Report of Results of Smart Meter RF Testing - Maui Prepared by CASCADIA PM, LLC. And Presented to HAWAII NATURAL ENERGY INSTITUTE

Size: px
Start display at page:

Download "Report of Results of Smart Meter RF Testing - Maui Prepared by CASCADIA PM, LLC. And Presented to HAWAII NATURAL ENERGY INSTITUTE"

Transcription

1 Report of Results of Smart Meter RF Testing - Maui Prepared by CASCADIA PM, LLC And Presented to HAWAII NATURAL ENERGY INSTITUTE April 15, 2014

2 Executive Summary 15 April 2014 RE: Report of EMR assessment of Smart Grid Meters and Access Point performed on 20 Feb This report reflects the pre and post antennae activation electromagnetic radiation assessment operating Smart Meters at 5 locations: Meter Mapu Place Kihei, Maui ', ' Meter Kupulau Drive Kihei, Maui ', ' Meter Keha Drive Kihei, Maui ', ' Meter Pawali Street Kihei, Maui ', ' Meter Kupulau Drive Kihei, Maui ', ' and one Access Point (AP) location: AP 1 near 1060 Kupulau Drive Kihei, Maui ', ' The results contained in this report are summarized below. For a detailed technical discussion of our findings the reader is referred to the complete report attached to this summary. Table 1 below tabulates the pre-activation average and maximum readings in milliwatts per square centimeter (mw/cm 2 ) in column A, the the post-activation average and maximum readings in milliwatts per square centimeter (mw/cm 2 ) in column B, and the average and maximum readings of the postactivation readings in percentage of the IEEE Standard obtained in each area assessed in column C. Columns D and E present the acceptable FCC standard guideline for the general population and occupational standard in the State of Hawaii. General population or uncontrolled exposures apply in situations in which the general public may be exposed, or in which persons that are exposed as a consequence of their employment may not be fully aware of the potential for exposure or cannot exercise control over their exposure. Occupants of the homes where the meters are installed fall into this category of general population. Column C lists the occupational exposure percent of standard maximum for the five smart meter locations surveyed. The readings near the meters did not exceed 0.015% of the maximum permissible exposure (MPE) limit of 0.6 mw/cm 2. Occupational or controlled limits apply in situations in which persons are exposed as a consequence of their employment. These persons should be fully aware of the potential for exposure and can exercise control over their exposure. Limits for occupational exposure also apply in situations when an individual is transient through a location where occupational/controlled limits apply provided he or she is made aware of the potential for exposure. Column C lists the occupational exposure percent of standard maximum for the access point location surveyed. The readings did not exceed % of the higher 10 mw/cm 2 standard near the access point located atop a utility pole. Report - Smart Meter RF Testing prepared by Cascadia PM April 2014 Page 2

3 Table 1. Summary of Survey Results Site No. / ( A ) ( B ) ( C ) Test Location No. / Pre activation Post activation Post activation HF 35C orientation Power Density Power Density (H or V) (µw/m 2 ) (µw/m 2 ) (% of standard D) Meter 1/1 H % Meter 1/1 V % Meter 1/2 H % Meter 1/2 V % Meter 1/3 H % Meter 1/3 V % Meter 1/4 H % Meter 1/4 V % Meter 2/1 H % Meter 2/1 V % Meter 2/2 H % Meter 2/2 V % Meter 2/3 H % Meter 2/3 V % Meter 2/4 H % Meter 2/4 V % Meter 3/1 H % Meter 3/1 V % Meter 3/2 H % Meter 3/2 V % Meter 3/3 H % Meter 3/3 V % Meter 3/4 H % Meter 3/4 V % Meter 4/1 H % Meter 4/1 V % Meter 4/2 H % Meter 4/2 V % Meter 4/3 H % Meter 4/3 V % Meter 4/4 H % Meter 4/4 V % Meter 5/1 H % Meter 5/1 V % Meter 5/2 H % Meter 5/2 V % Meter 5/3 H % Meter 5/3 V % Meter 5/4 H % Meter 5/4 V % ( D ) ( E ) FCC State of HI General population / Occupational / uncontrolled standard controlled standard ( µw/m 2 ) (100,000,000 µw/m 2 ) Report - Smart Meter RF Testing prepared by Cascadia PM April 2014 Page 3

4 Site No. / ( A ) ( B ) ( C ) Test Location No. / Pre activation Post activation Post activation HF 35C orientation Power Density Power Density (H or V) (µw/m 2 ) (µw/m 2 ) (% of standard D) Access Point 6/1 H always on not tested NA Access Point 6/1 V always on not tested NA Access Point 6/2 H always on % Access Point 6/2 V always on % Access Point 6/3 H always on % Access Point 6/3 V always on % Access Point 6/4 H always on % Access Point 6/4 V always on % ( D ) ( E ) FCC State of HI General population / Occupational / uncontrolled standard controlled standard ( µw/m 2 ) (100,000,000 µw/m 2 ) 100,000, ,000, ,000, ,000, ,000, ,000, ,000, ,000,000 Measured signal levels in this survey do not create a hazard to the public. The measured levels are well within United States FCC guidelines for the limitation of human exposure to radio frequency (RF) energy. Review of the data tabulated above indicates that the average power density readings at the five smart meter sites do not exceed 0.015% of the maximum exposure level standard for the general population and the readings taken at the access point site do not exceed % of the maximum level for occupational controlled conditions. Report - Smart Meter RF Testing prepared by Cascadia PM April 2014 Page 4

5 21 March 2014 Mr. Christian Rawson Hawaii Natural Energy Institute School of Ocean & Earth Science Technology University of Hawaii at Manoa 1680 East-West Road, POST 109 Honolulu, HI Report of EMF assessment of Smart Grid Meter and AP performed on 20 February 2014 Dear Mr. Rawson: The results of electromagnetic radiation (EMR) survey that was conducted by the undersigned investigator at the five smart meter sites at residences and one access point (AP) site installed on a utility pole located in Kihei, Maui is documented herein. The survey was conducted to assure that residents of the five smart metered homes, MECo personnel working on the utility pole links, and other individuals who can be near the smart meters, are not potentially overexposed to electromagnetic radiation generated and transmitted by the smart meter or access point transmitter. This survey was conducted on the morning on 19 February 2014 between 8:30AM and 5:30 PM on a normal weekday. Radio frequency (RF) field measurements were taken at multiple locations on the grounds around the Smart Meter and from a bucket truck around the pole mounted Access Point. The weather was sunny and degrees on the day of our inspection. The GE I-210 Smart Meter is the subject of the tests conducted. Specifically, the radio transmitter, manufactured by Silver Sprint Networks, is the device under test. The radio is similar to a cell phone transmitting at 1 Watt effective radiated power (ERP), but in the Industrial-Scientific-Medical (ISM) frequency band from MHz. The radio transmitter in the meter transmits data intermittently to the nearest access point device, which relays the data to the MECo data collection station via existing private telecommunication infrastructure. Electromagnetic radiation (EMR) measurements from the smart meter and access point devices were recorded utilizing a Gigahertz Solutions HF-35C 800 MHz to 2.5 GHz RF Analyzer. The Gigahertz Solutions HF-35C RF Analyzer is fitted with a Log-Periodic antenna array, which when pointed in the direction of the transmitter, will measure the strength of the radiation field density around the smart meter. The test instrument has a signal measurement range from 1 uw/m 2 to 2000 uw/m 2 to capture the expected signal levels. The instrument readings in microwatts per square meters can be converted to milliwatts per square centimeters in the range of mw/cm 2 to mw/cm 2. The Gigahertz Solutions HF-35C test instrument was purchased in 2014 and the manufacturer calibrated the instrument. The accuracy of these standards is traceable to the National Institute of Standards and Technology (NIST) to the extent allowed by accredited NIST s calibration facilities. Measurements are generally obtained at arm s length in direction of the emitters. The probe was held at the maximum distance from the tester s body and away from potential reflective objects. The RF measurements were logged for each axis (horizontal and vertical) in order to obtain a temporal and spatial average power density value. Report - Smart Meter RF Testing prepared by Cascadia PM April 2014 Page 5

6 Measurement results The measurements of the actual RF emissions from the five individual smart meters were recorded from various locations around the smart meters. The measurement of the energy emissions covered the radio frequency range of MHz microwave band signals generated by the smart meter device. The smart meter transmits at in the 900MHz frequency band. The RF emission measurements were made in front of the smart meter antenna, 5 feet away, 20 feet away and 50 feet away from the meter. The tests made immediately in front of the meter (position 1 in Figure 1 below) were found to be inconsistent due to the physics of wave generation the meter specification requires a minimum of 5 feet from the transmitter to measure reliably. Figure 1: Depiction of top and side views of the test locations near the meter. The test readings were taken twice at each test location for each meter site, once in the horizontal plane and once in the vertical plane while the smart meter device was off (pre activation); and twice with the smart meter on (post activation). The variance in the pre and post activation readings shall represent the measured RF emissions from the smart meter transmitter. Average and peak values were measured and recorded at each site, for reference. Silver Springs, manufacturer of the radio within the meter, stated that spurious peak readings could be caused in the near field due to the test equipment picking up reflections off the meter or other objects or noise by other RF sources. Therefore, the RMS readings are an industry standard measurement of the average continuous power density and best represents the effect of exposure over time to a human being. Report - Smart Meter RF Testing prepared by Cascadia PM April 2014 Page 6

