PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

Similar documents
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

HOW TO SAFE GUARD THE TRANSFORMER..???

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

OIL-IMMERSED ARC-SUPPRESSION COILS

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

Distribution transformers Part 2 Ground mounted transformers not closecoupled

Liquid-Filled Transformers

SECTION TRANSFORMERS

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

General Electricity Company of Libya

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

COMMISSION REGULATION (EU) No /.. of XXX

DISTRIBUTION TRANSFORMERS

Introduction. Centrado leading-edge transformer. Introduction

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

Substation Preventive Maintenance

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

Basic Principles and Operation of Transformer

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

Distribution Transformers

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

TECHNICAL SPECIFICATION

7. INSPECTION AND TEST PROCEDURES

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

INTERNATIONAL STANDARD

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

ELETTROMECCANICA. Since english OIL IMMERSED DISTRIBUTION TRANSFORMERS

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

TRANSFORMER OPERATIONAL. Principles, Selection & Troubleshooting

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

EE059: Transformer Operation, Maintenance, Diagnosis & Testing

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

INTERPLANT STANDARD - STEEL INDUSTRY CODE OF PRACTICE FOR TESTING & COMMISSIONING OF TRANSFORMERS AND RELATED SWITCHGEARS

ECP DISTRIBUTION TRANSFORMER COMMISSIONING PROCEDURE

SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers

Powering Your Business

1ZSC AAJ en, Rev. 1. Vacuum on-load tap-changers, type VUBB Technical guide

PPC TECHNICAL SPECIFICATION D/ NCMD / THREE-PHASE DISTRIBUTION TRANSFORMERS

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

Substation transformers

Howard Smart Transformer Specification Guide

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

TECHNICAL SPECIFICATION

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

Distribution/Substation Transformer

Distribution Equipments - Technology and Applications. Training Module for DISTRIBUTION TRANSFORMER

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

Reference Number PPS 05 - (RIC Standard: EP SP)

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

Reactor and inductor are names used interchangeably for this circuit device.

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Transformer Protection

NSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

GUJARAT TECHNOLOGICAL UNIVERSITY, AHMEDABAD, GUJARAT

MODERN POWER TRANSFORMER PRACTICE BIBLIOGRAPHY

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

Distribution and Power Transformers

PS REV NO: 01 PAGE : 2 OF 22

American Electrical Institute

Particulate Control O&M Training. APC/PCUG Conference July 12-16, 2009 The Woodlands, TX

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

Cast resin transformers HARMONY TM

Article 250 Grounding & Bonding

THREE-PHASE DISTRIBUTION TRANSFORMERS

Arc Suppression Coils

Power Transformers Basics

User s Manual For CT Model IMB

DISTRIBUTION TRANSFORMER kv

installation guide For Oil and Synthetic Ester filled Transformers

Mechanical Design. Brian Brinson Mechanical Design Manager.

Transcription:

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n

Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established under the BIS Act 1986 for the harmonious development of the activities of standardization, marking and quality certification of goods New BIS Act 2016 has also been passed by the Parliament.

BIS is involved in various activities as given below: a.standards FORMULATION b.product Certification Scheme c.compulsory Registration Scheme d.foreign Manufacturers Certification Scheme e.hall Marking Scheme f.laboratory Services g.laboratory Recognition Scheme h.sale of Indian Standards i.consumer Affairs Activities j.promotional Activities k.training Services, National & International level l.information Services

Areas of Standardization Chemical Food and Agriculture Metallurgical Engineering Civil Engineering Management and Systems Petrochemical, Coal & Related Products Transport Engineering Electronics and Information Technology Electrotechnical Mechanical Engineering Medical Equipment and Hospital Planning Production and General Engineering Water Resources Textiles

Indian Standards developed through involving all concerned Stakeholders. technical committees Presently, there are 43 technical committees working under the Electrotechnical Division Council. Transformers Sectional Committee, ETD 16 is one of these technical committees formulating Standards related to Transformers. Decisions in BIS technical committees are reached through consensus.

