Wireless Temperature Transmitters Series XYR 5000, Model WT5xx/WT5xxR/WT5xxT Specifications - Americas

Similar documents
PRODUCT SPECIFICATION AND MODEL SELECTION GUIDE

Wireless Dual Discrete Input Transmitter Series XYR 5000, Model WW59x Specifications - Americas

XYR 5000 Wireless Temperature Transmitters Model WT530 Specifications - Europe

Wireless Acoustic Transmitters Series XYR 5000, Model WN571 Specifications - Americas

Wireless Base Radio. Wireless Transmitters

XYR5000 Series Wireless Transmitters

Wireless Multi Discrete Input Transmitter Series XYR 6000, Model STXW500 Specifications

Accutech GP10. Wireless gauge pressure field unit

Accutech AP10. Wireless absolute pressure field unit

PRODUCT SPECIFICATION AND MODEL SELECTION GUIDE

Accutech TC10. Wireless thermocouple temperature field unit

Accutech DP20. Wireless differential pressure field unit

XYR 6000 Wireless Temperature/Discrete Input Transmitter Series 400 Specifications

Accutech RT10. Wireless RTD temperature field unit

XYR 5000 Wireless Differential Pressure Transmitter

Accutech FL10. Wireless float level field unit

Accutech AM20. Wireless acoustic monitor field unit

STT 3000 Smart Temperature Transmitter Series STT170 Specifications

Wireless Transmitter Gauge Pressure Models Series XYR 6000 Specifications

Accutech AI10 & AV10. Wireless multi-input field unit

Wireless Transmitter Series XYR 6000 Absolute Pressure Model STAW94L 0 to 500 psia 0 to 35 bara Specifications

Two-Wire Programmable Transmitter for:

Wireless Pressure Transmitter Differential Pressure Models Series XYR 6000 Specifications

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

XYR 5000 Wireless Transmitters SIMPLE. SAFE. SECURE. Honeywell Solutions for Wireless Data Acquisiton and Monitoring

XYR 6000 Wireless High Level Analog Input Transmitter Model STIW600 0 to 5 Volts 1 to 5 Volts 0 to 20 ma 4 to 20 ma

0 2 1 â Ó. itemp HART TMT182. Technical Information

Specification and Model Selection Guide. Introduction 34-XY /14/07. Figure 1 XYR6000 Temperature Transmitters

0 2 1 â Ó. itemp HART TMT182. Technical Information

The Rosemount 848T Wireless Temperature Transmitter

Temperature transmitter itemp PCP DIN rail TMT 121

PROGRAMMABLE FIELD TEMPERATURE TRANSMITTER

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

itemp HART DIN rail TMT112

SFC Smart Field Communicator Model STS103. Specification 34-ST /24/06. Description. Function. Page 1 of 5

Fisher 646 Electro Pneumatic Transducer

600T Series Transmitters. Specification Sheet. Model 653T Electronic temperature transmitter (PC programmable)

Accutech AI10 & AV10. Wireless multi-input field unit

Temperature transmitter itemp RTD DIN rail TMT 127

Rosemount 702 Discrete Input Transmitter

Fisher 646 Electro-Pneumatic Transducers

Temperature head transmitter itemp PCP TMT 181

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

Temperature Measurement

Temperature Transmitter itemp RTD DIN rail TMT 127

2-Wire Toroidal Conductivity Transmitters Series APT2000 Specifications

600T Series Transmitters Model 653L Electronic temperature transmitter (PC programmable for RTD and resistance) Specification Sheet

Temperature head transmitter itemp TC TMT 188

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting

itemp PA TMT184 Technical information

Temperature Input Module for Zone 1 Series 9482/32

Temperature Measurement Transmitters for mounting in sensor head

â Ó itemp TC TMT128 Technical information DIN rail mounted Temperature Transmitter for Thermocouples (TC)

Rosemount 248 Wireless Temperature Transmitter

Process display RIA 261

[ Rosemount 648 Wireless Temperature Transmitter. Rosemount 648 Wireless. Quick Installation Guide , Rev CA August 2011

SmartPower Solutions. Product Data Sheet February , Rev AD

Head mounted Temperature Transmitter TF02/TF02-Ex

Temperature Measurement Transmitters for mounting in sensor head

â itemp Pt100 TMT127 Technical information Pt100 transmitter for DIN rail mounting for high accuracy temperature monitoring

Rosemount 848L Logic Transmitter with FOUNDATION Fieldbus

STT 3000 Smart Temperature Transmitter

GS Strain gauge reader/ transmitter. GS series of wireless industrial sensors. Features: General Description: Applications:

TEK-TEMP 2100A. Explosion-Proof Temperature Transmitter. TEMPERATURE. Technology Solutions

DOC. NO. : C3200-E04A APPROVED. Smart PressureTransmitter for Gauge and Absolute Pressure Measurement MODEL APT3200

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.

