International Journal of Advance Engineering and Research Development CONTROL OF REDUCED-RATING DYNAMIC VOLTAGE RESTORER

Similar documents
UPQC System With an Improved Control Method Under Distorted and Unbalanced Load Condition

ISSN Vol.03,Issue.11, December-2015, Pages:

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Synchronous Reference Frame Theory (SRF) along with PI Controller Based Dynamic Voltage Restorer

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

Multi level DVR with Energy Storage System for Power Quality Improvement

Mitigation of Voltage Sag/Swell by Using Battery Energy Storage DVR for Induction Motor Drive Applications

Application of Dynamic Voltage Restorer for Voltage Balancing with ASD Load Using DQO Transformation

Design Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Performance of DVR under various Fault conditions in Electrical Distribution System

MITIGATION OF VOLTAGE SAG IN A DFIG BASED WIND TURBINE USING DVR

Protection from Voltage Sags and Swells by Using FACTS Controller

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

SRF CONTROLLED DVR FOR COMPENSATION OF BALANCED AND UNBALANCED VOLTAGE DISTURBANCES

Power Quality enhancement of a distribution line with DSTATCOM

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Voltage Sag and Swell Identification Using FFT Analysis and Mitigation with DVR

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Design Requirements for a Dynamic Series Compensator for Voltage Sags Mitigation in Low Voltage Distribution System

DYNAMIC VOLTAGE RESTORER (DVR) FOR VOLTAGE SAG COMPENSATION WITH FUZZY LOGIC CONTROLLER. Chennai, Tamilnadu, India. Chennai, Tamilnadu, India.

Power Quality improvement of a three phase four wire system using UPQC

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Sag/Swell Compensation and Displacement Factor Improvement using IDVR in Distribution Network

Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

Compensation of Different Types of Voltage Sags in Low Voltage Distribution System Using Dynamic Voltage Restorer

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review

Mitigation of Voltage Complication by a Novel Control Algorithm Based Dynamic Voltage Restorer

INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES Volume V /Issue 4 /AUG 2015

Mitigation of Power Quality Problems Using DVR in Distribution Network for Welding Load

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Modelling And Analysis of DVR With SEPIC Converter And Supercapacitor

Voltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Performance of DVR & Distribution STATCOM in Power Systems

Simulation and Implementation of DVR for Voltage Sag Compensation

Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory for Balanced and Unbalanced Loads

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

A CONTROL TECHNIQUE FOR INSTANT MITIGATION OF VOLTAGE SAG/SWELL BY DYNAMIC VOLTAGE RESTORER

Voltage Sag Matigation in Distribution Network by Dynamic Voltage Restorer

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Voltage Sag/ Voltage Swell Compensation and Reduction Harmonic Distortion using Dynamic Voltage Restorer

Enhancement of Power Quality Using Advanced Series Active Power Filters

Compensation of Balanced and Unbalanced voltage disturbance using SRF controlled DVR

SUPER CONDUCTING MAGNETIC ENERGY SYSTEM WITH DVR FOR VOLTAGE QUALITY IMPROVEMENT USING PSO BASED SIMPLE ABC FRAME THEORY

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

ABSTRACT I. INTRODUCTION

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

A Cost Effective Topology of DVR for a 3 Phase 4 Wire Distribution System

Mitigation of voltage sags/swells unbalanced in low voltage distribution systems

Investigation of Dynamic Voltage Restorer for Compensation of Voltage Sag and Swell

ISSN Vol.07,Issue.21, December-2015, Pages:

Voltage Quality Enhancement in an Isolated Power System through Series Compensator

Power Quality Improvement using Hysteresis Voltage Control of DVR

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

Analysis & Function of Unified Power Quality Conditioner for Power Quality Improvement of Distributed Network

By Dynamic Voltage Restorerfor Power Quality Improvement Subhro Paul * SujaySarkar ** SurojitSarkar ***Pradip Kumar Saha 1, Gautam Kumar Panda 2

Design of Dynamic Voltage Restorer for three phase network as steady state device in the Distribution System

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Mitigation of Voltage Sag/Swell Using UPQC

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

Modelling of Dynamic Voltage Restorer for Mitigation of Voltage Sag and Swell Using Phase Locked Loop

Power Quality and the Need for Compensation

Improvement of Dynamic Voltage Restorer (DVR) Using Proportional Integral (PI)Controller for Mitigation of Voltage Sag

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Design of Interline Dynamic Voltage Restorer for Voltage Sag Compensation

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT

Control of grid connected inverter system for sinusoidal current injection with improved performance

SIMULATION OF D-STATCOM IN POWER SYSTEM

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Investigation of D-Statcom Operation in Electric Distribution System

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Voltage Sag Mitigation of DVR using Matlab Simulation

