2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd

Similar documents
2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices

2P48 Potential Selecting Relay

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602

1M122A Transformer Parallel Control System

2V68-S User Guide. CT Supervision And Shorting Relay. User Guide

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work

Burdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com

BUS2000 Busbar Differential Protection System

Type MCAG 14, 34 T&D. High Stability Circulating Current Relay

3 Pole high impedance differential relay 7VH83

2V165 Transformer Parallel Control Relay

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

Electrical Protection System Design and Operation

ISSN: Page 298

SPAE 010, 011 High Impedance Protection Relay

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

RCTrms Technical Notes

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

2015 Relay School Bus Protection Mike Kockott March, 2015

Transformer Fault Categories

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software

RESTRICTED EARTH FAULT RELAY

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

LM78S40 Switching Voltage Regulator Applications

Solutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium Voltage Switchgears

Alternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Transformer Protection

Back to the Basics Current Transformer (CT) Testing

Innovative Science and Technology Publications

Conventional Paper-II-2013

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Protection of Microgrids Using Differential Relays

Ferroresonance Experience in UK: Simulations and Measurements

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Conventional Paper-II-2011 Part-1A

An easy-to-use Precision Power Analyser. The touch of a button gives direct readout of true power and a host of other useful measurements.

PIPSPC. Prepared by Eng: Ahmed Safie Eldin. And. Introduction. Protection Control. Practical. System. Power

Content. 1. Dimensiong of CT s. 2. Error definitions. 3. General design aspects. 4. Linear cores. Certified acc. to ISO 9001/14001, SN EN 45001

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Transformer Protection

SATURATION ANALYSIS ON CURRENT TRANSFORMER

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

LFR: flexible, clip-around current probe for use in power measurements

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems

Unit Protection Differential Relays

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

This is a preview - click here to buy the full publication

Accurate Current Measurement Transducer for Relaying Purpose

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Transformer differential protection

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

P3065 LOW PROFILE LINE MATCHING TRANSFORMER PRODUCT DATA SHEET. IEC 950, UL 1950 and EN certified UL Recognized Component

ABSTRACT 1 INTRODUCTION

Transformer & Induction M/C

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

Busbars and lines are important elements

P3065 LOW PROFILE LINE MATCHING TRANSFORMER PRODUCT DATA SHEET

Earth Fault Protection

LM2935 Low Dropout Dual Regulator

Line Protection Roy Moxley Siemens USA

LM2925 Low Dropout Regulator with Delayed Reset

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

LM125 Precision Dual Tracking Regulator

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

TABLE OF CONTENT

IJRASET: All Rights are Reserved

System Protection and Control Subcommittee

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

The power transformer

Appendix D Fault Levels

Power System Protection Manual

7PG21 Solkor Rf Feeder Protection Energy Management

Application of Low-Impedance 7SS601 Busbar Differential Protection

RC-19A relay - Current monitoring

Impact Assessment Generator Form

Transformer protection IED RET 670

Filter Considerations for the IBC

P2001 LINE MATCHING TRANSFORMER PRODUCT DATA SHEET. 12.6mm (0.5") seated height

Specifications. S&C BankGuard Plus Controls. For Substation Capacitor Banks and Shunt Reactors. Conditions of Sale

Fixed Series Compensation

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS

MV network design & devices selection EXERCISE BOOK

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

Transcription:

2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices

1. INTRODUCTION This document provides guidelines for the performance calculations required for high impedance circulating current protection. 2. PROCEDURE FOR PERFORMANCE CALCULATIONS 2.1 Data Required 2.1.1 System Information i) Maximum through fault level, S tf. ii) System voltage, V sys. iii) Minimum fault current, I min. iv) Circuit breaker short circuit rating, I cb. v) Maximum through fault current, I tf = S tf / ( 3 x V sys ). 2.1.2 Current Transformer Information The CTs used in this type of scheme should be of the high accuracy and low leakage reactance type. 1. All the current transformers should have identical turns ratio. 2. The knee point voltage of the current transformers should be at least twice the relay setting voltage. The knee point voltage is expressed as the voltage at fundamental frequency applied to the secondary circuit of the current transformer which when increased in magnitude by 10% causes the magnetizing current to increase by 50%. 3. The current transformers should be of the low leakage reactance type. Class PX current transformers to IEC60044 meet the above requirements and this type are recommended. i) CT turns ratio, T. ii) CT secondary resistance, R CT. iii) CT knee-point voltage, V K. iv) CT magnetizing characteristic, VI curve. v) CT lead loop resistance, R L. The CT lead resistances can be calculated from the layout drawings. In the worst case a maximum lead resistance can be estimated from the figures below. 2.5mm 2 wire = 7.6Ω/km = 0.0076Ω/m 4.0mm 2 wire = 4.2Ω/km = 0.0042Ω/m 6.0mm 2 wire = 3.0Ω/km = 0.0030Ω/m Page 2 of 12