7 Exposure significance The test results were taken under the worst conditions and therefore generated a conservative assessment of exposure by over-representing rather than under-representing the exposure over time. The meter was triggered to transmit continuously during testing. Normally, the meter transmits for 60 seconds every hour. The exposures allowable by the FCC are based on time, so the average RMS readings should be less than 1/60 th of the recorded readings when the meter is in the transmitting state. Moreover, the readings were compared to the IEEE Standard (0.6mW/cm 2 ) which is more than ten (10) times lower than the current Hawaii State occupational health and safety guidelines of (10mW/cm 2 ). Based upon these test results, the interpretation of the power density values with respect to a potential health hazard for workers and general population can now be readily assessed. The radiation being emitted by each of the five (5) smart meters are within the safe power density range covered by the IEEE Standard for general population and the State suggested guidelines of occupational conditions. The data collected during the pre and post activation survey of the area clearly indicated that the workers are not exposed to levels of radio frequency radiation higher than the IEEE Standard. The highest reading encountered in any location was.015% ( mw/cm 2 ) of the IEEE Standard maximum exposure level. These values are again below the most conservative standards published ( mW/cm 2 ) by the National Council on Radiation Protection 1. The values recorded do not constitute a hazard to the public, or to persons that are exposed as a consequence of their employment who may not be fully aware of the potential for exposure or cannot exercise control over their exposure. Referenced Exposure Guideline Standard-setting agencies in the U.S. and abroad have conducted independent surveys of the scientific literature to the end of recommending limits on exposure to RF fields. The National Council on Radiation Protection (NCRP), which was chartered by the U.S. Congress to develop exposure criteria for all forms of electromagnetic radiation, published an extensive review of the data based on biological effects of exposure to RF fields in The NCRP s Scientific Committee 53 made a distinction between occupational and general population exposures, which resulted in a two-tiered standard. The occupationally exposed worker (for example, an engineer or contractor installing or maintaining a radio transmitter) would be protected at the original ANSI-1982 limit on the SAR; no exposure in excess of 0.4 W/kg or 10 mw/cm 2. However, an additional five-fold reduction was recommended for members of the general population; no exposure in excess of 0.08 W/kg or 2 mw/cm 2. The NCRP s two-tier philosophy has been adopted by standard-setting bodies of many nationalities and by the International Radiation Protection Association (IRPA). The (1992) formulation of radio frequency exposure standards by the ANSI/IEEE has followed suit. In 1996, the National Council on Radiation Protection (NCRP) adopted new guidelines of compliance for human exposure to radiofrequency (RF) electromagnetic fields and published a new guidance document in Table 1 in appendix A of this document is reproduced below. 1 Evaluating Compliance with FCC Guidelines for Human Exposure to Radiofrequency Electromagnetic Fields, OET Bulletin 65, Edition 97-01, August Evaluating Compliance with FCC Guidelines for Human Exposure to Radiofrequency Electromagnetic Fields, OST Bulletin No. 65, October Evaluating Compliance with FCC Guidelines for Human Exposure to Radiofrequency Electromagnetic Fields, OET Bulletin 65, Edition 97-01,August Report - Smart Meter RF Testing prepared by Cascadia PM April 2014 Page 7

8 Table 1: LIMITS FOR MAXIMUM PERMISSIBLE EXPOSURE (MPE) NOTE 1: Occupational/controlled limits apply in situations in which persons are exposed as a consequence of their employment provided those persons are fully aware of the potential for exposure and can exercise control over their exposure. Limits for occupational/controlled exposure also apply in situations when an individual is transient through a location where occupational/controlled limits apply provided he or she is made aware of the potential for exposure. NOTE 2: General population/uncontrolled exposures apply in situations in which the general public may be exposed, or in which persons that are exposed as a consequence of their employment may not be fully aware of the potential for exposure or cannot exercise control over their exposure. Current Hawaii State occupational health and safety regulations allow workers to be exposed to 10 milliwatts per square centimeter (10 mw/cm 2 ) of electromagnetic radiation in the frequency range of 10 megahertz (MHz) to 100 gigahertz (GHz) as averaged during any 0.1-hour time period. The Hawaii State Occupational Safety and Health Standards (Title 12 sub-title 8, Part 8 Paragraph ) quoted in the previous paragraph are identical to the U.S. Department of Labor s criteria as promulgated by the Occupational Safety and Health Administration (OSHA). The Code of Federal Regulations (CFR Title 29, Parts are superseded in the State of Hawaii by the Hawaii State Department of Labor s criteria, but they are identical with one another. There are other guides, however, that are slightly more conservative and these are reviewed below. The American Conference of Governmental Industrial Hygienists (ACGIH) has published threshold Limit Values (TLVs) for a number of decades. Though they do not constitute federal, state, or other regulatory standards, they are nevertheless updated on an annual basis and are founded on verifiable scientific, medical, toxicological, and other technical reports and findings. The TLVs are used by professional industrial hygienists and cover both chemical substances and physical agents. In the case of radio frequency / microwave radiation, the ACGIH TLVs 4 refer to radiation in the frequency range from 30 kilohertz (khz) to 300 GHz, which covers a much broader range than the federal OSHA or Hawaii State regulations. Report - Smart Meter RF Testing prepared by Cascadia PM April 2014 Page 8

9 There are other standards generating organizations, but they do not recommend guides any different than those listed above. This is because they are all selected to limit the average whole body specific absorption rate (SAR) to 0.4 Watts per kilogram of body weight (W/kg) in any six-minute (0.1 hour) period of time for frequencies of 3 MHz to 300 GHz. This is a tenfold reduction below the consensus threshold of harm (4 W/kg) and the American National Standards Institute (ANSI) based their 1982 standard on this value. 5 Frequency Dependence of Effects The FCC exposure limit is frequency dependent. The maximum permissible exposure (MPE) limits depend upon the frequency of the signal to which a person is exposed because the human body absorbs energy differently at some frequencies than at others. Since the body absorbs FM radio signals between MHz more readily than MHz, the MPE level for signals from a smart meter is set at a higher maximum than the MPE for signals from a FM transmitter. The Chart 1 below graphically illustrates this point. Chart 1: FCC EXPOSURE LIMITS RELATIVE TO TRANSMITTED FREQUENCY Restating FCC Guidelines for Human Exposure to Radiofrequency Electromagnetic Fields, the maximum permissible exposure in the frequency range of 902 to 928 MHz is 0.6 milliwatts per square centimeter (0.6 mw/cm 2 ) as averaged during any 0.1-hour time period. 4 ACGIH 2001 adoption 5 Prior to 1988, C95 standards were developed by Accredited Standards Committee C95, and submitted to the American National Standards Institute (ANSI) for approval and issuance as ANSI C95 standards. Between 1988 and 1990, the committee was converted to Standards Coordinating Committee 28 (SCC 28) under the sponsorship of the IEEE Standards Board. In 2001, the IEEE Standards Association Standards Board approved the name International Committee on Electromagnetic Safety (ICES) for SCC 28 to better reflect the scope of the committee and its international membership. In accordance with policies of the IEEE, C95 standards are issued and developed as IEEE standards, as well as submitted to ANSI for recognition. Report - Smart Meter RF Testing prepared by Cascadia PM April 2014 Page 9

10 Conclusion Based on the foregoing, it is determined that the signal values measured do not create a hazard to the personnel working on the smart meter or to the general public who happen to pass the meter. The test results were taken under the worst conditions where the smart meter was transmitting. But in real operation, the meter is programmed to transmit only 60 seconds of a full hour. Considering the limited amount of actual signal transmission time, the low signal levels generated are conservative when you factor in the actual time the meter is transmitting a signal. The personnel working on or near the utility pole where the access point is installed are also not being exposed to levels of radio frequency radiation higher than the IEEE standard. Meter readings at no time exceeded.015% of the general population exposure standard. Should you have any questions or comments, please do not hesitate to contact us. Respectfully submitted, Reviewed and Approved, Cascadia PM, LLC Troy Thorhill Troy Thornhill Cascadia PM Matthew Miura Matthew K. Miura, PE Director - Cascadia PM Report - Smart Meter RF Testing prepared by Cascadia PM April 2014 Page 10

11 PRODUCT DATA SHEET Communications Module for Electricity Meters Adding twoway wireless communications to a broad array of meters: Offers one-watt transmitter to provide full, twoway wireless NAN communications Supports 2.4 GHz HAN communications Integrates with Silver Spring UtilityIQ application suite to support advanced metering and demand response Enables over-the-air firmware upgrades to reduce cost Provides full security and encryption to meet rigorous industry standards Smart Metering the Foundation of the Smart Grid The Silver Spring TM Smart Energy Platform combines network infrastructure, software, and professional services to enable a range of smart grid applications. Enabling two-way communications with next-generation electricity meters is fundamental to building the smart grid. The Silver Spring Communications Module integrates under glass inside partners electricity meters to provide wireless networking both back to the utility back office and into the customer s home. The module easily installs inside these meters and leverages Silver Spring network devices to form a highly resilient mesh network for the utility. The resulting two-way communications network gives utilities greater efficiency, more reliable service delivery, Utility Back-office Systems Silver Spring Message Bus Silver Spring Applications improved customer satisfaction, and a scalable platform for adding advanced smart grid applications both now and in the future. The Communications Module accesses demand, consumption, time-of-use and interval data, alarms, and power-quality data from the meter. Its two-way wireless functionality supports remote data acquisition, meter program management, and real-time asynchronous alerts for meter tampering or outages. Utilities can reprogram metering schedules over the air at any time for specific interval, register, or security reads, with access to both logged and instantaneous data. Depending upon the capabilities of the meter, utilities can also periodically monitor instantaneous voltage and temperature data. The Silver Spring Smart Energy Platform supports a range of smart grid applications on a single open standards-based network. UtilityIQ Unified Software GridScape Unified Management SilverLink Cloud Services CustomerIQ Customer Engagement WAN ACCESS POINT ETHERNET CELLULAR ACCESS POINT BRIDGE MASTER RELAY MICROMESH TECHNOLOGY LOAD CONTROL RELAY BRIDGE EVSE BRIDGE IEC METER GAS IMU ZIGBEE WATER FCI Advanced Metering Demand-side Management Distribution Automation About Silver Spring Networks Silver Spring Networks is a leading networking platform and solutions provider for smart energy networks. Our pioneering IPv6 networking platform, with 16.5 million Silver Spring enabled devices delivered, is connecting utilities to homes and business throughout the world with the goal of achieving greater energy efficiency for the planet. Silver Spring s innovative solutions enable utilities to gain operational efficiencies, improve grid reliability, and empower consumers to monitor and manage energy consumption. Silver Spring Networks is used by major utilities around the globe including Baltimore Gas & Electric, CitiPower & Powercor, Commonwealth Edison, CPS Energy, Florida Power & Light, Jemena Electricity Networks Limited, Pacific Gas & Electric, Pepco Holdings, Inc., and Progress Energy, among others. For more information please visit