Temperature transmitter with local display RIT 261

Technical Specification Datasheet

Accutech BR10. Wireless base radio

ER WIRELESS TRANSMITTER

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

Wireless Transmitter Series XYR 6000 Series 100 Gauge Pressure Models Specifications

Rosemount 648 Wireless Temperature Transmitter

APT3200L SMART PRESSURE TRANSMITTER. Application Areas: WITH DIAPHRAGM SEAL

Single-Channel Safety Barriers Series 9001

Temperature Measurement

MODEL: B3HU. Space-saving Two-wire Signal Conditioners B3-UNIT

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

ER WIRELESS TRANSMITTER

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With

Digital Input Module 24 V Ex n Inputs, 16 Channels Series 9471

Fisher 4200 Series Electronic Position Transmitters

WIRELESS MODBUS GATEWAY WGW410

MICROCOR WIRELESS TRANSMITTER

Intrinsically Safe Pressure Transmitter for highest pressure applications in hazardous environments Model IS-20-H

Coriolis Massflowmeter

Sarasota CM200 Sarasota HME900 Density Converter Electronics

Temperature head transmitter itemp PCP TMT 181

Rosemount 148 Temperature Transmitter

Temperature Transmitters TMT 136, TMT 137

SureCross DX99 Intrinsically Safe (IS) FlexPower Node with Integrated Battery

SEM210 SERIES. Programmable In-head Universal Temperature Transmitter INDEX SECTION CONTENTS PAGE NO.

Multilin DGT. Distributed Generation Trip Control Fast & Wireless Trip of Distributed Generators. Control. Advanced Communications

C330 / C330X PC-Programmable Universal, 2-wire Transmitter

MICROCOR ER WIRELESS TRANSMITTER

SPECIAL SPECIFICATION 6744 Spread Spectrum Radio

MEAS CAL ALARM CONF APT2000 TC

Temperature Transmitters - Head Mounted

SureCross DX80 FlexPower EZ-LIGHT Node with Integrated Battery

Transcription:

Wireless Temperature Transmitters Series XYR 5000, Model WT5xx/WT5xxR/WT5xxT Specifications - Americas 34-XY-03-02 February 2008 Function The WT5xx Temperature Transmitter is part of the XYR 5000 family of wireless products. These transmitters are wireless temperature transmitters that can be used to monitor a variety of processes in hazardous and remote areas. Since there are no wires to run, the transmitter can be installed and operational in minutes, quickly providing information about the variable being monitored. The Smart Response Manager allows the transmitter to adapt to changing process conditions, allowing greater visibility to process variation. Smart Response Manager allows the user to set thresholds which, when exceeded, cause the transmitter to increase sampling and data transmission rates. Optional discrete inputs are available for Base Radio Monitoring process variables Discrete monitoring at the base radio. The transmitter combines an integrated temperature sensor, with a Radio Frequency (RF) transceiver t operating in the 900MHz ISM license-free band. Communication is a digital protocol, using Frequency Hopping Spread Spectrum (FHSS). FHSS ensures data integrity by continually switching the carrier wave over a wide range of frequencies. Power is supplied by a C size 3.6 V lithium battery, with an expected lifetime of up to five years. Enjoy the benefits of wireless technology today: Improve Product Quality Wireless Transmitters Ensure High Uptime Reduce Maintenance and Operational Costs Meet Regulatory Requirements Enhance Flexibility

XYR 5000 WT5xx/WT5xxR/WT5xxT Wireless Temperature Transmitters 2 Probe Options Probe Type RANGE RANGE DEG. F DEG. C Pt100 RTD (DIN.00385) -328 to +900-200 to +482 Type B T/C +212 to +3,272 +100 to +1,800 Type C T/C +32 to +4,208 0 to +2,320 Type E T/C -58 to +1,832-50 to +1,000 Type J T/C -292 to +1,382-180 to +750 Type K T/C -292 to +2,282-180 to +1,250 Type L T/C -328 to +1,652-200 to +900 Type N T/C +32 to +2,192 0 to +1,200 Type R T/C +32 to +2,912 0 to +1,600 Type S T/C +32 to +2,822 0 to +1,550 Type T T/C -238 to +752-150 to +400 Type U T/C -148 to +1,112-100 to +600 Wireless General Specifications Wireless Communication RF Transmit Power Data Rate 902 MHz 928 MHz Frequency Hopping Spread Spectrum (FHSS) FCC certified ISM license-free band. Every data block transmitted is verified (CRC check) and acknowledged by the Base Radio. 31 mw, 17.8 mw typical. Configurable: 4.8 Kbps, 19.2 Kbps, or 76.8 Kbps. Antenna Omnidirectional Yagi Directional Signal Range Internal 3 omni-directional, ¼ wave, monopole. Up to 2000 feet (600 meters) from Base Radio with clear line of sight.* *Actual range may vary depending on site topography. Length: 18. Gain: 6 dbd. Weight: 1.5 lbs. Polarization: Vertical. Up to 5000 feet (1500 meters) from Base Radio with clear line of sight.* Site Survey Tools RSSI Link Test Received Signal Strength Indicator displays the RF signal strength in one of seven ranges. Link Test measures the wireless link performance of a transmitter running in normal operating mode. This function looks at wireless performance in both directions, from the transmitter to base radio and vice versa and assigns a rating to that performance or quality of signal. Self Diagnostics Self-checking software and hardware that identifies and reports out of spec conditions, and field unit low battery voltage.

