DSM Dynamic Shunt

Similar documents
200 Watt Passive Shunt Module

IC800SSD Hardware Manual Pub 348R5. for models. A publication of

LZS-A500-3 POWER SUPPLY Installation, Operation, and Maintenance Manual. IM-LZSA500-3 January 2008 Revision H

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz

CCH400 & CCH600 Series

LXM32CD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

CHAPTER MAINTENANCE AND TROUBLESHOOTING. In This Chapter... Maintenance and Inspection Troubleshooting...6 3

NEVO+1200M. 6 x6 x W. 1.2kg DATA SHEET MAIN FEATURES

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3

ATS22C21Q soft starter-ats22-control 220V-power 230V(55kW)/ V(110kW)

Frequency Range: MHz. Efficiency: 80% Temperature Range: -20 to 65 C Max VSWR: 3:1. Class: Supply Voltage: 32.0V

1394 External Shunt Resistor Kit

DYNAMIC BRAKING (DB) OPTION

SINGLE-PHASE VSV SWITCH

AC/DC Power Supply Series APPLICATION NOTE

HTA125A/250A. Power Amplifiers. Installation & Use Manual

The frequency inverter continues to carry hazardous voltages for up to 5 minutes after it was switched off.

POWER AMPLIFIER. Owner s Manual Mode d emploi Bedienungsanleitung Manual de instrucciónes CLIP SIGNAL TEMP PROTECTION POWER

VARAN Stepper Module VST 012

Installation and Operation Manual MSI. Multi-Sensor Interface Hub. Interface Module for all Sensors Network and Wireless CAUTION

LXM32MD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

Power Supplies 3. SDN-C Compact DIN Rail Series

Manual Overview...1 2

40 Amp Digital Bidirectional PWM Motor Controller with Regenerative Braking BIDIR-340-DR

AC/DC Power Supply Series APPLICATION NOTE

Installation Instructions

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

LXM32MU60N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

LXM32AD18M2 motion servo drive - Lexium 32 - single phase supply voltage 115/230V - 0.5/1kW

SmartBlock I/O Module - HE579DAC107/HE579DAC207 8/4 Channel Current and Voltage Output 0-5V / 0-10V / 4-20mA / 0-20mA - CsCAN

High Frequency Sinewave Guardian TM Filter

American Audio. User Instructions. American Audio 4295 Charter Strret Los Angeles Ca Revised 5/01

CX-A6 Amplifier Installation & User Guide V8.0

High Frequency SineWave Guardian TM Filter

AC/DC Power Supply Series APPLICATION NOTE

SI-125 Power Amplifier Manual 6205 Kestrel Road; Mississauga, Ontario; Canada; L5T 2A1 November 2016, Rev 0.5

AC/DC Power Supply Series APPLICATION NOTE

7I25 H-BRIDGE MANUAL

LXM32AD72N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

MODEL 3810/2 Line Impedance Stabilization Network

ACS600, ACS800. Installation Guide

SINGLE-PHASE VSV SWITCH

Hexa Multi Module 366HMM. Introduction. Design Specifications. Key Features

GT-1050A 2 GHz to 50 GHz Microwave Power Amplifier

Current Loop Interface Module M 2025D

Instruction Manual for Universal Ku-band 8W BUC [NJT5218 series]

User's Guide for type ACS55 AC Drives from 0.18 to 2.2 kw

R10-FA-01 Ruggedized Edge Filter for Xenus: User Guide

USER MANUAL. MODEL 457B Seven Port Active Twinax Star Hub. SALES OFFICE (301) TECHNICAL SUPPORT (301)

TECHNICAL DATASHEET #TDAX Universal Input, Single Output Valve Controller CAN (SAE J1939)

AC/DC Power Supply Series APPLICATION NOTE

E2V Technologies MG5222 X-Band Magnetron

This convection-cooled series is designed for use in commercial and industrial environments in temperatures up to 50 C.

BCV-1203 Barcode Verification System Users Guide Version 1.2

INTELLIMETER REGISTER

HITEK POWER OLH10K SERIES

G7 Adjustable Speed Drive PG Feedback Option Manual

MODEL KBWD-15 Pulse Width Modulated (PWM)

PowerFlex 400 Submittal

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

Dynamo Brushless DC Motor and GreenDriveTM Manual

XES-M50 Operating Instructions

Single-output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements.