COMPOSITION OF STANDARD FORMULATION COMMITTEE Professional & Academic Bodies Consulting Firms Public Sector Units Industry Association Chairman (Independent Body) Member Secretary (BIS) COMPOSITION of STANDARD FORMULATION COMMITTEE Consumer/ User Organization Manufactur er Laboratories/ R&D Institutions Government & Regulatory Bodies

STAGES OF STANDARD FORMULATION Stage 2 : Building consensus among committee members Stage 3: Building national consensus International Training Programme, 10 May 2012

IS 1180(Part 1): 1989 - Outdoor type three phase distribution transformers upto and including 100kVA 11 kv Part 1: Non sealed type. IS 1180(Part 2): 1989 - Outdoor type three phase distribution transformers upto and including 100kVA 11 kv Part 2: Sealed type. Scope was limited upto three phase 100 kva, 11kV.

IS 1180 (PART 1) : 2014 IS1180 (Part 1) has been revised by taking into account the needs of various stakeholders and technological developments taken place on transformer. Title of IS 1180 (Part 1) : 2014 Outdoor/Indoor Type Oil Immersed Distribution Transformers Up to and Including 2 500 kva, 33kV Specification: Part 1 Mineral Oil Immersed (Fourth Revision). Two amendments have been published.

SALIENT FEATURES OF IS 1180(Part 1): 2014 Includes Outdoor type as well as Indoor type three phase Distribution Transformers upto and including 2500 kva with nominal system voltage upto and including 33 kv (both sealed and non-sealed). Includes Single phase Distribution Transformers upto and including 100 kva (sealed type).

Following types of transformers are not covered: a) Inverter duty transformers; b) Traction transformers; c) Instrument transformers; d) Transformers for static converters; e) Starting transformers; f) Testing transformers; p) Rectifier transformers; and h) Earthing transformers; g) Welding transformers; j) Mining transformers; k) Transformers for solar, wind power application; m) Transformers for railways (locomotive and other applications); n) Furnace transformers; q) Dual ratio in primary/secondary windings transformers. relevant CEA guidelines must be followed while using mineral oil filled DT s indoor. In case of indoor transformers and transformers installed in an enclosure, suitable ventilation, if required, shall be provided to maintain service conditions as per IS 2026 (Part 1).

WHAT IS A DISTRIBUTION TRANSFORMER A distribution transformer is a transformer that provides the final voltage transformation by stepping voltages down within a distribution circuit or from a distribution circuit to an end user or application. NOTE The distribution circuit voltages are 3.3 kv, 6.6 kv, 11 kv, 22 kv and 33 kv in the country. The power supply for the end users is 415 volt, 3 Phase (240 volt, 1 phase), 50 Hz. Transformers with primary voltages of 3.3, 6.6, 11, 22 or 33 kv and secondary voltage of 433 volt, 3 Phase (and 250 volt single phase) are called Distribution Transformers. The maximum rating of these transformers for the purpose of this standard is considered up to 2 500 kva, 3 Phase.

SERVICE CONDITIONS Service conditions shall be as per IS 2026 (Part 1) : 2011. In case of indoor transformers and transformers installed in an enclosure, suitable ventilation, if required, shall be provided to maintain service conditions as per IS 2026 (Part 1).

Sl Nominal System No. Voltage Standard Ratings (kva) 1. Up to and including 11 kv *6.3, *10,16, *20, 25, *40, 63, 100, 160, 200, 250, 315, 400, 500, 630, 800, 1 000, 1 250, 1 600, 2 000 and 2 500 2. Above 11 kv up to and including 22 kv 63, 100, 160, 200, 250, 315, 400, 500, 630, 800, 1 000, 1 250, 1 600, 2 000 and 2 500 3. Above 22 kv up to and including 33 kv 100, 160, 200, 250, 315, 400, 500, 630, 800, 1 000, 1 250, 1 600, 2 000 and 2 500 Note: * ratings are non preferred.

b) Single phase distribution transformers Sl Nominal System No. Voltage Standard Ratings (kva) 1. 11 kv 5, 10, 16, 25, *50, *75 & *100 2. 22 kv 10, 16, 25, *50, *75 & *100 3. 33 kv 16, 25, *50, *75 & *100 Note: * ratings are non preferred.