XYR 5000 WT5xx/WT5xxR/WT5xxT Wireless Temperature Transmitters 3 Features Automatic Re-transmit The field unit checks with the base radio to insure successful receipt of data. If data was not received, the transmitter retries on the next RF cycle. Ensures communication confidence in the harshest of industrial environments. At the maximum transmit rate this feature is inactive. Operating/Storage Conditions Humidity Temperature Ambient Sensor: Ambient Electronics: Process fluid: Display (Full visibility): Display (Reduced visibility): Storage: 95% RH (non-condensing). -40 to +230 F (-40 to +110 C) -40 to +149/+185 F (-40 to +65/+85 C) (see Model Selection Guide) -40 to +250 F (-40 to +121 C) -4 to +158 F (-20 to +70 C) -40 to +185 F (-40 to +85 C) -58 to +185 F (-50 to +85 C). Discrete Inputs (Optional) Discrete Input Switch (Dry Contact Only, no Voltage or Current Allowed) Maximum Impedance at Input 1 K ohm. Isolation 110 K ohms between Output (-) and Input (-). Wiring Plug Wire Size 28 to 16 gauge maximum. Warning No external voltage or current shall be applied to input terminals. Performance Accuracy ± 0.1% of full scale reading at operating conditions. For cold junction compensation (T/C only), add 1.8 F (± 1 C) at reference conditions. Linearization RTD and T/C linearization to ± 0.09 F (± 0.05 C). Custom linearization with 22 point curve. Ambient Temperature Effect RTD - ± 0.002% of reading per C T/C - ± 0.01% of reading per C Long Term Stability Stability deviation per year is less than 0.025%. Physical Specifications Thermowell Material Electronic Housing Process connections Vibration and Shock Random Vibration 304 SS, 316 SS. GE Lexan. V0 Rating and UV Stable. ½ - NPTM for probe only. ¾ - NPTM for well. Certified per IEC EN00068 2-6 (Vibration) and 2-27 (Shock) Certified to withstand 6 g s, 15 minutes per axis from 9 500 Hz. Net weight With Omnidirectional antenna With Yagi directional antenna 1.0 kg (2 lbs) 1.8 kg (3.5 lbs.) Electromagnetic Compatibility (CE Compliance) Operates within Specifications in fields from 80 to 1,000 MHz with Field Strengths to 10 V/m. Meets EN 50082-1 General Immunity Standard and EN 55011 Compatibility Emissions Standard.

XYR 5000 WT5xx/WT5xxR/WT5xxT Wireless Temperature Transmitters 4 Device Configuration Parameter Configuration RF Channel Setup: 1 to 16. Baud Rate: 4.8 Kbps, 19.2 Kbps, 76.8 Kbps. RF ID: 1 to 100. Password. Tag Name (up to 21 characters). Normal Transmit Rate: (1 5 sec, 10 sec, 15 sec, 20 sec, 40 sec, 1 min). Normal Sampling Rate: (1 10 sec, 15 sec, 20 sec, 30 sec, 1 min). Abnormal Transmit Rate: (1 5 sec, 10 sec, 15 sec, 20 sec, 40 sec, 1 min). Abnormal Sampling Rate: (1 10 sec, 15 sec, 20 sec, 30 sec). Temperature Normal Upper Value: Disabled/Enabled. Enabled to change Sampling and Transmit rates during abnormal process conditions. Temperature Normal Lower Value: Disabled/Enabled. Enabled to change Sampling and Transmit rates during abnormal process conditions. Engineering Units: Deg C, Deg F, Kelvin, Rankin. Probe Type. (WT531R will accept one RTD probe; WT531T will accept one or two T/C probes). Offset: User defined offset will be transmitted instead of actual value. Trim: Applies a user-defined one- or two-point correction curve to the actual value. Discrete Input parameters configured from the Wireless Management Toolkit Configuration Panel Integrated LCD display with membrane switch buttons for local configuration. LCD display is 7-digit (alternating) high contrast, anti-reflective monochrome. Display cycles between temperature level and RF status. Approvals Environmental protection NEMA 4, IP 65. Combined FM/CSA FM Intrinsically safe - Class I, Div. 1, Groups A,B,C,D,E,F,G,T4, Class I, Zone 0, AEx ia IIC T4, (Ta = -40 C to +85 C) Enclosure 4 CSA - Intrinsically safe - Class I, Div. 1, Groups A,B,C,D,E,F,G,T4, Class I, Zone 0, Ex ia IIC T4, (Ta = -40 C to +85 C) Enclosure 4 Combined CE/ATEX CE EMC Conformity, ETSI EN 300 489-1 Intrinsically Safe, Zone 0/1: Ex II 1 G EEx ia IIC T4 (Ta = -40 C to +65 C) IP65 Non-Sparking, Zone 2: Ex II 3 G EEx na, IIC T6 (Ta = -40 C to +85 C) IP65

