A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits

Similar documents
Case Study 38 Reduction in Break Down and Specific Energy Consumption by Reducing Harmonics at Usha Martin Wire Rope Plant.

HARMONIC MITIGATIONCASE STUDY

Active Harmonic Filter (AF3)

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

PQ Synergy Effective Harmonic Filter Designs for Commercial Implementation. Team Power Matrix, Sony Jacob.

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP

1C.4.1 Harmonic Distortion

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

Effective Harmonic Mitigation with Active Filters

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

Low Pass Harmonic Filters

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

Harmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients.

Thyristorised Automatic Power Factor

Harmonic Mitigating Transformer - Technical Guide

Understanding Input Harmonics and Techniques to Mitigate Them

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

Harmonic Distortion Evaluations

CHAPTER 8 Effect of HT Distribution Feeder Voltage on Distribution Transformer Losses

Economical Solutions to Meet Harmonic Distortion Limits[4]

Harmonics, its Mitigation & Result of Case study of Spinning Mill

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

Electromagnetic Harmonic Filters Technical Guide

CHAPTER 4 HARMONICS AND POWER FACTOR

Do You Have a Harmonic Problem?

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Harmonic Filters for Single Phase Equipment

PQ Audit - The right choice to ensure power system performance. Mr Lalit Kumar Wasan Tata Power- DDL

Power Quality Regulations for Distribution of Electricity in India

SHARDA Make Harmonics Filter

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 02 Issue: 04 July p-issn:

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

22.0 Harmonics in Industrial Power Systems

ZENER ELECTRIC PTY LTD

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks

Automatic capacitor banks with detuned filters

VARIABLE FREQUENCY DRIVE

HARMONICS CAUSES AND EFFECTS

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Harmonic Analysis and Power Factor Correction For Food Processing Industry

POWER QUALITY AND SAFETY

Harmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry

ECET Modern Power

Analysis of Harmonic Distortion in Non-linear Loads

Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners

New Methods to Mitigate Distribution System Harmonics

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

Technical Paper. Harmonic Distortion in Data Centers

Southern Company Power Quality Policy

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Harmonic Analysis to Improve Power Quality

Voltage Relays. Ensuring Reliable Protection for Electrical Systems against Voltage Faults. ISO 9001:2008 Certified.

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

NJWA - Harmonics and Drives Proper System Design

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

Voltage Quality Enhancement in an Isolated Power System through Series Compensator

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

Power quality report. A Manufacturing Plant

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF RESIDENTIAL LOAD

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Frequently Asked Question on Isolated Power Supply(IPS)

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

UNBALANCED CURRENT BASED TARRIF

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

POWER MONITORING For Energy Management Systems

REACTIVE ENERGY REGULATOR

Voltage Support and Reactive Power Control in Micro-grid using DG

New power tools provide quality and efficiency By

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

Harmonics Reduction using 4-Leg Shunt Active Power Filters

ULTRA RAPID POWER QUALITY ANALYZER

Roadmap For Power Quality Standards Development

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

POWER QUALITY ASSESSMENT AND MITIGATION AT WALYA-STEEL INDUSTRIES AND ETHIO-PLASTIC SHARE COMPANY

Harmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems

Tripping of circuit breakers in PV installations due to zero sequence field impedance

Power Quality Overview

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

McGill Power Sales & Engineering, INC.

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

Transcription:

CS 36 HOSP 14

36 Abstract A leading hospital in southern India faced chronic problems in terms of humming noise in capacitor bank, its failure, high temperature in transformer, and disturbances on the monitor of ultra sound machine. In order to rectify these problems hospital management carried out power quality study. During the study it was observed that harmonic content were quite high. As suggested by the consultant hospital management decided to install one 120 amperes active harmonic filter at the PCC level. Detailed measurement based study was conducted at the hospital to analyse benefits gained by the hospital. During the case study it was also observed that by reducing harmonic content, the hospital also reduced energy charges causing direct savings in energy cost. Introduction With the critical applicability of medical electronics equipment used in hospital and widespread use of microprocessor based equipment, it has become very important that power fed to such equipment is of high quality. Any deviation in power quality can result in malfunction of the medical equipment or failure of them. Failure of critical medical equipment in Operation Theatre during operation can have disastrous effect both on life and reputation. With rising cost of energy, reduction in energy consumption is also one of the important aspects that need address in a hospital. As many distribution companies like in Andhra Pradesh (India) are opting for kvah based billing, presence of harmonics in the system will definitely increase consumer s electricity bill. This case study illustrates typical power quality problems faced by a hospital, benefits achieved by the hospital by installing harmonic filter and scope of further improvement to maintain power quality as per standards. 2

