POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

Similar documents
Power Processor - Series 700F 10KVA to 150KVA

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System

Liebert Datawave. GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL

Power-Sure 700. Technical Data TD158001EN. Contents

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

TOSHIBA International Corp

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

ULTRA-K Series 600K - he

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

TOA PROFESSIONAL POWER AMP

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:

SECTION PANELBOARDS

SECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM

SINGLE-PHASE VSV SWITCH

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

B. Manufacturers: Square-D, G.E. or Westinghosue.

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

STATIC UNINTERRUPTIBLE POWER SYSTEM Revised 4/30/ Electrical Systems

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Power Commander. Power Commander Plus. Electronic Line Voltage Regulators. 15 kva 150 kva SINGLE PHASE 15 kva 450 kva THREE PHASE SERIES 900

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

Harmonic Correction Unit NEMA 1 Enclosure

PROFESSIONAL POWER AMP

Variable Transformers Product Design & Engineering Data

SINGLE-PHASE VSV SWITCH

SECTION TRANSFORMERS

2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS

CROSS Chassis from 160 A to 450 A

Straight Isolation - Plug In (171 Series)

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Phoenix DX Clean Power (18 Pulse) AC Drive

Industrial Electrician Level 3

PRODUCT FEATURES TYPICAL APPLICATIONS

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS

WRM-10 TM TRANSFORMER WINDING RESISTANCE METER

SECTION DISTRIBUTION SWITCHBOARDS

Est Triplen Power Distribution Unit TPDU kVA

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

Glossary 78 LIFETIME LIMITED WARRANTY. GREENLEE Phone: (International)

Device Interconnection

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated

Power IT LV Active Filters PQFA - PQFL - PQFT

Distribution/Substation Transformer

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

SULTANATE OF OMAN METERING AND DATA EXCHANGE CODE

S11 Adjustable Speed Drive Engineering Specification

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

UNITY/I TM. Installation Manual. UT3K, UT4K, UT5K and UT8K. Single-Phase Uninterruptible Power Systems

Installation requirements

Bypass Panels FRENIC-EcoPAK. Fuji Electric Corp. of America FECA-IN-105 / Information subject to change without notice.

SureTest Model ST-1THD & ST-1THDC Instructions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Generator Advanced Concepts

HPS Universal BUCK-BOOST TRANSFORMERS

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

MediaMatrix X-Frame 88

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK

SHORE TO SHIP FREQUENCY

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Design Specifications Low Voltage Active Harmonic Filter

The New Standard in High Power Redundant Microwave Amplifier Systems Has Arrived

Grounding Complications

Table of Contents. Facility EMI Filter Products

Preface...x Chapter 1 Electrical Fundamentals

AF91 Adjustable Frequency Drives Series B

ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL

7. INSPECTION AND TEST PROCEDURES

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

The New Standard in High Power Redundant Microwave Amplifier Systems Has Arrived

User's Guide. AC Circuit Load Tester. Model CT70

Q-SERIES. Amplifiers. QPAIR Redundancy Switch Amplifier System. Installation & Operation Manual

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

UNINTERRUPTIBLE POWER SUPPLY MODEL 9900B SPECIFICATIONS

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

TEACHER ASSESSMENT BLUEPRINT ELECTRICAL CONSTRUCTION TECHNOLOGY. Test Code: 5171 Version: 01

UNINTERRUPTIBLE POWER SUPPLY SPECIFICATIONS MODEL 1100B SERIES

DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters

INPUT VOLTAGE STARTING MINIMUM NORMAL MAXIMUM MAXIMUM INPUT RANGE VOLTAFE VOLTAGE VOLTAGE VOLTAGE CURRENT

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

Transcription:

