Fault Detection on Inverter Based Distribution Network

Similar documents
Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

Active Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Performance of DVR under various Fault conditions in Electrical Distribution System

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

A New Control Strategy for Three- Phase Inverter Applied To Induction Motor of Micro Grid

Control of Power Converters for Distributed Generation

EMERGING distributed generation technologies make it

Improved Transient Compensation Using PI-SRF Control Scheme Based UHVDC For Offshore Wind Power Plant

Voltage Unbalance Mitigation Using Positive Sequence Series Compensator

GRID CONNECTED HYBRID SYSTEM WITH SEPIC CONVERTER AND INVERTER FOR POWER QUALITY COMPENSATION

Modeling of Single Stage Grid-Connected Buck-Boost Inverter for Domestic Applications Maruthi Banakar 1 Mrs. Ramya N 2

Modelling and Simulation of High Step up Dc-Dc Converter for Micro Grid Application

SIMULATION AND EVALUATION OF A PHASE SYNCHRONOUS INVERTER FOR MICRO-GRID SYSTEM

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

State of Charge (SOC)-Based Active Power Sharing Method for Distributed Generations in an Islanded Microgrid

MODELING AND SIMULATON OF THREE STAGE INTERLEAVED BOOST CONVERTER BASED WIND ENERGY CONVERSION SYSTEM

World Journal of Engineering Research and Technology WJERT

ISSN: [Reddyrani* et al., 6(4): April, 2017] Impact Factor: 4.116

A Three Phase Power Conversion Based on Single Phase and PV System Using Cockcraft-Walton Voltage

Matlab Simulation of a High Step-Up DC-DC Converter for a Micro grid Application

Synchronization and Smooth Connection of Solar Photovoltaic Generation to Utility Grid

ISSN Vol.03,Issue.11, December-2015, Pages:

An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing In Inverter-Based Islanded Micro grids

Control of a Back-to-Back VSC from Grid Connection to Islanded Modes in Microgrids

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Grid Code Violation during Fault Triggered Islanding of Hybrid Micro-grid

UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Voltage Support and Reactive Power Control in Micro-grid using DG

Single Phase Bidirectional PWM Converter for Microgrid System

CONVERTERS IN POWER VOLTAGE-SOURCED SYSTEMS. Modeling, Control, and Applications IEEE UNIVERSITATSBIBLIOTHEK HANNOVER. Amirnaser Yazdani.

Unified Power Quality conditioner in Grid connected Photovoltaic System

Modular Grid Connected Photovoltaic System with New Multilevel Inverter

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

An Optimized Synchronous Techniques of Single Phase Enhanced Phase Locked Loop (EPLL)

A New Network Proposal for Fault-Tolerant HVDC Transmission Systems

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

Design and Simulation of Dynamic Voltage Restorer (DVR) Using Sinusoidal Pulse Width Modulation (SPWM)

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Simulation of Single Phase Grid Connected Photo Voltaic System Based On PWM Control Of Switched Boost Inverter For DC Nanogrid Applications

ISLANDING DETECTION USING DEMODULATION BASED FFT

Shunt Harmonic Compensator Design for Using Fuzzy Logic Controller

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

Design and Development of MPPT for Wind Electrical Power System under Variable Speed Generation Using Fuzzy Logic

Improved Grid Synchronization Algorithm for DG System using DSRF PLL under Grid disturbances

Short Circuit Calculation in Networks with a High Share of Inverter Based Distributed Generation

Charge Pump Phase Locked Loop Synchronization Technique in Grid Connected Solar Photovoltaic Systems

ACTIVE POWER ELECTRONIC TRANSFORMER A STANDARD BUILDING BLOCK FOR SMART GRID

Delhi Technological University (formerly DCE) Delhi-42, India

Protection of Extra High Voltage Transmission Line Using Distance Protection

II. RESEARCH METHODOLOGY

Fault Detection and Isolation of a Loop Type Low Voltage DC Bus Microgrid

Reactive Power Support to PV Grid System Using Voltage Source Converters to Enhance PV Penetration Level

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

SUPERCONDUCTING MAGNETIC ENERGY

A CONTROL TECHNIQUE FOR INSTANT MITIGATION OF VOLTAGE SAG/SWELL BY DYNAMIC VOLTAGE RESTORER

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Control of grid connected inverter system for sinusoidal current injection with improved performance

LOAD BALANCING IN PRIMARY DISTRIBUTION FEEDERS BY COMBINATION OF RENEWABLE ENERGY SOURCE AND VOLTAGE SOURCE INVERTER

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

An Accurate Power Sharing Method for Control of a Multi-DG Microgrid

Power Quality Improvement using Shunt Passive Filter

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

Control of Shunt Active Power Filter for Improvement of Power Quality

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Impact Factor: Student, SV University, Tirupati, India.