About the Facility The hospital is one of the major hospitals in Hyderabad with specialization in treatments of heart disease, neurology, neuro-surgery, cancer and other life threatening diseases. Diagnosis and treatment of these diseases require highly experienced doctors and medical professionals along with sophisticated machines and equipment. For diagnosis purpose, a doctor depends a lot on the results of these medical equipment and these sophisticated medical equipment become very important in terms of diagnosis of a particular ailment. Any error in the results can lead to wrong diagnosis and the life of a patient can be in danger. The facility has opted for best available technology in terms of medical equipment and electrical distribution system. The facility receives power from state electricity board at 11kV which is stepped down to 415volts using a 690 kva transformer. Single line diagram below shows distribution system of the facility. The facility has installed an active harmonic filter of 125 Ampere capacity at the PCC level to reduce harmonics along with APFC panel of 650KVAr. From PCC, number of panels distributes power to each floor where it is distributed further. On each floor, typical distribution of load consists of lighting, split air conditioners and medical equipment. Fig.no.1 Single line diagram of facility 3

Problem Faced by the Hospital The Hospital was facing following problems in the distribution system. 1. Higher temperature in the transformer 80-85 o C. 2. Humming noise in the capacitor bank 3. Higher energy charges as billing is based on kvah 4. Disturbance on the monitor on ultra sound machine In order to find root cause of above problems to avoid any breakdown, Hospital management decided to carry out detailed power quality study of the facility. Result of power quality study identified presence of high harmonics at PCC level. As per the study, total current harmonic distortions at the PCC level were up to 30%. Measurements and results below confirm presence of harmonic distortion beyond the limit prescribed by IEEE-519. Table 1 shows harmonic limit as prescribed by IEEE-519. Harmonic Current Limits for Non Linear load at the Point of-common-coupling with Other Loads, for voltages 120-69,000 volts Maximum Odd Harmonic Current Distortion in % of Fundamental Harmonic Order I SC /I L <11 11<17 17<23 23<35 35 TDD <20 4 2 1.5 0.6 0.3 5 20<50 7 3.5 2.5 1 0.5 8 50<100 10 4.5 4 1.5 0.7 12 100<1000 12 5.5 5 2 1 15 >1000 15 7 6 2.5 1.4 20 Table no.1 Harmonic limit as prescribed by IEEE 519 4

I SC /I L is the ratio of short circuit current value of the facility to the maximum load current. TDD-Total Demand Distortion Detailed measurement based study was carried out to find benefits gained by the hospital by installing harmonic filter. Measurement In order to carry out case study power analyzer suitable to carry out power quality study was installed at the PCC on transformer secondary side to record various parameters like harmonic order and percentage, power factor, power and demand. AHF was switched off for some time and measurements were recorded. Measurements were also carried out on HT side of the transformer as utility meter used for billing was installed on HT side. Sections below shows effect of harmonic filter on various parameters like harmonics, power (kw), demand (kva) and power factor. Harmonics Without AHF Detailed measurements were carried out at the PCC level on LT and HT side of the transformer in the absence of harmonic filter. Fig.no.2 Load Current diagram of facility Fig.no.3 Total Harmonic Distortion - Current 5

Figure 2 shows load current during normal operating hours. It can be seen from the snapshot that all phases of the wave form are distorted and are not close to a perfect sinusoidal wave form. Neutral current is 43 amperes which is quite high. Presence of harmonic current in the system distorts fundamental current wave forms. One of the reasons for high neutral current could be triplen harmonics Measurements for harmonics are shown in next section. Figure 3 shows a snap shot for the total current harmonic distortion in the system. For each phase total current harmonic distortion is different. In R phase, THDi is 13.7%, Y phase 30.4% and in B phase THDi is 23%. Variation in the difference of total current harmonic for the phases is due to presence of lighting load that is connected on Y phase. Some single phase medical equipment are also connected in the same phase Presence of these harmonic current distort fundamental wave form and also peak value of the wave form is increased. Snap shot below shows different order of harmonics present in the system in the absence of harmonic filter. From the figure4 it can be seen that 3 rd / 5 th and 7 th order of harmonics are I-THD 3 rd order 11% I-THD 5 th order 23% Fig.no.4 Order of current harmonics predominant in nature where as harmonics were present up to 25 th order and above. 3 rd order harmonics were found to be up to 11% where as 5 th order harmonics were up to 23%. High neutral current can be attributed to presence of triplen harmonics which are of the order 3 rd, 9 th and 15 th. 3 rd harmonic present in Y phase are up to 25 amperes. RMS value of 5th order harmonics was found to be up to 44 amperes. Table 2 shows percentage harmonic content in each phase and table 3 shows RMS value of individual order of harmonic in each phase. 6

