Comprehensive modeling of Dry type foil winding transformer to analyse inter turn insulation under Lightning Impulse Voltage

Similar documents
n 1 ENGINEER Turn-to-Turn Capacitance, (C tt) The capacitance between adjacent turns, (C tt) is calculated using the following formula [3].

Study of Design of Superconducting Magnetic Energy Storage Coil for Power System Applications

General Approach for Accurate Evaluation of Transformer Resonance Effects

The Influence of a Cable on the Voltage Distribution in Transformer Windings G. Hoogendorp, M. Popov, L. van der Sluis

Investigation into Resonant Overvoltages in Wind Turbine Transformers due to Switching Surges

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

LIGHTNING IMPULSE MODELING AND SIMULATION OF DRY-TYPE AND OIL-IMMERSED POWER- AND DISTRIBUTION TRANSFORMERS

Simulation Study of Voltage Surge Distribution in a Transformer Winding

GIS Disconnector Switching Operation VFTO Study

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Improved Method for Winding Deformation Detection Sensitivity in Transformer

Fast Front Transients in Transformer Connected to Gas Insulated Substations: (White+Black) Box Models and TDSF Monitoring

FAULT IDENTIFICATION IN TRANSFORMER WINDING

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Computation of Inter-turn Voltages in Transformer Windings with Interconnected Distribution Cable

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Electric Field Analysis of High Voltage Condenser Bushing

Ferroresonance Experience in UK: Simulations and Measurements

BE. Electronic and Computer Engineering Final Year Project Report

Computation of Very Fast Transient Overvoltages in Transformer Windings

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

(2) New Standard IEEE P (3) Core : (4) Windings :

Simulation Model of Partial Discharge in Power Equipment

936 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 2, APRIL /$ IEEE

Switching Induced Transients:

Comprehensive Study on Magnetization Current Harmonics of Power Transformers due to GICs

Lightning transient analysis in wind turbine blades

Research Article Transformer Winding Deformation Profile using Modified Electrical Equivalent Circuit

CASE STUDY ON TRANSFORMER MODELS FOR CALCULATION OF HIGH FREQUENCY TRANSMITTED OVERVOLTAGES

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad

AC CREEPAGE DISCHARGES IN SF 6, CO 2, N 2 AND SF 6 -CO 2 AND SF 6 - N 2 MIXTURES

High Frequency Modeling of Two Limb Series Loop Winding for Partial Discharge Localization

High frequency transformer model for calculations of transferred overvoltages. I. UGLESIC University of Zagreb, Croatia

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Shunt Capacitance Influences on Single-Phase Transformer FRA Spectrum

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

VARIATION OF LOW VOLTAGE POWER CABLES ELECTRICAL PARAMETERS DUE TO CURRENT FREQUENCY AND EARTH PRESENCE

EFFECT OF RADIAL AND AXIAL MOVEMENT OF WINDING ON COHERENCE FUNCTION IN A 220/132 KV, 100 MVA, AUTO TRANSFORMER

Generation of Sub-nanosecond Pulses

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

High-frequency Transformer Modeling for Transient Overvoltage Studies

Revision of TRV Requirements for the Application of Generator Circuit-Breakers

Target Temperature Effect on Eddy-Current Displacement Sensing

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

Chapter 2. Inductor Design for RFIC Applications

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

COMPARATIVE ASSESSMENT OF ABNORMAL VOLTAGE STRESSES IN AN ISOLATED MUTUALLY COUPLED TRANSFORMER MODEL WINDING WITH AND WITHOUT VARISTOR

Measurements for validation of high voltage underground cable modelling

ANALYSIS, SIMULATION AND TESTING OF TRANSFORMER INSULATION FAILURES RELATED TO SWITCHING TRANSIENTS OVERVOLTAGES.

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Investigation of Fast Transients Propagation in Layer-type Transformer Windings Measurements and Modelling

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

A Study on Ferroresonance Mitigation Techniques for Power Transformer

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

Lightning performance of a HV/MV substation

A SIMPLIFIED LIGHTNING MODEL FOR METAL OXIDE SURGE ARRESTER. K. P. Mardira and T. K. Saha s: and

Numerical Analysis of Breakage of Curved Copper Wires due to High Impulse Current

Electric Stresses on Surge Arrester Insulation under Standard and

A Fundamental Approach for Design and Optimization of a Spiral Inductor

Analysis of Insulation Strength of Connection of High Voltage Transformer with FEMLAB

High Voltage Engineering

Single-turn and multi-turn coil domains in 3D COMSOL. All rights reserved.

Units. In the following formulae all lengths are expressed in centimeters. The inductance calculated will be in micro-henries = 10-6 henry.