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A Line Conditioning and Power Distribution Unit. All systems are designed and manufactured to assure maximum reliability, flexibility, serviceability and performance. The overall function of the Series 7200A is to receive electrical building power, remove transients and noise from that power, and distribute the power through flexible cable and/or receptacles to peripheral equipment and components of the data processing facility. 2.0 GENERAL The Series 7200A Power Distribution Unit provides the following: 2.1 Complete power conditioning, including transient and noise attenuation, of the power to the computer room from main building electrical systems. 2.3 Single point silver plated ground for all computer room equipment. 2.4 Protection from overload conditions. 2.5 Distribution and protection of electrical power to each computer and peripheral devices. 2.6 Monitoring of the electrical power to the computer room. 2.7 Annunciate computer room status (optional). 2.8 Quick installation with junction box interface to building power and flexible cable and/or receptacle interface to the computer system. Page 1 of 10

3.0 ELECTRICAL CHARACTERISTICS 3.1 PERCENT IMPEDANCE 2% to 5% depending on size. 3.2 PERCENT REACTANCE 1.5% to 4% depending on size. 3.3 HARMONIC DISTORTION Less than 1% THD added. 3.4 AUDIBLE NOISE 45 db at full rated load. 3.5 COMMON MODE NOISE ATTENUATION 120 db or greater 3.6 TRANSVERSE NOISE ATTENUATION Transverse Mode noise attenuation is 3 db down at 1000 Hz, 40 db down per decade to below 50 db with a resistive load. 3.7 OPERATING FREQUENCY 57-63 Hertz (60 Hertz Models) Page 2 of 10

4.0 MAJOR COMPONENTS The power conditioning and distribution unit as described herein shall consist of two junction boxes, lightening arrestor (optional), flexible input cable, main circuit breaker, double shield isolation transformer, main output circuit breaker(s), (optional), branch circuit breakers, (optional) power monitor and alarm system (optional). 4.1 JUNCTION BOX 4.1.1 The junction boxes are all steel electrical enclosures for installation under the computer room raised floor. 4.1.2 The power section contains the main power terminal block for each hot line and the service ground and neutral. 4.1.3 The control section contains terminals, for low voltage control, to interface with the Remote Emergency Power Off (REPO) push button, air conditioning, water detectors, Halon, smoke and/or fire detectors, etc. 4.1.4 The junction box can be furnished mounted on an optional nine (9) square foot radio frequency (R.F.) suppression plate. The R.F. suppression plate will be constructed from a highly capacitive construction consisting of two copper plates separated by a dielectric material. 4.1.5 An optional, quick disconnect, power plug (Main power entry) is available on most power sizes. 4.2 MAIN INPUT POWER CABLE 4.2.1 The junction box and the Power Distribution Center will be interconnected by a flexible, water-proof, steel raceway, 12 feet long, having a copper shield grounding conductor wound between the raceway walls. 4.2.2 The flexible raceway will house four (4) conductors on three phase systems and are sized for 125% of the full load current rating. 4.2.3 One copper conductor shall be provided for each hot line, and one service ground. 4.2.4 Single phase systems will have two (2) hot conductors and a ground. Page 3 of 10

4.0 MAJOR COMPONENTS (continued) 4.3 MAIN CIRCUIT BREAKER 4.3.1 The main input circuit breaker with a rating of no less than 125% of the full load current will be used. 4.3.2 The main circuit breaker will incorporate a low voltage shunt trip mechanism to interface with the units protection circuitry including the Emergency Power Off (EPO) and optional Remote Emergency Power Off (REPO) circuits. 4.3.3 The main circuit breaker is mounted vertically in the main distribution center and has an interrupting capacity of not less than 10,000 A.I.C. 4.4 MAIN TRANSFORMER 4.4.1 The transformer windings are all copper conductor construction. 4.4.2 M-6 grade, grain oriented, stress relieved transformer steel is utilized for minimum losses and maximum efficiency. 4.4.3 Class H (Class 220) insulation is utilized throughout with operating temperatures well below the insulation class. 4.4.4 The transformer has a double copper shield to minimize interwinding capacitance and transient and noise coupling between primary and secondary windings. 4.4.5 All transformers are designed to operate at safe temperatures of less than 150 C (hot spot) above ambient. 4.4.6 Transformer over temperature shut down is provided at 200 C 4.5 OVER CURRENT PROTECTION 4.5.1 Main input circuit breaker protected. 4.6 MANUAL RESTART AND LOSS OF VOLTAGE TRIP An optional loss of voltage trip and manual restart can be incorporated to shunt trip the main input breaker in the event of low output voltage. The trip point is factory adjusted at approximately 108 Volts line to neutral. Page 4 of 10