XYR 5000 WT5xx/WT5xxR/WT5xxT Wireless Temperature Transmitters 5 Dimensions 97.5 3.84 97.5 3.84 131 5.19 204.2 8.0 mm inches

XYR 5000 WT5xx/WT5xxR/WT5xxT Wireless Temperature Transmitters 6 Model Selection Guide Model Selection Guides are subject to change and are inserted into the specifications as guidance only. Prior to specifying or ordering a model check for the latest revision Model Selection Guides which are published at: http://hpsweb.honeywell.com/cultures/en-us/products/instrumentation/productmodelselectionguides/default.htm Model Selection Guide 34-XY-16-02 Issue 13 Instructions Select the desired key number. Key Number I (Options) II (Approvals) - - KEY NUMBER Description Wireless Temperature Transmitter - Split Architecture with Omni Directional Antenna Single input - 4-wire RTD required (4-wire RTD supplied by customer) Wireless Temperature Transmitter - Split Architecture with Omni Directional Antenna Thermocouple(s) supplied by customer Wireless Temperature Transmitter - Split Architecture with Yagi Antenna Single input - 4-wire RTD required (4-wire RTD supplied by customer) Wireless Temperature Transmitter - Split Architecture with Yagi Antenna Thermocouple(s) supplied by customer Selection WT531R WT531T WT534R WT534T Availability TABLE I - OPTIONS Discrete Inputs (Note 1) DA Note 1 - no voltage or current allowed; dry contact only TABLE II - CERTIFICATION OPTIONS Certificate Approval Type Location or Classification Intrinsically CL I, II, III, Div 1, Gp A,B,C,D,E,F,G T4; Safe CL I, Zone 0, AEx ia IIC T4; Enclosure Type 4X Class I, Div 2, Groups A,B,C,D; Suitable for Nonincendive CL II, III, Div 2, Groups F,G, T4; Combined CL I, Zone 2, AEx na IIC T4; Enclosure Type 4X AG FM & CSA Intrinsically CL I, II, III, Div 1, Gp A,B,C,D,E,F,G T3; Safe CL I, Zone 0, Ex ia IIC T4; Enclosure Type 4X Class I, Div 2, Groups A,B,C,D; Suitable for Nonincendive CL II, III, Div 2, Groups F,G, T3; CL I, Zone 2, Ex n IIC T4; Enclosure Type 4X Multiple Marking** Ex II 1 G EEx ia IIC T4; Ta -40 to 65 ATEX* Int. Safe, Zone 0/1, or Ex II 3 G EEx nl, IIC T4; Ta -40 to 85 3G Non-Sparking, Zone 2 Enclosure IP 65 * See ATEX installation requirements in the Operator's Manual. ** The user must determine the type of protection required for installation of the equipment. The user shall then check the box [ ] adjacent to the type of protection used on the equipment certification label. Once a type of protection has been checked on the label, the equipment shall not then be reinstalled using any of the other certification type. b RESTRICTIONS Restriction Letter Available Only With Not Available With Table Selection Table Selection b Mutually exclusive - select one NOTE: Manuals are provided on CD with each shipment. Manuals may also be downloaded free of charge @ http://hpsweb.honeywell.com/cultures/en-us/products/instrumentation/xyr5000wireless/default.htm