SELF HEALING ANALYSIS AND PERFORMANCE APPRAISAL OF METALLIZED POLYPROPYLENE CAPACITORS

Effects of Transient Recovery Voltages on Circuit Breaker Ratings

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

ISSN: [IDSTM-18] Impact Factor: 5.164

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse

Impulse testing of coils and magnets: present experience and future plans

A Finite Element Simulation of Nanocrystalline Tape Wound Cores

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

Acoustic Performance of Helmholtz Resonator with Neck as Metallic Bellows

A review of shielding performance By Albert R. Martin

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor

ADVANCES in NATURAL and APPLIED SCIENCES

Transformer Engineering

Transcutaneous Energy Transmission Based Wireless Energy Transfer to Implantable Biomedical Devices

OPEN SOURCE CABLE MODELS FOR EMI SIMULATIONS

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Cell size and box size in Sonnet RFIC inductor analysis

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines

MATEFU Insulation co-ordination and high voltage testing of fusion magnets

Transcription:

Comprehensive modeling of Dry type foil winding transformer to analyse inter turn insulation under Lightning Impulse Voltage Grupesh Tapiawala Raychem Innovation Centre Raychem RPG (P) Ltd Halol, India Grupesh_Tapiawala@raychemrpg.com Ram Krishna Mishra Raychem Innovation Centre Raychem RPG (P) Ltd Halol, India Ram_Mishra@raychemrpg.com Abstract In the event of a lightning impulse to the high voltage terminal of a dry type transformer, uneven impulse stress occurs on its windings. The impulse voltage may further shoot up owing to resonance condition which results in additional turn to turn and coil to coil voltage difference. In this paper, comprehensive modeling of transformer is done by calculating circuit parameter of transformer for each turn. Self and mutual inductances are calculated for each turn using finite element analysis (FEA) and validated with analytical calculation. Further, impulse voltage behavior is studied at every turn by using LTSpice software. The voltage stresses thus got is used to analyze dielectric strength of insulating material by using ANSYS Maxwell software. This study was carried out on Dry type foil winding transformer. The achieved results indicate that electrical stress between turn to turn is drastically improved by designing initial turn of HV coil from outer side than inner side of HV winding. Keywords LTSpice, Lightning impulse, transformer modeling, Dry type foil winding I. INTRODUCTION Lightning impulse comprises of frequencies from tens of kilohertz to several megahertz and characterized by a very high-voltage (HV) rate of rise du/dt and may have a negative influence on the windings of transformers [1]. The winding inductances have no effect on the initial voltage distribution since the magnetic field requires a finite time to build up. When the applied voltage is maintained for a sufficient time (50 to 100 microseconds), appreciable current begin to flow in the inductances eventually leading to the uniform voltage distribution. Since there is difference between the initial and final voltage distributions, a transient phenomenon takes place during which the voltage distribution readjusts itself from the initial to final value [3]. This unfavorable phenomenon may result in deterioration in the insulation and ultimately lead to a dielectric breakdown [2]. Many studies have been done to investigate transient performance of transformer during switching of breaker for identifying behavior of transformer winding and protection method against very fast transient [1, 2, 4, 6]. Impulse analysis in transformer mainly focuses on initial voltage distribution with respect to winding length [9]. Now it is required to closely analyze minor insulation or inter turn insulation in order to optimize the design and to get better life expectancy of transformer. This study is mainly aimed on measurement of voltage generated between turns during lightning impulse by using LTSpice software. Further, this study is extended to electrostatic analysis in ANSYS Maxwell software to analyze electrical stresses generated between minor insulation and suggestions have been made to overcome the stresses. Detailed modeling of HV winding has been done by considering self and mutual inductance and capacitance of each turn. II. MODELING OF DRY TYPE TRANSFORMER A. Winding model description Lumped parameter modeling of transformer strongly depends upon type of winding and its configuration. Fig.1 shows a three phase dry type transformer considered for the study. Fig. 1. Test transformer. Both LV and HV winding are made of foil-type layers. In HV winding each turn represents one layer and each coil consists of N no of turns.