12 PRODUCT DATA SHEET Communications Module for Electricity Meters With its full, one-watt transmitter, the Communications Module provides broad reach and robust connectivity in the Neighborhood or Field Area Network (NAN or FAN). In addition to supporting a 900 MHz radio for the NAN, the Communications Module also features an optional 2.4 GHz radio for the Home Area Network (HAN). This radio supports the ZigBee Smart Energy Profile specification to communicate with a wide range of smart devices within the home. Because the specification is evolving, Silver Spring designed its ZigBee radio with upgradable hardware to support more sophisticated protocol requirements. The Communications Module is available in a variety of NIC models to support the needs of disparate utilities and geographic regions. Features Full, two-way communications One-watt transmitter Frequency Hopping Spread Spectrum (FHSS) Robust security and encryption Dynamic network discovery and self healing Scheduled and on-demand meter reads Alarm detection and clearing Communications Module Specifications General: NIC 300 product family Platform NAN communications Architecture: System-on-Chip (SoC) Processor: SoC-based ARM7, adjustable frequencies RAM: 4 MB Flash: 8 MB Data rates: 100 kbps Spread spectrum: FHSS Transmitter output: 27 to 30 dbm (500 mw to 1 W) Receiver sensitivity: -97 dbm for 1% PER HAN communications Protocols: IEEE , ZigBee Smart Energy Profile 1.1 Frequency: 2.4 GHz ISM Band Transmitter output: 20 to 23 dbm (100 to 200 mw) Receiver sensitivity: -97 dbm for 1% PER Protocols / Security Environmental Addressing: IPv6 Encryption: Advanced Encryption Standard (AES-128 or AES-256) Security: Secure Hash Algorithm 256-bit (SHA-256) and RSA-1024 or ECC-256 Key storage: Secure NVRAM with tamper detection and key erasure Operating temperature: -40 C to +85 C (-40 F to +185 F) Humidity: 0% to 95%, non-condensing Communications Module Specifications North America: NIC 310 Radio Frequencies: MHz Approvals: FCC , Industry Canada RSS-210 Network time management Interfaces Meter: ANSI C12.18/C12.19, serial Continuous neighbor monitoring and route calculation Over-the-air firmware upgrades and meter programming Power outage and restoration notification Support for a wide range of meters and forms Meters supported GE I GE I-210+c 1 GE kv2c 1 GE kv2c+ 1 2 L+G E330 FOCUS AX L+G E350 AX-SD Single Phase L+G E330 FOCUS AX Polyphase L+G E650 S4e Elster A3 ALPHA 1 Denotes Measurement Canada approval 2 Supported via External Communications Module NIC 310 and 310x

13 PRODUCT DATA SHEET Communications Module for Electricity Meters Communications Module Specifications Australia: NIC 320 Radio Frequencies: MHz Approvals: AS/NZS 4268 Interfaces Meters supported Secure i-credit 500 Secure Sprint 200 Secure Premier L+G E L+G E L+G E L+G E Meter: ANSI C12.18/C12.19, serial External: Optional serial communications port NIC 320 Communications Module Specifications Brazil: NIC 330 Radio Interfaces Meters supported Frequencies: MHz, MHz Approvals: ANATEL Meter: ANSI C12.18/C12.19, serial Nansen Spectrum M Nansen Spectrum K Elster A3 NIC 330 family, with 330e and 330x models Communications Module Specifications General: NIC 400 product family Platform NAN communications Architecture: ARM based SoC RAM: 4 MB Flash: 8 MB Data rates: 50 kbps to 300 kbps Spread spectrum: FHSS Transmitter output: 27 to 30 dbm (500 mw to 1 W) Receive sensitivity: Data Rate (kbps) Receive Sensitivity (dbm for 10% PER) Protocol: IEEE g NIC 400 HAN communications Protocols: IEEE , ZigBee Smart Energy Profile 1.1 Frequency: 2.4 GHz ISM Band Transmitter output: 20 to 23 dbm (100 to 200 mw) Receiver sensitivity: -97 dbm for 1% PER Protocols / Security Environmental Addressing: IPv6 Encryption: Advanced Encryption Standard (AES-128 or AES-256) Security: Secure Hash Algorithm 256-bit (SHA-256) and RSA-1024 or ECC-256 Key storage: Secure NVRAM with tamper detection and key erasure Operating temperature: -40 C to +85 C (-40 F to +185 F) Humidity: 0% to 95%, non-condensing

14 PRODUCT DATA SHEET Communications Module for Electricity Meters Communications Module Specifications North America: NIC 400 Series Radio Interfaces Frequencies: MHz Approvals: FCC , Industry Canada RSS-210 Meter: ANSI C12.18/C12.19, serial Meters supported Elster A3 Itron CENTRON II C L+G E330 FOCUS AX L+G E350 AX-SD Single Phase L+G E330 FOCUS AX Polyphase 1 Denotes Measurement Canada approval Communications Module Specifications Australia/New Zealand NIC 400 Series Radio Interfaces Frequencies: Australia: MHz New Zealand: MHz Approvals: AS/NZS 4268 Meter: ANSI C12.18/C12.19, serial External: Optional serial communications port Meters supported L+G E L+G E L+G E L+G E Communications Module Specifications Brazil: NIC 400 series Radio Interfaces Meters supported Frequencies: MHz, MHz Approvals: ANATEL Meter: ANSI C12.18/C12.19, serial, DLMS-COSEM Itron SL7000 Meter Patch Antenna Coupler Physical Interfaces Environmental Antenna connector: N Type, Female Antenna types: Various Cable length: cm (6 ) Operating temperature: -40 C to +85 C (-40 F to +185 F) Humidity: 0% to 95%, non-condensing Approvals FCC: The optional Meter Patch Antenna Coupler connects meters equipped with a Communications Module to an external antenna for greater signal range and coverage. silverspringnet.com Copyright 2013 Silver Spring Networks. All Rights Reserved. All trademarks are the properties of their respective owners. REV. 6/19/2013

15 Test Result Sheets of Smart Meter RF Testing Maui Prepared by CASCADIA PM, LLC

16 Typical Radio Frequency Signal Power Density measurements in actual conditions Bar Chart Comparison FCC Standard 600 uw/cm 2 Smart Meter at 10 feet away FM radio/tv broadcast Wi Fi Router at 3 feet away Smart Meter at 3 feet away Microwave oven 2 feet away Cell phone at your ear 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500 5,000 Notes: Measured in microwatts/cm 2

17 LOCATION 1 Date 2/20/2014 Address 3043 Mapu Place City, Island Kihei, Maui Latitude/Longitude ', '

18 SMART METER RF TEST FORM Test Number M 1001 Date 2/20/2014 Address 3043 Mapu Place City, Island Kihei, Maui Latitude/Longitude ', ' Time 9:30 a.m. Tax Map Key :018 Ground Level 315' AMSL Antenna Tip Height 6' 3" AGL Smart Meter Make GE I 210 Model NIC 314 Serial Number Meter Transmision Level Measurement Horizontal Orientation Vertical Orientation OFF or PRE µw/m 2 ON or POST µw/m 2 OFF or PRE µw/m 2 ON or POST µw/m 2 FCC Limit µw/m 2 Peak Average Peak Average Peak Average Peak Average Average Test Location 1 At Meter Test Location 2 5 feet away from meter Test Location 3 20 feet away from meter Test Location 4 50 feet away from meter Qualitative Description Test locations 3 and 4 were made from adjacent property and were barely obstructed by plants/trees Several readings were higher due to stray interferrence when testing close to the wall. Test Equipment Manufacturer Gigahertz Solutions Make Serial Number HF Calibration Date Serial Number ANT HF 35C 2/19/2014 Tested by Troy Thornhill Certified by Matt Miura

19 LOCATION 2 Date 2/20/2014 Address 627 Kupulau Drive City, Island Kihei, Maui Latitude/Longitude ', '

20 SMART METER RF TEST FORM Test Number M 1002 Date 2/20/2014 Address 627 Kupulau Drive City, Island Kihei, Maui Latitude/Longitude ', ' Time 12:00 p.m. Tax Map Key :022 Ground Level 481' AMSL Antenna Tip Height 6' 3" AGL Smart Meter Make GE I 210 Model NIC 314 Serial Number Meter Transmision Level Measurement Horizontal Orientation Vertical Orientation OFF or PRE µw/m 2 ON or POST µw/m 2 OFF or PRE µw/m 2 ON or POST µw/m 2 FCC Limit µw/m 2 Peak Average Peak Average Peak Average Peak Average Average Test Location 1 At Meter Test Location 2 5 feet away from meter Test Location 3 20 feet away from meter Test Location 4 50 feet away from meter Qualitative Description Test locations 3 and 4 were made from adjacent property and terrain elevation changed/increased slightly Several readings were higher due to stray interferrence when testing close to the wall. Test Equipment Manufacturer Gigahertz Solutions Make Serial Number HF Calibration Date Serial Number ANT HF 35C 2/19/2014 Tested by Troy Thornhill Certified by Matt Miura

