International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

Similar documents
Mitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Understanding Input Harmonics and Techniques to Mitigate Them

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

7/15/2002 PP.AFD.08 1 of 28

Harmonic control devices

Power Factor & Harmonics

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

NJWA - Harmonics and Drives Proper System Design

Harmonic Analysis and Its Mitigation Using Different Passive Filters

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

Emicon Engineering Consultants L.L.C.

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Principles for Controlling Harmonics

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System

Indirect Current Control of LCL Based Shunt Active Power Filter

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

SHUNT ACTIVE POWER FILTER

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

Improving the Power Factor Correction in the Presence of Harmonics by Reducing the Effect of Resonance and Harmonics

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

Harmonic Distortion and Variable Frequency Drives

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Power Quality improvement of a three phase four wire system using UPQC

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Harmonic Requirements

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

, ,54 A

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards

Harmonic control devices. ECE 528 Understanding Power Quality

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:

A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Active Harmonic Filter (AF3)

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

CHAPTER 4 HARMONICS AND POWER FACTOR

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

POWER FACTOR CORRECTION AND ITS PITFALLS

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

Thyristorised Automatic Power Factor

POWER- SWITCHING CONVERTERS Medium and High Power

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System

p. 1 p. 6 p. 22 p. 46 p. 58

DESIGN AND ANALYSIS OF ELIMINATION OF HARMONICS USING WIND ENERGY CONVERSION SYSTEMS

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

Question Paper Profile

Analysis of Harmonic Distortion in Non-linear Loads

International Journal of Advance Engineering and Research Development

Dynamic Harmonic Mitigation and Power Factor Correction

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

ISSN: ISO 9001:2008 Certified International Journal of Engineering and Innovative Technology (IJEIT) Volume 5, Issue 11, May 2016

Improving Passive Filter Compensation Performance With Active Techniques

Conventional Paper-II-2013

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

16B2011B1 EASY HARMONICS USER MANUAL

Effects of Harmonic Distortion I

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

VARIABLE FREQUENCY DRIVE

Literature Review for Shunt Active Power Filters

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

P2 Power Solutions Pvt. Ltd.

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control

Chapter 11. Alternating Current

Influence of Switching Elements on Harmonics and Power Factor Improvement

Study of Power Factor Correction in Single Phase AC-DC Converter

APPLICATION NOTE. Applying Type DD60 Capacitors in Harmonic Filter Applications. Total Power Factor PF = cosine ɸ

Voltage and Current Waveforms Enhancement using Harmonic Filters

How adjustable speed drives affect power distribution

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ABB drives. Technical guide No. 6 Guide to harmonics with AC drives

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

Long lasting transients in power filter circuits

Voltage Quality Enhancement in an Isolated Power System through Series Compensator

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

Power Quality Analysis in Power System with Non Linear Load

Harmonics, its Mitigation & Result of Case study of Spinning Mill

Harmonics White Paper

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

Outcomes of Harmonics & Its Reduction Techniques: A Comprehensive Review

Harmonic Filters for Single Phase Equipment

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation

Speed Control of Induction Motor using Multilevel Inverter

Transcription:

Scientific Journal of Impact (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 04, April -2018 e-issn (O): 2348-4470 p-issn (P): 2348-6406 ANALYSIS AND MITIGATI OF HARMICS IN MEDICAL FIELD Elango.P 1, Madhivadhani.D 2 1 Department of EEE, PERI Institute of Technology 2 Department of ECE, PERI Institute of Technology Abstract Among the various factors which causes poor power quality problems, harmonics are important one and Harmonics play significant role in deteriorating power quality, called harmonic distortion. Harmonic distortion in electric distribution system is mainly caused by the use of nonlinear loads. The rapid developments and use of nonlinear load leads to voltage and current harmonics, the controlling technique is important over the harmonic. Both passive and active filters have been used near harmonic producing loads or at the point of common coupling to block current harmonics. For harmonic compensation at medium/high voltage level Passive filters still dominate, whereas for low/medium voltage ratings active filters have been proclaimed. This paper presents an efficient model to compensate the current harmonics using the inverter based Active Filter, Passive Filter, and the combination of both. The system studies are carried for a medical center. The power flow studies are carried out to determine the data required to design the Capacitor banks The Medical Centre is analyzed for the harmonics through harmonic analysis based on which Active filters are designed. The study is conducted on Electromagnetic Transients Analysis Program (ETAP 12.6). Keywords- Current and Voltage Harmonics, Active and passive filter, factor, mitigation I. INTRODUCTI A Multispecialty Hospital getting Electrical supply from the electricity Board, this hospital commissioned with cardiology, neurosciences, orthopedics, nephrology and also having high level accuracy and separate measurement instruments. These hospitals have Generator, Ups and EB energy are used. An Electrical instruments connected in common grounding and neutral faced lot of problems due to harmonics. Harmonic is multiple of the fundamental frequency components in power system and are a result of non-linear electric loads. Harmonic frequencies in the power grid lead to power quality problems such as increased heating in the equipment and conductors, misfiring in variable speed drives, and torque pulsations in motors. Hence Reduction of harmonics is considered desirable. 1.1 CURRENT HARMICS Non linear loads such as rectifiers are main causes of Current harmonics. Non-linear load connected to the system draws non sinusoidal current. The current waveform depends on the type of load and its interaction with other components of the system. But practically it is possible to reduce the harmonic contents. 1.2. VOLTAGE HARMICS Voltage harmonics are caused by Current harmonics and the distortion the voltage provided by the voltage source the current harmonics depends on source impedance. For small value of the source impedance of the voltage source,current harmonics will cause only small voltage harmonics. But the voltage harmonics are indeed small when compare to current harmonics. Hence, it can be approximated by the fundamental frequency of voltage. In this approximation method, the average real power contributed by current harmonics is zero and the current harmonics produce no effect on the real power transferred to the load. However, for consideration of higher harmonics of voltage, the current harmonics do make a contribution to the real power transferred to the load. 1.3 HARMICS AND POWER FACTOR Harmonic currents are caused by non-linear loads connected to the distribution system. The harmonics presence in electrical system distorts the current and voltage waveforms and it is deviated from sinusoidal waveforms. The major nonlinear loads are Switch-mode power supplies (SMPS), variable speed drives, photocopiers, personal computers, laser printers, fax machines, battery chargers and UPSs. The ratio of the sum of the powers of all harmonic components to the power of the fundamental frequency component is known as total harmonic distortion (THD).Harmonic Distortion is the interference in an AC power signal caused by frequency multiples of the sine wave. Total Harmonic Distortion is used as a measure of the amount of Harmonic distortion in the system. A THD measurement shown in Fig: 2 can be made by applying a sine wave as an input to a system, and measuring the total energy which appears at the output of the system at harmonics of the input frequency. @IJAERD-2018, All rights Reserved 2174

Bus Voltage At PCC Total Harmonic Distortion THD (%) Fig 1.1 Harmonic Distortions Table 1.1 Total Harmonic Distortions Limits Individual Harmonics (%) Total Harmonic Distortion THD (%) V 1.0 KV 5.0 8.0 1.0 KV < V 69 KV 3.0 5.0 69 KV < V 161 KV 1.5 2.5 161 KV < V 1.0 1.5 Table 1.2 Total Harmonic Distortions Limits Pcc Based Current distortion Limits for General Distribution Systems (120V through 69,000V) Maximum Harmonic Current Distortion in Percent of load I sc / Load <11 11<=h<17 17<=h<23 23<=h <35 35<=h TDD (%) <20 4.0 2.0 1.5 0.6 0.3 5.0 20<50 7.0 3.5 2.5 1.0 0.5 8.0 50<100 10.0 4.5 4.0 1.5 0.7 12.0 100<1000 12.0 5.5 5.0 2.0 1.0 15.0 >1000 15.0 7.0 6.0 2.5 1.4 20.0 Even harmonics are limited to 25% of the odd harmonic limits above I sc =maximum short circuit current at PCC Load= maximum demand load current (fundamental frequency component) at PCC @IJAERD-2018, All rights Reserved 2175