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

SIMULATION VERIFICATION OF DYNAMIC VOLTAGE RESTORER USING HYSTERESIS BAND VOLTAGE CONTROL

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Enhancement of Power Quality in Distribution System Using D-Statcom

CHAPTER 6 MITIGATION OF VOLTAGE SAG, SWELL AND SINGLE PHASE OUTAGE USING MULTI WINDING TRANSFORMER

Using Fast Fourier Extraction Method Power Quality Improvement by Dvr for Unbalanced Voltage Sag-Swell Control

Transcription:

Scientific Journal of Impact Factor (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 06, June -2018 e-issn (O): 2348-4470 p-issn (P): 2348-6406 CONTROL OF REDUCED-RATING DYNAMIC VOLTAGE RESTORER 1 Kashyap viroja, 2 Prof. H. N. Raval 1 ME electrical, L D COLLEGE OF ENGINEERING, Ahmedabad, INDIA 2 Electrical Eng. Department L. D. College of Engineering, Ahmedabad, INDIA Abstract In this white paper, different voltage injection schemes for dynamic voltage restorers (DVRs) are analyzed with particular focus on a new method used to minimize the rating of the voltage source converter (VSC) used in DVR. A new control technique Is proposed to control the capacitor-supported DVR. The control of a DVR is demonstrated with a reduced-rating VSC. The synchronous reference frame theory is used. The compensation of the voltage sag, swell is showed using a reduced-rating DVR. Keywords Dynamic voltage restorer (DVR), power quality, voltage harmonics, voltage sag, voltage swell. I. Introduction Power Quality is surely an important concern in most industries today, because of the increase in the number of load sensitive to power disturbances. The power quality is an index to quality of current and voltage available to industrial, commercial and household consumers of electricity. The problem regards both the utilities and customers. For the utilities, to provide adequate power quality is a moving objective because of changes in user equipment and requirements. Power quality is a topic embracing a large field. On one side, several different events are involved in power quality: spikes or surges, sags, swells, outages, under and over voltages, harmonics, flicker, frequency deviations, and electrical noise. Voltage sags in electrical grid are not always possible to avoid because of finite clearing time of faults that cause the voltage sag. Voltage sag are the common reason for interruption in production plants and for end user equipment malfunctions in general. In particular, tripping of equipment in a production line can cause production interruption and significant costs due to loss of production. This project uses the DVR Custom power devices for power quality improvement in the distribution system. DVRs can eliminate most of the sags and minimize the risk of load tripping for very deep sag. The synchronous reference frame (SRF) theory is used for the control of DVR. Power Electronic Devices IT and Office Equipment Arcing Device Large Motor Starting Load Switching Sources of Power Quality Problems Power Quality Problems @IJAERD-2018, All rights Reserved 403

II. Dynamic Voltage Restorer A power electronic converter based series compensator that can protect critical loads from all supply side disturbances other than outages is called a dynamic voltage restorer. The restorer is capable of generating or absorbing independently controllable real and reactive power at its AC output terminal. This device employs solid-state power electronic switches in a pulse-width modulated (PWM) inverter structure. It injects a set of three-phase AC output voltages in series and synchronism with the distribution feeder voltages. The amplitude and phase angle of the injected voltages are variable thereby allowing control of the real and reactive power exchange between the device and the distribution system. The DC input terminal of the restorer is connected to an energy source or an energy storage device of appropriate capacity. Location of DVR DVR is a series connected solid state device that injects voltage in to the system in order to regulate the load side voltage. It is normally installed in a distribution system between the supply and the critical load feeder at the point of common coupling (PCC). The block diagram of the DVR The Synchronous Reference Frame (SRF) Theory (dq0 Transformation or PARK s Transformation). The park s transformation is used to control of a DVR. The dq0 method gives the sag depth and phase shift information with start and end times. The compensation for voltage sags using a DVR can be performed by injecting or absorbing the reactive power or the real power. When the injected voltage is in quadrature with the current at the fundamental frequency, the compensation is made by injecting reactive power and the DVR is with a self-supported dc bus. However, if the injected voltage is in phase with the current, DVR injects real power, and hence, a battery is required at the dc bus of the VSC. A. Control of DVR With BESS for Voltage Sag & Swell Fig.5.2 shows a control block of the DVR in which the SRF theory is used for reference signal estimation. The voltage sat the PCC vs and at the load terminal VL are sensed for deriving the IGBTs gate signals. Load voltages (VLa, VLb, VLc) are converted to the rotating reference frame using abc dqo conversion using Park s transformation with unit vectors (sinθ, cosθ) derived using a phase-locked loop as @IJAERD-2018, All rights Reserved 404