21 LOCATION 3 Date 2/20/2014 Address 3288 Keha Drive City, Island Kihei, Maui Latitude/Longitude ', '

22 SMART METER RF TEST FORM Test Number M 1003 Date 2/20/2014 Address 3288 Keha Drive City, Island Kihei, Maui Latitude/Longitude ', ' Smart Meter Make GE I 210 Model NIC 314 Serial Number Meter Transmision Level Measurement Horizontal Orientation Vertical Orientation OFF or PRE µw/m 2 ON or POST µw/m 2 OFF or PRE µw/m 2 ON or POST µw/m 2 FCC Limit µw/m 2 Peak Average Peak Average Peak Average Peak Average Average Test Location 1 At Meter Test Location 2 5 feet away from meter Test Location 3 20 feet away from meter Test Location 4 50 feet away from meter Qualitative Description Location 4 was tested from street Location 3 and 4 were barely obstructed by plants/trees and terrain elevation increased slightly Several readings were higher due to stray interferrence when testing close to the wall. Test Equipment Manufacturer Gigahertz Solutions Make Serial Number HF Calibration Date Serial Number ANT Time 12:30 p.m. Tax Map Key :049 Ground Level 593' AMSL Antenna Tip Height 6' 3" AGL HF 35C 2/19/2014 Tested by Troy Thornhill Certified by Matt Miura

23 LOCATION 4 Date 2/20/2014 Address 539 Pawali Street City, Island Kihei, Maui Latitude/Longitude ', '

24 SMART METER RF TEST FORM Date 2/20/2014 Address 539 Pawali Street City, Island Kihei, Maui Latitude/Longitude ', ' Test Number Time Tax Map Key Ground Level Antenna Tip Height M :15 p.m : ' AMSL 6' 3" AGL Smart Meter Make GE I 210 Model NIC 314 Serial Number Meter Transmision Level Measurement Horizontal Orientation Vertical Orientation OFF or PRE ON or POST OFF or PRE ON or POST µw/m 2 µw/m 2 µw/m 2 µw/m 2 FCC Limit µw/m 2 Peak Average Peak Average Peak Average Peak Average Average Test Location 1 At Meter Test Location 2 5 feet away from meter Test Location 3 20 feet away from meter Test Location 4 50 feet away from meter Qualitative Description Test locations 3 and 4 were made from adjacent property and were obstructed by plants/trees Several readings were higher due to stray interferrence when testing close to the wall. Test Equipment Manufacturer Gigahertz Solutions Make Serial Number HF Calibration Date Serial Number ANT HF 35C 2/19/2014 Tested by Troy Thornhill Certified by Matt Miura

25 LOCATION 5 Date 2/20/2014 Address 1148 Kupulau Drive City, Island Kihei, Maui Latitude/Longitude ', '

26 SMART METER RF TEST FORM Test Number M 1005 Date 2/20/2014 Address 1148 Kupulau Drive City, Island Kihei, Maui Latitude/Longitude ', ' Smart Meter Make GE I 210 Model NIC 314 Serial Number Meter Transmision Level Measurement Horizontal Orientation Vertical Orientation OFF or PRE µw/m 2 ON or POST µw/m 2 OFF or PRE µw/m 2 ON or POST µw/m 2 FCC Limit µw/m 2 Peak Average Peak Average Peak Average Peak Average Average Test Location 1 At Meter Test Location 2 5 feet away from meter Test Location 3 20 feet away from meter Test Location 4 35 feet away from meter Qualitative Description Test locations 3 and 4 were made from the left of the meter due to space constrictions Location 4 was measured from only 35' and not 50' due to space constrictions Several readings were higher due to existing stray interferrence when testing close to the wall. Test Equipment Manufacturer Gigahertz Solutions Make Serial Number HF Calibration Date Serial Number ANT Time 4:00 p.m. Tax Map Key :073 Ground Level 636' AMSL Antenna Tip Height 6' 0" AGL HF 35C 2/19/2014 Tested by Troy Thornhill Certified by Matt Miura

27 LOCATION 6 Date 2/20/2014 Address near 1060 Kupulau Drive City, Island Kihei, Maui Latitude/Longitude ', '

28 SMART METER RF TEST FORM Test Number AP 1001 Date 2/20/2014 Address near 1060 Kupulau Drive City, Island Kihei, Maui Latitude/Longitude ', ' Access Point Make n/a Model n/a Serial Number n/a Antenna Transmision Level Measurement Horizontal Orientation Vertical Orientation Note: Access point is continually trasmitting (no OFF or PRE tests available) FCC Limit µw/m 2 µw/m 2 µw/m 2 Peak Average Peak Average Average Test Location 1 At Access Point not taken not taken not taken not taken 100,000,000 Test Location 2 5 feet away from antenna ,000,000 Test Location 3 20 feet away from antenna ,000,000 Test Location 4 50 feet away from antenna ,000,000 Qualitative Description Test Equipment Manufacturer Gigahertz Solutions Make Serial Number HF Calibration Date Serial Number ANT Time Tax Map Key Ground Level Antenna Tip Height This sheet represents the measurements taken at the access point antenna (not at a smart meter) Measurements taken from "cherry picker" bucket approx. 40' in the air This site evaluated under the higher 'occupational' FCC standards HF 35C 2/19/2014 1:10 p.m. n/a 701' AMSL Approx. 40' AGL Tested by Troy Thornhill Certified by Matt Miura

Regulatory Authority of Bermuda report on

Regulatory Authority of Bermuda report on Regulatory Authority of Bermuda report on Bermuda Electric Light Company Smart Meter Maximum Permissible Exposure 14 June 2018 This report reflects the electromagnetic radio frequency Maximum Permissible

More information

WHITEPAPER WHITEPAPER

WHITEPAPER WHITEPAPER WHITEPAPER WHITEPAPER Radio Frequency Emissions Analysis of Radio Frequency Exposure Associated with Silver Spring Networks Advanced Metering Devices Executive Summary This document provides information

More information

2200 Noll Drive Lancaster, PA Latitude: N 40º (NAD 83) Longitude: W 76º (NAD 83) 362 AMSL

2200 Noll Drive Lancaster, PA Latitude: N 40º (NAD 83) Longitude: W 76º (NAD 83) 362 AMSL April 27, 2017 James M. Strong McNees Wallace & Nurick LLC 100 Pine Street, P.O. Box 1166 Harrisburg, PA 17108-1166 Subject: Electromagnetic Exposure Analysis WHEATLAND 2200 Noll Drive Lancaster, PA 17603

More information

CoServ Electric s RF Mesh Advanced Metering Infrastructure. RF/EMF Investigation

CoServ Electric s RF Mesh Advanced Metering Infrastructure. RF/EMF Investigation CoServ Electric s RF Mesh Advanced Metering Infrastructure RF/EMF Investigation Date Analysis Performed: 05/03/2012 Introduction CoServ Electric is a not-for-profit electric distribution cooperative and,

More information

Calculated Radio Frequency Emissions Report. Cotuit Relo MA 414 Main Street, Cotuit, MA 02635

Calculated Radio Frequency Emissions Report. Cotuit Relo MA 414 Main Street, Cotuit, MA 02635 C Squared Systems, LLC 65 Dartmouth Drive Auburn, NH 03032 (603) 644-2800 support@csquaredsystems.com Calculated Radio Frequency Emissions Report Cotuit Relo MA 414 Main Street, Cotuit, MA 02635 July 14,

More information

RADIOFREQUENCY ELECTROMAGNETIC FIELDS

RADIOFREQUENCY ELECTROMAGNETIC FIELDS CHAPTER 19. RADIOFREQUENCY ELECTROMAGNETIC FIELDS 19.1 INTRODUCTION 19.1.1 CONTEXT The proposed buildings of the World Trade Center Memorial and Redevelopment Plan (Proposed Action) are being designed

More information

RF EMISSIONS FROM SMART GRID ELECTRIC METERS, HAN DEVICES, AND THEIR RELATIONSHIP TO THE FCC MAXIMUM PERMISSIBLE EXPOSURE LIMIT (MPE)

RF EMISSIONS FROM SMART GRID ELECTRIC METERS, HAN DEVICES, AND THEIR RELATIONSHIP TO THE FCC MAXIMUM PERMISSIBLE EXPOSURE LIMIT (MPE) RF EMISSIONS FROM SMART GRID ELECTRIC METERS, HAN DEVICES, AND THEIR RELATIONSHIP TO THE FCC MAXIMUM PERMISSIBLE EXPOSURE LIMIT (MPE) PREPARED FOR BY Gordon W. Hudson 20 th September 2012 Table of Contents

More information

RADIO FREQUENCY NIER REPORT

RADIO FREQUENCY NIER REPORT RADIO FREQUENCY NIER REPORT City of Albany Cellular Sites Prepared for: City of Albany Prepared August 26, 2013 by: Peter Gruchawka, President Accord Communications (707) 833-5027 Accord Communications

More information

Model: M /800 MHz Mobile Radio

Model: M /800 MHz Mobile Radio Engineering and Testing for EMC and Safety Compliance Accredited Under NVLAP Lab Code 200061-0 RF Maximum Permissible Exposure (MPE) Report for Controlled and Uncontrolled Environments M/A-COM, Inc. 221

More information

Wireless Facility Radio Frequency Exposure Compliance Review

Wireless Facility Radio Frequency Exposure Compliance Review Wireless Facility Radio Frequency Exposure Compliance Review Gibraltar Peak Communications Site 3035 Gibraltar Road, Santa Barbara, CA 9/21/2015 Preiser Consulting 23836 La Posta Court, Corona, CA 92883

More information

Verizon Wireless Proposed Base Station (Site No Berkeley Bekins ) 2721 Shattuck Avenue Berkeley, California

Verizon Wireless Proposed Base Station (Site No Berkeley Bekins ) 2721 Shattuck Avenue Berkeley, California Statement of Hammett & Edison, Inc., Consulting Engineers The firm of Hammett & Edison, Inc., Consulting Engineers, has been retained on behalf of Verizon Wireless, a personal wireless telecommunications

More information

Royal Street Communications, LLC Proposed Base Station (Site No. LA0366A) 315 4th Avenue Venice, California

Royal Street Communications, LLC Proposed Base Station (Site No. LA0366A) 315 4th Avenue Venice, California Statement of Hammett & Edison, Inc., Consulting Engineers The firm of Hammett & Edison, Inc., Consulting Engineers, has been retained on behalf of Royal Street Communications, LLC, a personal wireless

