ACTIVE COMPENSATION OF HARMONICS IN INDUSTRIAL APPLICATIONS. Sergej Kalaschnikow, Steffan Hansen, Lucian Asiminoaei, Henrik Gedde Moos

Similar documents
Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications.

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Harmonics Elimination Using Shunt Active Filter

ISSN Vol.03,Issue.07, August-2015, Pages:

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions

Power Quality enhancement of a distribution line with DSTATCOM

Control Of Shunt Active Filter Based On Instantaneous Power Theory

p. 1 p. 6 p. 22 p. 46 p. 58

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

HARMONIC contamination, due to the increment of nonlinear

Literature Review for Shunt Active Power Filters

Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier

2020 P a g e. Figure.2: Line diagram of series active power filter.

Power Quality Improvement using Shunt Passive Filter

Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation

Power Quality improvement of a three phase four wire system using UPQC

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Voltage Flicker Mitigation in Electric Arc Furnace using D-STATCOM

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

STUDY OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT RAJIV KUMAR SINKU

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction


Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

A Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)

Chapter 2 Shunt Active Power Filter

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Mitigation of Voltage Sag/Swell Using UPQC

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

Voltage Flicker Compensation using STATCOM to Improve Power Quality

Investigation of D-Statcom Operation in Electric Distribution System

Performance of DVR under various Fault conditions in Electrical Distribution System

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

Voltage Sag and Mitigation Using Dynamic Voltage Restorer (DVR) System

Mitigation of Flicker Sources & Power Quality Improvement by Using Cascaded Multi-Level Converter Based DSTATCOM

A Review on Improvement of Power Quality using D-STATCOM

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online):

Harmonic Immunity And Power Factor Correction By Instantaneous Power Control Of D-STATCOM

Literature Review. Chapter 2

Multilevel Inverter Based Statcom For Power System Load Balancing System

Harmonics Reduction using 4-Leg Shunt Active Power Filters

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

IMPORTANCE OF VSC IN HVDC

Comparison of Reference Current Extraction Methods for Shunt Active Power Filters

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Kalman Filter Based Unified Power Quality Conditioner for Output Regulation

SHUNT ACTIVE POWER FILTER

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

Direct Power Control With Space Vector Modulation And Fuzzy DC- Voltage Control- PWM rectifier

Enhancement of Power Quality Using Advanced Series Active Power Filters

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Protection from Voltage Sags and Swells by Using FACTS Controller

Power Control Scheme of D-Statcom

Harmonic Reduction of Arc Furnaces Using D-Statcom

Using dspace in the Shunt Static Compensators Control

Mitigating Voltage Sag Using Dynamic Voltage Restorer

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Operation of a Three-Phase PWM Rectifier/Inverter

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

Mitigation of the Statcom with Energy Storage for Power Quality Improvement

WILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS

Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Power Quality Improvement in Distribution System Using D-STATCOM

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Handling System Harmonic Propagation in a Diesel-Electric Ship with an Active Filter

Analysis of Harmonic Distortion in Non-linear Loads

A Resistance Emulation Technique to Improve Efficiency of a PWM Adjustable Speed Drive with Passive Power Factor Correction

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

Harmonics White Paper

Transcription:

ACTIVE COMPENSATION OF HARMONICS IN INDUSTRIAL APPLICATIONS Sergej Kalaschnikow, Steffan Hansen, Lucian Asiminoaei, Henrik Gedde Moos Danfoss Drives A/S, 63 Graasten, Denmark, www.danfoss.com e-mail: sergej.kalaschnikow@danfos.com, s.hansen@danfoss,com, las@danfoss.com hgm@danfoss.com Keywords: power factor correction, power quality, harmonics, active filters ABSTRACT In industrial low and medium voltage mains, passive filters and PFC capacitors have traditionally been used to improve the supply quality. However, they cannot be rated only for the loads being compensated. They are affected by harmonic currents from other non-linear loads or by harmonics from the power system [1]. Compared with passive element compensators, an active harmonic compensator (AHC) can be used to improve the supply quality without worrying about all the problems associated with applying passive elements. I. INTRODUCTION The increased use of non-linear loads in general and of electrical drives in particular, typically connected to the mains with a diode or SCR rectifier, and loads such as arc furnaces with rapid fluctuations of reactive and active power consumption contribute to the degradation of power supply quality. Non-sinusoidal currents of the non-linear loads and fluctuations of the power consumption result in the distortion of the supply voltage wave form and cause voltage fluctuations (flicker) at the point of common coupling due to the finite supply impedance. These issues is recognized widely throughout the industry and in industrial mains passive filters are traditionally used to absorb harmonics generated by the non-linear load and PFC capacitor banks to compensate reactive currents, primarily due to their low cost. However, they have a number of significant drawbacks: - the mains impedance strongly influences the compensation characteristics; - they result in new resonances and theore magnify the levels of the other harmonics; - they cannot be rated only for the loads being compensated. They are affected by harmonic currents from other non-linear loads or by harmonics from the power system. The use of active mains compensation holds a number of advantages compared to the passive. The AHC: - Is easy to size to the application as the design is independent of line impedance - Does not generate resonance - Actively controls both harmonic and reactive currents. Despite the advantages, AHC s have a limited market share mainly due to high cost. However, a number of trends and factors indicate that this is about to change. - New developments enable the use of mass produced hardware in the active filter, which significantly will reduce the cost. - Due to the large amount of cobber and steel used in passive filter, the increase of material cost has a higher impact on passive solutions than on active solutions The AHC described in this paper was developed for industrial mains with non-linear loads and consumers with rapid fluctuations of reactive and active power consumption to improve the supply quality of other loads supplied from the same mains. As the AHC unit uses the same IGBT-inverter platform that is used for variable speed drives, thus the cost is limited compared to traditional AHCs. The goal of this paper is twofold: firstly, to present a general structure of the AHC, and secondly, to give some examples of industrial applications to improve the voltage quality of industrial networks with non-linear loads and consumers with rapid fluctuations of reactive and active power consumption. II. GENERAL STRUCTURE Fig.1 shows the block diagram of the AHC. The threephase voltage source inverters is connected to (see Fig.1) the industrial network. An industrial plant may include different types of electrical loads, divided into linear loads (regenerative power units, resistive loads, ac-machines) and non-linear loads (Adjustable Speed Drives, arcing devices, etc.) The Active Harmonic Compensator has to detect the current harmonics and generate a compensation current that cancels the harmonic component, leaving mainly the fundamental current to be drawn from the power supply. The control of the AHC consists of a closed loop

control for regulation of the inverter current and dcvoltage, and the detection and generation of compensation current erence. Thus, depending on applications, the AHC may include harmonic compensation, reactive current or flicker mitigation. Non-linear Loads Linear Loads A. Control system Fig.2 shows a block diagram of the control unit of the AHC. The control scheme is based on a cascade control with a current control in the inner loop without mains voltage sensors. The current controller sets the output voltage of the voltage source inverters for each sampling period of the control system so that the line current has a erence value. The voltage controller allows the dc voltage to have an almost constant value. The output signal of the dc-link voltage controller determines the value of the active current of the mains load and losses of the power unit of the restoring system [2,3]. The reactive current is calculated by the reactive power and flicker estimation module of the control unit (see Fig.2). To reduce the high-frequency switching-ripple of the AHC line current, a high frequency LCL filter is connected in between the mains and the AHC. B. Current control Fig. 1: Electrical diagram of the Active Harmonic Compensator connected to industrial plant. The control value of the current control loop is the supply current. This current is a result of the sum of the measured load current (see Fig.1) and the ac current of voltage inverter. These two three-phase system currents are added together and then are transformed to a signal of the two-phase quantities i. In Fig.2 this current is represented as i and Sα i. Sβ Sα, β Power supply/grid Source current Harmonic load current Non-linear Loads Active Harmonic Compensator control algorithm 3/2 i S abc 3/2 i abc F Harmonic compensation LCL current isα, β u Sα,β jω t e 1 u Wα,β i isα i i S β jω t Sα, β Fα, β e 1 ifα i F β L F PWM Inverter u d u d u d Reactive Power and Flicker Estimation Voltage Controller i d i q id,q jω t e 1 PLL jω t e 1 m i 1α, β Harmonic erence jmω1 t e m i md,q i α,β i α i β i Fα Current Controller u Wα u Wβ Select of switching sequence n C DC i Fβ Fig.2: Block diagram of the control unit