XYR 5000 WT5xx/WT5xxR/WT5xxT Wireless Temperature Transmitters 7 Model Selection Guide Model Selection Guides are subject to change and are inserted into the specifications as guidance only. Prior to specifying or ordering a model check for the latest revision Model Selection Guides which are published at: http://hpsweb.honeywell.com/cultures/en-us/products/instrumentation/productmodelselectionguides/default.htm Model Selection Guide 34-XY-16-20 Issue 13 Instructions Select the desired key number. The arrow to the right marks the selection available. Make six selections from Table I. Key Number I II (Approvals) _ - - KEY NUMBER Description Wireless Temperature Transmitter - Integrated Complete Selection WT532 Availability TABLE I - PROBE (A) Probe Type RTD R _ c Thermocouple T _ d (B) Process connection Spring Loaded Fitting Direct Insertion Weld _ S _ D e (C) Probe Lag Hardware Nipple Nipple/Union/Nipple N _ U _ (D) Length (Select From Sizing Enter Length (y) From Sizing Table 1 _ Y Table I) (E) Probe Type (Select From Probe Enter Probe Type (z) from Probe Table 2 Z _ Table 2) (F) Thermowell (3/4" NPT) 304 SS _ A (Insertion Length = Probe Length 316 SS _ B minus 1.5") No well _ C Example: WT532-RSNJPA List price = $1263 TABLE II - CERTIFICATION OPTIONS Certificate Approval Type Location or Classification Combined FM & CSA Intrinsically Safe Nonincendive Intrinsically Safe Nonincendive CL I, II, III, Div 1, Gp A,B,C,D,E,F,G T4; CL I, Zone 0, AEx ia IIC T4; Enclosure Type 4X Class I, Div 2, Groups A,B,C,D; Suitable for CL II, III, Div 2, Gp F,G, T4; CL I, Zone 2, AEx na IIC T4; Enclosure Type 4X CL I, II, III, Div 1, Gp A,B,C,D,E,F,G T4; CL I, Zone 0, Ex ia IIC T4; Enclosure Type 4X Class I, Div 2, Groups A,B,C,D; Suitable for CL II, III, Div 2, Gp F,G, T4; CL I, Zone 2, Ex n IIC T4; Enclosure Type 4X Multiple Marking** Ex II 1 G EEx ia IIC T4; Ta -40 to 65 ATEX* Int. Safe, Zone 0/1, or Ex II 3 G EEx nl, IIC T4; Ta -40 to 85 Non-Sparking, Zone 2 Enclosure IP 65 AG 3G b * See ATEX installation requirements in the Operator's Manual. ** The user must determine the type of protection required for installation of the equipment. The user shall then check the box [ ] adjacent to the type of protection used on the equipment certification label. Once a type of protection has been checked on the label, the equipment shall not then be reinstalled using any of the other certification type.

XYR 5000 WT5xx/WT5xxR/WT5xxT Wireless Temperature Transmitters 8 RESTRICTIONS Restriction Letter b c d e Table IE IF Available Only With Selection Mutually exclusive - select one P C Table IE Not Available With Selection P Sizing Table 1 Probe Table 2 Select option based on required Select option based on required probe length and enter option probe type and enter option in Table ID in Table IE Twell List Price Probe Length Option 304 SS 316 SS Probe Type Option 2.5 y = A 29 31 RTD z = P 3.0 y = B 32 35 T/C 3.5 y = C 35 40 B 4.0 y = E 26 31 C 4.5 y = F 39 48 E z = E 5.0 y = G 42 53 J z = J 5.5 y = H 45 57 K z = K 6.0 y = J 37 40 L 6.5 y = K 52 66 N 7.0 y = L 55 70 R 7.5 y = M 53 57 S 8.0 y = N 62 81 T 8.5 y = P 65 86 U 9.0 y = R 68 90 9.5 y = S 72 95 10.0 y = T 75 99 10.5 y = U 78 103 11.0 y = V 81 108 11.5 y = W 85 112 12.0 y = Y 88 117 NOTE 1: Manuals are provided on CD with each shipment. Manuals may also be downloaded free of charge @ http://hpsweb.honeywell.com/cultures/en-us/products/instrumentation/xyr5000wireless/default.htm NOTE 2: Special Order - Contact Product Marketing

XYR 5000 WT5xx/WT5xxR/WT5xxT Wireless Temperature Transmitters 9 For More Information Learn more about how Honeywell s Wireless Temperature Transmitters can be used to monitor a variety of processes in hazardous and remote areas, visit our website www.honeywell.com/ps/hfs or contact your Honeywell account manager. Honeywell Process Solutions 1860 West Rose Garden Lane Phoenix, Arizona 85027 Tel: 1-800-423-9883 or 1-800-343-0228 www.honeywell.com/ps 34-XY-03-02 February 2008 2010 Honeywell International Inc.

XYR 5000 Wireless Temperature Transmitters Model WT530 Specifications - Europe 34-XY-03-52 February 2008 Function The WT530 Temperature Transmitter is part of the XYR 5000 family of wireless products. These transmitters are wireless temperature transmitters that can be used to monitor a variety of processes in hazardous and remote areas. Since there are no wires to run, the transmitter can be installed and operational in minutes, quickly providing information about the variable being monitored. The Smart Response Manager allows the transmitter to adapt to changing process conditions, allowing greater visibility to process variation. Smart Response Manager allows the user to set thresholds which, when exceeded, cause the transmitter to increase sampling and data transmission rates. Optional discrete inputs are available for Wireless Transmitters Base Radio Monitoring process variables Discrete monitoring at the base radio. The transmitter combines an integrated temperature sensor, with a Radio Frequency (RF) transceiver operating in the 868 MHz license-free band. Communication is a digital protocol, using Frequency Hopping Spread Spectrum (FHSS). FHSS ensures data integrity by continually switching the carrier wave over a wide range of frequencies. Power is supplied by a C size 3.6 V lithium battery, with an expected lifetime of up to five years. Enjoy the benefits of wireless technology today: Improve Product Quality Ensure High Uptime Reduce Maintenance and Operational Costs Meet Regulatory Requirements Enhance Flexibility