More information

Health Issues. Introduction. Ionizing vs. Non-Ionizing Radiation. Health Issues 18.1

Health Issues. Introduction. Ionizing vs. Non-Ionizing Radiation. Health Issues 18.1 Health Issues 18.1 Health Issues Introduction Let s face it - radio waves are mysterious things. Especially when referred to as electromagnetic radiation the concept makes many people nervous. In this

More information

Radio Frequency Emissions Analysis Report Sprint Wireless Water Tank Facility

Radio Frequency Emissions Analysis Report Sprint Wireless Water Tank Facility Radio Frequency Emissions Analysis Report Sprint Wireless Water Tank Facility Site ID: BS3XC490 Site Name: Cedar St. Water Tank Address: 396 Cedar Street, Ashland, MA 0171 Latitude: 4.35300 Longitude:

More information

Florida Public Service Commission Staff Workshop on Smart Meters

Florida Public Service Commission Staff Workshop on Smart Meters Florida Public Service Commission Staff Workshop on Smart Meters d Don Control Reeves, SVP Overview Smart Grid Services & Operations 9/20/2012 0 Silver Spring Networks Celebrating a decade of success Company

More information

Human Exposure Requirements for R&TTE and FCC Approval

Human Exposure Requirements for R&TTE and FCC Approval Human Exposure Requirements for R&TTE and FCC Approval Derek Y. W. LEUNG Founding and Committee Member of EMC Chapter- IEEE-HK Requirements of Non-Specific Short Range Device (SRD) for CE Marking Radio

More information

Verizon Wireless Proposed Base Station (Site No Lake Cachuma ) 2680 Highway 154 Santa Barbara County, California

Verizon Wireless Proposed Base Station (Site No Lake Cachuma ) 2680 Highway 154 Santa Barbara County, California Statement of Hammett & Edison, Inc., Consulting Engineers The firm of Hammett & Edison, Inc., Consulting Engineers, has been retained on behalf of Verizon Wireless, a personal wireless telecommunications

More information

ELECTROMAGNETIC ENERGY (EME) EXPOSURE REPORT

ELECTROMAGNETIC ENERGY (EME) EXPOSURE REPORT ELECTROMAGNETIC ENERGY (EME) EXPOSURE REPORT Site Name: Site ID: USID: FA Location: Marin Avenue CCL04554 101927 10113497 Site Type: Location: Latitude (NAD83): NAD83): Longitude (NAD83): Report Completed:

More information

Verizon Wireless Proposed Base Station (Site No South Goleta ) 4500 Hollister Avenue Santa Barbara, California

Verizon Wireless Proposed Base Station (Site No South Goleta ) 4500 Hollister Avenue Santa Barbara, California Statement of Hammett & Edison, Inc., Consulting Engineers The firm of Hammett & Edison, Inc., Consulting Engineers, has been retained on behalf of Verizon Wireless, a personal wireless telecommunications

More information

Radio Frequency Electromagnetic Energy (RF-EME) Compliance Report

Radio Frequency Electromagnetic Energy (RF-EME) Compliance Report Page 1 of 16 Radio Frequency Electromagnetic Energy (RF-EME) Compliance Report Ashby & Adeline 2004 Emerson Street Berkeley, California 94704 Santa Clara County 37.854095; -122.268552 NAD83 Rooftop May

More information

AT&T Mobility Proposed Base Station (Site No. CN4779A) 1101 Keaveny Court Walnut Creek, California

AT&T Mobility Proposed Base Station (Site No. CN4779A) 1101 Keaveny Court Walnut Creek, California Statement of Hammett & Edison, Inc., Consulting Engineers The firm of Hammett & Edison, Inc., Consulting Engineers, has been retained on behalf of AT&T Mobility, a personal wireless telecommunications

More information

Radio Frequency Electromagnetic Energy (RF-EME) Compliance Report

Radio Frequency Electromagnetic Energy (RF-EME) Compliance Report Page 1 of 36 Radio Frequency Electromagnetic Energy (RF-EME) Compliance Report Site No. FN03XC065 Huntmount Medical Center 2999 Regent Street Berkeley, California 94705 Alameda County 37.855900; -122.256000

More information

FCC CFR47 PART 15 SUBPART C INDUSTRY CANADA RSS-210 ISSUE 7 CERTIFICATION TEST REPORT FOR g WIRELESS LAN + BLUETOOTH PCI-E MINI CARD

FCC CFR47 PART 15 SUBPART C INDUSTRY CANADA RSS-210 ISSUE 7 CERTIFICATION TEST REPORT FOR g WIRELESS LAN + BLUETOOTH PCI-E MINI CARD FCC CFR47 PART 15 SUBPART C INDUSTRY CANADA RSS-210 ISSUE 7 CERTIFICATION TEST REPORT FOR 802.11g WIRELESS LAN + BLUETOOTH PCI-E MINI CARD MODEL NUMBER: BCM94312HMGB REPORT NUMBER: 09U12439-2 ISSUE DATE:

More information

Modeling Electromagnetic Radiation on Lookout Mountain, Colorado

Modeling Electromagnetic Radiation on Lookout Mountain, Colorado Modeling Electromagnetic Radiation on Lookout Mountain, Colorado 1. Introduction 1.1. Goal of Research This Capstone project has been initiated in an attempt to model the Electromagnetic Radiation (EMR)

More information

ELECTROMAGNETIC ENERGY (EME) EXPOSURE REPORT

ELECTROMAGNETIC ENERGY (EME) EXPOSURE REPORT ELECTROMAGNETIC ENERGY (EME) EXPOSURE REPORT Site Name: Site ID: USID: FA Location: Scott and Coyote Creek CVL01624 47719 10102020 Site Type: Location: Latitude (NAD83): NAD83): Longitude (NAD83): Report

More information

Measurements of Exposures Around Vodafone New Zealand Limited Cellsites from June 2012 to May 2013

Measurements of Exposures Around Vodafone New Zealand Limited Cellsites from June 2012 to May 2013 Measurements of Exposures Around Vodafone New Zealand Limited Cellsites from June 2012 to May 2013 This report was prepared for: Vodafone New Zealand Limited Private Bag 92161 AUCKLAND By M Dirksen Reviewed

More information

FCC CFR47 PART 15 SUBPART C INDUSTRY CANADA RSS-GEN AND RSS-210 CERTIFICATION TEST REPORT FOR BROADCOM BLUETOOTH MODULE MODEL NUMBER: BCM92046MD

FCC CFR47 PART 15 SUBPART C INDUSTRY CANADA RSS-GEN AND RSS-210 CERTIFICATION TEST REPORT FOR BROADCOM BLUETOOTH MODULE MODEL NUMBER: BCM92046MD FCC CFR47 PART 15 SUBPART C INDUSTRY CANADA RSS-GEN AND RSS-210 CERTIFICATION TEST REPORT FOR BROADCOM BLUETOOTH MODULE MODEL NUMBER: BCM92046MD IC #: 4324A-BRCM1029 REPORT NUMBER: 07U11199-1C ISSUE DATE:

More information

Honeywell, Automation and Control Solutions

Honeywell, Automation and Control Solutions Honeywell, Automation and Control Solutions TH6320WF2003 FCC 2.1091:2016 802.11bgn SISO Radio Module Report # HNYW0156.1 NVLAP Lab Code: 200881-0 This report must not be used to claim product certification,

More information

RF EMISSIONS COMPLIANCE REPORT. Verizon Wireless. Report Status: Verizon Wireless is Compliant

RF EMISSIONS COMPLIANCE REPORT. Verizon Wireless. Report Status: Verizon Wireless is Compliant RF EMISSIONS COMPLIANCE REPORT Verizon Wireless Site: Site ID: 199 Address: TBD 8/12/2015 Report Status: Verizon Wireless is Compliant Prepared By: Sitesafe, Inc. 200 North Glebe Road, Suite 1000 Arlington,

More information

Verizon Wireless Proposed Base Station (Site No Palos Verdes ) 1506 Camino Verde Walnut Creek, California

Verizon Wireless Proposed Base Station (Site No Palos Verdes ) 1506 Camino Verde Walnut Creek, California Attachment 6 Statement of Hammett & Edison, Inc., Consulting Engineers The firm of Hammett & Edison, Inc., Consulting Engineers, has been retained on behalf of Verizon Wireless, a personal wireless telecommunications

More information

RF Exposure Assessment Report (FCC ID: 2AD8UAZRBRH1)

RF Exposure Assessment Report (FCC ID: 2AD8UAZRBRH1) 600-700 Mountain Avenue Room 5B-108 Murray Hill, New Jersey 07974-0636 USA RF Exposure Assessment Report () Regulation 47 CFR FCC Sections 1.1307 and 1.1310 Client Nokia Solutions and Networks Oy Product

More information

Radio Frequency Electromagnetic Energy (RF-EME) Compliance Report

Radio Frequency Electromagnetic Energy (RF-EME) Compliance Report Radio Frequency Electromagnetic Energy (RF-EME) Compliance Report Prepared for: Sprint Nextel c/o Black & Veatch Corporation 2999 Oak Rd. Suite 910 Walnut Creek,CA 94597 Hopkins of Berkely - St. Mary's

More information

R ICHARD T ELL A SSOCIATES, INC.