II. ELECTRICAL SYSTEM 2.1 EXISTING SYSTEM The Existing Electrical system used in a Hospital has been presented in Fig3.1 where Capacitor filter is used. Fig 2.1 Existing System UPS DETAILS: Critical UPS : 120KVA,96KW,3PHASE,415VOLTAGE Non Critical UPS : 20KVA,16KW,3PHASE 415VOLTAGE Transformer rating : Capacity : 1600 KVA Primary Voltage : 11KV Secondary voltage : 433 V Primary current : 84 Secondary current : 2133.4 Vector group : Dyn11 Current Ratio: Main in comer : 2500A/5A Voltage Ratio: Main in comer : 1:1 Transformer Rating = 0.63 MVA Transformer Voltage ratio =11/0.433 kv Frequency=50Hz Transformer Impedance=5% = 0.05 PUMV System fault level (Maximum)=40 ka MV System fault MVA= 3 x 40 x 11 = 762 MVA Total Impedance=0.63 / 0.0508 = 12.40 2.2 PROPOSED SYSTEM OF DETUNED CAPACITORS FOR POWER QUALITY IMPROVEMENT Harmonic contents in loads can be reduced with existing load equipment. The applied voltage is lowered to correct range there by an over excited transformer can be brought back to normal operation. PWM drives used to charge the dc bus capacitor directly from the line without any intentional impedance are exception to this problem. Harmonics reduction and transient protection can be achieved by series connection of a line reactor or transformer. Fifth and seventh harmonics can be reduced significantly Phase shifting transformer connections The flow of zero sequence harmonics from the line can be blocked using Delta connected transformers. Automatic power factor correction system (APFC) is based on fixed and predefined amount of KVAR. But main priority is not given to APFC. Detuned capacitors are used as harmonic filters and its advantages over plain capacitors for power factor correction is presented. The various problems caused by harmonics and how filters prevent them are reviewed, and a comparison between them is also presented. @IJAERD-2018, All rights Reserved 2176

Fig 2.2 Proposed Electrical System Construction Block Diagram Fig 2.3 Passive Filter Construction Block Diagram 2.3 CALCULATING PERCENT IMPEDANCE FOR AN AC LINE REACTOR The percent impedance value of the reactor depends on the percent of nominal voltage that would be dropped across the reactor and it is calculated with the rated current through it at fundamental frequency.as per the Ohm s Law the voltage drop across the inductor E = I X L X L = 2л f L Where: X L Inductive Impedance E Voltage (Volts) I Fundamental Current (Amps) f Fundamental Frequency (Hertz) So the formula for Percent Impedance would be as follows: %Z = L (in Henries) / [(V L-L / 1.732) / (I x 2π x f)] x 100 % 2.4 HARMIC RESANCE The Harmonic currents that are generated by the operation of non linear loads in a distribution system flow throughout the power system.the inductive reactance of the power system increases and the capacitive reactance decreases as the frequency increases, or as the harmonic order increases. If capacitor exists in a system, there will be a crossover point at a given harmonic frequency where the inductive and capacitive reactances are equal. At this cross over point power system has coincidental similarity of system impedances and this point is known as parallel resonant point. Parallel resonant point exists at every system with capacitor. 2.4 How to Avoid Harmonic Resonance Harmonic resonance can be avoided by using de-tuned harmonic filters or with the help of an appropriately sized capacitor.harmonic filters provide the same 60-Hz reactive compensation as capacitors, but they're typically designed with a parallel resonance point below any expected harmonics on the system. Frequency scanning and harmonic resonance evaluation are performed to avoid resonance to ensure financial benefits of applying capacitive compensation technique. 2.6 DETUNED CAPACITOR BANK DESIGN DATA 5.5% Low Loss, Iron Core, Al wound, Highly Linear Harmonic Filter Series Reactor suitable for Permissible Over loading 1.3 x Rated current Linearity 1.8 x Rated current 75Kvar, 525 V, 3Ph, 50 Hz -10 No 37.5Kvar, 525 V, 3Ph, 50 Hz -2 No. @IJAERD-2018, All rights Reserved 2177

