A DUMMIES GUIDE TO GROUND FAULT PROTECTION

Similar documents
Upgrading Your Electrical Distribution System To Resistance Grounding

Webinar: An Effective Arc Flash Safety Program

Effective System Grounding

2 Grounding of power supply system neutral

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Grounding System Theory and Practice

Grounding for Power Quality

EPG. by Chris C. Kleronomos

high RESISTANCE GROUNDING SYSTEM the power to protect www. ElectricalPartManuals. com Instruction Manual C-102

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Our Brands. Where we are?

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

high RESISTANCE GROUNDING SYSTEM the power to protect SLEUTH Instruction Manual C-408EM

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Summary of the Impacts of Grounding on System Protection

Optimal neutral ground resistor rating of the medium voltage systems in power generating stations

TECHNICAL INFORMATION

Grounding Recommendations for On Site Power Systems

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

> the power to protect. Ground Fault Protection on Ungrounded and High Resistance Grounded Systems. Application Guide.

Electrical Arc Hazards

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

FERRORESONANCE SIMULATION STUDIES USING EMTP

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

TN, TT & IT Earthing Arrangements

Safety through proper system Grounding and Ground Fault Protection

Specialists in HV and MV test and diagnostics. Testing in Substations

ARC FLASH HAZARD ANALYSIS AND MITIGATION

SUBJECT CODE : EE6702 SUBJECT NAME: Protection & switchgear STAFF NAME : Ms.J.C.Vinitha

Industrial and Commercial Power Systems Topic 7 EARTHING

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Protecting Large Machines for Arcing Faults

Power Quality Basics. Presented by. Scott Peele PE

Ground Fault Protection on Ungrounded and High Resistance Grounded Systems APPLICATION GUIDE

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc.

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Busbars and lines are important elements

Short Circuit Current Calculations

Continued from Part 1 Rules 1 25.

System Protection and Control Subcommittee

1C.6.1 Voltage Disturbances

System grounding of wind farm medium voltage cable grids

Wisconsin Contractors Institute Continuing Education

Cause, Effect & Mitigation Strategies

Los A LA-UR Los Alamos National Laboratory Los Alamos, New Mexico 87545

GOOD GROUNDING PRACTICES. A Brief Introduction to the Basics of Electrical Grounding for Power Systems

3Ø Short-Circuit Calculations

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Education & Training

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

Overvoltage and undervoltage. Dr Audih 1

Variable Transformers Product Design & Engineering Data

Arc Flash Hazard. Can HRG Technology play a role in prevention?

Circuit Breaker Based Feeder Pillar

Končar TMS - Bushing monitoring

2014 NEC Changes Part 1

Earthing of Electrical Devices and Safety

THREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES

HARMONICS CAUSES AND EFFECTS

EE 1402 HIGH VOLTAGE ENGINEERING

ACTIVE CURRENT INJECTION METHOD FOR LIMITING GROUND FAULT CURRENT HARMONICS IN UNDERGROUND COAL MINES

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Partial Discharge, Survey or Monitor?

TABLE OF CONTENT

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Fundamentals of Power Quality

Preface...x Chapter 1 Electrical Fundamentals

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Practical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems

How to maximize reliability using an alternative distribution system for critical loads

Why the IT system is often the best choice for power supply systems of all types

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority

VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK

Ground Fault Location. Turbo Sleuth. Instruction Manual

Electromagnetic interference at the mains ports of an equipment

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Generation Interconnection Requirements at Voltages 34.5 kv and Below

MVDC Grounding and Common Mode Current Control

Short-Circuit Current Calculations

Notes 1: Introduction to Distribution Systems

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

MIT510/2, MIT520/2 and MIT1020/2

Key factors to maintaining arc flash safety

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

Instruction Manual. Description Calibration. Excitation Sensor and Reverse Power Relay

LOW-RESISTANCE grounding resistors (LRGs) appear

WHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems

Introduction to Harmonics and Power Quality

GFL-1000 User Manual Ground Fault Locator

The Isolator/Surge Protector (ISP)

IV. Three-Phase Transfomers

Transcription:

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding means the connection of earth ground to non current carrying conductive materials such as conduit, cable trays, junction boxes, enclosures and motor frames. System grounding means the connection of earth ground to the neutral points of current carrying conductors such as the neutral point of a circuit, a transformer, rotating machinery, or a system, either solidly or with a current limiting device. Figure 1 illustrates the two types of grounding. Figure 1 What is a Grounded System? Grounded System a system in which at least one conductor or point (usually the middle wire or neutral point of transformer or generator windings) is intentionally grounded, either solidly or through an impedance. IEEE Standard 142-1991 1.2.

