Control Cable installation: Best Practice

Similar documents
HI-Physix Laboratory, L-83, Sector-1, DSIDC Industrial Area, Bawana, Delhi. Discipline Electronics Testing Issue Date

CONTINUING EDUC ATION

Contents. 1 Introduction. 2 System-Level Electrostatic Discharge (ESD) and Electrical Fast Transient. 3 Electromagnetic Interference

Lightning Strikes. Presented to the Greater Norwalk Amateur Radio Corporation Inc. February 8, 2017 Steven M. Simons W1SMS

APPLICATION FOR APPROVAL OF A IENG EMPLOYER-MANAGED FURTHER LEARNING PROGRAMME

A statistical survey of common-mode noise

Hands-On Noise Mitigation Transmission, Bonding, Grounding & Inductive Interference

Table of Contents. 1 Introduction. 2 System-Level Electrostatic Discharge (ESD) and Electrical Fast Transient (EFT) 3 Electromagnetic Interference

American Electrical Institute

Device Interconnection

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

Power Quality Solutions

Solution of EMI Problems from Operation of Variable-Frequency Drives

CP /240-MC4 User Manual

Article 250 Grounding & Bonding

Grounding and Bonding

Wisconsin Contractors Institute Continuing Education

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

6B.6 Substation Grounding

Outdoor Installation 2: Lightning Protection and Grounding

Drives 101 Lesson 5. Power Input Terminology for a VFD

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

Preface... xv Acknowledgments... xix. Chapter 1 An Overview of Vacuum Tube Audio Applications... 1

Name:... Date:... Use your mathematical skills to solve the following problems. Remember to show all of your workings and check your answers.

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

Ameritron RCS-10 INTRODUCTION

BVM Systems Limited. PQSensor MkIII Installation & Commissioning Manual - 1 -

Agenda. Earthing of Telecom Installations using Single Point Earthing. Reference Documents. How many earths? Earthing Issue...

Welcome Because the field of grounding is so broad, todays presentation is intended not to give you the keys to the gold mine, but to give you a

Lumewave and LumInsight IoT. Gateway and Base Station Installation Guide

3.7 Grounding Design for EAST Superconducting Tokamak

A-E01D1. Austin E-Cap Series Isolation Transformer

670K9 SORtrax Level Transmitter

VFD Level II: Application Considerations. Jason Fahey, Vice President John Fahey, President

EPG. by Chris C. Kleronomos

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

The Variable Threshold Neutral Isolator (VTNI)

MAINTAINING OPTIMAL ALARM MONITORING COMMUNICATION

KOLLMORGEN. Motion Technologies Group. EMC Installation and Application Guidelines for BDS4/5 Goldline Series MB4000H Issue 3

Table of Contents. Facility EMI Filter Products

RF LEVEL TRANSMITTER. Series RFLT 900

GROUNDING. What is it? Al Lewey K7ABL. Disclaimer

ALTAI A8N SERIES SUPER WIFI BASE STATION INSTALLATION GUIDE. Version 1.0 Date: September, Altai Technologies Ltd. All rights reserved

Installation instructions and notes on implementation of an intermeshed equipotential bonding system with EMClots

Earthing for EMC in Installations

Underground System Design TADP 547

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX

Collection of standards in electronic format (PDF) 1. Copyright

MV protection relay. Installation assistance guide. Sepam ranges

Grounding Systems and Their Implementation By: Charles Atkinson Canadian Broadcasting Corporation Toronto, Canada

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Earth Clamp / Ground Clamp Earth rod Clamp / Earthing rod Clamp Ground Clamp / Grounding Clamp

CONTENTS. 1. Introduction Generating Stations 9 40

Busbar and Modular Wiring Systems

60Hz Ratings. Typical Applications. Features & Characteristics. Ratings

OPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM

INTER PLANT STANDARD STEEL INDUSTRY VARIABLE VOLTAGE VARIABLE FREQUENCY SYSTEM (V.V.V.F.) V/F, VECTOR CONTROL / TORQUE CONTROL

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

DLS DEF1436. Case 2:13-cv Document Filed in TXSD on 11/19/14 Page 1 of 7 USE CASE SPECIFICATION VIEW ELECTION CERTIFICATE RECORD

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Q: What does it mean if the RF generator will not put out full power and the reflected power is nearly equal to forward power?

Acknowledgments...xvii. Introduction... Chapter 0: Setting Up and Useful Skills Chapter 1: The Reaction-Time Machine... 25

ISRAEL RAILWAYS LTD. INFRASTRUCTURE DIVISION TRACK AND RIGHT OF WAY DEPARTMENT. for

Moses E Emetere (Department Of Physics, Federal University Of Technology Minna P.M.B 65, Minna, Nigeria)

National Radio Astronomy Observatory Socorro, NM EVLA Memorandum 41 Lightning Protection for Fiber Optic Cable. T. Baldwin June 05, 2002

Com-Trol ADV-6000 Trouble Shooting Guide Click on red text to go to that page in guide

Electrical Wiring: Commercial, Seventh Canadian Edition

MATH 1112 FINAL EXAM REVIEW e. None of these. d. 1 e. None of these. d. 1 e. None of these. e. None of these. e. None of these.

