Annex: HVDC Code comments

Similar documents
FNN comments on NC HVDC submitted to ENTSO E

SELECTING NATIONAL MW BOUNDARIES

Parameters related to voltage issues

Using Fault Current Limiting mode of a Hybrid DC Breaker

Parameters related to frequency stability

DRAFT PROPOSAL FOR NC HVDC REQUIREMENTS OF GENERAL APPLICATION

FREQUENCY and VOLTAGE, ranges and durations

Network Code for HVDC Connections and DC-connected Power Park Modules Requirement Outlines

DRAFT PROPOSAL FOR STORAGE CONNECTION REQUIREMENTS

ENTSO-E Draft Network Code on High Voltage Direct Current Connections and DCconnected

Network Code for HVDC Connections and DC-connected Power Park Modules Explanatory Note

PROPOSAL FOR NC RFG REQUIREMENTS OF GENERAL APPLICATION

INCIDENTS CLASSIFICATION SCALE METHODOLOGY

Fault Ride Through Technical Assessment Report Template

TABLE 1 COMPARISION OF ENTSO-E RfG TO GB GRID CODE

PROPOSAL FOR NC RFG REQUIREMENTS OF GENERAL APPLICATION

Automatic connection/reconnection and admissible rate of change of active power

DC Line Protection for Multi-terminal (MT)- HVDC Systems

This paper has been published in the 2017 IEEE Manchester PowerTech conference proceedings.

A New Network Proposal for Fault-Tolerant HVDC Transmission Systems

U I. HVDC Control. LCC Reactive power characteristics

Partial Power Operation of Multi-level Modular Converters under Subsystem Faults

Requirements for Generators European Network Code High Level Implementation Issues

each time the Frequency is above 51Hz. Continuous operation is required

Modeling and control of HVDC grids: a key challenge for the future power system

TECHNICAL OVERVIEW OF IMPACTING REQUIREMENTS FOR THE CATEGORIZATION OF THE POWER GENERATING MODULES

Open Access Simulation Toolbox for Wind Power Transmission using High Voltage Direct Current Technology

Introduction to HVDC in GB. Ian Cowan Simulation Engineer 12 March 2018

This document is a preview generated by EVS

TECHNICAL SPECIFICATION

Recommendations for Harmonic and Power Measurements in Electrical Networks

ZERO PHASE SEQUENCE VOLTAGE INJECTION FOR THE ALTERNATE ARM CONVERTER

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS

Authors and affiliations. Introduction. Approach

High Voltage DC Transmission 2

Fault current contribution from PPMS & HVDC

USE OF HVDC MULTI TERMINAL OPTIONS FOR FUTURE UPGRADE OF THE NATIONAL GRID

The EU Network Code on Requirements for Generators A Summary

Digital Object Identifier: /PTC URL:

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Indication of Dynamic Model Validation Process

Considerations and Recommendations for the Harmonisation of Under Frequency Loadshedding Schemes in Multi Zone Meshed Grids

p. 1 p. 6 p. 22 p. 46 p. 58

MMC Design Aspects and Applications. John Strauss Siemens AG.

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

BOOST PFC WITH 100 HZ SWITCHING FREQUENCY PROVIDING OUTPUT VOLTAGE STABILIZATION AND COMPLIANCE WITH EMC STANDARDS

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

DC current interruption tests with HV mechanical DC circuit breaker

HVDC Solutions for Integration of the Renewable Energy Resources

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

GB FREQUENCY HVDC FREQUENCY RESPONSE PARAMTERS HVDC CONNECTIONS (TITLE II)

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

Harmonic Distortion Levels Measured at The Enmax Substations

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Digital Fault Recorder Deployment at HVDC Converter Stations

IMPORTANCE OF VSC IN HVDC

Fundamental Concepts of Dynamic Reactive Compensation. Outline

Voltage Stability Assessment through a New Proposed Methodology

Energy Networks Association

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

RfG Implementation Fault Ride Through

Overvoltage Phenomena in Offshore Wind Farms Following Blocking of the HVDC Converter