E2V Technologies M5187F X-Band Magnetron

EMC Feedthrough Capacitors

WARNING: DO NOT PROCEED WITHOUT READING THIS PAGE.

Parameter Min. Typ. Max. Min. Typ. Max. Units

NOsparc! MHXAC1F120! MHXAC1F240! MHXAC1F480 PATENTS AND PATENTS PENDING. Contact Arc Suppressor

USER MANUAL. Maxwell Technologies Ultracapacitor Energy Storage Modules. Models: BMOD0058 E016 B02 BMOD0006 E160 B02. Document

MEDIUM-MU AIR-COOLED POWER TRIODE 3CX15,000H3

Installing flat panels on the MPL15 wall mount

ECC100 Series. -40 ºC to +75 ºC Operation. 100 W - Baseplate Cooled. High Efficiency Resonant Topology. Screw Terminals Available.

Electrical Specifications

Series OLH10KD 10kW HIGH VOLTAGE POWER SUPPLIES

Mirage B-320-G FEATURES

20W Solid State Power Amplifier 6-18GHz. Parameter Min. Typ. Max. Min. Typ. Max. Units

WARNING: DO NOT PROCEED WITHOUT READING THIS PAGE.

An American Control Electronics Brand PCM4 SERIES USER MANUAL PCM4.

Current Loop Interface Module M-2025C

OPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM

Power supply CP-D 24/4.2 Primary switch mode power supply

The frequency inverter continues to carry hazardous voltages for up to 5 minutes after it was switched off.

Asia-Pacific North America Europe, Middle East Bel Power Solutions, Inc. BCD.

BROADBAND LINEAR AMPLIFIER Model P150

Pre-wired Photomicrosensor with Amplifier and Cable EE-SPW321/421 Compact, Thin-profile Photomicrosensor with special amplifier.

Installation requirements

PEAK OUTPUT CURRENT 1. MAP V 4.7V to 5.8V 8A 11A 0.2% ±1% 1% 4.9V to 5.1V PEAK OUTPUT CURRENT 4 LINE REGULATION

MDW-45 Converter RS RS-422/485

BOP 1 KILOWATT 1000 WATTS OF FOUR-QUADRANT BIPOLAR POWER FROM KEPCO AN ISO 9001 COMPANY

12 Input/12 Output Discrete Embedded TTL I/O Module with Pulse Width Modulation and DeviceLogix

SA-150, SA-300 Series Pure Sine Wave Inverter User s Manual

Installation & User Guide. For Powering Distributed Audio Systems A45-X2 TWO CHANNEL AMPLIFIER

INSTRUCTION SHEET STRUT DRIVER RETROFIT KIT PN: 22-79SDRF

Efficiency: 68% Temperature Range: +0 to 60 C Max VSWR: 5:1. Class: Supply Voltage:

Isolated RTD Modules Product Specifications and Installation Data

TRANSFORMER HD-HAMPTON HAMPTONBAY.COM

GE FANUC Spares. GE Fanuc Automation. Stepping Motor Cube with Pulse and Direction Interface. Programmable Control Products.

IB6 Series Solid-State Isolation Relay

WORLD-BEAM QS18AFF200 Sensors with Foreground Suppression

Transcription:

DSM Dynamic Shunt 401-30286-00 Installation Manual Part Number 108-31058-00 Giddings & Lewis Controls, Measurement & Sensing

NOTE Progress is an on going commitment at Giddings & Lewis. We continually strive to offer the most advanced products in the industry; therefore, information in this document is subject to change without notice. The illustrations and specifications are not binding in detail. Giddings & Lewis shall not be liable for any technical or editorial omissions occurring in this document, nor for any consequential or incidental damages resulting from the use of this document. DO NOT ATTEMPT to use any Giddings & Lewis product until the use of such product is completely understood. It is the responsibility of the user to make certain proper operation practices are understood. Giddings & Lewis products should be used only by qualified personnel and for the express purpose for which said products were designed. Should information not covered in this document be required, contact the Customer Service Department, Giddings & Lewis, 660 South Military Road, P.O. Box 1658, Fond du Lac, WI 54936-1658. Giddings & Lewis can be reached by telephone at (920) 921 7100. 108-31058-00 Version 4799 1999 Giddings & Lewis, LLC

