A Resistance Emulation Technique to Improve Efficiency of a PWM Adjustable Speed Drive with Passive Power Factor Correction

Similar documents
RECENTLY, the harmonics current in a power grid can

A New Single-phase Static PFC Inverter Using Pre-calculated Switching Angles

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Improving Passive Filter Compensation Performance With Active Techniques

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

SHUNT ACTIVE POWER FILTER

A Predictive Control Strategy for Power Factor Correction

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost Regulator

Current Rebuilding Concept Applied to Boost CCM for PF Correction

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL

Novelty Technique for Power factor Improvement by a Single phase Rectifier

SINGLE STAGE SINGLE SWITCH AC-DC STEP DOWN CONVERTER WITHOUT TRANSFORMER

A New Single Switch Bridgeless SEPIC PFC Converter with Low Cost, Low THD and High PF

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Power Quality Improvement in Distribution System Using D-STATCOM

Three Phase Rectifier with Power Factor Correction Controller

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

THE third-harmonic current injection is a method to reduce

e-issn: p-issn:

CHAPTER 1 INTRODUCTION

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

POWER FACTOR CORRECTION AND HARMONIC CURRENT REDUCTION IN DUAL FEEDBACK PWM CONTROLLED AC/DC DRIVES.

Design and Simulation of New Efficient Bridgeless AC- DC CUK Rectifier for PFC Application

Mitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives

A Proficient AC/DC Converter with Power Factor Correction

Third Harmonics Injection Applied To Three Phase/Three Level/Three Switch Unidirectional PWM Rectifier

ISSN Vol.03,Issue.42 November-2014, Pages:

Comparison of Lamination Iron Losses Supplied by PWM Voltages: US and European Experiences

A THREE-PHASE HIGH POWER FACTOR TWO-SWITCH BUCK- TYPE CONVERTER

Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

Bidirectional Ac/Dc Converter with Reduced Switching Losses using Feed Forward Control

SIMPLIFICATION OF HORMONICS AND ENHANCEMENT OF POWERFACTOR BY USING BUCK PFC CONVERTER IN NON LINEAR LOADS

THREE-PHASE converters are used to handle large powers

International Journal of Advance Engineering and Research Development

Improved Power Quality Bridgeless Isolated Cuk Converter Fed BLDC Motor Drive

Semi-Full-Bridge Submodule for Modular Multilevel Converters

A Current-Source Active Power Filter with a New DC Filter Structure

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

SIMULATION of EMC PERFORMANCE of GRID CONNECTED PV INVERTERS

ACTIVE COMPENSATION OF HARMONICS IN INDUSTRIAL APPLICATIONS. Sergej Kalaschnikow, Steffan Hansen, Lucian Asiminoaei, Henrik Gedde Moos

Modelling of Five-Level Inverter for Renewable Power Source

ATYPICAL high-power gate-turn-off (GTO) currentsource

Fabiana Pottker de Soma and Ivo Barbi

Experimental Results of a Single-Phase Shunt Active Filter Prototype with Different Switching Techniques

Simulation of Closed Loop Controlled PFC Boost Converter fed DC Drive with Reduced Harmonics and Unity Power Factor

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

SEVERAL static compensators (STATCOM s) based on

A Single Phase Single Stage AC/DC Converter with High Input Power Factor and Tight Output Voltage Regulation

A New Quadratic Boost Converter with PFC Applications

An Adjustable-Speed PFC Bridgeless Single Switch SEPIC Converter-Fed BLDC Motor

Converters with Power Factor Correction

Power Factor Correction of Non-Linear Loads Employing a Single Phase Active Power Filter: Control Strategy, Design Methodology and Experimentation

Harmonic Filtering in Variable Speed Drives

Power Factor Pre-regulator Using Constant Tolerance Band Control Scheme

Harmonic Analysis of Front-End Current of Three-Phase Single-Switch Boost Converter

Simulation of Improved Dynamic Response in Active Power Factor Correction Converters

A New 3-phase Buck-Boost Unity Power Factor Rectifier with Two Independently Controlled DC Outputs

Design and Implementation of a New PWM Based Active Impedance Power Factor Correction (AIPFC)

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

COMMON mode current due to modulation in power

A New Single-Phase PFC Rectifier (TOKUSADA Rectifier ) with Wide Output Voltage Control Range and High Efficiency