Are there different types of System Grounding? The types of system grounding normally used in industrial and commercial power systems are: Solid grounding Low-resistance grounding High-resistance grounding Ungrounded IEEE Std 242-1986 7.2.1 What is the purpose of System Grounding? System grounding, or the intentional connection of a phase or neutral conductor to earth, is for the purpose of controlling the voltage to earth, or ground, within predictable limits. It also provides for a flow of current that will allow detection of an unwanted connection between system conductors and ground [a ground fault]. What is a Ground Fault? A Ground Fault is an unwanted connection between the system conductors and ground. Why are Ground Faults concern? Ground faults often go unnoticed and cause havoc on plant production processes. Shutting down power and damaging equipment, ground faults disrupt the flow of products leading to hours or even days of lost productivity Undetected ground faults pose potential health and safety risks to personnel. Ground faults can lead to safety hazards such as equipment malfunctions, fire and electric shock. Ground faults cause serious damage to equipment and to your processes. During a fault condition, equipment can be damaged and processes shut down, seriously affecting your bottom line. I have Over-current protection. Do I need additional Ground Fault Protection? The over-current protection will act to interrupt a circuit for currents for which it was designed and set to operate. However, some ground faults, particularly low level arcing faults, will produce significant damage and create a fire- ignition source without ever reaching the level necessary to activate the over- current protective device. What is an ungrounded system? Electrical power systems which are operated with no intentional ground connection to the system conductors are generally described as ungrounded. In reality, these systems are grounded through the system capacitance to ground. Why do people choose to operate an ungrounded system? Two principal advantages are attributed to ungrounded systems. The first is operational: The first ground fault on a system causes only a small ground current to flow, so the system may be operated with a ground fault present, improving system continuity. The second is economic: No expenditures are required for grounding equipment What does IEEE say about ungrounded systems? Ungrounded systems employ ground detectors to indicate a ground fault. These detectors show the existence of a ground on the system and identify the faulted phase, but do not locate the ground, which could be anywhere on the entire system. If this ground fault is intermittent or allowed to continue, the system could be subjected to possible severe over-voltages to ground, which can be as high as six or eight times phase voltage. This can puncture insulation and result in additional ground faults. A second ground fault occurring before the first fault is cleared will result in a phase-to-ground-to-phase fault, usually arcing, with current magnitude large enough to do damage, but sometimes too small to activate over-current devices in time to prevent or minimize damage.

Ungrounded systems offer no advantage over high-resistance grounded systems in terms of continuity of service and have the disadvantages of transient over-voltages, locating the first fault and burn downs from a second ground fault. IEEE 242-1986 7.2.5 Why Consider Grounding your System? The intentional connection of the neutral points of transformers, generators and rotating machinery to the earth ground network provides a reference point of zero volts. This protective measure offers many advantages over an ungrounded system, including: Reduced magnitude of transient over-voltages Simplified ground fault location Improved system and equipment fault protection Reduced maintenance time and expense Greater safety for personnel Improved lightning protection Reduction in frequency of faults. What is a Solidly Grounded System? A solidly grounded system is one in which the neutral points have been intentionally connected to earth ground with a conductor having no intentional impedance. This partially reduces the problem of transient over- voltages found on the ungrounded system, provided the ground fault current is in the range of 25 to 100% of the system three phase fault current. However; if the reactance of the generator or transformer is too great, the problem of transient overvoltages will not be solved. Is Solidly Grounded Safer than Ungrounded? While solidly grounded systems are an improvement over ungrounded systems, and speed the location of faults, they lack the current limiting ability of resistance grounding and the extra protection this provides. The destructive nature of arcing ground faults in solidly grounded systems is well known and documented and are caused by the energy dissipated in the fault. What does IEEE say about solidly grounded systems? The solidly grounded system has the highest probability of escalating into a phase-to-phase or threephase arcing fault, particularly for the 480 and 600V systems. A safety hazard exists for solidly grounded systems from the severe flash, arc burning and blast hazard from any phase-to-ground fault. IEEE Standard 141-1993