Table of Contents Product Review...1 Important Information...1 Introduction...2 Performance Specifications...4 Continuous Shunt Capability...4 Installation...7 Mechanical Requirements...7 Wiring...11 Troubleshooting...12 Product Support...13 Distributor & Representative Network...13 Applications Engineers and Field Service...13 TOC-1

TOC-2 NOTES

Product Review Important Information Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. The illustrations, charts, and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Giddings & Lewis does not assume liability (to include intellectual property liability) for actual use based upon the examples shown in this publication. Throughout this manual notes are used to make you aware of safety considerations. For example:! This symbol identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss. Attention statements help you to: identify a hazard avoid the hazard recognize the consequences 1

Introduction The micro DSM sized drives do not have an internal shunt circuit to dissipated any excess energy and overvoltage faults could result. To ensure the smooth braking of large inertial loads, the use of a shunt regulator is recommended. The Dynamic Shunt Module is used in systems that see significant DC voltage regeneration from large intertial load applications. The Dynamic Shunt Module monitors the DC bus voltage of the drive and, if the voltage reaches the activation level, the Dynamic Shunt Module drops the DC bus voltage and dissipates the energy as heat. Figure 1 illustrates this drop in DC bus voltage. FIGURE 1: Shunt Activation on DC Bus Voltage Drops for at least 1 millsecond Activation level Bus voltage Actual shunt time Time Figure 2 shows information relating to the adjust screw and the LEDs that show shunt activity. Also see Figure 7 for more information. 2

FIGURE 2: Dynamic Shunt Module Adjustment Screw and LEDs Giddings & Lewis Giddings & Lewis Adjust (screw) The Adjust screw is used to set the activation level of the Dynamic Shunt. It is set at the factory and will not ordinarily need any further adjustment. Overtemp (LED) The Overtemp yellow LED will illuminate when the unit s thermostat has tripped. While the thermostat is tripped, the unit will not shunt excess voltage (the bus-drop feature will still work) and this will usually cause the host drive to fault on overvoltage. Once the LED turns on, only removing power will shut it off, even if the active shunt unit has cooled and is functioning again. DC Bus (LED) The DC Bus green LED will be on when there is sufficient bus voltage. The higher the bus voltage, the brighter the LED will glow. Active (LED) The active green LED will be on while the Dynamic Shunt is actually shunting. This LED indicates not only that the Dynamic Shunt is functioning, but can also be used to quickly see how much the shunt is running. 3

Performance Specifications The peak shunting capability is a direct result of using a 36 ohm shunt resistor. The peak shunt power can be calculated by dividing bus voltage squared, by 36. For example, if the bus voltage is 380V when the shunt comes on, the shunt power at that time is 4011watts or: 380volts 2 ----------------------- = 4011watts 36ohms Continuous Shunt Capability A shunt regeneration profile is defined by shunt time, cycle time, and peak power level. Figure 3 depicts a profile of regeneration during a machine cycle. FIGURE 3: Shunt Regeneration Profile Area = shunt energy (joules) Shunt power (watts) Shunt time (seconds) Cycle time or machine cycle Shunt power is the peak shunt power during the shunt time. Shunt time is the time the power pulse is dissipated by the shunt. The cycle time is the time from the beginning of one shunt to the beginning of the next shunt time. 4

If the required average shunt power over the machine cycle is < 300 seconds, the Dynamic Shunt Module can handle the application. Figure 4 depicts the capability of a Dynamic Shunt Module at 50 C ambient temperature. The different lines represent different cycle times (rates). The X-axis is the shunt power during the shunt time and the Y-axis is the maximum shunt time. for that power and cycle time. For example, the bottom line is a 5 second cycle time (meaning the shunt pulse comes every 5 seconds) and it intersects the 800 watt pulse for 2 seconds every five seconds in a 50 C or less ambient temperature. This means that the shunt can handle an 800 watt pulse lasting for two seconds, every 5 seconds if the ambient temperature is not above 50 C. Note: The limiting factor on how much average power can be dissipated is temperature. The shunt power capability increases about 5.5 watts for every 1 C drop in ambient temperature (3.1 watts/ F). Increasing the air flow across the heat sink can increase the continuous shunt capability significantly. Obstructing air flow can decrease it significantly. 5