The erence value for the current controller i (d and d,q q components) is transformed to the stationary erence frame α β. The transformation of the vector i dq to the, vector i 1αβ, is executed by e jω 1 t, derived from a phaselocked loop PLL (see Fig.2). The selection of the switching sequence for every switching operation of the both voltage source inverters is achieved through the use of a sliding mode controller. The selection of the switching sequence for every switching operation through the use of the sliding mode control is discussed in detail in [4-6]. This makes it possible to control the active filter without mains voltage sensors [7]. It significantly simplifies the hardware configuration of the active mains compensator, especially for medium and high voltage applications. The output signals of two P-controllers with saturation represent two components of the mains voltage vector u, Wα u which are used to detect the position of Wβ the voltage vector by PLL. To control harmonic amplitudes in the network, the harmonic calculator is used. The principle of the operation is based on the direct harmonic control method. This method is briefly described in [2,3]. C. DC-link Control With non-sinusoidal mains current of the voltage inverter, the dc-link voltage contains not only a ripple from transistor switching operations, but also a low frequency voltage ripple like the dc voltage at the dclink of the diode rectifier with capacitor. This low frequency voltage ripple must be filtered in the control loop by feeding back the dc voltage otherwise this voltage ripple would be increased by the proportional part of the voltage controller and it would be passed on to the line current control loop. Theore the line currents would be distorted [8]. To decrease the influence of the dc-link voltage ripple on the current control loop, the cut-off frequency of the feedback low-pass filter must be f =5 75Hz. The low cut-off frequency of the feedback filter causes the large delay time in the dc-voltage measurement and theore the dc-link voltage control has a low dynamic performance. To improve the time response of the dc-link voltage control, an adaptive control system is used, whose parameter values of the feedback filter and PI controller are changed in accordance with the value of the dcvoltage error [8]. III. SIMULATION RESULTS The simulation of AHC control shows very high dynamics. This is justified first by the high dynamic of the current controller, which is characteristic to the sliding mode control. Second, due to the implemented adaptive dc-voltage controller the AHC can overcome much faster the transient during the connection/ disconnection of the AHC or the harmonic load change. A simulation result is available in Fig. 3 (only a single phase is shown). The harmonic current is generated by a typical three phase diode rectifier Adjustable Speed Drive. Since the displacement power factor is close to unity there is no requirement of reactive power compensation in this case, but only harmonic current mitigation. At time.16 the AHC is connected to the power system and starts mitigating the harmonic currents from the ASD. The transient takes almost one fundamental period, until the source current resembles sinusoid waveform. V s [ p u ] I L [ p u ] I A H C [ p u ] I S [ p u ] 2-2.14.16.18.2.22.24 5-5.14.16.18.2.22.24 2-2.14.16.18.2.22.24 5-5.14.16.18.2.22.24 Time [s] Fig.3. Simulation results of AHC start-up. Due to its high dynamics the AHC is able to compensate the harmonic currents within one fundamental period. The current distortion of the non-linear load has a THD of 34 % while the source current reaches a THD of 4 %.

IV. APPLICATION EXAMPLES The AHC operates as a highly dynamically controlled reactive current source and, thanks to special control algorithms, the compensating reactive current is delivered at exactly the right moment. Thereby the load of the mains is decreased and the mains voltage changes and distortions are reduced to a safe value. A. Mitigation of Harmonics In industrial mains, passive filters are traditionally used to absorb harmonics generated by non-linear loads, primarily due to their low cost. This is a good approach when power factor correction is needed too. As they have a lot of drawbacks, the industrial application of passive filters is limited. Compared with a passive filter, an active filter can be used to reduce harmonics in industrial mains without worrying about all the problems associated with applying passive filters [1]. The AHC unit enables a controlled compensation of harmonics and reactive currents like active filters, independent of the mains- and current load configuration and without risk of compensator overload. The AHC unit can also be sized for the compensating load requirement only, leading to a reduction of the installation costs of the compensation unit. The following experimental wave forms show the high efficiency of the AHC system for mitigation of harmonics. These wave forms have been created by testing the AHC unit with the power rating 8 kvar on an industrial plant. The AHC unit was connected to 1 kv network by the 1/.4 kv step-down transformer. It was estimated that the active filter would adequately compensate five ac drives supplied by a 12-pulse current source inverter rated up to 1. MW. Fig. 4 shows the wave forms of the line current (one phase) of the ac drive (only one drive) and the phase current (the same phase) of the AHC. These currents were measured on the 1kV side of the transformer. The network current is presented in Fig.5. It is the sum current which is calculated by the oscilloscope from the measured currents from Fig. 4. From Fig. 5 it is seen that the sum network current has practically sinusoidal and periodical wave form. The harmonics of the ac drive current are practically eliminated as you can see from the Spectra of the ac drive current and spectra of network current (see Fig.6). Fig.4: The wave forms of the AHC current and the ac drive current (1kV mains, 2A/div) Fig.5: The currents sum of the measured non-linear load current and of the AHC current (2A/div). I,A 3 2 1 2 4 6 8 1 12 14 16 18 2 22 k Fig.6: Spectra of the ac drive current (lines) and the sum current (dots); the amplitude of the fundamental harmonic is not shown. K represents the number of harmonics. B. Flicker Mitigation Flicker, caused by large fluctuating loads, is one of the power quality problems that include interruption, voltage sags and dips. SCR controlled Static Var Compensators (SVC) are usually used to compensate reactive currents and to reduce the flicker. As it operates