Mitigation of the Statcom with Energy Storage for Power Quality Improvement

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

POWER QUALITY ASSESSMENT AND ENHANCEMENT IN A GRID CONNECTED RENEWABLE ENERGY SYSTEM USING DYNAMIC VOLTAGE RESTORER

Detection of Fault in Fixed Series Compensated Transmission Line during Power Swing Using Wavelet Transform

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

High Gain Step Up DC-DC Converter For DC Micro-Grid Application

Multi level DVR with Energy Storage System for Power Quality Improvement

FAULT PROTECTION OF A LOOP TYPE LOW VOLTAGE DC BUS BASED MICROGRIDS

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 01, 2016 ISSN (online):

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

Space Vector Modulated Voltage Source Converter for Stand Alone Wind Energy Conversion System

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Simulation And Comparison Of Space Vector Pulse Width Modulation For Three Phase Voltage Source Inverter

Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System

Internal DC Short-Circuit Fault Analysis and Protection for VSI of Wind Power Generation Systems

Analysis of Single Phase Self-Excited Induction Generator with One Winding for obtaining Constant Output Voltage

Improvement of AC Power Quality of Three Phase Inverter Using Voltage Drive Mode

Renewable Energy Integrated High Step-Up Interleaved Boost Converter for DC Microgrid Applications

CAPACITOR VOLTAGE BALANCING IN SINGLE PHASE SEVEN-LEVEL PWM INVERTER

Coordinated Control Strategy of Solar Photovoltaic Generators with MPPT and Battery Storage in Micro Grids

Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component

Transcription:

Fault Detection on Inverter Based Distribution Network Ravi 1, Pravesh 2 1,2 E.E Department, Deenbandhu Chhotu Ram University of Science & Technology, Murthal, Sonipat, Haryana, India Abstract This paper compares the two voltage based techniques of detecting fault on the inverter based distribution lines. The system comprises of power width modulated inverter feeding distribution network. Fast detection of fault is prime requirement in an electric power system. A protection system is developed based on voltage transformations. Studies are carried out in MATLAB software package. The studies reveal that both the techniques lead to protection of system against shunt faults and could be viable option for future inverter based distribution network. Keywords- Distributed Generation (DG), Power electronic converter (PEC), Micro Grid. I. INTRODUCTION In the last few years, increasing Co 2 levels in the environment have attracted the attention worldwide. One of the major causes of this is traditional plants for electricity generation i.e. coal/ diesel based plants. Moreover the demand of electricity is increasing day by day and building a new coal based/ hydro plant to meet this demand requires much time. Therefore one alternative is to use renewable energy source (RES), for generation of electricity. Some examples of renewable energy sources are solar plants, wind mills, fuel cell, micro turbines etc. But these plants have capacity of the order of 10Kw few Mega Watts [1]-[2]. These generations are inserted in distribution system, hence are called distributed generation. A distributed energy source may be either a distributed generation or any other kind of storage. Sometimes these distributed energy sources are combined with distribution network by power electronic converters. Introduction of power electronic based generation sources have many advantages such as: 1) Easy active and reactive power controls, 2) Synchronization of two sources with different voltage and frequencies, 3) Flexible and fast controls [3]. But as distribution lines are radial i.e. meant for power flow in one direction only, therefore there may be overvoltage on line if generation increases than load or sometimes the situation is reverse of it. Therefore such networks have to be designed to tackle the worst cases of maximum load/minimum voltage or minimum load/ maximum voltage. With power electronics based distributed energy resources at distribution network; the main concern is on impact on protection co-ordination of distribution network. In the event of fault, these power electronic converter based distributed energy source contributes less current comparatively and thus detection of fault becomes difficult. It is reported that during fault power electronic converters limit the current to twice its rated current [5]. Therefore fault detection has to be done by detecting the changes in voltage at point of common coupling (PCC). Fault on the power system creates unbalancing, which can be best studied by symmetrical components given by fortescue [6]. Symmetrical components define set of three voltages, positive sequence, negative sequence and zero sequence. For different types of faults power system is studied for different symmetrical component. Also three phase voltage can be transformed into d-q frame, as complex controls of three phase are simple in d-q frame. The objective of this paper is: To generate disturbance signals for detection of different faults by Vabc-Vdq0 transformation. To generate disturbance signals for same faults by symmetrical components transformation. To compare the performance of different fault detection disturbance signals (Vdist.). The proposed study is carried out in MATLAB software and a simulation model is developed. Section II of the paper discusses the system studied. Section III discusses the proposed technique. Section IV discusses about simulation studies, while section V deals with comparative analysis of the results. Conclusions are stated in section VI. II. INVERTER BASED DISTRIBUTION NETWORK A micro-grid is more or less like traditional power system but it is different in following ways: 1) different strategy of operation, 2) presence of large amount of power electronics based distributed energy sources, 3) need for fast synchronization, islanding detection, fault ride through, and reliable operation. Thus power electronics converters due to their complex controls make the concept of micro grid viable. The control loops of converters are either voltage controlled based or current controlled based, ISSN: 2348 8379 www.internationaljournalssrg.org Page 1