R ICHARD T ELL A SSOCIATES, INC. R ICHARD T ELL A SSOCIATES, INC. Supplemental Report on An Analysis of Radiofrequency Fields Associated with Operation of the PG&E SmartMeter Program Upgrade System October 27, 2008 Prepared for Pacific

More information

MAXIMUM PERMISSIBLE EXPOSURE STUDY

MAXIMUM PERMISSIBLE EXPOSURE STUDY MAXIMUM PERMISSIBLE EXPOSURE STUDY THEORETICAL REPORT Site Number: VW-MA-0057 Site Name: Wellfleet 6 Latitude: 41.89696667 Longitude: -69.984375 Address: 724 Route 6, Wellfleet, MA 02667 Conclusion: The

More information

Electric Imp, Inc. IMP003-FCC FCC :2014. Report # ELIM NVLAP Lab Code:

Electric Imp, Inc. IMP003-FCC FCC :2014. Report # ELIM NVLAP Lab Code: Electric Imp, Inc. IMP003-FCC FCC 2.1091:2014 Report # ELIM0007.3 NVLAP Lab Code: 200630-0 This report must not be used to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency

More information

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA Application of Pacific Gas and Electric Company for Approval of Modifications to its SmartMeter Program and Increased Revenue Requirements

More information

SAFETYTRAINING INFORMATION Your TYT ELECTRONICS CO.,LTD radio generates RF electromagnetic energy during transmit mode. This radio is designed for and

SAFETYTRAINING INFORMATION Your TYT ELECTRONICS CO.,LTD radio generates RF electromagnetic energy during transmit mode. This radio is designed for and SAFETYTRAINING INFORMATION Your TYT ELECTRONICS CO.,LTD radio generates RF electromagnetic energy during transmit mode. This radio is designed for and classified as Occupational Use Only, meaning it must

More information

Safety Code 6 (SC6) Measurement Procedures (Uncontrolled Environment)

Safety Code 6 (SC6) Measurement Procedures (Uncontrolled Environment) February 2011 Spectrum Management and Telecommunications Technical Note Safety Code 6 (SC6) Measurement Procedures (Uncontrolled Environment) Aussi disponible en français NT-329 Contents 1.0 Purpose...1

More information

Honeywell, Automation and Control Solutions

Honeywell, Automation and Control Solutions Honeywell, Automation and Control Solutions Model: RTH9580WF01 Report No. HNYW0043.3 FCC 2.1091: Maximum Permissible Exposure Level Report Prepared By Northwest EMC Inc. NORTHWEST EMC (888) 364-2378 www.nwemc.com

More information

HAZARDS OF NON-IONIZING RADIOFREQUENCY (RF) RADIATION

HAZARDS OF NON-IONIZING RADIOFREQUENCY (RF) RADIATION HAZARDS OF NON-IONIZING RADIOFREQUENCY (RF) RADIATION IS IT SAFE TO USE A CELL PHONE, BLUE TOOTH, AND WIFI HOTSPOTS??? Learning Objectives Non-Ionizing RF Radiation vs. Ionizing Radiation Biological effects

More information

SAR REPORT. TEST STANDARDS: FCC Part 15 Subpart C Intentional Radiator. ARRIS Model Spectrum 110A Set Top Box With Bluetooth (DSS) and RF4CE (DTS)

SAR REPORT. TEST STANDARDS: FCC Part 15 Subpart C Intentional Radiator. ARRIS Model Spectrum 110A Set Top Box With Bluetooth (DSS) and RF4CE (DTS) BEC INCORPORATED SAR REPORT TEST STANDARDS: FCC Part 15 Subpart C Intentional Radiator ARRIS Model Spectrum 110A Set Top Box With Bluetooth (DSS) and RF4CE (DTS) REPORT BEC-1839-08 CUSTOMER: ARRIS Group

More information

Ave output power ANT 1(dBm) Ave output power ANT 2 (dbm)

Ave output power ANT 1(dBm) Ave output power ANT 2 (dbm) Page 41 of 103 9.6. Test Result The test was performed with 802.11b Channel Frequency (MHz) power ANT 1(dBm) power ANT 2 (dbm) power ANT 1(mW) power ANT 2 (mw) Limits dbm / W Low 2412 7.20 7.37 5.248 5.458

More information

Order Number : GETEC-C FCC Part 1 Test Report Number : GETEC-E Page 2 / 15 CONTENTS

Order Number : GETEC-C FCC Part 1 Test Report Number : GETEC-E Page 2 / 15 CONTENTS Test Report Number : GETEC-E3-17-046 Page 2 / 15 CONTENTS 1. GENERAL INFORMATION... 3 2. INTRODUCTION... 4 3. PRODUCT INFORMATION... 5 3.1 DESCRIPTION OF EUT... 5 3.2 DEFINITION OF MODELS... 5 3.3 SUPPORT

More information

Report On. RF Exposure Assessment of the Sepura plc SRG3900 with AQHB Antenna. FCC ID: XX6SRG3900UW Industry Canada ID: 8739A-SRG3900UW

Report On. RF Exposure Assessment of the Sepura plc SRG3900 with AQHB Antenna. FCC ID: XX6SRG3900UW Industry Canada ID: 8739A-SRG3900UW Report On RF Exposure Assessment of the Sepura plc SRG3900 with AQHB Antenna FCC ID: XX6SRG3900UW Industry Canada ID: 8739A-SRG3900UW Document 75908189 Report 04 Issue 2 March 2010 TUV Product Service

More information

Contact person Date Reference Page Tomas Lennhager P03968-MPE 1 (2) Electronics

Contact person Date Reference Page Tomas Lennhager P03968-MPE 1 (2) Electronics issued by an FCC listed Laboratory Reg. no. 93866. The test site complies with RSS-Gen, file no: IC 3482A Contact person Tomas Lennhager 2016-06-10 6P03968-MPE 1 (2) Electronics +46 10 516 54 09 Tomas.Lennhager@sp.se

More information

Wireless Transmissions:

Wireless Transmissions: Wireless Transmissions: An Examination of OpenWay Smart Meter Transmissions in a 24-Hour Duty Cycle Jeff French Applications Engineer Mike Belanger Product Line Manager 2011, Itron Inc. All rights reserved.

More information

Before the Federal Communications Commission Washington, D.C

Before the Federal Communications Commission Washington, D.C Before the Federal Communications Commission Washington, D.C. 20554 In the Matter of ) ) Proposed Changes in the Commission s ) ET Docket No. 03-137 Rules Regarding Human Exposure to ) Radiofrequency Electronic

More information

Intertek Testing Services ETL SEMKO

Intertek Testing Services ETL SEMKO Page 1 of 6 Maximum Permissible Exposure (MPE) Evaluation Report Report No. : EME-030276 Model No. : ME101 Issued Date : Mar. 5, 2003 Applicant Test By : NETGEAR, Inc. 4500 Great America Parkway, Santa

More information

Wireless System Collocation Presents New Issues For Worker Protection

Wireless System Collocation Presents New Issues For Worker Protection Wireless System Collocation Presents New Issues For Worker Protection The electricity transmission and distribution community has been unaffected by standards covering radio frequency radiation until now.

More information

MAXIMUM PERMISSIBLE EXPOSURE ADDENDUM REPORT TO (Measurement)

MAXIMUM PERMISSIBLE EXPOSURE ADDENDUM REPORT TO (Measurement) MAXIMUM PERMISSIBLE EXPOSURE ADDENDUM REPORT TO 98384-9 (Measurement) FOR THE Device: SRR+RV50WWAN+WIFI+GPSRx Models: CCU100B, CCU100B Repeater, CCU100RB, CCU100RB Repeater & CCU100TB Report No.: 98384-9A

More information

After having perused the Decree Law No. (31) of 2002 on Protection from Radiation,

After having perused the Decree Law No. (31) of 2002 on Protection from Radiation, Minister of Environment Decision No. (116) of 2013 on the Issuance of the National Instructions for the Protection from Electromagnetism Radiation Emitted from Operating Radio Frequencies Equipments The

More information

TRANSMITTER MODEL: KAS-2030M

TRANSMITTER MODEL: KAS-2030M Page 1 of 16 FCC PART 15, SUBPART B and C TEST REPORT for TRANSMITTER MODEL: KAS-2030M Prepared for WILDLIFE TECHNOLOGIES 115 WOLCOTT STREET MANCHESTER, NEW HAMPSHIRE 03103 Prepared by: KYLE FUJIMOTO Approved

More information

SHENZHEN LCS COMPLIANCE TESTING LABORATORY LTD. FCC ID: WXLRAMV Report No.: LCS E-03 FCC MPE TEST REPORT. 47 CFR FCC Part 2 2.

SHENZHEN LCS COMPLIANCE TESTING LABORATORY LTD. FCC ID: WXLRAMV Report No.: LCS E-03 FCC MPE TEST REPORT. 47 CFR FCC Part 2 2. FCC MPE TEST REPORT 47 CFR FCC Part 2 2.1091 Report Reference No....: FCC ID....: Date of Issue....: Testing Laboratory Name...: Address...: Applicant s name...: Address...: Test specification...: LCS1511070542E-03

More information

IOSH Webinar. Control of Electromagnetic Fields at work regulations 2016 Part 2 EMF exposure assessment 4 th May 2017 Julia Clark FSRP CMIOSH

IOSH Webinar. Control of Electromagnetic Fields at work regulations 2016 Part 2 EMF exposure assessment 4 th May 2017 Julia Clark FSRP CMIOSH IOSH Webinar Control of Electromagnetic Fields at work regulations 2016 Part 2 EMF exposure assessment 4 th May 2017 Julia Clark FSRP CMIOSH www.linkmicrotek.com Previously Webinar part one covered: Definition

More information

White Space Devices (WSDs)

White Space Devices (WSDs) Issue 1 February 2015 Spectrum Management and Telecommunications Radio Standards Specification White Space Devices (WSDs) Aussi disponible en français - CNR-222 Preface Industry Canada s Radio Standards

More information

Wireless Facility Engineering Review

Wireless Facility Engineering Review Page 1 of 8 Wireless Facility Engineering Review Sprint Application for Site (Site No. FN03XC064) 1760 Solano Avenue, Berkeley, CA 10/9/2013 RCC Consultants, Inc. - Western Regional Office 266 E. 33 rd

More information

TABLE OF CONTENTS 1. GENERAL INFORMATION... 4

TABLE OF CONTENTS 1. GENERAL INFORMATION... 4 TABLE OF CONTENTS 1. GENERAL INFORMATION... 4 1.1. EUT DESCRIPTION... 4 1.2. TEST STANDARDS AND RESULTS... 5 1.3. FACILITIES AND ACCREDITATIONS... 6 1.3.1. FACILITIES... 6 1.3.2. TEST ENVIRONMENT CONDITIONS...

