power Hardware-in-the-Loop Simulation to Compensate for the Time Delay. E. Guillo-Sansano efren.guillosansano@strath.ac.uk A.J. Roscoe andrew.j.roscoe@strath.ac.uk

More information

Power Quality Measurements the Importance of Traceable Calibration

Power Quality Measurements the Importance of Traceable Calibration Power Quality Measurements the Importance of Traceable Calibration H.E. van den Brom and D. Hoogenboom VSL Dutch Metrology Institute, Delft, the Netherlands, hvdbrom@vsl.nl Summary: Standardization has

More information

A Control Method of Parallel Inverter for Smart Islanding of a Microgrid

A Control Method of Parallel Inverter for Smart Islanding of a Microgrid A Control Method of Parallel Inverter for Smart Islanding of a Microgrid M. Hojo 1, K. Amo 1, T. Funabashi 2 and Y. Ueda 2 1 Institute of Technology and Science, the University of Tokushima 2-1 Minami-josanjima,

More information

International Journal of Advance Research in Engineering, Science & Technology

International Journal of Advance Research in Engineering, Science & Technology Impact Factor (SJIF): 3.632 International Journal of Advance Research in Engineering, Science & Technology e-issn: 2393-9877, p-issn: 2394-2444 (Special Issue for ITECE 2016) Harmonic Mitigation of Fluctuating

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

On the Evaluation of Power Quality Indices in Distribution Systems with Dispersed Generation

On the Evaluation of Power Quality Indices in Distribution Systems with Dispersed Generation European Association for the Development of Renewable Energies, Environment and Power Quality International Conference on Renewable Energies and Power Quality (ICREPQ 09) Valencia (Spain), 1th to 17th

More information

Mitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM)

Mitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM) Vol. 3, Issue. 4, Jul. - Aug. 2013 pp-2367-2373 ISSN: 2249-6645 Mitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM) B. Giri Prasad Reddy 1, V. Obul

More information

Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems

Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems Brian Kingham, Utility Market Manager, Schneider Electric, PMC Division Abstract: Historical power quality measurement

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

MAINS SIGNAL PROPAGATION THROUGH DISTRIBUTION SYSTEMS. J. Stones*, S. Perera*, V. Gosbell* and N. Browne**

MAINS SIGNAL PROPAGATION THROUGH DISTRIBUTION SYSTEMS. J. Stones*, S. Perera*, V. Gosbell* and N. Browne** ABSTRACT MAINS SIGNAL PROPAGATION THROUGH DISTRIBUTION SYSTEMS J. Stones*, S. Perera*, V. Gosbell* and N. Browne** *School of Electrical, Computer and Telecommunications Engineering University of Wollongong

More information

Current Rebuilding Concept Applied to Boost CCM for PF Correction

Current Rebuilding Concept Applied to Boost CCM for PF Correction Current Rebuilding Concept Applied to Boost CCM for PF Correction Sindhu.K.S 1, B. Devi Vighneshwari 2 1, 2 Department of Electrical & Electronics Engineering, The Oxford College of Engineering, Bangalore-560068,

More information

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN Eugenio PEREA*, Eduardo ZABALA*, J. Emilio RODRÍGUEZ*, Asier GIL DE MURO*, Hugo GAGO * * * Fundación LABEIN,

More information

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER IOSR Journal of Electronics & Communication Engineering (IOSR-JECE) ISSN(e) : 2278-1684 ISSN(p) : 2320-334X, PP 68-73 www.iosrjournals.org INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE

More information

STATCOM BASED ON REDUCTION OF PQ ISSUES IN MICRO GRID APPLICATION SYSTEMS

STATCOM BASED ON REDUCTION OF PQ ISSUES IN MICRO GRID APPLICATION SYSTEMS STATCOM BASED ON REDUCTION OF PQ ISSUES IN MICRO GRID APPLICATION SYSTEMS D.Prasad 1, T.V.S. Lakshmi Durga 2, Patti. Ranadheer 3 1,2,3 Assistant Professor, E.E.E., PACE Institute of Technology & sciences,