and thus are classified as voltage source converter or current source converter. Most of these converters employ complex current controlled loops. These power electronics converters are used to interface distributed generation with the grid [10]. A. Single line Diagram of System Under Study For study purpose an equivalent AC source integrated with a ac-dc-ac power electronic converter is modelled as distributed energy source. With introduction of PWM technique in the converters, the harmonics intrusion in the network is negligible, the output obtained is a pure sine wave [7]. The transformer typically is a isolation transormer meant for excluding any transient to enter in the distribution network. A. Three Phase Voltage(Vabc) to Rotating d-q Transformation The three phase voltage is transformed into reference frame. It becomes easy to perform control in d-q frame. Now this d-q values are used to detect the fault [7]. Figure 1.3 Shows proposed model for fault detection using abc to d-q transformation. Three phase stationary voltage is transformed into rotating d-q frame according to the following equations [7]: PCC Distrib -uted energy source PWM conver -ter Distributi -on network (1) Here Vds, Vqs, V0s are transformation of Va, Vb, Vc in stationary d-q frame. Further, DG Load Figure 1.1 Inverter Based Distribution Network B. Power Elecronic Converter PWM converter is modelled as shown in figure 1.2. The PWM converter control comprises of outer voltage regulation loop and inner current controlled loop [8]. The circuit for a PWM converter is shown in figure 1.2. (2) Vdr, Vqr are d-q values in rotating reference frame. These Vdr and Vqr are then used to detect the fault. It can be detected either by constructing a protection model similar to shown in fig.1.2 or by utilizing various wavelet transforms. b q- axis a d-axis c Figure 1.3 Relation Between Three Phase And D-Q Frame Figure 1.2 Power Electronic Converter Here controller works on error signals obtained from proposed voltage transformations. Switching transients at the output are filtered by L-C filter. Pulse width modulation is used to provide gate signals to three phase converter. III. PROPOSED TECHNIQUE This paper discusses two voltage based fault detection methods, B. Three phase voltage(vabc) to symmetrical components(v012) transformation During faults system enters in unbalanced condition, and unbalanced faults are dealt with study of symmetrical components. Therefore voltage at PCC is being converted into positive, negative and zero sequence component. The governing equations for this transformation are, Transformation equations are: (3) ISSN: 2348 8379 www.internationaljournalssrg.org Page 2