2.7 NEED FOR DETUNING CAPACITORS Non-linear loads in industry typically contain a high fifth harmonic. At the fifth harmonic, the tuned filter has a better behavior than the detuned filter. In order ensure the proper operation, the voltage rating of Capacitor bank must be higher than the voltage level required for detuned filters. Because detuned filters absorb less harmonics, they also carry lower harmonic currents than the tuned filters. These features make Detuned filters more. 2.8 ERECTI OF ACTIVE FILTER Fig 2.4 Active Filter Connection Block Diagram Active Harmonic Filter/Active current conditioners are Static Compensator (STATCOM) based devices where compensating current of any shape or size are generated using an IGBT based inverter. Active Current Conditioners are used for reactive power compensation, harmonic mitigation, load balancing and neutral correction. They can be used for compensation on grid supply and are also fully compatible with DG operation. Electronic power quality devices are designed to measure the load current and the variance from objectives set by the user is calculated to inject the right amount of current to make the supply current to meet the objective levels for harmonics, displacement PF, or load balancing. For harmonic mitigation, the load current is measured and harmonic current spectrum, amplitude and phase angle is calculated for every harmonic to the 50th order using appropriate logic. The amplitude to be injected at the opposite phase angle for each harmonic order selected for mitigation is determined by proper Logic. Based on that a control signal is generated and the semiconductors (IGBT) are directed to duplicate the control signal as injected current into the supply. Thus the supply side harmonic component of current is greatly reduced. The speed of response is controlled by: 1) the logic calculation method, 2) the switching rate of the IGBT and 3) the speed of the microprocessor in the control logic. The carrier frequencies and microprocessors are generally fast enough to provide per cycle response. III RESULTS AND OBSERVATIS 3.1 COMPARIS BETWEEN HARMIC WAVE FORM WITH AND WITHOUT FILTERS Fig 3.1 Harmonic wave form with and without filters @IJAERD-2018, All rights Reserved 2178

3.2 PROPOSED ELECTRICAL SYSTEM (SINGLE LINE DIAGRAM) Fig 3.2 Proposed ETAP Diagram The results obtained after the installation of the combination of active and passive filter is show in the table 7.1. It shows the comparison of results between the existing and proposed system. @IJAERD-2018, All rights Reserved 2179

COMPARIS OF RESULTS BETWEEN EXISTING AND PROPOSED SYSTEM Type of System Existing System Proposed System OFF Capacitor Bank Passive Filter Active Filter Both Filters 0.87 33.45 0.94 58.47 Nil Nil Nil Nil Nil Nil Nil Nil Nil Nil 0.98 10.25 0.84 2.28 0.90 0.98 Table 3.1 Comparison Of Results Between Existing and Proposed System From the table 3.1 We can see that there is a significant difference in the factor and THD by replacing the existing system with the proposed system. The power factor improved from 0.87 to 0.90 and the THD reduced to 0.98% from 58.46% respectively. IV CCLUSI The load flow studies were performed on the existing and proposed system.the harmonics observed in the existing system was above the standards given by IEEE and CEA. These harmonics not only affect the electricity board but also the sensitive and expensive analog equipment used. Therefore, a solution for both power factor correction and harmonic mitigation was found and implemented by installing appropriate combination of Active and Passive filters in the proposed system. This improved the power factor very much and also the harmonics were brought to the standards. The future scope of this project is that when a further expansion of the medical system takes place, the filters can be redesigned for the respective up gradations. Also, this technique of using a combination of Active and Passive filters together can be implemented in various systems which include Railway networks, Industries etc. REFERENCES [1] Ewald F. Fuchs, Mohammad A.S. Masoum. Quality in Systems and Electrical Machines, 1 st Edition, University of Colorado. [2] Francisco C. De La Rosa. Harmonic and Systems, Taylor & Francis Group, LLC, 2006. [3] Gonzalo Sandoval & John Houdek. A Review of Harmonic Mitigation Techniques, Allied Industrial Marketing, USA, 2005. [4] Gradner, Leo Fuchs. Comparison of harmonic mitigation solutions, Schneider Electric company, Germany, 2012. [5] Jos Arrillaga, Bruce C Smith Neville R Watson, Alan R Wood. System Harmonic Analysis, 2nd Edition, University of Canterbury, New Zealand, 2000.Radebaugh, R., Marquardt, E.D., Gary, J., and O'Gallagher, A., "Regenerator Behavior with Heat Input at Intermediate Temperatures," Cryocoolers 11, Plenum Publishers, New York (2000). @IJAERD-2018, All rights Reserved 2180