More information

Medtronic MiniMed TEST REPORT FOR. GST3 Glucose Sensor Transmitter, MMT-7763A. Tested To The Following Standards:

Medtronic MiniMed TEST REPORT FOR. GST3 Glucose Sensor Transmitter, MMT-7763A. Tested To The Following Standards: Medtronic MiniMed TEST REPORT FOR GST3 Glucose Sensor Transmitter, MMT-7763A Tested To The Following Standards: FCC Part 15 Subpart C Sections 15.247 Date of issue: October 31, 2013 This test report bears

More information

RF-EXPOSURE ASSESSMENT REPORT

RF-EXPOSURE ASSESSMENT REPORT RF-EXPOSURE ASSESSMENT REPORT EN 62311 RF-Exposure evaluation of electronic equipment Report Reference No.... : G0M-1206-2043-TEU311E-V01 Testing Laboratory... : Address... : Storkower Str. 38c 15526 Reichenwalde

More information

Report On. Radio Frequency Exposure Testing of the Winland Electronics, Inc. EnviroAlert Electronic Multi-Zone Environmental Alarm System

Report On. Radio Frequency Exposure Testing of the Winland Electronics, Inc. EnviroAlert Electronic Multi-Zone Environmental Alarm System America Report On Radio Frequency Exposure Testing of the Winland Electronics, Inc. EnviroAlert Electronic Multi-Zone Environmental Alarm System EN62311 January 2008 AS/NZS 2772.2:2011 October 2017 REPORT

More information

JERROLD T. BUSHBERG Ph.D., DABMP, DABSNM HEALTH AND MEDICAL PHYSICS CONSULTING

JERROLD T. BUSHBERG Ph.D., DABMP, DABSNM HEALTH AND MEDICAL PHYSICS CONSULTING JERROLD T. BUSHBERG Ph.D., DABMP, DABSNM HEALTH AND MEDICAL PHYSICS CONSULTING 7784 Oak Bay Circle Sacramento, CA 95831 (800) 760-8414 jbushberg@hampc.com Darrell W. Daugherty PLANcom Inc. 302 State Place

More information

Verizon Wireless Site ID Lime Site Name Lime Site Compliance Report

Verizon Wireless Site ID Lime Site Name Lime Site Compliance Report 200 North Glebe Road, Suite 1000, Arlington, VA 22203-3728 703.276.1100 703.276.1169 fax info@sitesafe.com www.sitesafe.com Verizon Wireless Site ID Lime Site Name Lime Site Compliance Report 680 East

More information

Cambium PMP 450 Series PMP 430 / PTP 230 Series PMP/PTP 100 Series Release Notes

Cambium PMP 450 Series PMP 430 / PTP 230 Series PMP/PTP 100 Series Release Notes POINT TO POINT WIRELESS SOLUTIONS GROUP Cambium PMP 450 Series PMP 430 / PTP 230 Series PMP/PTP 100 Series Release Notes System Release 13.1.3 1 INTRODUCTION This document provides information for the

More information

Technical Specifications for Broadband Terminal Equipment of Mobile Broadband Business

Technical Specifications for Broadband Terminal Equipment of Mobile Broadband Business Technical Specifications of the Telecommunications Land Mobile 10 (PLMN10) Inspection Requirements Date: 12 March 2018 Technical Specifications for Broadband Terminal Equipment of Mobile Broadband Business

More information

PUBLIC INFORMATION SESSION ON AMR ELECTRICAL METERS. February 22, 2012 WELCOME

PUBLIC INFORMATION SESSION ON AMR ELECTRICAL METERS. February 22, 2012 WELCOME WELCOME AGENDA (SK) Welcome Mayor Ashton. Introduction of the moderator Mayor Ashton Explanation of the process Steve King Introduction of City presenters Mitch Moroziuk Introduction of Kevin Proteau presenters

More information

DEPARTMENT OF ECONOMIC DEVELOPMENT, JOBS, TRANSPORT AND RESOURCES QUANTIFYING SMART METER RF EME LEVELS IN VICTORIAN HOMES

DEPARTMENT OF ECONOMIC DEVELOPMENT, JOBS, TRANSPORT AND RESOURCES QUANTIFYING SMART METER RF EME LEVELS IN VICTORIAN HOMES DEPARTMENT OF ECONOMIC DEVELOPMENT, JOBS, TRANSPORT AND RESOURCES QUANTIFYING SMART METER RF EME LEVELS IN VICTORIAN HOMES VICTORIA June 2015 Total Radiation Solutions Pty Ltd Page 1 of 84 Table of Contents

More information

FCC RF Exposure Report

FCC RF Exposure Report Page 1 of 6 EMC Technologies Pty Ltd ABN 82 057 105 549 176 Harrick Road Keilor Park Victoria 3042 Australia Telephone +61 3 9365 1000 Facsimile +61 3 9331 7455 Email sales@emctech.com.au FCC RF Exposure

More information

Pico 900MHz 1W FHSS Module Model: p900 FCC ID: NS913P900. Applicant:

Pico 900MHz 1W FHSS Module Model: p900 FCC ID: NS913P900. Applicant: Pico 900MHz 1W FHSS Module Model: p900 Applicant: Microhard Systems Inc. 150 Country Hills Landing NW Calgary, Alberta Canada T3K 5P3 In Accordance With Federal Communications Commission (FCC) Part 15,

More information

TEST REPORT. Table of Contents

TEST REPORT. Table of Contents Page:2 of 43 Table of Contents 1. DOCUMENT POLICY AND TEST STATEMENT... 4 1.1 DOCUMENT POLICY... 4 1.2 TEST STATEMENT... 4 2. DESCRIPTION OF EUT AND TEST MODE... 4 2.1 GENERAL DESCRIPTION OF EUT... 4 2.2

More information

Radiofrequency (RF) Safety Overview Massachusetts Environmental Health Association

Radiofrequency (RF) Safety Overview Massachusetts Environmental Health Association Radiofrequency (RF) Safety Overview Massachusetts Environmental Health Association May 16, 2018 Kevin McManus Senior Program Director kmcmanus@ebiconsulting.com 781-254-5727 (cell) Agenda 1) RF-EME 101

More information

Cell Phone and RF Safety Awareness

Cell Phone and RF Safety Awareness Cell Phone and RF Safety Awareness by Kazimierz Kai Siwiak, Ph.D., P.E. TimeDerivative Inc. Material to support this course appear in Chapters 9 and 1 of the text book Radiowave Propagation and Antennas

More information

ENGINEERING TEST REPORT # C LSR Job #: C-2411 Compliance Testing of: RM186-SM

ENGINEERING TEST REPORT # C LSR Job #: C-2411 Compliance Testing of: RM186-SM W66 N220 Commerce Court Cedarburg, WI 53012 USA Phone: 262.375.4400 Fax: 262.375.4248 www.lsr.com ENGINEERING TEST REPORT # 316062C LSR Job #: C-2411 Compliance Testing of: RM186-SM Test Date(s): 3-28-16

More information

Regulatory Guidance and Safety Standards

Regulatory Guidance and Safety Standards Regulatory Guidance and Safety Standards Andrew H. Thatcher, MSHP, CHP Thatcher.drew@comcast.net March 19, 2018 University of Washington Overview 60 Hz power frequency exposure standards Static Fields

More information

NON-IONIZING ELECTROMAGNETIC EXPOSURE ANALYSIS & ENGINEERING CERTIFICATION

NON-IONIZING ELECTROMAGNETIC EXPOSURE ANALYSIS & ENGINEERING CERTIFICATION NON-IONIZING ELECTROMAGNETIC EXPOSURE ANALYSIS & ENGINEERING CERTIFICATION SITE NAME: SEA Dutch Cup SITE ADDRESS: 1102 E Main Street Sultan, WA 98294 DATE: June 2, 2017 PREPARED BY: B. J. THOMAS, P.E.

More information

OUTDOOR SOUND MODULE/TRANSMITTER MODEL: THE BANDIT

OUTDOOR SOUND MODULE/TRANSMITTER MODEL: THE BANDIT Page 1 of 16 FCC PART 15, SUBPART B and C TEST REPORT for OUTDOOR SOUND MODULE/TRANSMITTER MODEL: THE BANDIT Prepared for MINASKA OUTDOORS 6517 PLATTE AVENUE LINCOLN, NEBRASKA 68507 Prepared by: KYLE FUJIMOTO

More information

Measurement of RF Interference from a Canopy 900MHz Access Point and Subscriber Module Using A Yagi Antenna

Measurement of RF Interference from a Canopy 900MHz Access Point and Subscriber Module Using A Yagi Antenna Measurement of RF Interference from a Canopy 900MHz Access Point and Subscriber Module Using A Yagi Antenna For : Motorola, Inc. 1301 East Algonquin Road Schaumburg, IL 60196 P.O. No. : 40335 Date Tested

More information

Area Network Applications] Notice: This document has been prepared to assist the IEEE P It is

Area Network Applications] Notice: This document has been prepared to assist the IEEE P It is Project: IEEE P802.15 Working Group for Wireless Personal Area Networks N (WPANs) Submission Title: [RF Safety Considerations for Body Area Network Applications] Date Submitted: [] Source: [Kamya Yekeh

More information

Product Safety and RF Energy Exposure Booklet for Mobile Two-Way Radios Installed in Vehicles or as Fixed Site Control Stations ATTENTION!