2.1.3 Protection Relay Information i) Operating current or current setting range, I s. ii) Operating voltage or relay burden expressed in voltage, V r. 2.2 Relay Setting Voltage The protection relay must remain stable under maximum through fault conditions, when a voltage is developed across the protection due to the fault current. The relay setting voltage must be made equal or greater than this maximum voltage for the protection to remain stable. That is: V s > V stab...(1) V s V stab = relay setting voltage. = stability voltage. The fault current may contain a transient d.c. component current which can cause saturation of the current transformer core and thus distortion of the secondary current. Therefore in order to calculate the required setting voltage, it is assumed that one of the protection CT s saturates. Under these conditions the healthy CT s are driving current through the parallel impedance of the saturated CT with leads and the protection relay. The saturated CT impedance is represented by its secondary winding resistance, and the maximum lead loop resistance between the CT and the relay must also be considered. Page 3 of 12

For the simple case of two current transformers, the voltage developed across the relay is given by: V stab = I tf x T x (R CT + R L )...(2) V stab I tf T R CT R L = stability voltage. = maximum through fault current. = CT turns ratio. = CT secondary winding resistance. = CT lead loop resistance. In most practical systems where more than two current transformers exist, the same equation is used based on the fact that this represents the most onerous condition. R L is chosen for the longest distance between any two CT s in parallel. For reliable in zone operation the relay setting voltage should be less than half of the knee point voltage of any CT in the protection scheme. That is: V s < V K / 2...(3) V s V K = relay setting voltage. = CT knee point voltage. The criteria outlined above establishes maximum and minimum values for the relay setting voltage. 2.3 Stabilising Resistor The relay voltage setting range may not be sufficient to be set to the required level of V s as calculated previously, due to the relay s low burden. In such cases a stabilizing resistor is provided in series with the relay to increase the relay circuit setting. Page 4 of 12

The resistor is sized as follows: V s - V r = I s R s...(4) R s I s V r = stabilising resistance required. = Relay current setting. = Relay voltage (derived from the relay burden characteristics). Using the maximum and minimum voltages calculated by (2) & (3), a resistance range is obtained from which a suitable resistor can be chosen. After which the actual relay circuit setting voltage can be calculated. 2.4 Thermal Rating of Resistors The resistors incorporated in the scheme must be capable of withstanding the associated thermal conditions. 2.4.1 Continuous Power Rating The required continuous power rating of a resistor is defined as: P con = ( I con )² R...(5) P con I con R = resistor continuous power rating. = continuous resistor current i.e. the operating current of the relay. = resistance. 2.4.2 Half-second Power Rating The resistor must be capable of withstanding the associated power dissipation due to a fault condition. The rms voltage developed across a resistor for maximum internal fault conditions is defined as: V f = ( V k ³ x R x I fs ) ¼ x 1.3...(6) V f V K R I fs = rms voltage across resistor. = CT knee point voltage. = resistance. = maximum secondary fault current which can be calculated from the circuit breaker rating, I cb, if the maximum internal fault current is not given. The maximum internal fault current is usually the same as the maximum through fault current. Page 5 of 12

The half-second power rating is given by: P half = V f ² /R...(7) P half V f R = half-second power rating. = rms voltage across resistor. = resistance. 2.5 Voltage Limiting Resistor The previous calculations produced a voltage setting for through fault stability, now the case for an internal fault needs to be considered. The maximum primary fault current will cause high voltage spikes across the relay at instants of zero flux since a practical CT core enters saturation on each half-cycle for voltages of this magnitude. If this voltage exceeds 3kV peak then it is necessary to suppress the voltage with a non linear resistor (Metrosil) in a shunt connection which will pass the excess current as the voltage rises. The formula to calculate this voltage is: V pk = 2 x ( 2V k [V fs - V k ] ) ½...(8) V pk V K V fs = peak value of the voltage waveform. = CT knee point voltage. = value of voltage that would appear if CT did not saturate. V fs R r = ( I tf / N ) x ( R s + R r ) (9) = is relay resistance The Metrosil must be chosen to match the relay circuit setting voltage (i.e. its characteristic must not change significantly until beyond the relay setting V s ) and it must be capable of passing the maximum prospective fault current that can be transformed by the CT. The type of Metrosil required is chosen by its thermal(energy) rating as defined by the formula: P = ( 4 / π ) x I fs x V k...(10) P = thermal metrosil rating, Joules π = pi = 3.14159265. I fs = maximum secondary fault current which can be calculated from the circuit breaker rating, I cb, if the maximum internal fault current is not given. The maximum internal fault current is usually the same as the maximum through fault current. = CT knee point voltage. V K Page 6 of 12