B. HV winding representation The geometrical structure of one phase is shown in Fig.2. First foil turn of HV coil starts from inner side of HV winding and continues up to N th turn, hence 1 st turn is nearer to LV winding and N th turn is on the farther end of LV winding. Since first turn is nearer to LV winding, it has a strong capacitance with LV winding. The aim of this study is to analyze voltage difference between turns, hence it is required to calculate inductance and capacitance for every turn. Inductance matrix is formed by considering each turn of the coil and its mutual inductance with respect to all other remaining turn within the coil, hence inductance matrix for each coil is of NxN. Fig.3 (a) represents inductance and capacitance network for three turns, L1, L2, L3 are the inductances of turn 1, 2, 3 respectively and C1, C2 are capacitances between turn 1-2 and turn 2-3 respectively. Above circuit can be simplified by assuming an equipotential line in the middle of the coil as shown in Fig.3 (b) [4]. Hence C1/2 and C2/2 are added to the edges of the coils L1, L2, L3 respectively. The circuit can further be streamlined by considering an equipotential surface between layers, which is explained in Fig.3 (c) [4,5]. Hence the capacitance between layers can be added as a cross-over capacitance at each layer with the value half from each side. After this simplification each layer is represented by one inductance and one capacitance as shown in Fig.3 (d) Fig. 2. Test transformer configuration. Layer to layer capacitance, coil to coil capacitance for each turn and LV to HV capacitance is considered to make study more accurate. Since dry type transformer doesn t have tank, ground capacitance with respect to tank is neglected for this study. Equivalent circuit can be simplified by rearranging capacitances [4]. Fig. 3. Rearranging turn to turn capacitance. Fig. 4. Equivalent circuit of HV winding. Fig. 4 shows final equivalent circuit of HV winding with lumped parameter. First turn of each HV coil has capacitance with respect to LV winding. This can be considered as gound capacitance [6]. The capacitances from first and last coil to core i.e. ground are very small in this case. It can be seen from Fig. 2 that only a part of the surface of the coil is nearer to core hence capcitance from coil to core is neglected as it is mostly the geometry of the surface that influences the value [7]. Coil to coil capacitance is considered for every turn to analyse voltage distribution accurately. C. Determination of lumped parameters 1) Capacitance As shown in Fig. 4 there are three types of capacitances present in the circuit. (i) Turn to turn capacitance, (ii) Coil to coil capacitance for each turn and (iii) HV to LV capacitance. Since it is a foil type winding, turn to turn and HV to LV capacitance can be straight away calculated by using basic formula of cylindrical capacitors. For better accuracy capacitance of individual turn of coil 1 is calculated with respect to respective turn of coil 2 instead of calculating coil to coil capacitance by considering N turn as a one plate. Parallel plate capacitance formula was used to calculate Coil to coil capacitance for each turn.

2) Inductance Calculation According to calculation methodology in [8], the mutual inductance between foil-type turns is calculated by ( ) [ ] ( ) per unit length ( ) between turns has been analyzed by using LTSpice software. An impulse voltage of 170kVp is applied to 33kV HV winding as per IEC_60076_3. All NxZ no of turns are modeled using a total of NxZ inductors and [2(NxZ) +2Z] capacitors. The line with sampling point and the thick line as shown in Fig.5 indicate voltage difference between 1 st and 2 nd turn and 2 nd and 3 rd turn respectively. Major voltage difference was observed between first two turns i.e. 22kV and rest of the layers has voltage difference less than 4kV. Hence electrostatic study was performed on first two turns to check the electric stress vs insulation strength. And self-inductance is calculated by [ ] ( ) Fig. 5. Voltage difference between 1 st and 2 nd turn, 2 nd and 3 rd turn. The self-inductance of first turn and mutual inductance between first and second turn of the first coil is calculated using these formulae. Then, 2D-axisymmetric model is developed for first two turn and same inductances are calculated using commercial FEA software ANSYS Maxwell. The results are compared in table 1. IV. ELECTROSTATIC ANALYSIS The input for electrostatic analysis is taken from output of transient analysis. 2D-axisymmetric model of turn to turn insulation is modeled in ANSYS Maxwell software as shown in Fig. 6. 22kV is applied to turn 1 and 2 nd turn is at ground potential, Fig. 7 gives idea about how equipotential lines are passing and voltage is distributed across the insulation. TABLE I. COMPARISON OF ANALYTICAL AND FEA RESULTS Analytical Result FEA Result Self-Inductance of 1 st Coil 1.2191 μh 1.2167 μh Mutual Inductance between 1 st and 2 nd Coil 1.2025 μh 1.2036 μh After FEA methodology is validated with analytical calculation, it is then extended to calculate self and mutual inductance of complete N turns in the coil. III. TRANSIENT ANALYSIS Standard lightning impulse i.e. 1.2/50µs was applied to equivalent circuit shown in Fig. 4 and voltage distribution Fig. 6. 2D-axisymetry geometry for turn to turn insulation analysis Highest electrical stresses coming out from the analysis is at the edge of the turn as shown in Fig. 7. Safety margin is calculated by considering electrical stress and insulation