FIGURE 4: Dynamic Shunt Module Thermal Capacity 10000 Pulse Time vs. Pulse Power Different cycle times for the Dynamic Shunt (Lower left of lines is safe, upper right is not safe) 50 C ambient temperature, 110 C thermostat 120 95 87 83 76 1000 1000 100 10 1 0.1 600 405 300 230 180 171 38 30 24 19.2 (showing seconds) 43 19 9.6 5 4 3.2 1.6 0.8 Shunt Power (Watts) 41 41 21.5 9.5 2.4 0.4 Shunt Cycle one-shot 5 min cycle 2 min cycle 30 sec. cycle 5 sec. cycle 100 Shunt Time (Seconds) 6

Installation Mechanical Requirements Mount the unit in an enclosure providing IP54 protection (protected against dust and splashing water), or IP65 protection (dust free and protected against water jets) as the work environment dictates.! Warning: Avoid contaminating electronic components. Provide a quality air source to cabinets; free of debris, oil, corrosives, or electrically conductive contaminates. All cabinets should have scheduled inspections and be cleaned as needed. Failure to observe these safety procedures could result in breakdown and damage to equipment. Many NEMA (National Electrical Manufacturers Association) Type 4 cabinets provide this level of protection. Provide adequate clearance and ventilation to dissipate heat generated by the shunt module. The minimum recommended space surrounding the shunt module for cooling air intake and fan exhaust is: 5 cm (2 in) above, 5 cm (2 in) below, 1.25 cm (0.5 in) sides, and 2.5 cm (1.0 in) in front which includes additional cable clearance Position the shunt module on a flat, solid, grounded surface. Bolt the unit to the cabinet using the mounting slots in the case. Mounting dimensions are shown in Figure 5. The surface and mounting hardware should meet or exceed the specified requirements for vibration and shock, altitude and humidity, air flow clearance, temperature, and size (see the following tables). 7

Table 1: Vibration and shock, altitude, humidity, temperature, and air flow limits Environmental Condition Value Vibration 2g at 10 to 2000 Hz Shock 15g 11 msec half sine Altitude 1500 m (5000 ft) Humidity 5% to 95% non-condensing Ambient operating temperature 1 0 to 50 C (32 to 140 F) Air flow clearances 50 mm (2 in) above and below unit for air flow 1. Power performance increases about 5.5 W for every 1 C drop in ambient temperature. Table 2: Recommended mounting hardware Mounting Hardware Size Metal Screws #10 Hex Cap Screws 1/4-20 Hex Cap Screws (Metric) M5 Table 3: Wiring Wiring Size 75 C copper wire 12 AWG (4.0mm 2 ) or 14 AWG (2.5mm 2 ) Table 4: Terminal Block Screws Chrome plated brass Torque 11 in-lbs. (1.2 Nm) Table 5: Unit Weight ASM-300 Product DSM Dynamic Shunt Unit Weights 1.23 kg (3.3 lbs.) Table 6: Ferrites for CE radiated emissions compliance Mfg. Part/No. D E Impedance SS28B2034 0.250 0.120 125 Ω SS28B2037 0.350 0.200 154 Ω SS28B2032 0.500 0.200 230 Ω Box shaped ferrite assembly in fully enclosed nylon case. End ports are surrounded with flexible spring flutes to grip a range of cable diameters from.125 to.500 (3.2 to 12.7mm). FerriShield, Inc. 350 Fifth Avenue, Suite 7310 New York, NY 10118-7591 8

FIGURE 5: Mounting Dimensions - Front View 2.56 65.10.25 6.30 1.50 38.10.73 18.60.52 13.30 CLEARANCE HOLES FOR #10 (M5) SCREWS. 7.35 186.70 NOTE: 1. ALLOW 3.0 (76.2 mm) CLEARANCE IN FRONT OF UNIT FOR CABLES. 2. ALLOW.50 (12.7 mm) ON BOTH SIDES OF UNIT 3. ALLOW 2.0 (5 cm) ABOVE AND BELOW 9