(4) Table 1.1 Distributed Energy Source Specifications S.NO. RATING 1. Phase to phase voltage 25Kv 2. frequency 60Hz 3. Three phase S.C level 10MVA V1=aV V Table 1.2 Filter Specifications S.NO. ELEMENT LOAD SIDE FILTER INVERTER SIDE FILTER 1. Capacitor 3 10-3 Farad 5 10-3 Farad 2. Inductor 2 10-3 Henry 2 10-4 Henry V2=a 2 V Figure 1.4 Relation Between Three Phase Voltage and Symmetrical Components. Here V, V, V represents positive, negative and zero sequence component respectively [9]. The protection model for fault detection is represented in figure 1.5. Three phase oltage from power electronic converter is first transformed into said transformation, i.e either in d-q reference frame or in symmetrical components. Thus any disturbance during fault is also get transformed. This disturbance signal (Vdist.) is then compared with their reference values in respective transformation frames and obtained signal is error signal. Based on this error signal fault is detected. This is depicted in equation (5): The two methods for fault detection are simulated for three different faults and voltage disturbance signals are generated. A. D-q Transformation: Simulations are performed for three different faults: 1) Three Phase to Ground Fault. Voltages in dq0 frame are shown in figure 1.7. the error signal for fault detection is obtained by comparing Vd, Vq and V0 with their respective reference values and then mean value obtained is the error signal. V errror = V reference V disturbance (5) Vabc from Power electronic converter Vabc to Vdq0 Filter Vabc to Vdq0 Compara -tor Vabc Vdist. Verror Figure 1.7 Vd, Vq, V0 For Three Phase To Ground Fault. Figure 1.6 Proposed Protection model IV. SIMULATION STUDIES To implement fault detection method MATLAB is used to build time domain simulation model of figure 1.1.system implemented is rated according to table 1.1-1.2. simulations are performed for a fault duration of 0.1 second 0.2 second. ISSN: 2348 8379 www.internationaljournalssrg.org Page 3

The non-linearities presesnt in signal needs to be to be processed by a filter. A low pass FIR filter diminish these non-linearities. 3) Single Phase Toground Fault: Figure 1.8 Vdq Error Signal For Three Phase To Ground Fault From figure 1.7-1.8 it is observed that the error signal is decaying but as soon as fault occurs the error signal increases at once, now this rate of change can be detected easily and thus is helpful in fault detection. Figure 1.11 Vd, Vq, V0 For Single Phase To Ground Fault 2) Two Phase to Ground Fault: Vdq0 signals and error signals are shown in figure 1.9-1.10. Figure 1.12 Vdq Error For Single Phase To Ground Fault Figure 1.11-1.12 reveals the Vd, Vq, V0 signals and error signal for fault detection during single phase to ground fault. The error signal shows disturbance in duration 0.1 second to 0.2 second. Figure 1.9 Vd, Vq, V0 For Two Phase to Ground Fault. B. Symmetrical Component Transformation Simulation studies with this transformation are carried out for three faults: 1) Three Phase to ground fault: Figure 1.13 & 1.14 displays V0, V1, V2 for three phase to ground fault & V012 error signal. Figure 1.10 Vdq Error Signal For Two Phase to Ground Fault Figure 1.13 V012 For Three Phase to Ground Fault. ISSN: 2348 8379 www.internationaljournalssrg.org Page 4

3) Single phase to ground: For single phase to ground the symmetrical components and error signal are depicted in the figure in 1.17 & 1.18 respectively. Figure 1.14 V012 Error Signal For Three Phase To Ground Fault. For a three phase to ground fault the error signal observed is produce instant change as soon as fault occurs. 2) Two Phase to ground fault: Symmetrical components for this fault is shown in the figure 1.15 & 1.16 Figure 1.17 V012 For Single Phase Faults. Figure 1.15 V012 For Two Phase To Ground Fault. Figure V012 Error For Single Phase To Ground Fault. V. RESULTS & ANALYSIS During both the scenarios studied on existing system, disturbance signals show good response to fault occurrence. Thus a definite rate of change can be observed from point where fault starts and it ends. Figure 1.16 V012 Errror For Two Phase To Ground Fault. A. For Three Phase to Ground Fault : Thus error signal is more linear, abrupt and constant in symmetrical component transformation and detect fault in no time, but signal is somewhat negative so it is required to calculate its mean value. B. For Two Phase to Ground Fault: With two phase fault the error signal in d-q transformation is non-linear, while error signal in symmetrical component it is still linear, abrupt and constant. The mean value of this error signal of V012 transformation gives an abrupt and linear signal. ISSN: 2348 8379 www.internationaljournalssrg.org Page 5