6. Internal lightning protection

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

Education & Training

Instruction Manual. The AquaSun 3RP is a premium automatic solar controller with temperature adjustment, manual, winter mode features.

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION

ANNEX TO THE RESOLUTION Number 442, JULY, 21 st, 2006

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

POTENTIAL TRANSFORMER

Instruction Manual for Digital Grounding Resistance Meter

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

Lightning Protection. Wisconsin Broadcasters Association Broadcasters Clinic. 14 th October 2009 Jeff Welton Regional Sales Manager, Central U.S.

XDC 6000 Watt and Watt Series Digital Programmable DC Power Supply. Operating Manual

Central Inverter SUNNY CENTRAL 200 / 250 / 250HE / 350

Power Commander. Power Commander Plus. Electronic Line Voltage Regulators. 15 kva 150 kva SINGLE PHASE 15 kva 450 kva THREE PHASE SERIES 900

Revised Curriculum for Bachelor of Computer Science & Engineering, 2011

DJA3000. Cellular Communication Jammer. Installation and Operations Manual. Series DJA3000. Description: Cellular Communication Jammer

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

Economical Solutions to Meet Harmonic Distortion Limits[4]

Protection from electromagnetic environment effects

IC800SSD Hardware Manual Pub 348R5. for models. A publication of

LED Driver Compact fixed output. Udriver LC 25/30/35/40W 600/700/800/900mA fixc SC ADV ADVANCED series

VSD cables in. Working with. industrial & automation applications

Unit PO0205K Knowledge of Applying Fillers and Foundation Materials

LC31L-BAT Link Coupler

LED Driver Compact fixed output

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

AC Voltage- Pipeline Safety and Corrosion MEA 2015

Medium Voltage Power Cables

Transcription:

Control Cable installation: Best Practice Years of experience has taught Irri-Gator Product s technical personnel that it is virtually impossible to predict an installation s sensitivity to surges (whether from power supply side, lightning or inductive current) or its sensitivity to Total Harmonic Distortion (THD) or Electromagnetic Interference (EMI). In the case of surges we mostly have a proactive approach since we have learned to do the best you can from the start (yet budget constraints could unfortunately hamper such efforts, also nothing can provide 100% protection against lightning). With THD and EMI, in most cases we will however have a more reactive approach if there is a problem, we will address it else save your money. There is however a few basic, relatively economical steps that one can take during installation already in order to reduce the risk and effects of surge damage or interference (THD or EMI) and at same time minimize maintenance cost. This document covers basic practical installation considerations regarding extra low and low voltage power supply to control devices, as well as control and monitoring circuits from such devices to extra low voltage auxiliary equipment with the aim to mitigate potential problems. The document is not intended as a comprehensive guide with regards to power supply, earth networks and protection. For more detailed information regarding protection and safety considerations, please refer to SANS 10142 i. Note that in South Africa, SANS 10142-1:2017 now also applies to external power supply wiring of extra low voltage applications (<50 VAC and <120 VDC) and include agricultural applications among others. ii 1. Definitions 1.1 Power Surge Definition: an unexpected, temporary, uncontrolled increase in current or voltage in an electrical circuit; a voltage spike [yourdictionary.com] The source of this voltage spike could be due to a fault originating at the supply side (power utility or generator). This could be due to single phasing in a 3-phase system, where a live phase is lost, the loss of the neutral conductor, under-usage by other users on the grid, incorrect or faulty transformer tapping etc. Surges can also be caused by lightning and in extreme cases due to inductive current where the electromagnetic field in one conductor (usually carrying a higher voltage), influence the current / voltage in a second conductor that runs parallel to the first one. 1