strength, which is 11% for the corner of inter turn insulation. Whereas safety margin for insulation across turn is 41%. voltage difference between rests of the turns is observed less than 3kV. Once again electrostatic study was carried out with new value of voltages, table II shows the comparison between two winding design. Fig. 7. Equipotential surface and Electric field plot for turn to turn. Since voltage difference between turns is very high, the stress value is also quite high at the edges. Stresses at the edge can be reduced by improving corner radius but it being a foil type winding, there is a limitation to corner radius for such a thin layer. To overcome the problem of voltage stress, a change in winding configuration is suggested. The new winding configuration is shown in Fig. 8. V. REVISED WINDING MODEL Fig. 9. Voltage difference between turns. TABLE II. Existing winding configuration Proposed winding configuration COMPARISON OF EXISTING AND PROPOSED WINDING CONFIGURATION Inter turn Voltage Safety margin at edge Insulation Safety margin across insulation 22kV 11% 41% 3.5kV 80% 90% % improvement 84.09% 69% 49% Fig. 8. Rewound HV winding. HV winding is rewound by keeping all parameters constant but in the new configuration first foil turn of HV coil starts from outer side of HV winding and continued up to N th turn, hence 1 st turn is farther from LV winding and N th turn is nearer to LV winding. Since first turn is far away from LV winding, there is no capacitance between first turn and LV winding. Hence ground capacitance will come in to picture only after (N-1) th turn. Equivalent circuit is also modified as described above and transient analysis was performed on rewound winding. The results are shown in Fig. 9. It can be seen from Fig. 9 that voltage difference between 1 st two turns are drastically reduced from 22kV to 3.5kV. Also, VI. CONCLUSION Detailed modeling of Dry type foil winding transformer is done by considering each turn. This study explains the methodology to analyze inter turn insulation under Lightning Impulse Voltage or any kind of transient response when each individual turn is modeled as shown in equivalent circuit, Fig. 4. A validated FEA model is developed to calculate self and mutual Inductance matrix of NxN. Impulse voltage distribution is analyzed using LTSpice software, which provided input voltage for electrostatic study to find out electrical stress on the insulation. Analysis shows how winding configuration affects voltage distribution between turns. Only by changing winding start and end points/direction of winding, a big difference in voltage can be observed between inter turns. Since in initial design ground capacitance comes in to picture in the first turn itself, major voltage was dropped between first two turns, whereas in the modified design ground capacitance comes after (N-1) th turn and by that time voltage gets distributed uniformly. Hence the study indicates that ground capacitance plays an important role in voltage distribution during Impulse. It is observed that more than 84% improvement can be achieved in voltage difference between turns by changing winding configuration, which directly replicates in reduction of electrical stress on inter turn insulation more than 82% and safety margin was improved in the range of 50% to 70%.

VII. ACKNOWLEDGEMENT The authors would like to thank management of Raychem RPG (P) Ltd for supporting the presented work. Inputs from the design team specially Mr. Pradeep Mujumdar, Mr. Arun Kumar Goel, Mr. Swapnil S Patil are also appreciated and acknowledged. REFERENCES [1] D. Smugala, W. Piasecki, M. Ostrogorska, M. Florkowski. M. Fulczyk and O. Granhaug, Wind Turbine Transformers Protection Method Against High-Frequency Transients, IEEE transactions on power delivery, vol. 30, no. 2, april 2015 [2] M. Popov, L. Van der Sluis, and J. L. Roldan, Analysis of very fast transients in layer-type transformer windings, IEEE Trans. Power Del., vol. 22, no. 1, pp. 238 247, Jan. 2007. [3] S.V.Kulkarni, S.A.Khaparde, Chapter 7: Surge Phenomena in Transformers, Book: Transformer Engineering Design and Practice, 2004. [4] M. Popov, R.P.P. Smeets, L. van der Sluis, H. de Herdt and J. Declercq, Analysis of Voltage Distribution in Transformer Windings During Circuit Breaker Prestrike, International Conference on Power Systems Transients (IPST2009) in Kyoto, Japan June 3-6, 2009. [5] G. Stein: A Study of the Initial Surge Distribution in Concentric Transformer Windings, AIEE Transaction, September 1964, pp. 877-892. [6] Andreas Theocharis, Marjan Popov, Robert Seibold, Stephan Voss, and Martin Eiselt, Analysis of Switching Effects of Vacuum Circuit Breaker on Dry-Type Foil-Winding Transformers Validated by Experiments, IEEE transactions on power delivery, vol. 30, no. 1, february 2015. [7] M. Popov, L. van der Sluis, R.P.P. Smeets, Complete analysis of Very Fast Transients in Layer-type Transformer Windings, International Conference on Power Systems Transients (IPST 07) in Lyon, France on June 4-7, 2007 [8] T. H. Fawzi and P. E. Burke, The accurate computation of self and mutual inductances of circular coils, IEEE Trans. Power App. Syst., vol. PAS-97, no. 2, pp. 464-468, Mar./Apr. 1978. [9] R. Jayaratchagan, B. Shriram, Impulse Voltage Distribution, International Journal of Engineering Research & Technology (IJERT), ISSN: 2278-0181, Vol. 2 Issue 4, April 2013.