Basic insulation level values given are MINIMUM VALUES. NOTE: Insulation coordination of all relevant fittings and accessories corresponding to higher BIL values shall be ensured. a) For three phase DTs Sl No. (1) 1. Nominal System Voltage (kv) (2) 3.3 Minimum BIL (kvp) (3) 40 1. 6.6 60 1. 11 75 1. 22 125 1. 33 170

b) For single phase DTs Sl No. (1) Minimum BIL (kvp) (3) 1. Nominal System Voltage (kv) (2) 11 1. 22 125 1. 33 170 75

TAPPINGS No taps are generally required upto 100 kva, unless specified. Standard tapping range is given below: Transformer range No. of tap positions Voltage variation 3 phase transformers upto and including 200 kva 4 +2.5% to -5% of HV in steps of 2.5 percent 3 phase transformers higher than 200 kva and upto and including 2500 kva 7 +5% to -10% of HV in steps of 2.5 percent for variation of HV NOTE: 1) For ratings 500 kva and above, on load tap changers may be provided for variation of HV voltage from +5 percent to 15 percent in steps of 2.5 percent 2) Off-circuit tap-changing is permitted Provision of any other tapping range and tapping step is subject to agreement between the user and the supplier

LOSSES Losses given in Table 3, Table 6 and Table 9 are MAXIMUM TOTAL LOSSES These losses are only for transformers upto 11kV voltage class For 22 kv and 33 kv class higher losses values permitted (as given in the next slide) Losses for non-preferred ratings have been added throung amendment.

Maximum total losses for voltage class above 11 kv is given in table below: Voltage class Maximum total losses for 3 phase transformers upto and including 200 kva Maximum total losses for 3 phase transformers higher than 200 kva and upto and including 2500 kva Above 11 kv and upto and including 22 kv Shall not exceed by 5% Shall not exceed by 5% of the of the maximum total maximum total losses given in losses given in Table 3 Table 6 Shall not exceed by 7.5% of the maximum total losses given in Table 9 Above 22 kv and upto and including 33 kv Shall not exceed by 7.5% of the maximum total losses given in Table 3 Shall not exceed by 10% of the maximum total losses given in Table 3 Shall not exceed by 7.5% of the maximum total losses given in Table 3 Maximum total losses for single phase transformers upto and including 25 kva

LIMITS OF TEPERATURE RISE Limits are given as below: Transformer class Limits for temperature rise 3 phase transformers upto and including 200 kva For transformer winding - 40 C (when measured by resistance method) For top oil - 35 C (measured by thermometer) 3 phase transformers higher For transformer winding - 45 C (when measured by than 200 kva and upto and resistance method) including 2500 kva For top oil - 40 C (measured by thermometer) single phase transformers upto and includng 25 kva For transformer winding - 40 C (when measured by resistance method) For top oil - 35 C (measured by thermometer) These are maximum limits of temperature rise. Lower temperature rise limits are acceptable but it might increase the cooling equipment cost.

% IMPEDENCE VALUES Values of % impedance given in IS 1180 (Part 1) : 2014 are only RECOMMENDED VALUES. Manufacturers can prefer other values while designing. Higher impedance values might lead to poor regulation, more stray losses and heating, therefore small variation in these values is suggested.

STANDARD MATERIALS Major material used in the transformer shall conform to the following Indian Standards: a) Cold rolled grain oriented electrical steel IS 3024 b) Amorphous core material (IS 16585) c) Copper/Aluminum conductor IS 191, IS 1897, IS 7404, IS 12444, IS 13730/IS 6162 series as given in Annex A. d) Kraft paper IS 9335 series as given in Annex A. e) Press board IS 1576 f) f) Mineral oil IS 335 NOTE Use of other insulating liquids namely natural ester, synthetic organic ester IS 16081 subject to agreement between the user and the supplier

MOUNTING ARRANGEMENT Mounting arrangement is given in cl 14: a) Upto 200 kva: two channels of minimum size 75 mm 40 mm shall be provided. Note added under Fig. 6 Any other mounting dimensions are subject to agreement between the user and the supplier. b) Beyond 200 kva Bidirectional rollers can also be used as per mutual agreement between the user and the supplier. Any other mounting dimensions are subjected to agreement between the user and the supplier.

