A NOVEL METHOD FOR ENERGIZING TRANSFORMERS FOR REDUCING INRUSH CURRENTS

Similar documents
ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

MATHEMATICAL MODELING OF POWER TRANSFORMERS

ANEW, simple and low cost scheme to reduce transformer

of the improved scheme is presented. Index Terms Inrush current, power quality, transformer.

Simultaneous AC-DC Transmission Scheme Under Unbalanced Load Condition

Electromagnetic Oscillations and Currents. March 23, 2014 Chapter 30 1

Mitigation of an Inrush Current of Power Transformer by using PWM-Inverter based Series Voltage Compensator

PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS

Abstract- At the time of transformer energization, a high current will be drawn by the transformer. The mentioned current

The power transformer

Combined analytical and FEM method for prediction of synchronous generator no-load voltage waveform

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

TEST VOLTAGES INFLUENCE ON TURN RATIO TESTING ndb Technologies model ART-3D

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

FERRORESONANCE SIMULATION STUDIES USING EMTP

ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT

Comprehensive Study on Magnetization Current Harmonics of Power Transformers due to GICs

Transformer Thermal Impact Assessment White Paper Project (Geomagnetic Disturbance Mitigation)

Effect of Harmonics on the Performance Characteristics of Three Phase Squirrel Cage Induction Motor

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

ESO 210 Introduction to Electrical Engineering

Transformer Protection

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor

Effects of Harmonic Distortion I

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Transformer Thermal Impact Assessment White Paper (Draft) Project (Geomagnetic Disturbance Mitigation)

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

CHAPTER 9. Sinusoidal Steady-State Analysis

86 chapter 2 Transformers

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

Beyond the Knee Point: A Practical Guide to CT Saturation

Long lasting transients in power filter circuits

v o v an i L v bn V d Load L v cn D 1 D 3 D 5 i a i b i c D 4 D 6 D 2 Lecture 7 - Uncontrolled Rectifier Circuits III

Transients under energizing multiple power filter circuits

MILWAUKEE SCHOOL OF ENGINEERING LABORATORY SESSION 4 THREE PHASE TRANSFORMERS

Speed control of double stator synchronous machine supplied by two independent voltage source inverters

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Lecture 4 - Three-phase circuits, transformer and transient analysis of RLC circuits. Figure 4.1

Simulation and Analysis of Ferroresonance in Power System

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Wireless Communication

Harmonic Immunity And Power Factor Correction By Instantaneous Power Control Of D-STATCOM

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

TPL is a new Reliability Standard to specifically address the Stage 2 directives in Order No. 779.

El-Hawary, M.E. The Transformer Electrical Energy Systems. Series Ed. Leo Grigsby Boca Raton: CRC Press LLC, 2000

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Tab 2 Voltage Stresses Switching Transients

Summary of the Impacts of Grounding on System Protection

Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component

Improvement of Power Quality Using a Hybrid Interline UPQC

ENERGISING INRUSH CURRENT TRANSIENTS IN PARALLEL-CONNECTED TRANSFORMERS

Demagnetization of Power Transformers Following a DC Resistance Testing

Investigation of Magnetic Field and Radial Force Harmonics in a Hydrogenerator Connected to a Three-Level NPC Converter

Evaluating the Impact of Increasing System Fault Currents on Protection

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

In power system, transients have bad impact on its

CH 1. Large coil. Small coil. red. Function generator GND CH 2. black GND

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Chapter 16: Mutual Inductance

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

FRIENDS Devices and their Coordination

CHAPTER 1 INTRODUCTION

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Experiment 1 LRC Transients

Bahram Amin. Induction Motors. Analysis and Torque Control. With 41 Figures and 50 diagrams (simulation plots) Springer

DC-GRID PHYSICAL MODELING PLATFORM DESIGN AND SIMULATION*

Estimation of Vibrations in Switched Reluctance Motor Drives

Advanced electromagnetism and electromagnetic induction

Address for Correspondence

Introduction to Rectifiers and their Performance Parameters

Innovative Science and Technology Publications

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

Bucking Coils produce Energy Gain Cyril Smith, 2015

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Sensorless Control of a Novel IPMSM Based on High-Frequency Injection

Open Access Research on Fast Response Characteristic of Magnetic Control Reactor

A Switched Boost Inverter Fed Three Phase Induction Motor Drive

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Power. Power is the rate of using energy in joules per second 1 joule per second Is 1 Watt

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM

Exercise 9: inductor-resistor-capacitor (LRC) circuits

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

Unit-4. Magnetic Circuits

Pre-insertion Resistor of Switching Shunt Capacitor Banks

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Importance of Transformer Demagnetization