Hybrid Matrix Converter Based on Instantaneous Reactive Power Theory

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

TO LIMIT degradation in power quality caused by nonlinear

A Control Circuit Small Wind Turbines with Low Harmonic Distortion and Improved Power Factor

Performance Analysis of Three-Phase Four-Leg Voltage Source Converter

AC : PSCAD SIMULATION IN A POWER ELECTRONICS APPLICATION COURSE

AN IMPROVED ZERO-VOLTAGE-TRANSITION INTERLEAVED BOOST CONVERTER WITH HIGH POWER FACTOR

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Performance of Indirectly Controlled STATCOM with IEEE 30-bus System

Comparison Between two Single-Switch Isolated Flyback and Forward High-Quality Rectifiers for Low Power Applications

HARMONIC contamination, due to the increment of nonlinear

Power Factor Correction of LED Drivers with Third Port Energy Storage

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Power factor improvement of SMPS using PFC Boost converter

A BRIDGELESS CUK CONVERTER BASED INDUCTION MOTOR DRIVE FOR PFC APPLICATIONS

A Modular Single-Phase Power-Factor-Correction Scheme With a Harmonic Filtering Function

A VARIABLE SPEED PFC CONVERTER FOR BRUSHLESS SRM DRIVE

POWER FACTOR CORRECTION OF ELECTRONIC BALLAST FOR FLUORESCENT LAMPS BY BOOST TOPOLOGY

Three phase six-switch PWM buck rectifier with power factor improvement

An Active Interphase Transformer for 12-Pulse Rectifier System to Get the Performance Like 24- Pulse Rectifier System

CHAPTER 6 BRIDGELESS PFC CUK CONVERTER FED PMBLDC MOTOR

Comparison of Power Factor Correction Techniques for Generator-Sets for SHEVs

THE converter usually employed for single-phase power

BOOST PFC WITH 100 HZ SWITCHING FREQUENCY PROVIDING OUTPUT VOLTAGE STABILIZATION AND COMPLIANCE WITH EMC STANDARDS

Design And Simulation of Single stage High PF Electronic ballast with boost topology for multiple Fluorescent lamps

Mitigation of Power Quality Problems Using DVR in Distribution Network for Welding Load

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

A NEW SINGLE STAGE THREE LEVEL ISOLATED PFC CONVERTER FOR LOW POWER APPLICATIONS

I. INTRODUCTION. 10

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

Fuzzy Logic Based Power Factor Correction AC- DC Converter

Harmonics Elimination Using Shunt Active Filter

POWERED electronic equipment with high-frequency inverters

A Novel H Bridge based Active inductor as DC link Reactor for ASD Systems

ANALYSIS OF POWER QUALITY IMPROVEMENT OF BLDC MOTOR DRIVE USING CUK CONVERTER OPERATING IN DISCONTINUOUS CONDUCTION MODE

A Unity Power Factor Boost Rectifier with a Predictive Capacitor Model for High Bandwidth DC Bus Voltage Control

Transcription:

A Resistance Emulation Technique to Improve Efficiency of a PWM Adjustable Speed Drive with Passive Power Factor Correction R. CARBONE A. SCAPPATURA Department I.M.E.T. Università degli Studi Mediterranea REGGIO CALABRIA ITALY Abstract: - An approach recently introduced to correct the power factor of single-phase and three-phase diode rectifiers is extended to high-power PWM adjustable speed drives (ASDs). The proposed AC/DC stage of the drive is based on a new three-phase diode rectifier, obtained by properly connecting three single-phase diode rectifiers. The power factor of each single-phase rectifier is corrected by using a passive correction technique based on a resistive-capacitive branch connected at the DC-terminals of the rectifier. To improve efficiency of the whole circuit, a resistance emulation technique is introduced, analyzed and discussed. The designing procedure of the passive correcting branches and of the introduced resistance emulator circuit, for the power factor correction, is investigated. Analyses of performances of the new PWM ASD scheme are developed with the help of several PSPICE simulations, on a case-study PWM ASD for an asynchronous motor of about 1.5 MW of active power and under different working conditions. Key-Words: - Adjustable Speed Drives, Power Factor, Total Harmonic Distortion Factor, Efficiency, Threephase Rectifiers, Passive Power Factor Correctors. 1 Introduction Traditionally, conversion of electrical power from AC to DC, for medium to high power PWM ASD for asynchronous motors, is done by using a three-phase diode bridge rectifier with inductive/capacitive DC output filter, as shown in Fig.1. Supply System e 1 (t) e 2 (t) e 3 (t) i 1 (t) i o (t) To the PWM inverter Fig.1. Conventional three-phase diode rectifier Three-phase bridge rectifiers are characterized by a non-linear behavior because of the timevariant characteristic of their switching devices (diodes) and, thus, they have the disadvantage of Vo L f C f absorbing highly distorted AC line current, i 1 (t), with large fifth and seventh harmonic components. The increased use of this kind of power electronic equipments has put attention to quality aspects of electrical power; in order to achieve power quality at acceptable levels, recommended practices specify harmonic limits of power converters and the use of power factor correctors (PFCs) is strongly encouraged. At present many PFCs are available for threephase rectifiers. They are essentially based on the use of additional circuit components with different kind of complexity [1-7]. Recently, a simple passive PFC has been introduced for three-phase rectifiers [5-7]. It is essentially based both on the rearrangement of the conventional rectifier circuit topology and on the use of R-C passive branches to be properly inserted on the DC-side of the circuit. The AC-line currents are effectively improved without introducing high frequency harmonics and low cost and high performances are also expected, especially with respect to other passive PFCs [6]. In [7] it was evidenced that this passive circuit can be effectively used also to correct PF of high power PWM ASD for asynchronous motors. In [6, 7] it was evidenced that the main drawback of this passive PFC is efficiency, that is low

because of the additional power losses on the circuit resistors, requested for power factor correction. In the paper, the aforementioned passive PFC is recalled and briefly described, with reference to high power PWM ASD for asynchronous motors. Then, with the aim to avoid power losses on the resistors of the passive PFC and to improve circuit efficiency, a resistance emulation technique is introduced, analyzed and discussed. Several PSPICE numerical simulations, of a high power PWM ASD case-study circuit, are performed; the results are critically analyzed in order to give evidence of the effectiveness of the proposed resistance emulation technique. 2 A passive PFC for three-phase diode rectifiers In [4] a simple passive PFC was introduced and discussed with reference to single phase diode rectifiers. In order to make possible the extension of the aforementioned passive power factor correction technique also to three-phase diode rectifiers, in [5] the conventional three-phase rectifier bridge topology has been rearranged by using three singlephase rectifiers connected in series at their DC-side terminals. Then each single phase rectifier is corrected by using the same passive correction technique; the PFC passive components are designed by using a procedure able to account for the new circuit topology. Figure 2 shows the rearranged three phase rectifier circuit. e 1 (t) e 2 (t) e 3 (t) i 1 (t) i DC (t) i * (t) i 0 (t) V 0,r (t) Lf To the load V 0 (t) Fig.2. The rearranged three-phase rectifier, with passive PF correction branches. From figure 2, it is evident that the passive correction technique essentially consists of adding, at the DC-side terminals of each single-phase rectifier, a branch with passive elements (, ). Extra and properly settled currents, i*(t), absorbed by these additional branches, are added to the rectifier output current, i 0 (t), so making possible the correction of the rectifier AC line absorbed currents, i 1 (t). In order to make sinusoidal the AC line currents absorbed by the rearranged three-phase rectifier, the and parameter values have to be selected so that the equivalent impedance as seen from the DC-side terminals of each single-phase rectifier results resistive and equal to: Vo Ro =, Io where Vo and Io are the mean values of the rectifier output voltage and output current, respectively. In [5] it was demonstrated that, in order to achieve this goal, it must be: Ro R * =, 3 while is suggested to be selected as greater as possible, taking into account its cost and also the expected circuit performances. Fortunately, in [5] it has been shown that circuit performances do not rapidly worsen when value rapidly decreases. For the sake of brevity, some more details on the recalled PF correction technique are postponed to [5-7]. In [7], the rearranged three-phase diode rectifier has been used as AC/DC conversion stage of a three-phase PWM ASD for high power asynchronous motors. It has been shown that this rearranged rectifier with passive PF correction is able to significantly improve the circuit PF, both under nominal and low load power working conditions. In the next section, the performances of the aforementioned circuit are briefly recalled for the sake of readability. 3 Performances of a rearranged PWM ASD with passive power factor correction 3.1 The case-study It consists of a three-phase PWM ASD for an asynchronous motor of about 1.5 MW of active power.