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

Deleted: 9 4 anuary ... [1] Deleted: much more. Formatted ... [2] Formatted Table. Formatted: Indent: Left: 0.06 cm

RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

Fast Frequency Support Control in the GB Power System using VSC-HVDC Technology

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

INITIAL RfG FREQUENCY PARAMETER SELECTION. BASED ON DRAFT RfG VALUES. Requirement Range Suggested GB Value Comments

System Requirements for Wind Farms and Distributed Generation. Giuseppe Di Marzio

Selective Wave-Front Based Protection Algorithm for MTDC Systems

Max voltage in 400 kv Networks

Application of Model Predictive Control in PV-STATCOM for Achieving Faster Response

The University of Nottingham

Deliverable 16.1: Definition and Specification of Test Cases

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

Power Transmission of AC-DC Supply in a Single Composite Conductor

B.Tech Academic Projects EEE (Simulation)

P3 Policy 3: Operational Security

Project acronym: Multi-island

Robustness Evaluation of Fast Breaker Failure Backup Protection in Bipolar HVDC Grids

AEIJST - July Vol 3 - Issue 7 ISSN A Review of Modular Multilevel Converter based STATCOM Topology

Digital Object Identifier: /PESMG URL:

Voltage Source Converter Modelling

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

Generation and Load Interconnection Standard

Facilitating Bulk Wind Power Integration Using LCC HVDC

Compliance activities

Wide Area Control Systems (1.4) Mani V. Venkatasubramanian Washington State University (

System Operability Framework 2014

Analysis of the Effectiveness of Grid Codes for Offshore Wind Farms Connected to Onshore Grid via VSC-Based HVDC

Company Directive POLICY DOCUMENT: SD4/7. Relating to 11kV and 6.6kV System Design

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/

SYSTEM MONITORING FAULT RECORDING

FREQUENTLY ASKED QUESTIONS

Transcription:

EnergyVille Thor Park 8300 Poort Genk 8300 3600 Genk Annex: HVDC Code comments Dr. Geraint Chaffey, Dr. Willem Leterme, Firew Dejene, Mian Wang, Alejandro Bayo Salas, Thomas Roose, Ozgur Can Sakinci, prof. Jef Beerten, prof. Dirk Van Hertem Department of electrical engineering (ESAT), Research Group Electa, KU Leuven Electrical networks group, EnergyVille Contact: Prof.dr.ir. Dirk Van Hertem (dirk.vanhertem@esat.kuleuven.be) Prof.dr.ir. Jef Beerten (jef.beerten@esat.kuleuven.be) Introduction This letter provides comments on the public consultation on the Elia grid code for HVDC. Given the experience of our research group in the field, we found it important to highlight the possible issues with the current version as proposed by Elia. We are aware that the current version builds on the ENTSO-E grid code, and no fundamental changes to that grid code are made. Some of the comments made below relate indirectly to the ENTSO-E grid code, or to Elia s interpretation of this code. We have also included some limited comments to the DCC code. We would be happy to provide further details on the statements made below when deemed necessary. General comments As a general note, the grid code is specifically favouring the installation of one technology, the voltage source converter (VSC). However, an LCC-based HVDC installation can also be considered for some of the HVDC-link schemes defined in the code. This is specifically seen in those articles defining any reactive and active power controllability with specified times because the LCC is slower than the VSC. Also, this is applicable to the FRT or voltage control requirements. If the requirements are defined as now, this will increase the cost of an LCC-based HVDC link because of the required use of more advanced technologies to compensate the reactive power, which might not otherwise be necessary. Particularly, most of the LCC-based HVDC links installed up to date do not make use of such reactive power installations - this is based on experience from this kind of installation developed for more than 20 years. More generally, technology is evolving, and new types of technology are continuously developed, potentially leading to completely new converter types that behave fundamentally different from traditional converters. For example, the dynamic behaviour of the 2-level converter differs from the MMC, and future converter types might differ also. This might lead to cost reductions (e.g. Diode rectifier units, DRU, for offshore connections and MMC converters with DC fault

