TCS2P125. Automatic Transfer Switch Control Unit for 1 Phase System Operation Manual

Similar documents
ATS-01 Ver1.2 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

Monicon International Co., Ltd ATS 100 ATS 100 Controller User Manual

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SECTION 16496G CONTACTOR BASED AUTOMATIC TRANSFER SWITCHES LOW VOLTAGE

VTSC100. Transfer Switch Controller

ATC-100 Logic Panel Controller. High efficiency Comprehensive function The new generation VFD

O & M Manual for the EATON ATC-300 Automatic Transfer Switch Controller

ATC Controllers. High efficiency Comprehensive function The new generation VFD

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

ATS-I USER MANUAL. Tecnoelettra srl Dal Via Vioni Dimo, S.Rocco di Guastalla (RE)

O & M Manual for 1600A (480 Vac) ATC-300+/800 & Non-Automatic, 3-Position Fixed Mount Contactor Based Transfer Switch

Installation and Operating Instructions. Power IT Power Factor Controller RVC

With Audible Detect Signal

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009

MODEL 421 Over/Under Motor Load Monitor

CS-200. PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL

Technical Datasheet. True RMS Digital Protection Relay. Voltage Protection Relay

EA05A. Generator Automatic Voltage Regulator Operation Manual. Self Excited Automatic Voltage Regulator 5 Amp AVR For General Generators

0E4343-F LOAD CIRCUIT BREAKER ACCESS DOOR P/N 0E4708 REV.- TVSS STATUS UTILITY FAULT ( RED - SURGE FAILURE )

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 919 RAILROAD PREEMPTION INTERFACE. January 15, 2016

Owner s Manual POWER SYSTEMS, INC. GENERACR. Automatic Transfer Switch. Model Numbers , , ,

RELIABLE SOLUTIONS in POWER ELECTRONICS VRST SERIES. Power Management Instruments ELECTRONIC STABILIZER FROM PMI & OES GROUP COMPANIES SUD

EA06 (220V) Generator Automatic Voltage Regulator Operation Manual

Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay

ADVR-2100M. Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

AMU-214 Auxiliary Monitor Unit Operations Manual

SUGGESTED SPECIFICATION DUAL OPERATOR OPEN TRANSITION AUTOMATIC TRANSFER SWITCH WITH RPTCS MICROPROCESSOR CONTROL

Mounting Instructions / Manual MV1171

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

itl impulse relays IEC/EN itls: IEC/EN itls b Allows remote indication of its operating state (open/closed)

Relay. Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay

... yet still led out of the terminal quickly and safely in an emergency.

Technical Data Sheet

TM Analogic. Serie TM. Cod. rev

AMIK Three Phase Digital Panel Meters

Technical Data Sheet. x1000. kwh R Y B

Guidelines to Using a Three Phase Voltage Monitor

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

SUPPLY NETWORK ANALYZER. CVMk SERIES. CVMk-4C SERIES INSTRUCTION MANUAL. ( M / 00 B - Manual 1 / 2 ) (c) CIRCUTOR S.A.

MODEL 9050 EXTENDED SPECIFICATIONS. 50ppm TRANSPORTABLE CALIBRATOR

TC 204 Heating Controller

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY

Data Sheet. RISH Master Record %THD

VX-3000 Series Voice Alarm and Public Address System

Phase and neutral overcurrent protection

TOSHIBA International Corp

Sentry Digital Timers

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16

SECTION AUTOMATIC TRANSFER SWITCH

ST-250MAK-05E. Switching Power Supply SPECIFICATION

SDMO. Changeover switch VERSO 200

12/2 Product overview. 12/3 7KT1 14, 7KT1 53 E-counters. 12/9 7KT1 11, 7KT1 12 digital measuring devices. 12/11 7KT1 0 analog measuring devices

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

DRTS-6. DRTS-6 has been designed to test: DRTS-6. Advanced Protection Relay Test Set and Measurement System

CROSS Chassis from 160 A to 450 A

The MP SERIES CONTROLLER. User s Manual. ISE, Inc.

Technical Specification

EA3012 TRANSCONDUCTANCE AMPLIFIER OPERATION MANUAL

Green LED (right of 'D' type connector)

SUNDIAL Light Dimmer. User's Manual

3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2. (Code to ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

Technical Data Sheet AMIK 300 / 301

2) APRV detects and records low frequency events (voltage drop, over-voltages, wave distortion) with a sampling frequency of 6400 Hz.