The diode rectifier operates with a supplying line to line voltage amplitude of Vrms= 6 kv, at the line frequency of fac=50 Hz. i1 (t) [A] = 2mF THD% = 3.6 AC supply-side Lf Cf motor-side AC/DC DC-link DC/AC 380 TIME [ms] Fig.3. The PWM ASD case-study scheme. With reference to Fig.3, in Table 1 the DC-filter inductance, L f, the DC-filter capacitance, C f, and the maximum value of the switching frequency of the PWM inverter devices, f sw,max, are also reported. Table 1. Values of the circuit main parameters L f [mh] C f [µf] f sw,max [Hz] 30 450 With reference to the nominal power of the motor, the, and parameter values, to be utilized in the new three-phase rectifier scheme (as shown in Fig.2) for power factor correction, are calculated as indicated in section 2 and are reported in Table 2. Table 2. PFC parameter values, utilized for the case-study analysis [mf] 2.0 [Ω] 18 3.2 Simulation results PSPICE has been utilized to perform numerical simulations under different working conditions, as fully referred in the following. Nominal conditions are firstly considered; furthermore, different values of the power requested by the motor are also considered, in order to estimate the sensitivity of the corrected circuit to motor power variations. Figure 4 shows the waveform and the THD of the AC line currents absorbed, under nominal conditions, by the corrected PWM ASD, by using different values of. It is well evident as, with respect to the conventional PWM ASD, circuit performances are significantly improved, also for low values of. = 1mF THD% = 4.0 380 = 0.4mF THD% = 6.3 380 Fig.4. AC current waveforms absorbed by the rearranged PWM ASD case study circuit, under nominal condition and for different values of In Figure 5, the AC absorbed current waveforms, obtained by loading PSPICE for different values of the power requested by the motor (from 100% to about 35% of the nominal value) and, consequently, for different values of the motor frequency and of the PWM inverter modulation index, are reported together with their THD percentage values. In order to avoid a strong worsening of the current THD at very low motor power (for more details see [7]), a value of settled with reference to about the 80% of the motor nominal power has been used, instead of that previously settled referring to the motor nominal power (22 Ω instead of 18 Ω). It is evident that at very low power the THD of the absorbed current is sensibly worsen (THD=23%), even if it results better to that previously calculated for the conventional circuit operating under nominal power working condition (THD=27%).

Proceedings of the 5th WSEAS Int. Conf. on Power Systems and Electromagnetic Compatibility, Corfu, Greece, August 23-25, 2005 (pp570-576) The basic idea starts from the consideration that a single-phase rectifier corrected at the DCi 1 (t) [A] 380 P mot = 100%P n THD% = 7.8 P mot = 82%P n THD% = 5.0 3.3 Circuit sensitivity to correcting resistor value In order to evaluate how much the circuit is sensitive to the variation of the value of the resistor needed for the PF correction, a sensitivity analysis is performed referring to the nominal power working condition and taking into account of a resistance value variation between ±10% around its nominal value (=18 Ω), with a step of a 2%. In Fig. 6, the results are reported in terms of AC side current THD versus the percentage variation of the value of the resistor requested for PF circuit correction, around its nominal value. It clearly results that the AC current THD is very little sensitive to resistance variations. 380 TIME [ms] P mot = 65%P n THD% = 6.6 4,4 4,2 4 3,8 3,6 3,4 3,2 THD 3,89 Rn -10% -6% -2% 2% 6% 4,27 10% 380 P mot = 50%P n THD% = 13.9 380 P mot = 36%P n THD% = 23.0 380 TIME [ms] Fig.5. Waveforms of the AC absorbed currents, for the PWM ASD case study circuit rearranged as in Fig.2, for different values of the motor power and with settled with respect to the 80% of the nominal power (=22 Ω) Fig.6. AC side current THD, under nominal working condition and versus the % variations of the, around its nominal value 3.4 Circuit efficiency The efficiency of the circuit rearranged as indicated in Fig.2 results significantly worsen with respect to that of the conventional circuit, because of the additional power losses on the resistive elements,, of the correcting passive branches. With reference to the case-study circuit working under nominal conditions and corrected by using for the resistors the value settled with respect to the 80% of the motor nominal power in order to better compensate the motor power variations, a circuit efficiency equal to 0.81 has been calculated. It is important to underline that, under the same working condition, an efficiency significantly higher (equal to about 0.96) has been calculated for the conventional and uncorrected circuit. Efficiency of the rearranged circuit can be improved by introducing the idea of a resistance emulator to be used instead of, as fully explained in the next section. 4 A resistance emulator circuit