C. For single Phase to Ground Fault: It is observed that the error signal obtained in single phase to ground fault during d-q transformation is more non-linear while that of symmetrical transformation is still linear. Thus fault detector best works on mean error signals of symmetrical component transformation while error signals obtained with d-q signals need to be processed first. Thus on inverter based distribution networks instant changes in error signals reveals fast detection of faults. VI. CONCLUSION & FUTURE SCOPE It is observed that disturbance signal obtained by d-q transformation exhibits following properties: For three phase faults it is approximately linear. For two phase to ground fault it is almost linear but have some fluctuations. For single phase to ground fault it shows ripples. Symmetrical components transformation exhibits following properties: For three phase faults it is extremely linear and changes abrupt from 1 to 0. For two phase to ground fault it is linear but it goes negative for a while but mean of this signal is taken for controller. For single phase to ground fault it is linear and exhibits negative nature, so mean of this signal is better for controller to operate. With concept of DG, protection of inverter based system has become a prime issue. Based on developed disturbance signal, new fault detectors can be developed such as: By calculating THD of the disturbance signal. By performing wavelet analysis on disturbance signal. By developing an adaptive relay based on these disturbance signal. REFERENCES [1] S. S. Venkata, A. Pahwa, R. E. Brown, and R. D. Christie, What future distribution engineers need to learn, IEEE Trans. Power Syst., vol. 19, no. 1, pp. 17 23, Feb. 2004. [2] C. Wang and M. H. Nehrir, Analytical approaches for optimalplacementof distributed generation sources in power systems, IEEE Trans. Power Syst., vol. 19, no. 4, pp. 2068 2076, Nov. 2004. [3] R. H. Lasseter, Microgrid, in Proc. IEEE Power Eng. Soc. WinterMeeting, New York, Jan. 2002, vol. 1, pp. 305 308. [4] F. Katiraei, M. R. Iravani, and P. W. Lehn, Micro-grid autonomous operation during and subsequent to islanding process, IEEE Trans. Power Del., vol. 20, no. 1, pp. 248 257, Jan. 2005. [5] J. Keller and B. Kroposki, Understanding Fault Characteristics of Inverter-Based Distributed Energy Resources, NREL, report, January 2010. [6] J.B Gupta, Power System Analysis, Dhanpat rai Publications, page no.-,new Delhi, India. [7] H Al-Nasseri and M A Redfern, Control and Transient Operation of Grid-Connected Voltage Source Converter under Unbalanced Voltage Conditions. CIGRE Symposium Power Systems with Dispersed Generation, Athens 13-16th April 2005. [8] R.C Dugan, Mark F. McGranaghan, Surya Santoso, H. Wayne Beaty Electrical Power Systems Quality, 2 nd ed., Tata Mc-Graw-Hill Edition 2008, New Delhi, India. [9] Sohrab Mirsaedi, Mohammad Reza Miveh, Micro grid protection using a designed relay based on symmetrical componenets, Middle east journal of scientific research, jan. 2012 [10] F. Blaabjerg, Z. Chen, and S. Kjaer, Power electronics as efficient interface in dispersed power generation systems, IEEE Trans. Power Electron., vol. 19, no. 5, pp. 1184 1194, Sep. 2004. [11] Y. Yorozu, M. Hirano, K. Oka, and Y. Tagawa, Electron spectroscopy studies on magneto-optical media and plastic substrate interface, IEEE Transl. J. Magn. Japan, vol. 2, pp. 740-741, August 1987 [Digests 9th Annual Conf. Magnetics Japan, p. 301, 1982]. [12] Hassan Nikkhajoei, Reza Iravani, Steady-State Model and Power Flow Analysis of Electronically-Coupled Distributed Resource Units, IEEE transactions on power delivery, vol. 22, no. 1, January 2007. [13] Natthaphob Nimpitiwan, Gerald Thomas Heydt, Raja Ayyanar, Siddharth Suryanarayanan, Fault Current Contribution From Synchronous Machine and Inverter Based Distributed Generators, IEEE transactions on power delivery, vol. 22, no. 1, January 2007. ISSN: 2348 8379 www.internationaljournalssrg.org Page 6