blocking capability). These evolutions might lead to a significant decrease of cost (DRU) or increase of possibilities (FB MMC). As a second note, some requirements are interacting with ancillary services markets (voltage control, black start, frequency control and, probably, a future synthetic inertia market). Despite the technical capabilities of the technology to fulfil the technical requirements, the future HVDC station will usually be a TSO-owned asset and the use of those capabilities will interact in the mentioned markets, thereby potentially adversely affecting other installations participating in these markets. As ancillary services markets are expected to undergo several changes in the upcoming years, it would be prudent to avoid creating a grid code that might hinder the development of such markets. Furthermore, it is important to note that the grid code should be equally open to TSO projects as to merchant projects. We feel the latter might be overregulated or could be potentially blocked due to the possibility to create too stringent limits. Page 7: 'Current HVDC knowledge and translation of this knowledge in general or site-specific requirements'. We believe the maturity of HVDC is grossly underestimated. Elia's HVDC experience might be limited still, but it cannot be said that current HVDC experience/knowledge is limited. HVDC systems have been in operation for over 60 years. HVDC VSC is not experimental - perhaps this was true when the ENTSO-E grid code was drafted, but it is not the case today. Elia Group including 50Hertz has HVDC experience. Academic research is not in the early stages, quite the contrary: although specific research is still needed, there is much work already done. One example of this: it should be considered how existing knowledge regarding AC/DC interactions might be extended and acted upon. Specific comments on the grid code and comments on particular articles Reference to RSO can be removed throughout. Are these regional operation centres, and are they the same as an RST? Reference to relevant TSO throughout unnecessary. 2.1.2.4: 10 ms seems arbitrary (no technical requirement to be so fast), although we are aware of the fact that the number comes from the ENTSO-E code. 2.1.2.5 Active power reversal The requirement of active power reversal in less than 2 s may limit the HVDC technologies which can be used. 2.1.2.6: Is it necessary to always have automatic remedial actions in the grid code? Seems that this could be too strict. Aren't these ancillary services? There is some technical requirement for this within the grid code - doesn't this interfere with the ancillary services / markets? If it is a market product, activation should be done according to the market rules.

2.1.3.2: Synthetic inertia - Is this really 'site specific'? Not a local problem, but a system problem - perhaps project specific? 2.1.4: Comment on ancillary services as above (comment on 2.1.2.6). 2.1.6: 2.2.1.4: To allow for different options towards multi-terminal extension, the parameter specify limit for maximum loss of active power could be extended with an interval during which this active power is lost. The interval specification during which the active power is lost, is considered in standardization working groups (CENELEC) and is an ongoing topic within research (Promotion, Abedrabbo et al.). (CENELEC) CENELEC TC 8X/WG 06, "System Aspects of HVDC Grids," 2016. (Promotion) Promotion WP 4, D4.2 Broad comparison of fault clearing strategies for DC grids, Final Report, 2017 (Abedrabbo et al) M. Abedrabbo et al., "Impact of DC grid contingencies on AC system stability," in Proc. 13th IET International Conference on AC and DC Power Transmission (ACDC 2017), Manchester, UK, Feb. 2017, 7 pages. This is a significant fault ride though period - 3 seconds is a very long time and perhaps this could block technology. Why is the period taken to be 3 seconds? Technology-wise, this is possible, but it comes at a cost. Compared to other grid codes, this seems a stringent limit, and quite slow (below a comparison to Tennet is included a European TSO with extensive experience with HVDC). It would be preferable to reduce the mandatory recovery time and have longer conditions in site specific cases. [Tennet grid code - High and extra high voltage 2015] 2.2.5.2 Reactive power control mode (b) STATCOM mode: Under given events, such as a DC link fault, this requirement is not possible unless the use of a very specific converter configuration (not available with all HVDC