More information

AC : PSCAD SIMULATION IN A POWER ELECTRONICS APPLICATION COURSE

AC : PSCAD SIMULATION IN A POWER ELECTRONICS APPLICATION COURSE AC 2007-2855: PSCAD SIMULATION IN A POWER ELECTRONICS APPLICATION COURSE Liping Guo, University of Northern Iowa Liping Guo received the B. E. degree in Automatic Control from Beijing Institute of Technology,

More information

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source International Journal of Emerging Engineering Research and Technology Volume 2, Issue 3, June 2014, PP 220-229 ISSN 2349-4395 (Print) & ISSN 2349-4409 (Online) Load Compensation at a Reduced DC Link Voltage

More information

Power Quality Summary

Power Quality Summary Power Quality Summary This article provides an overview of how voltage harmonic distortion is managed on the distribution network and focuses on the current at future issues surround the connection of

More information

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India

More information

Virtual FFT Analyser for identification of harmonics and inter-harmonics metrological aspects

Virtual FFT Analyser for identification of harmonics and inter-harmonics metrological aspects NPL seminar 30 of November 005 Virtual FFT Analyser for identification of harmonics and inter-harmonics metrological aspects M. Jerzy Korczyński Institute of Theoretical Electrotechnics, Metrology and

More information

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System Anju Gupta Department of Electrical and Electronics Engg. YMCA University of Science and Technology anjugupta112@gmail.com P.

More information

UNBALANCED CURRENT BASED TARRIF

UNBALANCED CURRENT BASED TARRIF UNBALANCED CURRENT BASED TARRIF Hossein ARGHAVANI Tehran Electricity Distribution (TBTB) Co.-Iran hosein.argavani@gmail.com ABSTRACT The voltage &current unbalance are serious power quality problems with

More information

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Maher G. M. Abdolrasol maher_photo@yahoo.com Dept. of Electrical Engineering University of Malaya Lembah Pantai, 50603

More information

A Five Level Inverter for Grid Connected PV System Employing Fuzzy Controller

A Five Level Inverter for Grid Connected PV System Employing Fuzzy Controller Vol.2, Issue.5, Sep-Oct. 2012 pp-3730-3735 ISSN: 2249-6645 A Five Level Inverter for Grid Connected PV System Employing Fuzzy Controller M. Pavan Kumar 1, A. Sri Hari Babu 2 1, 2, (Department of Electrical

More information

RECENTLY, energy sources such as wind power systems,

RECENTLY, energy sources such as wind power systems, 550 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 25, NO. 3, MARCH 2010 Ripple Current Reduction of a Fuel Cell for a Single-Phase Isolated Converter Using a DC Active Filter With a Center Tap Jun-ichi

More information

Delhi Technological University (formerly DCE) Delhi-42, India

Delhi Technological University (formerly DCE) Delhi-42, India American International Journal of Research in Science, Technology, Engineering & Mathematics Available online at http://www.iasir.net ISSN (Print): 2328-3491, ISSN (Online): 2328-358, ISSN (CD-ROM): 2328-3629

More information

Multilevel Inverter Based Statcom For Power System Load Balancing System

Multilevel Inverter Based Statcom For Power System Load Balancing System IOSR Journal of Electronics and Communication Engineering (IOSR-JECE) e-issn: 2278-2834,p- ISSN: 2278-8735 PP 36-43 www.iosrjournals.org Multilevel Inverter Based Statcom For Power System Load Balancing

More information

Power Quality Requirements for Connection to the Transmission System

Power Quality Requirements for Connection to the Transmission System Power Quality Requirements for Connection to the Transmission System Revision: 1.0 Date: September 2015 Introduction and Purpose of this Document The purpose of this document is to provide clarity to Customers

More information

ANALYSIS OF PWM STRATEGIES FOR Z-SOURCE CASCADED MULTILEVEL INVERTER FOR PHOTOVOLTAIC APPLICATIONS

ANALYSIS OF PWM STRATEGIES FOR Z-SOURCE CASCADED MULTILEVEL INVERTER FOR PHOTOVOLTAIC APPLICATIONS U.P.B. Sci. Bull., Series C, Vol. 77, Iss. 2, 215 ISSN 2286-354 ANALYSIS OF PWM STRATEGIES FOR Z-SOURCE CASCADED MULTILEVEL INVERTER FOR PHOTOVOLTAIC APPLICATIONS Ramalingam SEYEZHAI* 1 MultiLevel Inverters

More information