WT530 Wireless Temperature Transmitters 2 Probe Options Probe Type RANGE RANGE DEG. F DEG. C Pt100 RTD (DIN.00385) -328 to +900-200 to +482 Type B T/C +212 to +3,272 +100 to +1,800 Type C T/C +32 to +4,208 0 to +2,320 Type E T/C -58 to +1,832-50 to +1,000 Type J T/C -292 to +1,382-180 to +750 Type K T/C -292 to +2,282-180 to +1,250 Type L T/C -328 to +1,652-200 to +900 Type N T/C +32 to +2,192 0 to +1,200 Type R T/C +32 to +2,912 0 to +1,600 Type S T/C +32 to +2,822 0 to +1,550 Type T T/C -238 to +752-150 to +400 Type U T/C -148 to +1,112-100 to +600 Wireless General Specifications Wireless Communication 869.4 to 869.65 MHz Frequency Hopping Spread Spectrum (FHSS) Every data block transmitted is verified (CRC check) and acknowledged by the Base Radio. RF Transmit Power 10 dbm (10 mw), 6-8 dbm typical (7.8 to 9 dbm) Data Rate 4.8 Kbps. Update 5 seconds @ 4.8 Kbps. Antenna Omnidirectional Yagi Directional Site Survey Tools Signal Range Internal 3 omni-directional, ¼ wave, monopole. Up to 2000 feet (600 meters) from Base Radio with clear line of sight.* *Actual range may vary depending on site topography. Length: 18. Gain: 6 dbd. Weight: 1.5 lbs. Polarization: Vertical. Up to 5000 feet (1500 meters) from Base Radio with clear line of sight.* RSSI Link Test Received Signal Strength Indicator displays the RF signal strength in one of seven ranges. Link Test measures the wireless link performance of a transmitter running in normal operating mode. This function looks at wireless performance in both directions, from the transmitter to base radio and vice versa and assigns a rating to that performance or quality of signal.

WT530 Wireless Temperature Transmitters 3 Features Automatic Re-transmit The field unit checks with the base radio to insure successful receipt of data. If data was not received, the transmitter retries on the next RF cycle. Ensures communication confidence in the harshest of industrial environments. At the maximum transmit rate this feature is inactive. Self Diagnostics Self-checking software and hardware that identifies and reports out of spec conditions, and field unit low battery voltage. Operating/Storage Conditions Humidity Temperature Ambient Sensor: Ambient Electronics: Process fluid: Display (Full visibility): Display (Reduced visibility): Storage: 95% RH (non-condensing). -40 to +230 F (-40 to +110 C) -40 to +149/+185 F (-40 to +65/+85 C) (see Model Selection Guide) -40 to +250 F(-40 to +121 C) -4 to +158 F (-20 to +70 C) -40 to +185 F (-40 to +85 C) -58 to +185 F (-50 to +85 C) Discrete Inputs (Optional) Discrete Input Switch (Dry Contact Only, no Voltage or Current Allowed) Maximum Impedance at 1 K ohm. Input Isolation 110 K ohms between Output (-) and Input (-). Wiring Warning Plug Wire Size 28 to 16 gauge maximum. No external voltage or current shall be applied to input terminals. Performance Accuracy Linearization Ambient Temperature Effect ± 0.1% of full scale reading at operating conditions. For cold junction compensation (T/C only), add 1.8 F (± 1 C) at reference conditions. RTD and T/C linearization to ± 0.09 F (± 0.05 C). Custom linearization with 22 point curve. RTD - ± 0.002% of reading per C T/C - ± 0.01% of reading per C Long Term Stability Stability deviation per year is less than 0.025%.