Fig.7: Voltage changes at a 11kV- mains network without AHC (1V/div) Fig.8: Voltage changes at a 11kV- mains network with AHC (1V/div) at the fundamental frequency, the capability of the SVC is limited [9]. Thanks to a delay time of only 2ms the AHC is highly suitable for the flicker compensation. Fig.7 shows the measured voltage changes at the 11kVnetwork during a test of an engine without a compensation unit. The maximum mains voltage change was approximately 1.2%, a number which, for this frequency, is already over the standard limit value for the flicker. The measured value of the short-time flicker P st equals 1.5. In Fig.8 the measured voltage changes is shown at the same test of the motor but this time using the AHC. The mains voltage change is approximately.3% and lies clearly under the standard limit value. The measured value of the short-time flicker P st =.5. C. Compensation unbalanced current from a welding machine Welding machines are well known to draw a high non sinusoidal current in short periods. Even unbalanced line current, where only 2 phases are loaded are common. An example hereof is shown in Fig. 9, where only phase t and s are loaded with a peak current of 12A, while phase r remains unloaded.. Note also the non sinusoidal shape of the current. The AHC will compensate the harmonic distortion as well as the unbalance between the phases as shown in Fig 1. As a result of that load is shared by all three phases, the peak current is significant lower, which also improves voltage quality. The peak current of above 12A in phase s is reduced to 4 A in all three phases.

V CONCLUSION The proposed active harmonic compensation AHC for industrial networks can be successfully used with nonlinear loads and consumers with rapid fluctuations of reactive and active power consumption to improve the supply quality of other loads supplied from the same mains. Clear reduction of the voltage wave form distortion and the voltage changes (flicker effects) as well as the stabilisation of the mains voltage are the main advantages of the proposed AHC. These all make the application of the power electronics to improve the supply voltage quality in industrial networks more effective in comparison to passive filters and PFC capacitors. REFERENCES [1] Akagi, H.: New Trends in Active Filters for Power Conditioning. IEEE Transactions on Industry Applications, Vol.32, No.6, pp. 1313-1322, 1996. [2] Kalachnikov, S. Three-phase rectifier for AC-Drives incorporated with Active Power Filter, Proceedings of the International Power Electronics and Motion Conference, 1998, Prague, Czech Republic., pp. 2125-213. [3] Rummich,E., Kalaschnikow, S.,Oberschwingungs- arme Netzeinspeisung von Windkraftanlagen mit Hilfe von aktiven Filtern, e&i 117. Jg.(2), H.2, pp 129-133. [4] Sabanovic, N., Sabanovic, A., Jezernik, K., Kaynak, O.M.,: Current Control in three-phase switching Converters and ac electrical Machines. In: Proceedings of IECON 94, Italy, 1994, pp. 581-586. [5] Gao, W., Wang, Y., Homaifa, A.,: Discrete-time variable Structure Control System. In: IEEE Transactions on Industrial Electronics, Vol.42, No.2, pp. 117-122, 1995. [6] Fernando, J, Orlandi, E., Pais, M.: Sliding Mode Control of Unity Power Factor Three Phase Boost Converters, Proceedings of International Power Electronics and Motion Conference,1998, Czech Republic.,pp.1125-113. [7] Kalachnikov, S.: Control of the Switch-Mode Rectifier without Mains Voltage Sensors, SPEEDAM 98, Italy, pp.125-128 [8] Kalachnikov, S., Berger, H.: A New Control Strategy for DC-Link Voltage of a Three-Phase Bi-directional PWM Rectifier, EPE`95, Spain, 1995, pp 2558-2562. [9] Guillaume de Préville: Flicker mitigation. Application to a STATCOM, Proceedings of the European Conference on Power Electronics and Applications,21, Austria. Fig.9: The wave forms of the welding machine line currents without AHC Fig.1: The wave forms of the welding machine line currents with AHC