Digital Multifunction Instrument - Rish Master 3440

Technical data Sheet HLD30-60 series

ELECTRONIC SHEAR PIN MODEL ESP 1 & 2 INSTRUCTION MANUAL

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

Starbox. Installation guide

SOCOMEC - Réf.: A

BECAUSE MOTOR & GENERATOR FAILURE IS NOT AN OPTION USCG

Shelti, Inc. 333 Morton Street Bay City, MI Phone Fax. Bayside Dollar Bill Acceptor Pool Table Manual & Instructions

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

NT240 TIMER. PROGRAMMABLE TIMER INSTRUCTIONS MANUAL V20x G TIMER OUTPUTS INTRODUCTION SPECIFICATIONS AUXILIARY SUPPLY OUTPUT INSTALLATION TIMER INPUTS

Onsite Mobile AC High Voltage Test System

MODEL 9041 EXTENDED SPECIFICATIONS. 25ppm TRANSPORTABLE CALIBRATOR

TS-700/1000 INVERTER Instruction Manual

Q-SERIES. Amplifiers. QPAIR Redundancy Switch Amplifier System. Installation & Operation Manual

KEY FEATURES. Selectable modes of control : Phase Angle or Burst Fire (Single- Cycle/Dual-Cycle & adjustable STD Burst Firing)

Product Catalog PRODUCT CATALOG. Power supply system & test equipment

Applications Avionics Testing Power Line Simulation Production Test - Power Supplies - UPS - Telecom. SMARTWAVE Programmable AC/DC Power Source

SC-225/SC-250/SC-325/SC-350 STATIC CONTACTOR

Dual Technology Wall Mount Occupancy Sensor

LCE-MBP-400. User Manual. TDI Transistor Devices Inc. 85 Horsehill Road, Cedar Knolls, NJ USA Phone: Fax:

IXIAN TM class V 1.5. EC Transmitter This is an evolving document. EC Transmitter IXIAN TM. Features

AMIK 200 / 201 Technical Data Sheet

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

DIN Rail Time & Twilight Switches

vacon 100 flow ac drives application manual

TLC3-BCR-U Series Thermostat

PROCESS & TEMPERATURE CONTROLLERS

RS Pro ENGLISH. Datasheet

INTAC Microprocessor Humidifier Controller

NT240 TIMER. PROGRAMMABLE TIMER INSTRUCTIONS MANUAL V20x A INTRODUCTION TIMER OUTPUTS SPECIFICATIONS AUXILARY SUPPLY OUTPUT INSTALLATION TIMER INPUTS

SPECIFICATION SWITCHING POWER SUPPLY BPS-300SP/2U 6-OUTPUT WITH ACTIVE PFC FUNCTION SINGLE POWER 300W BEST POWER SOLUTIONS, INC.

Device manual Multifunction display and evaluation system FX 360. Mode/Enter

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control

Strain Gauge Measuring Amplifier BA 662

DLVP A OPERATOR S MANUAL

DDC control of package units, heat pumps, unit ventilators, and other terminal unit applications

BATCHMATE 1500 Batch Control Computer Technical Bulletin

Transcription:

TCS2P125 Automatic Transfer Switch Control Unit for 1 Phase System Operation Manual Single Phase 2P 125 Amp Rated Voltage 250 Vac Patent Number : U.S. Pat. No. 7,557,683 KUTAI ELECTRONICS INDUSTRY CO., LTD. TEL : +886-7-8121771 FAX : +886-7-8121775 Website : www.kutai.com.tw Headquarters : No.3, Lane 201, Chien Fu St., Chyan Jenn Dist., Kaohsiung 80664, TAIWAN