There are two types of Metrosil available the 3 inch type with a maximum rating of 8kJ/s and the 6 inch type with a maximum rating of 33kJ/s. A 6" Metrosil is recommended as standard with 2C73. 2.6 Primary Fault Setting The primary operating current or fault setting may be calculated from: I p = ( ni e + I s + I nlr ) / T...(11) I p n I e I s I nlr T = primary fault setting. = number of CTs in parallel. = exciting current of each CT at the relay circuit setting voltage (assuming all CTs are identical). = operating current of relay at the relay circuit setting voltage. = current in metrosil at the relay circuit setting voltage. = CT turns ratio. I p should fall within the recommended fault setting given by the relevant standard, the clients specification or in the absence of these good engineering practice, and be greater than a specified minimum, I m (where I m is a percentage of the minimum primary fault current, I min ). If the calculated primary fault setting I p is lower than a specified minimum (i.e. it is too sensitive) small increases can be achieved by increasing the relay setting voltage V s and hence increasing the CT exciting current I e. Alternatively, when the required increase in fault setting is large, the correct setting can be obtained by connecting a shunt setting resistor. The current required through the shunt resistor is given by: I sh = I m T - ni e - I s - I nlr...(12) I sh I m T n I e I s I nlr = current through shunt resistor. = percentage of the minimum primary fault current I min. = CT turns ratio. = number of CTs in parallel. = exciting current of each CT at the relay circuit setting voltage (assuming all CTs are identical). = operating current of relay at the relay circuit setting voltage. = current in non linear resistor at the relay circuit setting voltage. Page 7 of 12

Therefore, the shunt setting resistance is: R sh = V s / I sh...(13) R sh V s I sh = shunt resistance. = relay circuit setting voltage. = current through shunt resistor. Page 8 of 12

3. WORKED EXAMPLE The following worked example is based on the application shown in figure 1. Figure 1 - Simplified circulating current scheme Example shown for: I f = 15kA, C.T. RATIO 500/1, single busbar, 4 circuits F2 15 ka A B C D 10000A No current through relay A B C D 30A through relay 5A 9A 6A 20A 5A 9A 6A 10A 2500A 4500A 3000A F1 15 ka 5000A 2500A 4500A 3000A 5000A EXTERNAL FAULT of 15 ka RELAY CURRENT = 5 + 9 + 6-20 = 0A INTERNAL FAULT of 15 ka Relay Current = 5 + 9 + 6 + 10 = 30A 3.1 Data 3.1.1 System Information i) Maximum through fault level, S tf = 570MVA ii) System voltage, V sys = 22kV iii) Minimum fault current, I min = 2kA iv) Circuit breaker short circuit rating, I cb = 25kA 3.1.2 Current Transformer Information The CTs are low leakage reactance type having an accuracy class PX in accordance with IEC 60044. 500/1A, 0.05PX200R1.0 i) CT turns ratio, T = 1/500 ii) CT secondary resistance, R CT = 1.0Ω iii) CT knee-point voltage, V K = 200V iv) CT lead loop resistance, R L = 1.0Ω (assume figure for worst case) Page 9 of 12

3.1.3 Protection Relay Current Setting (2C73) Criteria 1 Class PX CTs are permitted to have a turns ratio error not exceeding ±0.25%. The relay must not operate for a CT spill condition due to turns ratio error on through faults. For I tf = 15,000A I spill = [ ( 2 x turns ratio error ) / 100 ] x I tf x T = [ ( 2 x 0.25 ) / 100 ] x 15,000 x ( 1 / 500 ) = 150mA I s > I spill > 150mA Criteria 2 The primary operating current of the relay circuit is : I p = ( ni e + I s + I nlr ) / T...(11) Application is a single busbar with 4 circuits, n= 4 Assume CT magnetizing current at setting voltage I e = 20mA (refer to CT VI curve for actual figure). The current passing through the Metrosil at the setting voltage is ignored. The relay circuit is not to operate at levels < 10% of the minimum primary fault current. i.e. 10% of I min = ( 10 / 100 ) x 2kA = 200A From eqn (11) I s > ( I p x T ) - ni e - I nlr > ( 200A x 1 / 500 ) - 4 x 0.02 > 320mA To satisfy Criteria 1 and 2 choose I s = 400mA i) The 2C73[B][A][*] has a 1A CT input with a current setting range of 200 to 800mA with 7 x 10% plug setting steps. Select Is = 400mA ii) The a.c burden < 1.2VA at pickup Relay voltage is given by V r = VA RELAY /I s = 1.2/0.4 = 3 V also R r = VA RELAY /( I s ) 2 = 7.5 Ω 3.2 Relay Setting Voltage Primary through-fault current: I tf = S tf / ( 3 x V sys ) Itf = 570 x 10 3 kva / ( 3 x 22kV) I tf = 15,000A Page 10 of 12