Suitable pole mounting arrangement may be alternatively provided for 3 phase transformers upto 500 kva, subject to agreement between user and supplier. Single phase transformers are pole mounted type and shall be provided with two mounting lugs suitable for fixing the transformer to a single pole by means of two bolts of 20 mm diameter. Both mounting lugs are made with steel of minimum 5 mm thickness.

PAINT THICKNESS Measuring Paint Thickness is not a part of the tests specified in IS 1180 (Part 1). This is for guidance to the stakeholders. It is to be ensured by the Inspecting agencies at the time of factory visit. CONSTRUCTION REQUIREMENTS FOR TRANSFORMER TANK Given under clause 15. Minimum thickness at the corrugations shall be 1.0 mm

STANDARD FITTINGS given under clause 20.1 These fittings shall be provided by the manufacturer. a) Two earthing terminals with the earthing symbol ; b) Oil level gauge indicating oil level at minimum, 30 C and maximum operating temperature; NOTES 1 Minimum and maximum positions correspond to the operating temperature of 5 C and 90 C respectively (for non-sealed type transformer). 2 Only minimum position corresponding to the operating temperature of 30 C (for sealed type transformers). c) Air release device (for non-sealed type transformers); d) Rating and terminal marking plates; e) Dehydrating breather shall be provided for non-sealed type transformers; f) Drain-cum-sampling valve preferably steel with plug for three phase transformers (for ratings above 500 kva); NOTE Valve size shall be as per agreement between the user and the supplier.

g) Thermometer pocket with cap; h) Oil/Nitrogen/Air filling hole having (1¼ nominal size thread) with cover (for sealed type transformers without conservator); j) Lifting lugs for the complete transformer as well as for core and winding assembly; k) Pressure relief device or explosion vent [for sealed type transformers (for all ratings) and non-sealed type transformers (for ratings above 200 kva)]; m) One filter valve on the upper side of the tank (for transformers above 200 kva); n) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); p) LV earthing arrangement for single phase transformers; q) Buchholz relay for transformers above 1 000 kva; and r) Arcing horns for HT side (one number per phase).

OPTIONAL FITTINGS given under clause 20.2: These fittings may be provided at the option of the user wherever specified. a) Dehydrating breather in lieu of plain breathing device for transformers up to 200 kva; b) Filter valve for transformers up to 200 kva; NOTE Valve size shall be as per agreement between the user and the supplier. a) Suitable rating lightning arrestors for HT side (one number per phase); b) Bird guard; c) Terminal connectors d) Oil temperature indicator and winding temperature indicators for transformers above 200 kva; e) Jacking pads (for transformer above 1 600 kva); f) Buchholz relay (for transformers above 200 kva); j) Magnetic oil level gauge (for transformer above 1 600 kva) with low oil level alarm contact;

k) Non return valve (for conducting pressure test); m) Pressure relief device or explosion vent (upto 200 kva for non-sealed type transformers); n) Protection relay for sealed type transformers for internal parameters that is pressure, temperature, oil level and gas detection; p) 4 Nos anti-theft stainless steel fasteners with breakaway nut shall be provided at top cover (up to 200 kva). NOTE IS 3639 describes some of the fittings and accessories. q) Unidirectional flat rollers (for transformers above 200 kva); r) Drain-cum-sampling valve preferably steel with plug for three phase transformers (for transformers upto 500 kva); and NOTE Valve size shall be as per agreement between the user and the supplier. s) Self protection/disconnection devices subject to agreement between the user and the supplier: 1) Thermo-magnetic circuit breaker as self protection device on secondary side as per IS/IEC 60947-2 : 2003; and 2) Expulsion fuse as disconnection device on primary side as per IS 9385 (Part 2) : 1980. NOTE Additional requirements for transformers with self protection/disconnection devices are under preparation.