manufacturers) or the installation of additional equipment to both disconnect the line and supply voltage to the converter DC side. 'All previously specified' is not clear. Is this 'in this article'? 2.2.5.4: 'of the change of reactive power' - we assume that this relates to the time constant of the controllers, but it must be clarified. 2.2.5.5: 'range of 99%' - this should be ±1%. This is very unclear and should be rephrased. 2.2.6.1: What is 'low and high voltage' - is this defined? 2.2.7.1: As a general practice in industry, it is the responsibility of the TSO to ensure that the harmonic voltage distortion level is below the planning level at all nodes where customers are connected. This is a practice used in all the international IEC standards or IEEE recommended practices, see IEC 61000 or IEEE 519-2014. In both documents, distribution equipment is only required to ensure a given harmonic current distortion level below to the defined limits. The code states that 'the level of allowed distortion or fluctuation of the supply voltage on the network at the connection point of a transmission-connected demand facility will not alter from what is stated in article 46 of the current Federal Grid Code'. However, the level of allowed distortion of the supply voltage is set by the TSO harmonic planning levels and, consequently, it is a responsibility of the TSO. This can be controlled, as it is typically the case, by allowing a lower maximum admissible harmonic current injection limits from the load installation. However, this article is directly giving the responsibility of the harmonic voltage distortion to the load, against international standards and practices. 2.3.1.1: How does this differ from 2.2.1.4? 2.3.1.5 FRT capability Point (a) is defining a very specific control philosophy to the converter. The way how the converter is controlled (or whether it has a current controller) should be a decision of the manufacturer based on its experience and practice. The requirement should only request for the controllability of positive and negative sequence components during a fault instead of 'there shall be separate positive and negative sequence current controllers'. As an additional note, during an asymmetrical fault, it may be also desired to control the negative sequence of the voltage (not stated here). For this reason, we suggest to define it more generically to avoid giving an unfair competitive advantage to certain manufacturers. Point (c) is not clear because the HVDC converter needs to make use of a second harmonic current in order to control the negative sequence during the asymmetrical fault. We imagine that the objective of this point is to require that this event does not result in any transfer of a distortion through the DC link, but this is not clear from the text. However, as the grid code is only related to the interaction with the AC side, the operation at the DC side should not be defined here. 2.4. Requirements for control - Network characteristics We find that the code should give some indications about network characteristics in order to already face, obtain and prepare the models to be used in future connections. Particularly, different interactions and dynamics from different equipment will have an influence in the network characteristics at the relevant point of connection. The code should define the type of studies which need to be conducted in order to allow and request the necessary models to all

the stakeholders as specified in Article 27. These network characteristics must contain, but not be limited to, short circuit analysis, phasor-domain, voltage stability and harmonic studies. As a particular experience in our research group, the harmonic network models must be well represented in a sufficiently wide frequency spectrum, extended to frequencies higher than the limits defined at present in IEC 61000 standards. We consider that by setting some guidelines here, efforts and the necessary improvements in developing the necessary tools and methodologies will be triggered. However, by setting now vague indications, the relevant external parties (tool developers, manufacturers, or operators...) will not have the incentive to provide and conduct necessary modifications and improvements. 2.4.1.1: Clarify voltage constraints in the last sentence - what level is this? This is unclear. Deviation should be maximum 5%! Please note that it is also wrongly phrased in the ENTSO-E grid code. 2.4.6.2 Network characteristics: What are the items that should be specified? Contain but are not limited to: harmonic impedance of the transmission grid up to sufficiently high frequencies. This is an unusual specification to include in a grid code. 2.5.1.1: 'Proof that the system owner will demonstrate that protection system has not been used in other similar installations'. This is overly restrictive and should be deleted. 2.5.2.1: 3 months seems very slow for Elia to review a protection and control scheme. This should be project specific. Section 3: There are many proposals for the technology for future wind farm connections with HVDC (e.g. Diode Rectifier Unit ). This requirement could be blocking novel technologies and should be restricted. Different technologies fundamentally change this whole section. 4.1.1.1: Why would the TSO set the control hierarchy? Again, this raises questions on implicitly favouring manufacturer-specific implementations. What level of controller is meant heredispatch? This should be clarified or removed. 4.1.1.2: Operation should follow the other grid codes. More specifically, it is expected that the HVDC link is either a regulated link, and will follow the ENTSO-E network codes on system operations, emergency and restoration, Forward Capacity allocation, electricity balancing and Capacity allocation & Congestion Management. 4.1.4.1: RST - what is this? Should this be RSO? Under what conditions are these models provided? Should this be under NDA? Mutual agreement on how detailed this should be of sufficient detail? HVDC non-exhaustive requirements POWER QUALITY - 'specify voltage and distortion limits' In this document, as well in other grid codes, such as the DCC code, harmonic limits are defined to the connectee by the maximum allowable voltage distortion limits. As a general practice in the industry, it is the responsibility of the TSO to ensure that the harmonic voltage distortion