side terminals as previously indicated in section 2 practically absorbs, from the AC supplying system, a sinusoidal current, proportional to the supplying voltage; this is to say that it has a behavior like that of a resistor, then it can be utilized as a resistance emulator circuit, RE. Starting from this idea, each correcting resistor in Fig.2 can be substituted by an electronic single-phase diode rectifier properly corrected at its DC-side terminals by using low power - passive branches with and correcting elements. In order to give back to the motor the RE absorbed active power and to improve the circuit efficiency, the three single-phase and low power RE, to be utilized instead of, can be connected in series among them and in parallel to the inverter DC-side terminals. Furthermore, in order to make actually possible the connection of the whole RE (three single-phase RE connected in series at the DC-side) with the inverter, first of all the whole RE output voltage mean value has to be made equal to that of the main (high power) rectifier, and to achieve this goal an input - low power - transformer is needed for each single-phase RE, to properly regulate its output voltage level. Finally, the whole RE has to be decoupled to the main rectifier, in order to avoid interactions between them; this can be accomplished by using an uncoupling - low power inductor, with an L e * value as greater as possible, taking into account its cost, volume, weight together with the expected circuit performances. The scheme of each single-phase RE is shown in Fig.7, while the scheme of the rearranged threephase diode rectifier with the whole RE is shown in Fig.8 (the inverter scheme is omitted for the sake of readability). To the load Fig.7. The proposed Resistance Emulator circuit Once defined the circuit topology in presence of the whole RE, the procedure for calculation of the and parameter values has to be investigated. First of all, the transformation ratio, n, of the three RE single-phase transformers has to be calculated. This can be done by firstly taking into account the constraint that the mean value of the whole RE output voltage has to be equal to that of the main rectifier and by calculating also the time domain voltage at the terminals, on the circuit without resistance emulation. From this last, the mean value of the whole RE output voltage with unity transformation ratio of the single-phase transformers can be easily estimated. Lf To the PWM inverter i1(t) e1(t) ie(t) Le* Vo(t)=Ve(t) Cf e2(t) e3(t) Fig.8. The rearranged three-phase diode rectifier with the whole Resistance Emulator circuit

Finally, the transformation ratio of the three singlephase transformers can be calculated as the ratio between the mean value of the main rectifier output voltage and the mean value of the whole RE output voltage with unity transformation ratio of the single-phase transformers. Then, a procedure similar to that described in section 2 for the calculation of and values can be now applied to calculate the and values. Also in this case, an equivalent resistance, Re, as seen from the DC terminals of the whole RE can be defined: Vo R E =, I E where Ie is the mean value of the whole RE output current. The following value has to be used for PF correction of each single-phase RE: RE =. 3 Also in this case and for the reasons explained in [5], for it is suggested to use a value as greater as possible, taking into account its cost together with the expected circuit performances. In practice, in this new contest, the main problem to solve is the calculation of the aforementioned I E value and this can be done by developing some considerations on the active power saved by introducing the RE circuit. Firstly, the active power, P*, wasted on in the circuit without resistance emulation can be easily calculated, together with the rectifier input power, P IN, the load voltage, V 0, and the load current, I 0, by simply simulating the circuit. Assuming that the aforementioned power P* is a percentage of the rectifier input power, P IN, the coefficient, K, defined as the ratio between the whole power (3P*) wasted on and the rectifier input power can be also calculated: 3P * K =. (1) PIN Likewise, - because of the circuit similarity - also the power, Pe*, wasted on the resistor of each single-phase RE correcting branches of Figg.7 and 8 can be assumed to be a percentage of the singlephase RE input power (that is also equal to the power wasted on ), with the same aforementioned coefficient K: Pe* K =. (2) P * By following this approach, the power that the whole RE can give back to the load, P S, can be expressed as a function of the rectifier input power: PS = 3P * 3Pe* = (1 K) K PIN, (3) and then, the value can be easily calculated: V I 0 E PS = (1 K) K PIN = V 0 I E 2 PIN = PLOAD + 3Pe* = V 0 I 0 + K PIN V 0 (1 + K) RE V 0 = R E = = = I 0 K 3 I 0 (1 + K) 3K (4) 5 Performances of a rearranged PWM ASD with passive power factor correction and with resistance emulation In order to give evidence of the effectiveness of the proposed resistance emulation technique, the case-study PWM ASD presented in section 3.1 is corrected as indicated in Fig.8 and analyzed with the help of several PSPICE simulations, under both nominal an low motor power working conditions. The analysis is performed in terms of AC absorbed current THD, for all the examined working conditions, while circuit efficiency is calculated only with reference to nominal motor power working condition. By following the designing procedure proposed in section 4 and with reference to the circuit depicted in Fig.8, the additional parameter values used for circuit simulations are reported in Table 3. Table 3. Additional circuit parameter values, in presence of the whole RE n Le* [mh] [mf] [Ω] 5.7 210 1.0 118.0 Figure 9 shows the AC line currents absorbed by the PWM ASD with the proposed whole RE and for different values of the motor power; the resulting current THD are also reported, as a percentage of their respective current fundamental components. It is well evident that the current THD is always at acceptable levels and, at low motor power, it results also better than that obtained by means of the circuit without resistance emulation. Furthermore, under nominal working condition, the efficiency of the circuit with the proposed whole RE has been calculated equal to 0.95, while a significantly lower efficiency of 0.81 was previously calculated for the circuit without resistance emulation. It can be concluded that the introduced whole RE circuit produces positive effects on both circuit efficiency and AC absorbed current THD, both under nominal and low motor power working conditions.