WT530 Wireless Temperature Transmitters 4 Device Configuration Parameter Configuration RF Channel Setup: 1 to 4 Baud Rate: 4.8 Kbps. RF ID: 1 to 42. Password. Tag Name (up to 21 characters). Normal Transmit Rate: (5 sec, 10 sec, 15 sec, 20 sec, 40 sec, 1 min). Normal Sampling Rate: (1 10 sec, 15 sec, 20 sec, 30 sec, 1 min). Abnormal Transmit Rate: (5 sec, 10 sec, 15 sec, 20 sec, 40 sec, 1 min). Abnormal Sampling Rate: (1 10 sec, 15 sec, 20 sec, 30 sec). Temperature Normal Upper Value: Disabled/Enabled. Enabled to change Sampling and Transmit rates during abnormal process conditions. Temperature Normal Lower Value: Disabled/Enabled. Enabled to change Sampling and Transmit rates during abnormal process conditions. Engineering Units: Deg C, Deg F, Kelvin, Rankin. Probe Type. (WT531R will accept one RTD probe; WT531T will accept one or two T/C probes). Offset: User defined offset will be transmitted instead of actual value. Trim: Applies a user-defined one- or two-point correction curve to the actual value. Discrete Input parameters configured from the Wireless Management Toolkit Configuration Panel Integrated LCD display with membrane switch buttons for local configuration. LCD display is 7-digit (alternating) high contrast, anti-reflective monochrome. Display cycles between temperature level and RF status. Physical Specifications Thermowell Material Electronic Housing Process connections Vibration and Shock Random Vibration Net weight (no probe or well) Electromagnetic Compatibility (CE Compliance) 304 SS, 316 SS. GE Lexan. V0 Rating and UV Stable. ½ - NPTM for probe only. ¾ - NPTM for well. Certified per IEC EN 60068-2-6 (Vibration), and EN 60068-2-27 (Shock). Certified to withstand 6 g s, 15 minutes per axis from 9 500 Hz. With Omnidirectional antenna With Yagi directional antenna 1.0 kg (2 lbs) 1.8 kg (3.5 lbs.) Operates within Specifications in fields from 80 to 1,000 MHz with Field Strengths to 10 V/m. Meets EN 50082-1 General Immunity Standard and EN 55011 Compatibility Emissions Standard. Approvals Environmental protection NEMA 4, IP 65. Combined FM/CSA FM Intrinsically safe - Class I, Div. 1, Groups A,B,C,D,E,F,G,T4, Class I, Zone 0, AEx ia IIC T4, (Ta = -40 C to +85 C) Enclosure 4 CSA - Intrinsically safe - Class I, Div. 1, Groups A,B,C,D,E,F,G,T4, Class I, Zone 0, Ex ia IIC T4, (Ta = -40 C to +85 C) Enclosure 4 Combined CE/ATEX CE EMC Conformity, ETSI EN 300 489-1 Intrinsically Safe, Zone 0/1: Ex II 1 G EEx ia IIC T4 (Ta = -40 C to +65 C) IP65 Non-Sparking, Zone 2: Ex II 3 G EEx na, IIC T6 (Ta = -40 C to +85 C) IP65

WT530 Wireless Temperature Transmitters 5 Dimensions 112.5 4.44 97.5 3.84 204 8.05 131 5.19 131 5.19 mm inches

WT530 Wireless Temperature Transmitters 6 Model Selection Guide Model Selection Guides are subject to change and are inserted into the specifications as guidance only. Prior to specifying or ordering a model check for the latest revision Model Selection Guides which are published at: http://hpsweb.honeywell.com/cultures/en-us/products/instrumentation/productmodelselectionguides/default.htm Model Selection Guide 34-XY-16-20 Issue 13 Instructions Select the desired key number. The arrow to the right marks the selection available. Make six selections from Table I. Key Number I II (Approvals) _ - - KEY NUMBER Description Wireless Temperature Transmitter - Integrated Complete Selection WT532 Availability TABLE I - PROBE (A) Probe Type RTD R _ c Thermocouple T _ d (B) Process connection Spring Loaded Fitting Direct Insertion Weld _ S _ D e (C) Probe Lag Hardware Nipple Nipple/Union/Nipple N _ U _ (D) Length (Select From Sizing Enter Length (y) From Sizing Table 1 _ Y Table I) (E) Probe Type (Select From Probe Enter Probe Type (z) from Probe Table 2 Z _ Table 2) (F) Thermowell (3/4" NPT) 304 SS _ A (Insertion Length = Probe Length 316 SS _ B minus 1.5") No well _ C Example: WT532-RSNJPA List price = $1263 TABLE II - CERTIFICATION OPTIONS Certificate Approval Type Location or Classification Combined FM & CSA Intrinsically Safe Nonincendive Intrinsically Safe Nonincendive CL I, II, III, Div 1, Gp A,B,C,D,E,F,G T4; CL I, Zone 0, AEx ia IIC T4; Enclosure Type 4X Class I, Div 2, Groups A,B,C,D; Suitable for CL II, III, Div 2, Gp F,G, T4; CL I, Zone 2, AEx na IIC T4; Enclosure Type 4X CL I, II, III, Div 1, Gp A,B,C,D,E,F,G T4; CL I, Zone 0, Ex ia IIC T4; Enclosure Type 4X Class I, Div 2, Groups A,B,C,D; Suitable for CL II, III, Div 2, Gp F,G, T4; CL I, Zone 2, Ex n IIC T4; Enclosure Type 4X Multiple Marking** Ex II 1 G EEx ia IIC T4; Ta -40 to 65 ATEX* Int. Safe, Zone 0/1, or Ex II 3 G EEx nl, IIC T4; Ta -40 to 85 Non-Sparking, Zone 2 Enclosure IP 65 AG 3G b * See ATEX installation requirements in the Operator's Manual. ** The user must determine the type of protection required for installation of the equipment. The user shall then check the box [ ] adjacent to the type of protection used on the equipment certification label. Once a type of protection has been checked on the label, the equipment shall not then be reinstalled using any of the other certification type.