5.0 INTERNAL BUS AND GROUND SYSTEM 5.1 NEUTRAL BUS The transformer neutral on the secondary wye of the transformer will be rated at 200% of the phase current and connected to the service ground from the building service and to the chassis of the Power Distribution Unit. The transformer neutral will also be connected to a bus for neutral (white) branch circuits. The ground pad is silver plated. 5.2 GROUNDING SYSTEM 6.0 DISTRIBUTION The service ground shall be connected to the Power Distribution Unit s chassis, the electrostatic shield of the isolation transformer, the neutral lug of the isolation transformer and terminals at the isolated computer ground bus. The ground pad will be silver plated. 6.1 MAIN OUTPUT CIRCUIT BREAKERS (Optional on 50 KVA & smaller) 6.1.1 Each 120/208 VAC panel board section can be protected by an optional main circuit breaker installed between the transformer and the distribution panel per the National Electric Code. 6.1.2 The circuit breaker is rated at not more than 125% of the transformer full-load output current but not greater than the panel board bus rating and it is protecting. The interconnecting cables are sized in accordance with this rating. 6.1.3 The circuit breaker shall have a thermal-magnetic trip device and a minimum of 10,000 amperes interrupting capacity. 6.2 DISTRIBUTION PANEL 6.2.1 The output circuit breaker panel will be vertically mounted and easily accessible through an optional glass door or a sheet metal door. 6.2.2 Additional circuit breakers and flexible cables can be easily added in the field by swinging the hinged door panel away from the output breakers and inserting the circuit breakers and additional flexible output cables from the front of the Power Distribution Center. 6.2.3 Each distribution sub-panel will be factory wired and will have no fewer than forty two (42) single pole circuit breaker positions. Page 5 of 10

6.0 DISTRIBUTION (continued) 6.2 DISTRIBUTION PANEL (continued) 6.2.5 The Cabinet is capable of accepting two additional 42 pole panels for a total of 126 poles. 6.2.6 Distribution sub-panel will be capable of accepting any combination of single pole (120V), two pole (208V, 1 phase) and three pole (208V, 3 Phase) circuit breakers with ratings up to and including 100 amperes. 6.3 BRANCH OUTPUT BREAKERS (Optional) 6.3.1 The output circuit breakers will be thermal magnetic and rated at 10,000 AIC. 6.3.2 The circuit breakers will have three positions to indicate if the breaker is on, off or in the tripped position. 6.3.3 Output circuit breakers will be manually operated and provide a switching position for each output. 6.3.4 All breakers will be clearly marked and identified with the associated output cable. 6.4 OUTPUT DISTRIBUTION CABLES (Optional) 6.4.1 Each cable assembly will be factory assembled and tested. 6.4.2 Cable raceways will be, multi-wall, flexible steel conduit with a plastic waterproof jacket. A copper shielding-grounding conductor will be wound between the steel walls of the flexible conduct. 6.4.3 Conductors in the flexible conduit will be all copper with THHN insulation. 6.4.4 Each cable will contain a parity sized grounding conductor. 6.4.5 Cables shall have a terminal or receptacle for proper interface with each computer component. Page 6 of 10