Chapter 33. Alternating Current Circuits

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Considerations for Choosing a Switching Converter

UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE

Power Factor & Harmonics

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

Transcription:

A OVEL METHOD FOR EERGIZIG TRASFORMERS FOR REDUCIG IRUSH CURRETS M.B.B. Sharifian, Farhad Shahnia, Ali Shasvand 3, Iraj hasanzadeh 4,3,4 Faculty of Electrical and Computer Engineering, University of Tabriz, Tabriz, Iran Eastern Azarbayjan Electric Power Distribution Company, Tabriz, Iran sharifian@tabrizu.ac.ir, shahnia@tabrizu.ac.ir, 3 alishasavand@yahoo.com, 4 hasanzadeh@tabrizu.ac.ir Abstract: Control and reduction of inrush currents of energizing transformers and reactors is an important problem in electric power systems where different methods are utilized for this purpose. In this paper, reviewing the most common methods, a novel method has been proposed and utilized for inrush current reduction in energizing transformers. In the proposed method, non simultaneous three phase switching is done within 0 cycles of time difference and a more little neutral point resistance has been utilized. Through the simulation results done with PSCAD/EMTDC, the efficiency of the proposed method in reducing the inrush current of energizing transformers as fast as possible is proved. Keywords: Inrush current, Transformer energizing, onsimultaneous switching I. ITRODUCTIO One of the most important facts about energizing the transformers and reactors in power systems is related to the inrush currents generated and distributed in the system. Several methods are utilized for controlling and reducing the amount of the inrush currents of energizing transformers. The conventional methods suffer from the high values of the resistances and the great amount of the loss, therefore, the studies on proposing and applying newer methods with less problems and loss are under investigation. Meanwhile, power quality standards and reconstruction of the power systems enforce the electric utilities to decrease the amount of the inrush current generated by energizing the transformers. The other significant disadvantages of the inrush currents are as follows: - Incorrect operation and failures of electrical machines and relay systems - Electrical and mechanical vibrations among the windings of the transformer - Irregular voltage distribution along the transformer windings - High amount of voltage drop at the power system at energization times - Possibility of resonances in the power system due to the various frequencies of the inrush current - Current disturbances and harmonics increase in the system and lower power quality characteristics Therefore, it is of great importance to propose and apply new methods for energizing the transformers in the power systems to prevent the mentioned problems while improving the power quality standards in the power system which will result in the satisfaction of the costumers. In this paper, reviewing the most common methods, a novel method has been proposed and utilized for inrush current reduction when energizing transformers. In the proposed method, non simultaneous three phase switching is done within 0 cycles of time difference and a more little neutral point resistance has been utilized. The proposed method is capable of reducing the inrush current faster than the other conventional methods with less generated loss in the system. Through the simulation results done with PSCAD/EMTDC, the efficiency of the proposed method in reducing the inrush current of energizing transformers as fast as possible is proved. II. A OVEL PROPOSED METHOD Inrush currents are due to the flux variations in the transformer core which is dependent to network voltage. Therefore, considering the network voltage as: U = U m sin( ω t + 0) () ϕ where U m,ω and ϕ 0 are the voltage amplitude, angular frequency and phase difference of the transformer fed voltage. Therefore, the transformer core flux equation is: r r t t L L t = ϕp + ϕl = ϕ m[cos( ωt + ϕ e 0 ) cosϕ 0 ] ± ϕreme ϕ () where L and r are the inductance and resistance of the primary winding, ϕ rem as the hysterisis flux and ϕ m as the maximum flux at the steady-state, ϕ p as the steady-state component and ϕ L as the transient component of the core flux. Therefore, the parameters in Eq. can be utilized for reducing the transient flux of the transformer which would result in decreasing the transformer inrush current. Some of the common solutions for this purpose are: - Reducing the hysterisis flux of the transformer - Switching on the transformer at voltage peak - Increasing the frequency at switching time - Reducing the voltage at switching time