TABLE OF CONTENTS Section Page SECTOIN 1 : INTRODUCTION 1.1 Safety Precautions... 3 1.2 Products Overview... 3 SECTOIN 2 : HARDWARE DESCRIPTION 2.1 Front Panel... 4 2.2 TCS2P125 Dimensions... 5 2.3 Panel Cut-Out For The TC-V2... 5 SECTOIN 3 : FUNCTION DESCRIPTION 3.1 General... 6 3.2 TDNE Setting... 6 3.3 TDEN Setting... 6 3.4 TDEC Setting... 6 3.5 TDES Setting... 6 3.6 TD-OFF Setting... 6 3.7 Plant Exerciser... 6 3.8 Over / Under Voltage Sensing... 6 3.9 Transfer Failure... 6 SECTOIN 4 : OPERATION 4.1 General... 7 4.2 AUTO Mode... 7 4.3 TEST Mode... 7 4.4 Programming Mode... 7 4.5 AC Voltage Display Adjustment... 7 4.6 Specification Summary... 7 4.7 System Setting Reference Table... 8 SECTOIN 5 : INSTALLATION INSTRUCTIONS 5.1 General... 9 5.2 Installation On The Plate... 9 5.3 TC-V2 Installation On The Door Panel... 10 SECTOIN 6 : TYPICAL WIRING 6.1 TCS2P125 Standard Wiring Diagram... 11 2 TCS2P125(TC-V2)

SECTION 1 : INTRODUCTION 1.1 Safety Precautions (WARNINGS) This manual covers the installation, operation and maintenance of the TCS2P125 Automatic Transfer Switch. It is intended for qualified personal only. WARNING High Voltages Can Kill. 1.2 Products Overview The TCS2P125 automatic transfer switch consist of two parts the TS2P125 switch and the TC-V2 electronic control unit : 1.2.1 TS125 Features The contacts on the Kutai TS2P125 transfer switch are class PC, this means that it is capable of making and withstanding short circuits but is not intended for breaking short circuit current. Rated operating Voltage:250 Vac Rated operating Current:125 Amps Number of poles:2p Coil operating voltage:110 / 220 Vac +/- 20% Compact size, light weight and low power consumption. Electrically operated and mechanically held. Manufactured using UL 94V-0 plastics. Adjustable time delay in OFF position when transferring. Designed for cell-phone repeaters, and many industrial and home ATS applications. 1.2.2 TC-V2 Digital Controller The TC-V2 digital control unit offers programming flexibility to customize the ATS to different customer requirements. The Controller : Monitor normal source for full phase over and under voltages. Monitor emergency source for single phase over and under voltages. Normal & emergency source voltage and frequency parameter display. TDEN, TDNE, TDEC and TD-OFF real time countdown display. Permit testing the transfer switch from the control panel. Permit system testing the transfer switch with or without load from the front panel. Built-in 1 to 4 weeks exerciser timer. Permit customer plant exerciser test with / without load on a preset period. Safely store customer / factory settings in permanent memory. Shows status and failure alarm LED s on the front panel. No need for PC connection and programming software. All settings can be made on site. Controller can be installed next to switch or separately on an enclosure panel. TS2P125 TC-V2 TCS2P125(TC-V2) 3

SECTION 2 : HARDWARE DESCRIPTION 2.1 Front Panel Load Connector Load Display Window Function Selector Manual Handle ATS Status Emergency Normal 4 TCS2P125(TC-V2)

2.2 TCS2P125 Dimensions (Unit : mm) 76.0 70.0 63.0 16.5 83.0 68.0 98.0 43.0 5.5 193.0 208.0 144.0 167.0 4.5 40.0 76.0 2.3 Panel Cut-Out for the TC-V2 (Unit : mm) 47.0±0.5 162.0±0.5 TCS2P125(TC-V2) 5