Product Safety and RF Energy Exposure Booklet for Mobile Two-Way Radios Installed in Vehicles or as Fixed Site Control Stations ATTENTION! Product Safety and RF Energy Exposure Booklet for Mobile Two-Way Radios Installed in Vehicles or as Fixed Site Control Stations ATTENTION! BEFORE USING THIS RADIO, READ THIS BOOKLET WHICH CONTAINS IMPORTANT

More information

CALCULATING RADIOFREQUENCY FIELD STRENGTH SAFETY CODE 6 SITE VALIDATION

CALCULATING RADIOFREQUENCY FIELD STRENGTH SAFETY CODE 6 SITE VALIDATION CALCULATING RADIOFREQUENCY FIELD STRENGTH SAFETY CODE 6 SITE VALIDATION FOR SITE: W2352 Study conducted by: RF Designer: Henry Phan, P.Eng Henry Phan, P.Eng Report Date: August 19, 2013 Department: Radio

More information

Quick Start Guide: FLEX-RP-B/FLEX-RP-B-LL. Connect Battery. Warnings

Quick Start Guide: FLEX-RP-B/FLEX-RP-B-LL. Connect Battery. Warnings 1 Connect Battery Open repeater Unlatch the two hinges. Open the repeater cover. a Connect Battery Connect battery cable to circuit-board connector (a). DO NOT PINCH OR STRESS CABLES. Wait approximately

More information

RF FIELD SURVEY REPORT

RF FIELD SURVEY REPORT RF FIELD SURVEY REPORT MANLY NATIONAL BUILDING 22 CENTRAL AVE, MANLY, NSW RFNSA #: 2095004 DATE OF SURVEY: 18TH NOVEMBER 2016 REPORT VERSION: R1 Accredited for compliance with ISO/IEC 17025 The results

More information

WIFI and Your Health

WIFI and Your Health WIFI and Your Health WIFI Operation: WIFI Networking equipment operates within the unlicensed 2.4 and 5.0 GHz frequency bands. These frequency ranges (bands) are available for use in 100+ countries worldwide

More information

Measurement of RF Emissions from a Caterpillar Inc. MSS3s RF ID Key Fob

Measurement of RF Emissions from a Caterpillar Inc. MSS3s RF ID Key Fob Measurement of RF Emissions from a Caterpillar Inc. MSS3s RF ID Key Fob For Caterpillar Inc. 330 S.W. Adams Street Peoria, IL 61630 P.O. Number JBL 11260 Date Tested May 11, 2016 Test Personnel Mark Longinotti

More information

> Microwave Ovens and their Hazards

> Microwave Ovens and their Hazards 1 of 6 16/02/2012 7:48 PM Home > OSH Answers > Physical Agents > Microwave Ovens and their Hazards Ask a Question Feedback Printer-friendly Why do people worry about microwave radiation? How do microwave

More information

EN 50371: 2002 TEST REPORT

EN 50371: 2002 TEST REPORT EN 50371: 2002 TEST REPORT For USB Dongle Trade Name / Model: Edimax / EW-7318Ug, GWU-E18G Issued to EDIMAX Technology Co., Ltd No. 3, Wu Chuan 3rd Road, Wu-Ku Industrial Park, Taipei Hsien, Taiwan, R.O.C

More information

RF Exposure Evaluation Report

RF Exposure Evaluation Report RF Exposure Evaluation Report APPLICANT EQUIPMENT BRAND NAME MODEL NAME IC FILING TYPE : TomTom International BV : GPS Navigation System : TomTom : 4CR51 : 5767A-4CR51 : Certification STANDARD : IC RSS-102

More information

Landis+Gyr. S4e MFMM Cellnet User Manual. Bulletin Revision A. DOCUMENT HISTORY Bulletin:

Landis+Gyr. S4e MFMM Cellnet User Manual. Bulletin Revision A. DOCUMENT HISTORY Bulletin: S4e MFMM Cellnet User Manual Bulletin 051101 Revision A Information in this document is subject to change without notice. No part of this document may be reproduced or transmitted in any form or by any

More information

American National Standard for Methods of Measurement. Frequency allocations and radio treaty matters; general rules and regulations

American National Standard for Methods of Measurement. Frequency allocations and radio treaty matters; general rules and regulations IAS Accreditation Number Company Name Address TL-637 UL Korea, LTD Suwon Laboratory 218 Maeyeong-Ro, Yeongtong-Gu Suwon-Si, Gyeonggi-Do 16675 Republic of Korea Mr. YongJin Suk, Laboratory Manager Contact

More information

FCC CFR47 PART 22 SUBPART H FCC CFR47 PART 24 SUBPART E INDUSTRY CANADA RSS-132 ISSUE 2 INDUSTRY CANADA RSS-133 ISSUE 5 CLASS II PERMISSIVE CHANGE

FCC CFR47 PART 22 SUBPART H FCC CFR47 PART 24 SUBPART E INDUSTRY CANADA RSS-132 ISSUE 2 INDUSTRY CANADA RSS-133 ISSUE 5 CLASS II PERMISSIVE CHANGE FCC CFR47 PART 22 SUBPART H FCC CFR47 PART 24 SUBPART E INDUSTRY CANADA RSS-132 ISSUE 2 INDUSTRY CANADA RSS-133 ISSUE 5 CLASS II PERMISSIVE CHANGE CERTIFICATION TEST REPORT FOR EUT: PCI EXPRESS MINI CARD

More information

Multilin DGT. Distributed Generation Trip Control Fast & Wireless Trip of Distributed Generators. Control. Advanced Communications

Multilin DGT. Distributed Generation Trip Control Fast & Wireless Trip of Distributed Generators. Control. Advanced Communications Multilin DGT Distributed Generation Trip Control Fast & Wireless Trip of Distributed Generators The desire for green power and rapid developments in renewable energy sources are driving the growth of distributed

More information

FCC 47 CFR PART 15 SUBPART C INDUSTRY CANADA RSS-210 ISSUE 8 BLUETOOTH LOW ENERGY CERTIFICATION TEST REPORT FOR. 2.4GHz LE MODULE MODEL NUMBER: RN4020

FCC 47 CFR PART 15 SUBPART C INDUSTRY CANADA RSS-210 ISSUE 8 BLUETOOTH LOW ENERGY CERTIFICATION TEST REPORT FOR. 2.4GHz LE MODULE MODEL NUMBER: RN4020 FCC 47 CFR PART 15 SUBPART C INDUSTRY CANADA RSS-210 ISSUE 8 BLUETOOTH LOW ENERGY CERTIFICATION TEST REPORT FOR 2.4GHz LE MODULE MODEL NUMBER: RN4020 REPORT NUMBER: 14U17191-1 ISSUE DATE: MARCH 21, 2014

More information

RF EXPOSURE REPORT. For. Model: SVI Trade Name: BOSCH

RF EXPOSURE REPORT. For. Model: SVI Trade Name: BOSCH IEEE C95.1 KDB 447498 D01 v06 47 C.F.R. Part 1, Subpart I, Section 1.1310 47 C.F.R. Part 2, Subpart J, Section 2.1091 RF EXPOSURE REPORT For Smart Home Indoor Camera Model: SVI-1609-5 Trade Name: BOSCH

More information

FCC Part Transmitter Certification. Test Report

FCC Part Transmitter Certification. Test Report FCC Part 15.247 Transmitter Certification Hybrid Spread Spectrum Transmitter Test Report FCC Rule Part: 15.247 ACS Report Number: 04-0170-15C247 Manufacturer: Onity, Inc. Equipment Type: Modular Radio

More information

XBee Series 2 OEM RF Module Model No.: XBEE2 FCC ID: OUR-XBEE2. Applicant: MaxStream, Inc. 355 South 520 West Suite 180 Lindon, UT 84042

XBee Series 2 OEM RF Module Model No.: XBEE2 FCC ID: OUR-XBEE2. Applicant: MaxStream, Inc. 355 South 520 West Suite 180 Lindon, UT 84042 XBee Series 2 OEM RF Module Model No.: XBEE2 Applicant: MaxStream, Inc. 355 South 520 West Suite 180 Lindon, UT 84042 In Accordance With Federal Communications Commission (FCC) Part 15, Subpart C, Section

More information

Itron, Inc. TEST REPORT FOR. RF Telemetry Device Model: CCU100. Tested To The Following Standards:

Itron, Inc. TEST REPORT FOR. RF Telemetry Device Model: CCU100. Tested To The Following Standards: Itron, Inc. TEST REPORT FOR RF Telemetry Device Model: CCU100 Tested To The Following Standards: FCC Part 15 Subpart C Sections 15.247 and RSS 210 Issue 8 Date of issue: April 25, 2013 This test report

More information

Wireless Facility Peer Engineering Review

Wireless Facility Peer Engineering Review Page 1 of 11 Wireless Facility Peer Engineering Review Regarding Verizon Wireless Application 2750 Dwight Way, Berkeley, CA August 10, 2015 Page 2 of 11 Introduction RCC Consultants, Inc. has been engaged

More information

Product Safety and RF Energy Exposure Booklet for Portable Two-Way Radios

Product Safety and RF Energy Exposure Booklet for Portable Two-Way Radios Product Safety and RF Energy Exposure Booklet for Portable Two-Way Radios The information provided in this document supersedes the general safety information contained in user guides published prior to

More information

IEEE Electromagnetic Compatibility Standards (Active & Archive) Collection: VuSpec

IEEE Electromagnetic Compatibility Standards (Active & Archive) Collection: VuSpec IEEE Electromagnetic Compatibility Standards (Active & Archive) Collection: VuSpec This value-packed VuSpec represents the most complete resource available for professional engineers looking for best practices

More information

NEW IEEE C RF SAFETY STANDARD

NEW IEEE C RF SAFETY STANDARD NEW IEEE C95.1-2005 RF SAFETY STANDARD C-K. Chou, Ph.D. IEEE International Committee on Electromagnetic Safety Technical Committee 95, Subcommittee 4 New York, New York, USA. IEEE RF Safety Standard History

More information

Wireless Facility Radio Frequency Compliance Review

Wireless Facility Radio Frequency Compliance Review Wireless Facility Radio Frequency Compliance Review ATT Application Modification of Existing Wireless Facility 554 El Camino Real, Belmont, CA 94002 Site ID: CCL00730 7/10/2017 Preiser Consulting 23836

More information