- Utilizing starting resistances Since the inrush currents of the transformer are unbalanced, this will result in the inrush current flow through the transformer neutral point. Utilizing a series resistance in the neutral point of the transformer will behave as a starting series resistance and can improve the inrush current reduction. The schematic diagram of the proposed method is shown in Fig. where a low rating switch is also needed. There would not be great decrease in the inrush current when the three phases of the transformer are switched on simultaneously but it decreases greatly when they are switched on non-simultaneously and respectively. Fig. 3. Inrush current waveform in three-phase simultaneous switching method at peak voltage of one phase (custom method). C (without considering the initial peak magnitude) is respectively equal to 67, 80 and 87 amperes. on-simultaneous switching at peak voltage without neutral resistance (custom method) In this transformer energizing method, non-simultaneous switching of three phases occurs at peak voltage of each phase where the related inrush current of the transformer is as shown in Fig. 4. Fig.. Proposed method of energizing transformer utilizing neutral point resistance. III. AALYSIS AD SIMULATIO OF THE PROPOSED METHOD A 00 MVA, 30/66 kv Y three phase transformer has been simulated with PSCAD/EMTDC software for studying the inrush current characteristics of energizing the transformer with different methods. Later on, the proposed method has also been applied to study the reduction of the inrush currents, too. Simultaneous switching without neutral resistance (custom method) In this transformer energizing method, simultaneous switching of three phases occurs at any time except peak voltage of the phases (for example when voltage of phase A is zero) where the related inrush current of the transformer is as shown in Fig.. Fig.. Inrush current waveform in three-phase simultaneous switching method (custom method). C is respectively equal to 83, 575 and 556 amperes. Simultaneous switching at peak voltage without neutral resistance (custom method) In this transformer energizing method, simultaneous switching of three phases occurs at peak voltage of one phase (for example phase A) where the related inrush current of the transformer is as shown in Fig. 3. Fig. 4. Inrush current waveform in three-phase non simultaneous switching method at peak voltage of each phase (custom method). C (without considering the initial peak magnitude) is respectively equal to 74, 48 and 50 amperes. Studying these simulation results, it is proved that nonsimultaneous switching at peak voltage of each phase is more capable of reducing transformer inrush current when energizing, in comparison with other conventional methods. on-simultaneous switching at peak voltage (proposed method) The most significant parameter of the proposed method is the neutral point resistance. Through the simulation results, it is proved that the higher the resistance value, the more reduction in the inrush current of the first phase since the resistance is in series with the first phase. But this leads to an increase in the first phase when switching the second phase. This characteristic has been shown in Fig. 5. Fig. 5. Current flow characteristics for energizing second phase. Increasing the resistance value ( R = ), the three-phase transformer circuit is equal to two line voltage fed singlephase transformers in series with each other which results

in an increase of the inrush current. The inrush current also increases when switching the third phase while the resistance is connected to the circuit. Therefore, it is preferred to disconnect the resistance when switching the third phase. This can show the poor performance of the described non-simultaneous energizing method where the problem is about energizing the second and third phases. For example, the energizing method for switching the second phase of the transformer is shown in Fig. 6. Fig. 6. Schematic diagram of proposed transformer energizing method. Since, a no-load transformer is equal to three coupled windings, the electrical equations of the transformer at the steady state can be written as: Axf X s X m X m I V = xf = VBxf j X m X s X m I B (3) VCxf X m X m X s IC Where X s and X m are mutual and self inductances of each equal branch of the transformer (without considering the resistances) and V xf as shown in Fig. 6. The most important parameter is the voltage on the switch of phase B which is shown as VB in Fig. 6. According to the characteristics of the circuit, we have: I. If V B = 0, the second phase switching would not cause any transients in the current waveforms. II. If the saturation effect of the transformer is neglected, the second phase switching would cause current transients with the amplitude equal to VB. III. If the saturation effect of the transformer is considered, the current transients due to the second phase switching would increase in according with the increase in VB where the relation of the inrush current and V B is nonlinear. Since, the inrush current amplitude can be controlled by VB indirectly, the relation between VB and R should be studied. Therefore, according to Fig. 6, VB can be written as: V = R I VB = EB VB E X s X m X m I + VB = j X m X s X m 0 (4) VC X m X m X s 0 Solving the equations for VB, we have: X m + X s + 3R VB = E 3 + ( X m X s ) (5) R + X s Similarly, the same equations can be written for the steady state condition of the circuit before the third phase switching as: V R ( I + I B ) V = E V = A C C C E X s X m X m I + VB = j X m X s X m I B VC X m X m X s 0 Solving the equations for VC m ) m ), we have: VC = E 9R + ( X s + X 4R + ( X s + X (7) The best point for selection of neutral point resistance is when V = V, therefore, we have: B C 9R + ( Xs + Xm) Xm + Xs + 3R = 3+ ( X ) m Xs 4R + ( Xs + Xm) R + Xs (8) Since, Eq. 8 can not be solved through analytical methods, numerical methods can be applied. This equation shows R variations in accordance with X S and X m parameters. X S and X m parameters of the transformer can be calculated through short-circuit and no-load tests of the transformer. Since the short-circuit impedance of the transformer is littler in comparison with no-load impedance, we have: X S = X open X m = X open 3 3 (9) Inserting Eq. 9 in Eq. 8, the optimized value of the neutral pointy resistance of the transformer is calculated as: 3 3R X open + 3X open 7R = 9R + 4X open 36R + X open (0) Therefore, we have: R Optimal 0. 085X open () (6) V Optimal 0. 68E () The neutral point resistance, varies the steady-state voltage of the third phase switch, therefore, if the resistance voltage is equal to zero, the third phase switch would be zero, as shown in Fig. 7. Finally, it should be noticed that utilizing non-simultaneous three phase switching and disconnecting the neutral point resistance, the inrush current due to the third phase switching will disappear. Fig. 7. Magnetic flux flow characteristics for energizing the third phase. As shown in Fig. 7, the first and second phases are energized, so the core flux of the third phase is equal to: φ C = ( φa + φb ) (3) And the induced voltage in the third phase is equal to:

dφ c d( φa + φb ) dφa dφ v b c = = = = ea eb = ec (4) dt dt dt dt Eq. 4 proves that the induced voltage is equal to the source voltage therefore no inrush current would happen at the third phase switching. In addition, if R is great enough, the energizing conditions would be the same as energizing the second phase; therefore, the neutral point resistance selection is of great importance in inrush current reduction. In the simulations done with PSCAD/EMTDC, a nonsimultaneous switching within 0 cycles has been applied for energizing the transformer. The neutral point resistance has 0., and 000 kilo ohms values which are disconnected at third phase switching time. Fig. 9. Inrush current waveform in non simultaneous switching method in peak voltages with a kilo ohms resistance at neutral point (proposed method) for Phases A, B, C, three windings fluxes and the current of three phases (from top to bottom respectively). Fig. 8. Inrush current waveform in non simultaneous switching method in peak voltages with a 00 ohms resistance at neutral point (proposed method) for Phases A, B, C, three windings fluxes and the current of three phases (from top to bottom respectively). Fig. 0. Inrush current waveform in non simultaneous switching method in peak voltages with a Mega ohms resistance at neutral point (proposed method) for Phases A, B, C, three windings fluxes and the current of three phases (from top to bottom respectively). DC current injection through three adjustable current sources In this method, utilizing three adjustable DC current sources, some DC current is injected to the transformer prior to energizing which results in decreasing the inrush

current through varying the transformer hysterisis flux. The schematic diagram of this method is also shown in Fig.. IV. COCLUSIO In this paper, different methods for control and reduction of inrush currents of energizing transformers in electric power systems were studied and a novel method was proposed. The proposed method is based on nonsimulations three phase switching within 0 cycles where a little neutral point resistance has also been utilized. Through the simulation results done in PSCAD/EMTDC, the efficiency of the proposed method in reduction of inrush currents as fast as possible was proved. Fig.. Transformer energizing method utilizing DC current injection method. Utilizing this method for the simultaneous switching of the transformer at the peak voltage of phase A, when energizing, the required DC current to be injected to the transformer equals 0.0, 0 and 0. amperes for phases A, B and C, respectively. Studying the waveforms of the windings fluxes and inrush currents in this method as shown in Fig., it is proved that the inrush current of the transformer has been reduced greatly. V. REFERECES [] Y. Cui, S.G. Abdulsalam, S. Chen, W. Xu, "A sequential phase energization technique for transformer inrush current reduction- part I, IEEE Trans. on Power Delivery, Vol. 0, o., April 005. [] W. Xu, S.G. Abdulsalam, Y. Cui, X. Liu, "A sequential phase energization technique for transformer inrush current reduction- part II, IEEE Trans. on Power Delivery, Vol. 0, o., April 005. [3] J.H. Brunke, K.J. Frdhlich, "Elimination of transformer inrush currents by controlled switching", IEEE Trans. on Power Delivery, Vol. 6, o., April 00. [4] M. Steurer, K. Frohlich, "The impact of inrush currents on the mechanical stress of high voltage power transformer coils", IEEE Trans. on Power Delivery, Vol. 7, o., Jan. 00. Fig.. Waveforms of fluxes of windings (top) and inrush currents of phases (bottom) in simultaneous switching method utilizing DC current injection method. Applying this method for the proposed non-simultaneous switching of the transformer within 0 cycles and injecting -0.0576, -0.0339 and -0.66 amperes, the inrush current of the transformer has been reduced greatly as shown in Fig. 3. Studying this figure, it is shown that the inrush current exists in the first 0 cycles and before the third phase switching which disappears by switching the third phase of the transformer. Fig. 3. Waveforms of fluxes of windings (top) and inrush currents of phases (bottom) in non-simultaneous switching method utilizing DC current injection method.