level is below the planning level at all nodes where customers, or other types of connectees, are connected. This is a practice used in the international IEC standards or IEEE recommended practices, see IEC 61000 or IEEE 519-2014. In both documents, connected installations are only required to ensure a given harmonic current distortion level below to the defined limits. The DCC code states that 'the level of allowed distortion or fluctuation of the supply voltage on the network at the connection point of a transmission-connected demand facility will not alter from what is stated in article 46 of the current Federal Grid Code', The HVDC code is giving the same message by 'specify voltage and distortion limits'. However, the level of allowed distortion of the supply voltage is set by the TSO harmonic planning levels and, consequently, it is a responsibility of the TSO. This can be controlled, as it is typically the case, by allowing a lower maximum admissible harmonic current injection limits from the installation. However, this requirement is directly giving the responsibility of the harmonic voltage distortion to the connected installation, against all international standards and practices. HVDC system owner Throughout the text, the description 'HVDC system owner' is used to describe the technology vendor and manufacturer. This is very confusing because the vendor does not own and utilise the installation, nor does it control the requested features to provide ancillary services in the AC system. DCC Code 1.2. HV requirements The code details that HV equipment has proven the capability to withstand the required voltage levels in the article. However, it is not clear whether all the different load technologies could withstand and operate correctly under the required voltage levels. Or, this requirement would result in overrating the installation. As a general practice, operators hold the responsibility to ensure sufficient quality in the voltage in order to supply loads in the most effective way. Therefore, this requirement is forcing installations to withstand the maximum levels defined for HV equipment. Whereas, from the connectees point of view, it should be the TSO who must operate within the voltage limits that connectees can withstand. 1.4.2 Reactive requirements This requirement decreases the maximum reactive import at demand points because of the reactive consumption of the power transformer, which is an asset of the TSO. Consequently, the code is initially locating the need of investing the necessary equipment to compensate the reactive consumption of a TSO-owned power transformer to the distribution/demand units. 1.9 Power quality A similar comment applies as for the HVDC installations: As a general practice in the industry, it is the responsibility of the TSO to ensure that the harmonic voltage distortion level is below the planning level at all nodes where customers are connected. This is a practice used in the international IEC standards or IEEE recommended practices, see IEC 61000 or IEEE 519-2014. In both documents, distribution equipment is only required to ensure a given harmonic current distortion level below to the defined limits. The code states that 'the level of allowed distortion or fluctuation of the supply voltage on the network at the connection point of a transmission-connected demand facility will not alter from what is stated in article 46 of the

current Federal Grid Code'. However, the level of allowed distortion of the supply voltage is set by the TSO harmonic planning levels and, consequently, it is a responsibility of the TSO. This can be controlled, as it is typically the case, by allowing a lower maximum admissible harmonic current injection limits from the load installation. However, this article is directly giving the responsibility of the harmonic voltage distortion to the load, against international standards and practices.