What is a Resistance Grounded System? There are two broad categories of resistance grounding: low resistance and high resistance. In both types of grounding, the resistor is connected between the neutral of the transformer secondary and the earth ground. How do I determine what size of Neutral grounding Resistor I require? The resistor must be sized to ensure that the ground fault current limit is greater than the system s total capacitance-to-ground charging current. If not, then transient over-voltages can occur. What is Low Resistance Grounding? Low resistance grounding of the neutral limits the ground fault current to a high level (typically 50 amps or more] in order to operate protective fault clearing relays and current transformers. These devices are then able to quickly clear the fault, usually within a few seconds. The importance of this fast response time is that it: Limits damage to equipment, Prevents additional faults from occurring, Provides safety for personnel, Localizes the fault. The limited fault current and fast response time also prevent overheating and mechanical stress on conductors. However, like the solidly grounded neutral system, the circuit must be shut down after the first ground fault. Low resistance grounding resistors are typically rated 400 amps for 10 seconds, and are commonly found on medium and high voltage systems. What is High Resistance Grounding? High resistance grounding of the neutral limits the ground fault current to a very low level (typically under 25 amps). It is used on low voltage systems of 600 volts or less, under 3000 amps. Why Consider Resistance Grounding? Resistance grounding is by far the most effective and preferred method. It solves the problem of transient over-voltages, thereby reducing equipment damage. It accomplishes this by allowing the magnitude of the fault current to be predetermined by a simple ohms law calculation. Thus the fault current can be limited, in order to prevent equipment damage. In addition, limiting fault currents to predetermined maximum values permits the designer to selectively co-ordinate the operation of protective devices, which minimizes system disruption and allows for quick location of the fault.

What does IEEE say about High Resistance Grounded systems? High-resistance grounding helps insure a ground-fault current of known magnitude, helpful for relaying purposes. This makes it possible to identify the faulted feeder with sensitive ground-fault relays. IEEE Std 242-1986 7.2.4 Highresistance grounding provides the same advantages as ungrounded systems yet limits the steady state and severe transient over-voltages associated with ungrounded systems. There is no arc flash hazard, as there is with a solidly grounded system, since the fault current is limited to approximately 5A. IEEE Std 141-1993 7.2.2 Why limit the current through Resistance Grounding? 1) to reduce burning and melting effects in faulted electric equipment, such as switchgear, transformers, cables and rotating machines. 2) to reduce mechanical stresses in circuits and apparatus carrying fault currents 3) to reduce electric-shock hazards to personnel caused by stray ground fault currents in the ground return path 4) to reduce arc blast or flash hazard to personnel who may have accidentally caused or who happen to be in close proximity to the fault current 5) to reduce the momentary line-voltage dip occasioned by the occurrence and clearing of a ground fault 6) to secure control of transient over voltages while at the same time avoiding the shutdown of a faulty circuit on the occurrence of the first ground fault Do I have to shutdown my system to look for a fault? By limiting the ground fault current, the fault can be tolerated on the system until it can be located, and then isolated or removed at a convenient time. This permits continued production, providing a second ground fault does not occur If I have a fault and a second fault appears, what happens? Should a second ground fault occur on another phase before the first ground fault is removed, a line-to-line fault is created which can result in significant damage and a hazard to personnel. Is there any protection against second fault damage? The DSP relay system is designed to provide an alarm but not trip when one ground fault occurs on the system thus retaining system continuity. The relay does provide phase and feeder indication as well as fault magnitude. The DSP is the only relay to offer second fault protection through the SIFT system (Selective Instantaneous Feeder Trip). This enables the user to prioritise the feeders and upon the occurrence of a second fault on a different phase to select which feeder will instantaneously trip.

I have heard that pulsing makes fault finding faster, what is pulsing? Through the use of a specially designed resistor, the fault current is changed to provide a distinct signal that can be traced by qualified personnel to facilitate fault finding. This can often reduce the time required from hours to minutes. What if I do not have qualified personnel who can locate or clear the fault? I-GARD has partnered up with service organizations who have received specialized training and as qualified I-GARD Integrators have the necessary experience, training and products to assist you with fault location and clearing. Contact I-GARD to find the Integrator nearest you. How can I learn more before making a decision on what I need? Technical Seminars on Ground Fault Protection are offered by I-GARD, contact us!