A poor earth system could create voltage potential difference between two points of an installation and will magnify the potential damage caused by power surges. 1.2 Harmonics Harmonic voltages and currents in an electric power system are a result of non-linear electric loads and are typically caused by switch-type power supplies, fluorescent lights, UPSes, VSDs etc. Worst case, harmonic frequencies in the power grid can be a cause of power quality problems. Harmonics in power systems result in increased heating in the equipment and conductors, misfiring in variable speed drives, and torque pulsations in motors. More often however it will only cause interference with (mostly unshielded and economy range) electronics and controllers. Reduction of the detrimental effects of harmonics (and other harmful effects caused by electrical equipment) is however required by SANS iii and therefore all means possible should be pursued to do so. This includes following best practice cabling guidelines. Total harmonic distortion or THD is a common measurement of the level of harmonic distortion present in power systems. THD can be related to either current harmonics or voltage harmonics, and it is defined as the ratio of total harmonics to the value at fundamental frequency x 100%. [Wikipedia.org] Normal AC Sine Wave Resultant (Square ) Wave According to international standards a level of <3% is required for medical grade installations and <5% is still seen as acceptable for other less sensitive installations. 5th Harmonic 3 rd Harmonic Figure 1 - Example of the effect of harmonic distortion on an AC Sine Wave. NB: All non-linear electrical load generators, including VSDs, will cause some level of harmonic distortion, even if it does operate within the SANS standard related to this phenomenon. Standards pertaining to acceptable levels of THD do however not pertain to just one component in the system, but to the TOTAL installation and is measured at the Point of Common Coupling (PCC). Factors that influence THD includes, but is not limited to: cable diameter and distance, quality of earth, supply side transformer size, quality of power entering your premises etc. A further complication is that, as with EMI, some 3 rd party equipment might be more sensitive than others. This makes it extremely difficult to predict whether relatively expensive counter- measure should be installed from the start hence our more reactive approach to this. 2

1.3 Electromagnetic Interference EMI (electromagnetic interference) is the disruption of operation of an electronic device when it is in the vicinity of an electromagnetic field (EM field) in the radio frequency (RF) spectrum that is caused by another electronic device. [techtarget.com] 2. Best Installation Practice 2.1 Positioning and Shielding of Electrical Equipment 2.1.1 Position electrical equipment where it will be readily accessible for installation, maintenance and repair iv. The same approach should apply to cabling where possible. 2.1.2 Do not install potentially sensitive electronic equipment close to (or in the same enclosure as) devices like VSDs that has the potential to generate harmonic distortions or EMI. 2.1.3 Shield potentially sensitive electronic equipment by installing it in metal enclosures. 2.2 Earth System Ensure that a quality earth network is in place. According to SANS, an earth bonding system of < 0.2 Ohm is required in South Africa v. Establishing a high quality ground / earth system includes, but is not limited to: 2.2.1 Separation of Earth and Neutral Conductors vi. Although these two conductors are for example both jointed together on the star side of a supply transformer, the Neutral is a current carrying conductor, while the earth conductor is for protection only and should be left current free vii (Figure 2). Using the same conductor for both E and N will reduce the effectiveness of any surge protection installed in the system. Accidental disconnect of the conductor, if a shared conductor is used for E and N, a single phase 110 V or 220 V systems might experience a power increase up to 240 V or 400 V, which will fry your equipment. As an alternative, if separation of E and N is not practical or financially viable, the installation of an isolating transformer could be investigated (e.g. 400:240V). Figure 2 - Separation of Earth and Neutral Conductors 2.2.2 Use of a copper conductor of at least the same diameter as the live conductors in the power system as the Earth conductor. Using only the armoured shielding of a cable is not enough viii. 3

2.2.3 Installation of earth pegs at the transformer (should be standard) and at each outlet / building on the local low voltage grid. Also ensuring that all these pegs are interconnected and that connections are bonded properly ix. In very sensitive installations, it might be advisable to contact an earth expert to do a risk assessment x that will include analysing soil samples as to determine how a quality earth network can be established. His findings might result in the use of longer earth pegs, special preparation of the area where the peg is to be installed or the establishment of an earth mat instead of relying on single pegs. Establishing a proper ground / earth system is the first step to protect electronic equipment against power surges, harmonics and EMI xi. 2.3 Phase Balance and Surge Protection 2.3.1 In a multiphase system, ensure that phases are balanced xii. This will potentially reduce the effects of harmonic interference and other harmful phenomena. 2.3.2 A multi-tier approach should be taken when installing surge arrestors. Some equipment, like a VSD, might come with surge arrestors, but might only be sufficient for secondary protection. Primary protection should already be installed at the distribution enclosure. The decision to install Class I vs Class II protection at this level will likely be influenced by the budget available, but SANS require at least Class II at the distribution board xiii. As previously mentioned, the quality of your earth plays a major role in effectiveness of any surge protection devices xiv. 2.4 Wiring Considerations 2.4.1 Select conductor size according to SANS standards xv. 2.4.2 Use braided (double) shielded cables (Figure 3) for your control or signal cables. Earth the braided shield on one side at a common point xvi. In some Figure 3 - Braided Shield Cable cases Surfix cable (that has a metal insulation) or installation of normal cables in Bosal steel conduit might be sufficient (See Figure 4). Standardizing on a combination of braided shield cables installed in steel conduit will be first prize. Metal Conduit Figure 4 - Control cable installed in metal conduit and high voltage cables separated from control cable (2.4.2 and 2.4.4) Separated Control & Power Cables 4