% Harmonic Current Order of Harmonics R Y B 3 rd 3.5 13.2 3.3 5 th 10.8 23.5 19.4 7 th 6.1 7.9 8.8 9 th 0.1 1.7 0.8 Table no. 2 Percentage of harmonic current RMS Value of Current Order of Harmonic R Y B 3 rd 6.22 25.6 6.8 5 th 21.38 44.0 38.0 7 th 12.4 14.3 17.2 9 th 0.19 3.3 1.5 Table no. 3 RMS value of harmonic current From the above measurements, it was evident that high percentages of harmonics were present in the system. In order to mitigate harmonics, hospital management decided to install 120 ampere active harmonic filter recommended by PQ auditor. Installed Harmonic Filter at the Facility 7

Harmonics - With AHF Figure 5 shows when harmonic filter was in line, distortion level of the wave forms was much lower as compared to the condition when harmonic filter was switched off. The waveform was close to sinusoidal waveform as compared to waveform in figure number 2. Also current in the neutral is significantly reduced from 43 amperes to 32.6 amperes. Fig.no.5 Load Current From the figure 6 it can be seen that 3 rd / 5 th and 7 th order of harmonics are reduced to considerable extent. Reduction in triplen harmonics also reduced current flowing in the neutral of the system. After installation of harmonic filter 3 rd, 5 th, and 7 th order of harmonics are reduced to 2.2%, 3.2% and 2.1% respectively. Fig.no.6 Order of current harmonics Table number 4 and 5 shows percentage of individual order of harmonic and their RMS values. % Harmonic Current Order of Harmonics R Y B 3 rd 0.7 2.2 0.7 5 th 1.7 2.8 3.2 7 th 1.8 2.1 2.1 9 th 0.2.01 0.9 Table no. 4 Percentage of harmonic current RMS Value of Current Order of Harmonic R Y B 3 rd 1.3 4.3 1.4 5 th 3.3 5.5 6.3 7 th 3.5 4.1 4.1 9 th 0.4 0.2 1.8 Table no. 5 RMS value of harmonic current 8

THD % Case Study 36 From the above table it can be seen that after installation of active harmonic filter, the harmonic current are reduced by considerable extent. Benefits accrued by installing Active Harmonic Filter In order to analyse benefits accrued to the hospital by installing active harmonic filter measurements, data was logged for longer duration of time. During this time active harmonic filter was switched off for some time. Sections below show affect of active harmonic filter on various parameters like harmonics, power factor, kw and kva. Current Harmonic Distortion As the measurements recorded, graphs-1 below shows effects of harmonic filters in ON and OFF condition. 35 30 AHF OFF 25 20 15 10 5 AHF ON AHF ON 0 Time ITHD 1 ITHD 2 ITHD 3 AVG ITHD 1 AVG ITHD 2 AVG ITHD 3 Graph-1 Total Current Harmonic Distortion with and without AHF Graph-1 shows total harmonic distortion in percentage against time. It can be seen from above graph that when active harmonic filter was switched ON, there is drastic reduction in total 9

harmonic distortion in current. When active harmonic filter is OFF, THD percentage is up to 25% but when active harmonic filter is switched ON, THD percentage is reduced to below 5%. From the above measurements, it can be seen that by installing active harmonic filter, magnitude of harmonic distortion is reduced to considerable extent within the limits prescribed by IEEE and as desired by the hospital. The harmonics that are being fed to the upstream of the grid are within IEEE limits. As of now there is no penalty by the distribution company on the harmonic distortion, but in future if levied then the harmonics are within limits.this would enable customer to avoid any penalty imposed due to distortion in future by distribution company. Power Factor Graph -2 below shows effect of harmonic filter on power factor. In the absence of harmonic filter power factor was close to 0.97 and when harmonic filter was switched on power factor improved to 0.995 and above. A major concern arising from the use of capacitors in a power system is the possibility of system resonance. This effect imposes voltages and currents that are considerably higher than would be the case without resonance. The reactance of a capacitor bank decreases with frequency, and the bank, therefore, acts as a sink for higher harmonic currents. This effect increases the heating and dielectric stresses.the result of the increased heating and voltage stress brought about by harmonics is a shortened capacitor life. One of the indicator of resonance is humming noise coming out of capacitor bank. This phenomenon was also observed at the facility. When harmonic filter were switched off, it was observed that there was a continous humming noise coming from capacitor bank. When harmonic filter was switched onthere was no humming noise coming from the capacitor bank. 10