A -A 380 TIME [ms] A -A 380 TIME [ms] A P mot = 100%P n THD% = 5.5 P mot = 82%P n THD% = 6.1 P mot = 65%P n THD% = 8.4 6 Conclusions The AC/DC stage of a conventional PWM ASD has been rearranged by using three single-phase diode rectifiers connected in series at the DC-side terminals. Then, power factor of the whole circuit has been corrected by means of a very simple passive correction technique. In order to improve efficiency of the rearranged circuit a resistance emulator circuit is introduced and utilized instead of passive resistors needed for passive power factor correction. The analyses of the results, obtained by loading several PSPICE simulations on a PWM ASD case study for an asynchronous motor of about 1.5 MW of active power and under different working conditions, have shown the effectiveness of the introduced resistance emulator circuit. The proposed circuit seems to be able to improve both the circuit efficiency and the AC line current THD, under both nominal and low motor power working conditions. References: -A 380 TIME [ms] A -A 380 A P mot = 50%P n THD% = 11.0 P mot = 36%P n THD% = 13.4 -A 380 Fig.9. AC absorbed current waveforms for the PWM ASD case study circuit with the whole RE, for different values of the motor power [1] W. B. Lawrance, W. Mielczarski: Harmonic current reduction in a three-phase diode bridge rectifier. IEEE transaction on Industrial Electronics, vol. 39, n. 6, Dec. 1992, p. 571. [2] P. Pejovic : Two three-phase high power factor rectifiers that apply the third harmonic current injection and passive resistance emulation. IEEE Trans. on industrial electronics, vol. 47, n. 2, Apr. 2000, p. 497. [3] P. D Ziogas : An Active Power Factor Correction Technique for Three-Phase Diode Rectifiers. IEEE Trans on power electronics, vol. 6, n.1, Jan. 1991. [4] R. Carbone, A. Scappatura: "A high efficiency power factor corrector for single phase bridge diode rectifier". IEEE Conf. PESC 04, June 20-25, 2004, Aachen, Germany. [5] R. Carbone, P. Corsonello, A. Scappatura: A Three-Phase Diode Rectifier With Low Current Harmonics. ICIT 2003, 10-12 Dec. 2003, Maribor, Slovenia. [6] R. Carbone, A. Scappatura: A Comparative Analysis of Passive Power Factor Correctors For Three-Phase Rectifiers. 4 th IASTED Intern. Conf. on Power and Energy Systems EUROPES 2004, June, 2004 Rodhes, Greece. [7] R. Carbone, A. Scappatura: "A High Power PWM Adjustable Speed Drive with Low Current Harmonics ". IEEE Conf. ISIE 05, June 20-23, 2005, Dubrovnik, Croatia.