SECTION 3 : FUNCTION DESCRIPTION 3.1 General Operation of the TCS2P125 electronic control. 3.2 TDNE Settings TDNE provides a time delay when transferring from Normal to Emergency. Timing begins when the Emergency Source (generator) becomes available. TDNE:Adjustable from 0 to 99 seconds. 3.3 TDEN Settings TDEN provides a time delay when transferring from Emergency to Normal. This permits stabilization of the Normal Power before transferring back to normal. Timing begins when the Normal Power returns and becomes available and steady. TDEN:Adjustable from 0 to 99 seconds. 3.4 TDEC Settings TDEC timer keeps the generator running without load (Engine Cool-down) after the ATS transfer back to Normal Power. Timing begins when the transfer back to normal is completed. TDEC:Engine Cool-down - from 0 to 99 sec. 3.5 TDES Setting TDES is the time delay for Engine Start when the Normal Source voltage is in over or under-voltage (OV or UV). If power return to normal while timing, the TDES timer resets and starts again. When the exerciser is activated the exerciser LED (EX) on the right side of display flashes and turns on during the exercise period. 3.8 Over / Under Voltage Sensing The TC-V2 constantly monitors normal & emergency power. When power falls outside the programmed voltages this LED turns RED from GREEN and flashing to show OV / UV problems. Adjustable over voltage range:110 530 Vac Over voltage reset:when voltage falls below 10 Vac of the OV setting. Adjustable under voltage range:80 470 Vac Under voltage reset:when voltage exceeds 10 Vac of the UV setting. 3.9 Transfer Failure When a transfer is made the TS125 communicates it s position to the TC-V2 controller by using two small internal micro-switches, if this signal is not received, it will try switching 3 more times every 2 seconds or until the connection is made. A flashing light indicator and a FAIL signal displayed an incomplete transfer and that the ATS mechanism or wiring is defective. If the ATS fails, the TC-V2 controller stops all ATS functions and starts flashing until the failure is corrected and the control is reset. To reset the transfer fail alarm: 1. Manually move the ATS to the correct position. 2. Press any button (Auto, Program or Test) on the front panel to reset the alarm. TDES:Adjustable from 0 to 30 seconds. 3.6 TD-OFF Setting Time Delay on OFF this timer keeps the switch in the center neutral OFF position (completely disengaged) before transferring to the other side. You can preset the switch in Neutral or OFF from 0 to 18 seconds (Normally 2 to 3 sec). TD-OFF:Adjustable from 1 to 20 seconds. 3.7 Plant Exerciser This feature provides for automatic test operation of the generator. The interval is fixed at once per 1 to 4 weeks with a specific test day and time. The exerciser can be set for either testing with load or without load. 6 TCS2P125(TC-V2)

SECTION 4 : OPERATION 4.1 General This section specifically describes the operation and functional use of the TC-V2 controller. 4.2 AUTO Mode In AUTO the TC-V2 controller automatically transfer and retransfers from source to source as directed by the pre-programmed instructions. In AUTO the controller monitors the condition of both normal and standby power sources providing the logic for the transfer operation. 4.3 TEST Mode The TC-V2 is equipped with a test pushbutton that simulates the loss of normal source. Pushing the Test key the TC-V2 will execute a test on the ATS. The TDES and TDNE programmed time delays will be performed as part of the test. There are two test modes: Testing with load Testing without load 4.4 Programming Mode The TC-V2 controller is fully programmable from the front panel when in the Program Mode. The build-in program buttons have multiple functions: Real time clock displaying Programming mode operating To enter programming mode, push and hold Program button for 10 seconds. In the first 10 seconds the screen showing internal real time clock and then the word Vr 1.0 will appears on the front display window for 2 seconds indicating the version of the software. At this time start a line by line programming sequence. To advance to the next line, push the Program button on the front panel. To change each line s programming parameters, press the increase ( ) and decrease ( ) buttons. When pressing and releasing the ( ) or ( ) key the displayed parameter can be increased or decreased by one. The parameter will continue to scroll if the ( ) or ( ) button is pressed and not released. If you like to return to factory settings, stay in programming mode and simultaneously press all 3 buttons ( ), ( ) and Program buttons for 4 seconds. The TC-V2 will now automatically program itself to factory settings and the word Au.Po will appear on the display window. 4.5 AC Voltage Display Adjustment The TC-V2 controller continually monitors normal & emergency power displaying volts and frequency on the front panel. (The voltage value is calibrated and adjusted at the factory). But when the ATS works on high capacitive or inductive loads the waveform distortion may cause the displayed to have slight differences from the users measuring instrument. You can adjust the display value to equal to the users own instruments, by entering the setting mode to perform adjustment the parameter. Once the adjustment is completed, the voltage sensing value will increase or decrease according to the adjusted value and display it on the screen. The TC-V2 over and under voltage protection follow the adjusted value as the actual system voltage and perform the monitoring according to the new parameter. See Table lines 2, 3, 4, 5 for voltage display setting. 4.6 Specification Summary ITEM Rated Voltage Rated Current Rated Frequency Poles Switch Type ATS Class Operation Life Transfer Current Remote Start Contactor N & E On Contactor Power Consumption Operating Temperature Storage Temperature SPECIFICATION 250 Vac 125 Amp 50/60 Hz 2P Double Throw Class PC Over 6000 Times W/L 3.0A @ 220 Vac 6.0A @ 110 Vac 6A @ 277 Vac Max 7A @ 250 Vac Max < 1W -10 to +70 C -20 to +80 C Operating Humidity 0 to 95% Weight 1.8 kg +/- 2% Always push the Program button to advance to the next line or until the word End appears on the screen. To immediately end the programming mode, you simply push the Program button for 4 seconds. Then the word End shows on the screen indicating the end of the programming mode. TCS2P125(TC-V2) 7