To ensure stability for through faults apply eqn (2) V stab > I tf x T x (R CT + R L )...(2) V stab > (15000A / 500) x (1 + 1) > 60V From eqn (3) V s < V K / 2...(3) V s < 200V / 2 < 100V Thus to maintain stability for maximum through fault current and reliable operation for an in zone fault : 60V < V s < 100V. 3.3 Stabilising Resistor The calculated relay voltage of 3V developed by the 2C73 is insufficient to achieve the derived value of relay setting voltage Vs, thus a series stabilising resistor is required. Using eqn (4) a resistance range may be derived V s - V r = I s R s...(4) For V s > 60V => R s > (1/I s ) x (V s - V r ) R s > (1/0.4A) x (60V - 3V) = 142.5 Ω For V s < 100V => R s < (1/I s ) x (V s - V r ) R s < (1/0.4A) x (100V - 3V) = 242.5 Ω Choose R s = 200 Ω Using eqn (4) the relay circuit setting voltage is V s = I s R s + V r = 0.4A x 200 Ω + 3V = 83V 3.4 Thermal Rating of Stabilising Resistor 3.4.1 Continuous Power Rating From eqn (5) P con = (I con )² R...(5) P con = (0.4)² x 200 Ω = 32W continuously 3.4.2 Half-second Power Rating From eqn (6) V f = (V k ³ x R x I fs ) ¼ x 1.3...(6) V f = (200V³ x 200 Ω x 15,000A / 500) ¼ x 1.3 = 608 V Page 11 of 12

From eqn (7) P half = V f ² /R...(7) P half = 608 V ² / 200 Ω = 1848W for half a second A 100W or 200W resistor is generally used as standard. 3.5 Voltage Limiting Resistor If the voltage developed across the relay circuit exceeds 3kV peak then it is necessary to suppress the voltage with a non linear resistor (Metrosil) in a shunt connection which will pass the excess current as the voltage rises. From eqn (9) V fs = ( I tf T ) x ( R s + R r ) (9) = ( 15,000 A / 500 ) x ( 200 Ω + 7.5 Ω ) = 6,225 V From eqn (8) V pk = 2 x (2V k [V fs - V k ]) ½...(8) = 2 x (2 x 200V x [ 6,225V - 200V ]) ½ = 3,105 V The peak value is > 3kV, therefore a non linear resistor is required. The required energy rating for the non linear resistor is calculated from eqn (10). P = (4 / π) x I fs x V k...(10) = (4 / π) x (15,000A / 500) x 200V = 7.6 kj/s Use of a 3 Metrosil is border line. A 6" Metrosil is recommended as standard with the 2C73. Page 12 of 12

Australian Content Unless otherwise stated the product(s) quoted are manufactured by RMS at our production facility in Melbourne Australia. Approximately 60% of our sales volume is derived from equipment manufactured in house with a local content close to 90%. Imported components such as semi-conductors are sourced from local suppliers & preference is given for reasonable stock holding to support our build requirements. Quality Assurance RMS holds NCSI (NATA Certification Services International), registration number 6869 for the certification of a quality assurance system to AS/NZS ISO9001-2008. Quality plans for all products involve 100% inspection and testing carried out before despatch. Further details on specific test plans, quality policy & procedures may be found in section A4 of the RMS product catalogue. Product Packaging Protection relays are supplied in secure individual packing cardboard boxes with moulded styrene inserts suitable for recycling. Each product & packing box is labeled with the product part number, customer name & order details. Design References The products & components produced by RMS are based on many years of field experience since Relays Pty Ltd was formed in 1955. A large population of equipment is in service throughout Australia, New Zealand, South Africa & South East Asia attesting to this fact. Specific product & customer reference sites may be provided on application. Product Warranty All utility grade protection & auxiliary relay products, unless otherwise stated, are warranted for a period of 24 months from shipment for materials & labour on a return to factory basis. Repair of products damaged through poor application or circumstances outside the product ratings will be carried out at the customer s expense. Standard Conditions of Sale Unless otherwise agreed RMS Standard Terms & Conditions (QF 907) shall apply to all sales. These are available on request or from our web site. Relay Monitoring Systems Pty Ltd 6 Anzed Court, Mulgrave, Victoria 3170, AUSTRALIA Tel: +61 3 8544 1200 Fax: +61 3 8544 1201 Email: rms@rmspl.com.au Web: www.rmspl.com.au 2010 Relay Monitoring Systems Pty Ltd Due to RMS continuous product improvement policy this information is subject to change without notice.