7.0 CABINET 7.1 Cable and circuit breaker access will be through the front for ease of adding additional cables and circuit breakers. 7.2 The cabinet is furnished with casters with leveling jacks to fix the unit in position upon installation. 7.3 Cabinet layout is such that the input and output wiring are separated to minimize coupling between the two. 7.4 The cabinet is built out of at least 14 gauge steel. 7.5 Cabinet temperature is minimized at no more than 20 F above ambient with exhaust fans. 7.6 Swinging access doors will have lift off hinges and special fasteners. 7.7 The cabinet has the following separate compartments to optimize safety, Isolation and serviceability. 7.7.1 Breaker panel compartment. 7.7.2 Transformer and Regulator compartment. 7.7.3 Control and monitor compartments. 7.8 Silver plated ground bus is provided. 7.9 Texture baked on paint finish with proper pretreatment is provided. 8.0 RESERVED Page 7 of 10

9.0 POWER SYSTEM ANALYZER A microprocessor based Analyzer will be provided and have a 40 character back lit Liquid Crystal Display (LCD), True RMS Metering, Function Key Pad, and a Lighted, Guarded, Emergency Power Off push button. 9.1 MONITORING The Analyzer has Key Pad Buttons to simultaneously read the following parameters: 9.1.1 Input Voltage Line to Line on all three phases. 9.1.2 Output Voltage Line to Neutral on all three phases. 9.1.3 Output Voltage Line to Line on all three phases. 9.1.4 Output Currents on all three phases. 9.1.5 Frequency, Neutral Current, and Ground Current. 9.1.6 System KW and KVA. 9.1.7 Percent Load per phase. 9.1.8 Alarm Message. 9.1.9 Daily and Monthly KW Hour consumption. 9.1.10 Time and Date. 9.1.11 Power Factor per phase. 9.1.12 Automatic Scan of all Monitoring Parameters. 9.1.13 Alarm Silence. 9.1.14 Set Time and Date. 9.1.15 Programmable Alarm Limits. 9.1.16 Scroll through all alarms or set points Page 8 of 10

9.0 POWER SYSTEM ANALYZER (continued) 9.2 SYSTEM ALARMS System alarms and shut downs are incorporated for the following key parameters: 9.2.1 Output Over Voltage The output over voltage alarm/shut down is user programmable and factory preset at 228 volts to shut down the system when the output voltage is greater than the set point. Alarm Only or Alarm and Shut down is user programmable. 9.2.2 Output Under Voltage The output under voltage alarm/shut down is adjustable and factory preset at 187 volts to shut down the system when the output falls below the set point. Alarm Only or Alarm and Shut Down is user programmable. 9.2.3 Phase Loss Upon loss of any one of the phases an alarm will be initiated. Alarm Only or Alarm and Shut Down is user programmable. 9.2.4 Ground Over Current Upon detection of a ground over current condition an alarm will be initiated. 9.2.9 Output Over Current Upon detection of an output over current condition an alarm will be initiated. 9.2.10 Neutral Over Current Upon detection of a neutral over current condition an alarm will be initiated. 9.2.11 Frequency Deviation An alarm will be initiated should the frequency deviate more than + 3 Hertz. 9.2.12 Phase Rotation An alarm and shut down will be initiated upon detection of incorrect phase rotation. Page 9 of 10

9.0 POWER SYSTEM ANALYZER (continued) 9.2.13 Building I/O #1 thru I/O #6 9.3 CONTROLS Eight optional building I/O circuits can be provided. Each I/O is capable of accepting either a dry N.O. contact or a 120 volt A.C. signal. Each I/O is user programmable to alarm only or alarm and shut down. 9.3.1 Alarm Silence The alarm silence will silence the audible alarm without resetting the alarm message. A visual alarm message will remain lit until the fault is cleared. 9.3.2 Integral Emergency Off The emergency stop (EPO) is an illuminated and guarded push button to shunt trip the main breaker. 9.3.3 The Analyzer is capable of remotely displaying all monitoring parameters thru an optional RS 232 port to an IBM compatible computer and a Hayes compatible modem. 9.4 ENVIRONMENTAL 9.4.1 Time and Date Page 10 of 10