4.7 System Setting Reference Table ITEM DESCRIPTION SETTING FACTORY SETTING 1 Is this ATS operating in 1 Phase or 3 Phase? 01 1 Phase 02 3 Phase 02 2 3 4 5 Normal power VL12 voltage display adjustment setting Normal power VL23 voltage display adjustment setting Normal power VL31 voltage display adjustment setting Emergency power VL12 voltage display adjustment setting -99 99 V 00-99 99 V 00-99 99 V 00-99 99 V 00 6 TDNE Time Delay Normal to Emergency 00 99 sec. 10 sec. 7 TDEN Time Delay Emergency to Normal 00 99 sec. 10 sec. 8 TDES Time Delay Engine Start 00 30 sec. 5 sec. 9 TDEC Time Delay Engine Cool-down 00 99 sec. 60 sec. 10 TD-OFF Time Delay on OFF position 01 20 sec. 5 sec. 11 Normal source over voltage setting 11 53 ( 110 530V ) 25 (250V) 12 Normal source under voltage setting 8 47 ( 80 470V ) 18 (180V) 13 Time delay if there is a problem with normal source voltage output 00 99 sec. ( 0 = Without volt monitor function ) 10 sec. 14 Standby source over voltage setting 11 53 ( 110 530V ) 25 (250V) 15 Standby source under voltage setting 8 47 ( 80 470V ) 18 (180V) 16 Time delay if there is a problem with standby source voltage output 00 99 sec. ( 0 = Without volt monitor function ) 10 sec. 17 Current day of week setting 1 7 ( Monday to Sunday ) current 18 Current hour setting 00 23 current 19 Current minute setting 00 59 current 20 Plant exerciser test day of week 1 7 ( Monday to Sunday ) 6 21 Plant exerciser hour 00 23 12 22 Engine run time on exerciser 00 60 min ( 0 = Without exerciser function ) 00 23 Exerciser cycle 01) Once a week 02) Once every 2 weeks 03) Once every 3 weeks 04) Once every 4 weeks 24 Plant exerciser test with or without load 01) Without load 02) With load 01 25 Plant manual test with or without load 01) Without load 02) With load 02 01 8 TCS2P125(TC-V2)

SECTION 5 : INSTALLATION INSTRUCTIONS 5.1 General The TC-V2 controller is modular and is designed for installation next to switch or on the front door panel. A longer harness is required for door installation. 5.2 Installation On The Plate STEP-1 STEP-3 STEP-2 STEP-4 TCS2P125(TC-V2) 9

5.3 Installation On The Door Panel STEP-1 STEP-3 STEP-2 STEP-4 10 TCS2P125(TC-V2)

CN1-4 CN1-3 CN1-2 CN1-11 CN1-6 CN1-10 CN1-9 YELLOW ORANGE RED PINK BLUE BLACK WHITE CN1-1 BROWN CN2-12 CN2-4 CN2-3 CN2-2 CN2-11 CN2-6 CN2-10 CN2-9 CN2-1 SECTION 6 : TYPICAL WIRING 6.1 TCS2P125 Standard Wiring Diagram (110 or 220V) #NLS>>Normal Auxiliary Switch #ELS>>Emergency Auxiliary Switch LOAD L1 L2 TS2P125 NORMAL N1 SOURCE N2 CS1 CS1 CS2 CS2 E1 EMERGENCY E2 SOURCE NLS ELS 220V COIL CN1 Connector CN1-12 RED/WHITE CN2 Connector TC-V2 Controller Remote Start TCS2P125(TC-V2) 11