PF Case Study 36 Power Factor 1 0.99 0.98 0.97 AHF ON AHF OFF AHF ON 0.96 0.95 0.94 0.93 0.92 Time PF Average PF Graph-2 Power Factor With and without AHF By reducing current harmonics, power factor is improved and humming noise is eliminated from the capacitor bank.also it is reported that capacitor bank failure is heavily reduced. Reduction in Energy Charges Most of the utility boards are now opting for kvah billing instead of kwh billing. In kvah billing, harmonics distortion makes a great impact as compared with kwh billing. Graph-3 shows difference in kw and kva when harmonic filter was switched ON and OFF. 180 175 170 165 160 155 150 145 140 135 130 125 120 kw kva AVG kw AVG KVA Graph-3 kw and kva with and without AHF 11

From the graph it can be seen that in the absence of harmonic filter, average values for both kw and kva has increased. When active harmonic filter was switched off, average value for load was 149.45kW. As soon as harmonic filter was switched ON, average load came down to 145.5kW. For kva, average value dropped down to 146kVA from 153.6kVA when harmonic filter was switched ON. The average difference in kw was 3.94kW whereas average difference in kva was 7.5kVA. In order to include losses in transformer and overall effect on billing, measurements were carried out on HT of the transformer to find difference in kva by filtering out harmonics. From the graph-4 it can be seen that harmonic content were in the range of 20-25% in the absence of harmonic filter. These measurements also indicate that harmonics were being exported to the grid. The harmonic contents are quite high as prescribed by the limits in IEEE 519. 30 25 20 15 THD % 10 5 0 THD1 THD2 THD3 Graph-4 THD level on HT side of Transformer 12

From the graph it can be seen that when AHF was switched ON, total current harmonic distortion which were being exported to the grid were reduced. In the absence of AHF, THD current were up to 25% but in the presence of AHF, THD current were reduced to below 5%. Graph-5 below shows reduction in kva in the presence of harmonic filter on HT side of the transformer. In the absence of harmonic filter average kva value was 216 kva. When harmonic filter was switched ON average recorded kva value was 204 kva. In the presence of active harmonic filter demand is reduced by 12 kva. With energy cost of INR 7.5 per kvah, annual cost saving by installing harmonic filter at the facility is around 788,400.00 Indian rupees per annum. 300 250 200 Average KVA = 216 Average KVA = 204 Reduction in KVA = 12 150 100 50 0 KVA Average KVA Graph-5 kva on HT side of the transformer Average reduction in kva - 12 kva Annual operating hours - 8760 hours Unit energy cost - INR 7.5 per kvah Annual saving - INR 788,400.00 Investment - INR 750,000.00 Payback - 1 year 13

By installing active harmonic filter hospital management gained substantial monetary benefit in terms of reduced electricity charges. In other words it conserved energy. With an investment of around INR 750,000.00, energy charges are reduced by INR 788,400.00. Simple payback period for installation of active harmonic filter was just under one year. Benefits gained by the hospital As mentioned above in the measurement based case study, the hospital is getting benefits in following aspects. 1. Reduction in total harmonic distortion being injected in the grid thus avoiding any future penalty levied on THD limits by state electricity Distribution Company. 2. Reduced demand Demand on transformer is reduced by 12 kva 3. Reduced kvah consumption Monetary saving of INR 788,400.00 per year 4. Reduction in humming noise at the capacitor bank 5. Temperature of transformer was found to be around 45 o C Problem still faced by the Hospital Problem faced in the ultra sound machine for disturbance on the screen was still present even after installation of active harmonic filter. In order to find possible reason and solution to the problem, some more detailed measurements were carried out. As indicated in the above single line diagram, active harmonic filter was installed at the point of common coupling. Measurements were carried out at the MCC in the distribution system from which supply to particular ultra sound machine was fed through sub feeders. The load on that particular MCC was hospital equipment like ultrasound machine, lighting load other diagnostic equipment. The particular ultrasound machine is fed through a single phase supply to a 2 kva single phase UPS. Output of UPS is connected to the ultra sound machine. The machine is operated on the electricity board supply. There is a disturbance on the screen of the ultra sound machine making diagnostic a bit difficult. Photograph - 1 below shows the disturbance on the screen. When power supply from EB is switched off but the plug of the machine is still in the socket, 14