WT530 Wireless Temperature Transmitters 7 Model Selection Guide 34-XY-16-20 Issue 13 Instructions Select the desired key number. The arrow to the right marks the selection available. Make six selections from Table I. Key Number I II (Approvals) _ - - KEY NUMBER Description Wireless Temperature Transmitter - Integrated Complete Selection WT532 Availability TABLE I - PROBE (A) Probe Type RTD R _ c Thermocouple T _ d (B) Process connection Spring Loaded Fitting Direct Insertion Weld _ S _ D e (C) Probe Lag Hardware Nipple Nipple/Union/Nipple N _ U _ (D) Length (Select From Sizing Enter Length (y) From Sizing Table 1 _ Y Table I) (E) Probe Type (Select From Probe Enter Probe Type (z) from Probe Table 2 Z _ Table 2) (F) Thermowell (3/4" NPT) 304 SS _ A (Insertion Length = Probe Length 316 SS _ B minus 1.5") No well _ C Example: WT532-RSNJPA List price = $1263 TABLE II - CERTIFICATION OPTIONS Certificate Approval Type Location or Classification Combined FM & CSA Intrinsically Safe Nonincendive Intrinsically Safe Nonincendive CL I, II, III, Div 1, Gp A,B,C,D,E,F,G T4; CL I, Zone 0, AEx ia IIC T4; Enclosure Type 4X Class I, Div 2, Groups A,B,C,D; Suitable for CL II, III, Div 2, Gp F,G, T4; CL I, Zone 2, AEx na IIC T4; Enclosure Type 4X CL I, II, III, Div 1, Gp A,B,C,D,E,F,G T4; CL I, Zone 0, Ex ia IIC T4; Enclosure Type 4X Class I, Div 2, Groups A,B,C,D; Suitable for CL II, III, Div 2, Gp F,G, T4; CL I, Zone 2, Ex n IIC T4; Enclosure Type 4X Multiple Marking** Ex II 1 G EEx ia IIC T4; Ta -40 to 65 ATEX* Int. Safe, Zone 0/1, or Ex II 3 G EEx nl, IIC T4; Ta -40 to 85 Non-Sparking, Zone 2 Enclosure IP 65 AG 3G b * See ATEX installation requirements in the Operator's Manual. ** The user must determine the type of protection required for installation of the equipment. The user shall then check the box [ ] adjacent to the type of protection used on the equipment certification label. Once a type of protection has been checked on the label, the equipment shall not then be reinstalled using any of the other certification type.

WT530 Wireless Temperature Transmitters 8 RESTRICTIONS Restriction Letter b c d e Table IE IF Available Only With Selection Mutually exclusive - select one P C Table IE Not Available With Selection P Sizing Table 1 Probe Table 2 Select option based on required Select option based on required probe length and enter option probe type and enter option in Table ID in Table IE Twell List Price Probe Length Option 304 SS 316 SS Probe Type Option 2.5 y = A 29 31 RTD z = P 3.0 y = B 32 35 T/C 3.5 y = C 35 40 B 4.0 y = E 26 31 C 4.5 y = F 39 48 E z = E 5.0 y = G 42 53 J z = J 5.5 y = H 45 57 K z = K 6.0 y = J 37 40 L 6.5 y = K 52 66 N 7.0 y = L 55 70 R 7.5 y = M 53 57 S 8.0 y = N 62 81 T 8.5 y = P 65 86 U 9.0 y = R 68 90 9.5 y = S 72 95 10.0 y = T 75 99 10.5 y = U 78 103 11.0 y = V 81 108 11.5 y = W 85 112 12.0 y = Y 88 117 NOTE 1: Manuals are provided on CD with each shipment. Manuals may also be downloaded free of charge @ http://hpsweb.honeywell.com/cultures/en-us/products/instrumentation/xyr5000wireless/default.htm NOTE 2: Special Order - Contact Product Marketing

WT530 Wireless Temperature Transmitters 9 For More Information Learn more about how Honeywell s WT530 Wireless Temperature Transmitters can be used to monitor a variety of processes in hazardous and remote areas, visit our website www.honeywell.com/ps/hfs or contact your Honeywell account manager. Honeywell Process Solutions 1860 West Rose Garden Lane Phoenix, Arizona 85027 Tel: 1-800-423-9883 or 1-800-343-0228 www.honeywell.com/ps 34-XY-03-52 February 2008 2010 Honeywell International Inc.