TEST REQUIREMENTS All routine, type and special tests as described in 21.2 to 21.4 shall be performed as per relevant parts of IS 2026. ROUTINE TESTS (to be conducted on all units) a) b) c) d) e) f) g) Measurement of winding resistance [IS 2026 (Part 1)]. Measurement of voltage ratio and check of phase displacement [IS 2026 (Part 1)]. Measurement of short-circuit impedance (principal tapping, when applicable) and load loss at 50 percent and 100 percent load [IS 2026 (Part 1)]. Measurement of no-load loss and current [IS 2026 (Part 1)]. Measurement of insulation resistance [IS 2026 (Part 1)]. Induced over-voltage withstand test [IS 2026 (Part 3)]. Separate-source voltage withstand test [IS 2026 (Part 3)]. Note: For single phase transformer with 11/ 3 or 22 / 3 or 33/ 3 kilo volts and with 1.0 kv neutral bushing, this test shall be conducted at test voltage of neutral (3 kv rms for one minute). h) Pressure test (see 21.5). j) Oil leakage test (see 21.5).

TYPE TESTS (to be conducted on one unit) a. Lightning impulse test [IS 2026 (Part 3)]. b. Temperature-rise test [IS 2026 (Part 2)]. c. Short-circuit withstand test [IS 2026 (Part 5)] (up to 200 kva). NOTE Routine tests before and after short circuit test shall be conducted as per IS 2026 (Part 1). a. Pressure test requirements given for both single phase as well as three phase transformers. i. Upto 200 kva: Test requirements for corrugated tanks added Limits of deflection given. Permanent deflection is not applicable for corrugations ii. Beyond 200 kva Test requirements for corrugated tanks added Limits of deflection given. Permanent deflection is not applicable for corrugations Additional information on leakage test has been provided in ANNEX E

c) SPECIAL TESTS (to be conducted on one unit) a) Determination of sound levels [IS 2026 (Part 10)] b) Short-circuit withstand test [IS 2026 (Part 5)] (above 200 kva) NOTE Routine tests before and after short circuit test shall be conducted as per IS 2026 (Part 1). c) No load current at 112.5 percent voltage (see 5.9.3). d) Paint adhesion tests. The test is performed as per ASTM D3359 (Standard Test Methods for measuring adhesion by Tape test). e) BDV and moisture content of oil in the transformer (IS 335). NOTE Tests at (d) and (e) may be carried out on more than one unit subject to agreement between user and supplier. These are subject to agreement between user and supplier

The efficiency to be declared is the ratio of the output in kw to the input in kw and calculated as under. Efficiency = output/input = input- total losses/ input Total losses comprise: No-load loss, which is considered to be constant at all loads : and Load loss, which varies with load. The total loss, on load is the sum of above losses.

The following information should be given in all cases: Particulars of the specification to be complied with; Application of Transformer e.g. normal Distribution Transformer, Solar duty, wind application, Motor starting etc. Single or three phase unit; Number of phases in system; Frequency; Indoor or outdoor type; Type of cooling; Rated power (in kva) Rated voltages (for each winding); State if tappings are required and if on-load or off-circuit tap-changers, or links are required. Highest voltage for equipment (for each winding); Method of system earthing (for each winding); Insulation level (for each winding), power frequency test level/impulse level; Connection symbol; Neutral terminals, if required (for each winding) and their insulation level to earth; Special requirements of installation, assembly, transport and handling; Fittings required and an indication of the side from which meters, rating plates, oil-level indicator, etc. may be readable.

The following additional information may be required to be given: If a lightning impulse voltage test is required, whether or not the test is to include chopped waves [see IS 2026 (Part 3)]. Impedance voltage at rated current, if specific value is required; Altitude above mean sea-level, if in excess of 1 000 m; Whether transformers will be subjected to frequent overcurrent, for example, furnace transformers and traction feeding transformers; Any other exceptional service conditions; Whether noise level measurement is to be carried out; Vacuum withstand of the transformer tank, if a specific value is required; Type of Tap-changer controls required (if OLTC is provided); Type of mounting for example pole mounted, ground mounted etc. Any other appropriate information, including reference to any special tests not referred to above which may be required.