and ultra sound machine is operated on UPS, the problem persists. When the power supply is switched off and plug was still in the socket, neutral and earth was still connected, hence the circuit was not completely isolated from the main system. However, when the supply from electricity board is completely isolated by taking out plug from the socket, then image is clear. This is shown in photograph -2. In order to find cause of the problem, measurements were taken from the distribution board till UPS. Photograph-1: Image quality when supplied through EB power and when supplied through UPS but plug still in socket Photograph-2: Image quality when supplied through UPS and plug is disconnected from socket When measurements were taken at the particular MCC feeding the floor on which ultra sound machine is placed, it was found that harmonic content were quite high. Although a harmonic filter is installed, but this filter is only filtering out harmonics from going to the grid. However harmonic current generated by different load are still present in the system and needs to be filtered out from re-circulating in the system. Following graphs shows content of harmonic distortion at the feeder. 15

Figure 7 Total Harmonic Distortion at MCC Figure 8 Harmonic order and content From the above two figures it can be seen that total harmonic distortion in the Y phase is more than 50%. Also 3 rd and 5 th orders were predominant harmonics present in the system. 35 30 25 20 15 10 5 0 Load Distribution in Amperes R Y B N Graph-6 Load distribution on the floor Graph-6 shows load in terms of amperes in the particular floor. From the graph it can be seen that: 1. High degree on unbalance in terms of load distribution 2. Current in the neutral quite high Lighting load was fed through Y phase for that particular floor where as all other loads were fed through remaining two phases. Due to presence of triplen harmonics and unbalance in the load, current in the neutral is quite high. All neutral conductors in the distribution system were half size. As harmonic current, 16

particularly triplen harmonic has a tendency to flow in the neutral of the conductor; temperature of neutral conductor was high. High current in neutral will constantly heat up the conductor and can lead to fire. It is recommended to go for a full size neutral conductor.. Measurements were also carried out at the supply of ultra sound machine. Figure-9 shows current in phase (Red colour), neutral (yellow colour) and leakage current (blue). Figure 10 shows current in neutral when switch was switched off but plug was still in the socket, there was flow of current in neutral even when supply was switched off. Figure 9 Current in phase, neutral and leakage Figure-10 Current in neutral As there was no protection or mitigation measure adopted to filter out harmonics generated by different loads, some of these harmonics were flowing in the system and rest were going in the upstream of the network to the grid. It is recommended to install an isolation transformer at the incomer of ultra sound machine. Isolation transformer will ensure that electrical noise will not be transferred to the ultrasound machine by creating a floating neutral. 17

Conclusion By installing active harmonic filter, the hospital is being benefited by: 1. Reduction in total harmonic distortion being injected in the grid thus avoiding any future penalty levied on THD limits by state electricity distribution company. 2. Reduced demand Demand on transformer is reduced by 12 kva 3. Reduced kvah consumption Monetary saving of INR 788,400.00 per year 4. Reduction in humming noise at the capacitor bank and its failure 5. Operating Temperature of transformer was found to be around 45 o C, a healthy condition However, the problem in the ultrasound machine is not due to harmonics. The problem is due to noise present in the neutral cable and this can be mitigated by isolating neutral using an ultra isolation transformer. The high neutral current if allowed to be persistent can cause fire accidents over time due to deterioration of insulation and eventual failure. This can be addressed by using full size neutral or eliminating triplen harmonics through filters etc that is generally costly compared to over sizing neutral option. The problems arising due to harmonics are taken care by active harmonic filter. ------------------------------------------------------------------------------------------------------------------------------ 18

About the Author: Author Name: M Srinivas Email: sreenu.munnoori@gmail.com Mr. Srinivas is an Electrical engineer with more than 6 years of experience in healthcare industry. He is associated with a leading hospital in southern India. He is responsible for the reliability of the equipment used in healthcare industry. He has experience in operation and maintenance of facility, project management for the new projects, and design engineering. Disclaimer: The sole responsibility for the content of this document lies with the authors. It does not represent the opinion of the Asia Power Quality Initiative and /or ICPCI/ICA network. APQI and ICA network are not responsible for any use that may be made of the information contained therein. 19