FIGURE 6: Mounting Dimensions Giddings & Lewis 10

Wiring The Bus (+) connection (the topmost pin of the main connector) on the Dynamic Shunt must be connected to the Bus (+) connection of the micro DSM size Drive. Likewise, the Bus (-) connection (the next one down) must be connected to the Bus (-) connection of the micro DSM size Drive. Use 12 AWG (4.0mm 2 ) or 14 AWG (2.5mm 2 ) twisted 75 C, copper wire for wiring and tighten the terminal block screws to 11 in-lbs. (1.2 Nm). The wire should not be longer than 10 feet (3m). The AC inputs can be wired to the AC terminals of the micro DSM size Drive or the same AC power source. If used, the shunt module will sense when the AC is lost to the drive and, after 0.25/sec, will drop the bus. Use 12 AWG (4.0mm 2 ) or 14 AWG (2.5mm 2 ) twisted 75 C, copper wire for wiring and tighten the terminal block screws to 11 in-lbs. (1.2 Nm). The chassis ground should be connected to earth ground. To comply with the CE radiated emissions standards, ferrites must be added to the ends of the DC bus wires. Route both twisted wires through the ferrites. Ferrites with an impedance at 100 MHz between 100 Ω to 200 Ω were found to be effective. Table 6 lists some readily available ferrites with effective impedance ratings. FIGURE 7: Dynamic Shunt Module Cabinet Layout NOTE: 1. ALLOW 1.0 (2.5 cm) CLEARANCE IN FRONT OF UNIT FOR CABLES. 2. ALLOW.50 (1.25 cm) ON BOTH SIDES OF UNITS 3. ALLOW 2.0 (5 cm) ABOVE AND BELOW 11

Troubleshooting FIGURE 8: Troubleshooting Symptoms, Diagnosis, and Solution Symptom Overtemp light is on Bus Overvoltage faults from the drive with the Dynamic Shunt functioning and the Overtemp light off Diagnosis and Solution The internal thermostat in the shunt unit is getting too hot. To fix this problem: Reduce the average shunt power, Reduce the ambient temperature of the air around the shunt, or Increase the amount of air passing over the heat-sink fins. Once the LED turns on, only removing power will shut it off, even if the dynamic shunt unit has cooled and is functioning again. There are two situations where this can happen. 1. First, if the Bus Overvoltage trip level on the drive is too low. Since this is not adjustable the solution is to reduce the activate level on the Dynamic Shunt. This is done be turning the Adjust pot counter-clockwise. 2. Second, if the regeneration power exceeds the shunt power for too long. It is possible for the drive to generate more power than the Dynamic Shunt can handle. There are two possible solutions to this situation. The first is to adjust the regeneration profile so that the drive generates less power for a longer time. The drive current limit parameters may be useful here. The second is to reduce the shunt activate level. This turns on the shunt earlier in the regeneration profile and may help. 12

Product Support Giddings & Lewis product support is available over the phone. When you call, you should be at your computer and have the hardware and software manuals at hand. Be prepared to give the following information: The version numbers of the hardware and software products. The type of hardware that you are using. The fault indicators and the exact wording of any messages that appears on your screen. How you have tried to solve the problem. Distributor & Representative Network The Giddings & Lewis has a wide network of distributors that are trained to support our products. If you encounter problems, call the distributor or representative where you purchased the product before contacting the factory. Applications Engineers and Field Service In the United States you can reach the Giddings & Lewis factory based support staff by phone between 7:00 AM and 5:00 PM (CST) Monday through Friday at 1-800-558-4808. The applications engineers can assist you with programming difficulties as well as ideas for how to approach your automation task. Should your problem require on-site assistance, field service is available. The applications engineers can also be reached via fax at 1-920-906-7669. The fax machine is open 24 hours 7 days a week. Faxes will be answered during regular business hours only. In Europe, support can be obtained through Giddings & Lewis. The support staff may be reached by telephone between 8:30 and 17:30 local time, Monday through Friday at 011-44-15154-62010, or via fax at 011-44-15154-72801. 13

14 NOTES