2.4.3 Wiring and Installation of Transducers and other Electronic Sensors: 2.4.3.1 Use a 0.75 mm or smaller diameter cable only (since sensors in general do not carry current, this will be sufficient). 2.4.3.2 Use braided (double) shielded cable (Figure 3) as described in point 2.4.2 xvii. 2.4.3.3 Although seemingly crude, we have found that installing a simple glass fuse (50 ma) on a 4 20 ma sensor cable has the potential to protect the system to a large degree against power surges. 2.4.3.4 Installation of surge arrestors that are specifically designed for 4 20 ma sensor circuits are at times even more expensive than the sensor itself, but is an option. Effectiveness of such devices will largely depend on the quality of the earth network. 2.4.3.5 Isolate the transducer or sensor from any metal structures or pipes by means of non-conductive elements. For example, use a PVC or PP bush between your pressure transducer and a metal pipe. 2.4.3.6 Make sure that metal structure or pipe is properly earthed (bonded) as described in point 2.2 xviii. 2.4.3.7 Seal the cable connector with silicone tape around the cable gland as well as the connector side. Silicone spray can also be used on the screw terminals to expel moisture. 2.4.4 Positioning and fixing of cables xix : 2.4.4.1 Separate any signal or control cable from high voltage carrying cables xx. This will reduce the risk of EMI, harmonic interference or surges due to conductive current (Figure 4). Recommended distance to keep is 0.5 1 m. If possible try to keep the 1 m recommendation. This will likely mean two sets of cable rack is required, one for high voltage and one for control cables. In trenches this is likely not possible. Try to keep the high voltage cables on one side and the control cable on the other side of the trench. The backfill soil will assist with shielding. Signal / Control Cables include: Pressure transducer cables, low voltage switching cables (24VAC), digital input cables from fertilizer and water meters, CAT5 LAN cables and antenna cables. 2.4.4.2 Make use of cable trays and trunking to lift cables off the floor. Water and fertilizer corrodes insulation and leads to short circuits. Avoid clamping cables to pipes or fittings that might in future be replaced xxi. Figure 5 - Cable Tray 5

2.4.4.3 Use UV resistant cables when working outdoors xxii and do not install cables on surfaces that can potentially get very hot (corrugated iron sheets for example). 2.4.4.4 Avoid cables with single strand cores, rather use cables with multi-stranded cores. 2.4.4.5 Use lugs or ferrules where possible to avoid bad contacts xxiii. 2.4.4.6 Avoid joining cables. Rather order a cable of the correct length. If a connection is necessary, solder the wires and install in a watertight epoxy connector. Keep the joint above ground and / or at a workable height for future troubleshooting xxiv. 2.4.4.7 Mark cables at both ends with a durable label to assist installation and future troubleshooting. 2.4.4.8 Do not over-tighten terminals, but do check all connections before commissioning and at least every 3 months thereafter. 2.5 Additional measures If interference is still experienced after above measures has been implemented, it might be necessary to install more expensive filters or reactors, for example an AC Input Reactor and/or a DC Reactor will decrease harmonic feedback generated by a VSD into the power grid. An EMI filter installed on the influenced device power supply might resolve EM related issues and Signal isolators might improve the quality and compatibility of analogue signals. Also see Endnote xxv. Figure 6- AC Input Reactor; DC Reactor; EMI Filter 6

Endnotes i Since this document is primarily intended for a South African audience, we will refer to SANS standards. Standards do however vary from country to country; therefore refer to the standards applicable in your country where necessary. ii SANS 10142-1:2017, pp. 1, 21, 22, 51. iii SANS 10142-1:2017, p. 70. iv SANS 10142-1:2017, p. 68. v SANS 10142-1:2017, p. 267. vi SANS 10142-1:2017, pp. 76, 169. vii SANS 10142-1:2017, p. 169. viii SANS 10142-1:2017, p. 165. ix SANS 10142-1:2017, pp. 164, 171 173. x SANS 10142-1:2017, pp. 160, 328 339. xi SANS 10142-1:2017, p. 165. xii SANS 10142-1:2017, p. 76. xiii SANS 10142-1:2017, p. 319. xiv SANS 61643-12 and SANS 10142-1:2017, p. 165, annex I.1. xv SANS 10142-1:2017, pp. 78 132, annex O. xvi SANS 10142-1:2017, pp. 74, 77, 164. xvii SANS 10142-1:2017, pp. 133 141. xviii SANS 10142-1:2017, pp. 170 173. xix SANS 10142-1:2017, pp. 78 132. xx SANS 10142-1:2017, pp. 77, 137. xxi SANS 10142-1:2017, p. 137. xxii SANS 10142-1:2017, p. 136. xxiii SANS 10142-1:2017, p. 77. xxiv SANS 10142-1:2017, pp. 136, 137. xxv SANS 10142-1:2017, annex O. 7