Similarly, reference load voltages (V *La, V *Lb, V *Lc) and voltages at the PCC Vs are also converted to the rotating reference frame. Reference DVR voltages (v* dvra, v* dvrb, v* dvrc) and actual DVR voltages (vdvra, vdvrb, vdvrc) are used in a pulse width modulated (PWM) controller to generate gating pulses to a VSC of the DVR. The PWM controller is operated with a switching frequency of 10 khz. System parameters : AC line voltage: 415 V, 50 Hz Line impedance: Ls = 3.0 mh, Rs = 0.01 Ω Linear loads: 10-kVA 0.80-pf lag DC voltage of DVR: 300 V AC inductor: 2.0 mh Gains of the d-axis PI controller: Kp1 = 0.5, Ki1 = 0.35 Gains of the q-axis PI controller: Kp2 = 0.5, Ki2 = 0.35 PWM switching frequency: 10 khz Fig : Simulink model of DVR with BESS Fig : Control block of DVR with BESS. Fig : Reference voltage generation @IJAERD-2018, All rights Reserved 405

Fig : Pulse generation Fig : Sag mitigation by DVR with BESS B. Control of Self-Supported DVR for Voltage Sag & Swell Fig. 5.3 shows a capacitor-supported DVR connected to threephase critical loads, and Fig. 5.4 shows a control block of the DVR in which the SRF theory is used for the control of selfsupported DVR. Voltages at the PCC vs are converted to the rotating reference frame using abc dqo conversion using Park s transformation. The harmonics and the oscillatory components of the voltage are eliminated using low pass filters (LPFs). The compensating strategy for compensation of voltage quality problems considers that the load terminal voltage should be of rated magnitude and undistorted. In order to maintain the dc bus voltage of the supported capacitor, a PI controller is used at the dc bus voltage of the DVR. Kp and Ki are the proportional and the integral gains of the dc bus voltage PI controller. The amplitude of load voltage VL at the PCC is calculated from the ac voltages (vla, vlb, vlc) as VL = Reference load voltages (v La, v Lb, v Lc) in the abc frame are obtained from a reverse Park s transformation. The error between sensed load voltages (vla, vlb, vlc) and reference load voltages is used over a controller to generate gating pulses to the VSC of the DVR. @IJAERD-2018, All rights Reserved 406

Fig : Self supported DVR Fig : Control of a self supported DVR Fig : Sag mitigation by self supported DVR III. Comparison DVR with BESS It works efficiently when its inject voltage at any angle with the current and inject both active as well as reactive power. Minimum possible rating when voltage injection is in-phase. As per the calculations the rating of the DVR is 10.392 KVA for the same system parameters It can affect on rating of energy storage. @IJAERD-2018, All rights Reserved 407

Capacitor Supported DVR It works efficiently when inject voltage only at the quadrature with the current and inject only reactive power to the system. No active power injection accept small losses. As per the calculations the rating of the DVR is 6.8 KVA for the same system parameters It can affects the rating of the voltage source converter. IV. Conclusion The operation of a DVR has been demonstrated with a new control technique using various voltage injection schemes. A comparison of the performance of the DVR with different schemes has been performed with a reduced-rating VSC, including a capacitor-supported DVR. The reference load voltage has been estimated using the method of unit vectors, and the control of DVR has been achieved, which minimizes the error of voltage injection. The SRF theory has been used for estimating the reference DVR voltages. It is concluded that the voltage injection in-phase with the PCC voltage results in minimum rating of DVR but at the cost of an energy source at its dc bus. References [1]. PYCHADATHIL JAYPRAKASH, BHIM SINGH, D.P. KOTHARI, AMBRISH CHANDRA,2014. Control Of Reduced Rating Dynamic Voltage Restorer With A Battery Energy Storage System IEEE Transactions On Industry Applications, Vol. 50, No. 2, March / April 2014. [2]. S. RAJESH, M. K. MISHRA, SRIDHAR K. Design And Simulation Of Dynamic Voltage Restorer Using Sinusoidal Pulse Width Modulation 16 th National Power Systems Conference, Dec 2010. [3]. ROSIL OMAR, N. ABD RAHIM Modeling And Simulation For Voltage Sag / Swells Mitigation Using Dynamic Voltage Restorer Australasian Universities Power Engineering Conference 2008 [4]. A. K. RAMASAMY, R. K. IYER, V. K. RAMACHANDARAMUTHY Dynamic Voltage Re [5]. R SEDAGATHI, N M AFROOZI, Y NEMATI, A ROHANI, A R TOORANI, N JAVIDTASH, ALI HEYDARZADEGAN AND H SEDAGHATI A Survey Of Voltage Sags And Voltage Swells Phenomena In Power Quality Problems International Journal Of Scientific Research And Management (IJSRM), Page 458-462, 2013. storer For Voltage Sag Compensation IEEE PEDS 2005 [6]. JOSEPH SEYMOUR TERRY HORSLEY The Seven Types of Power Problems American Power Conversion 2005 [7]. JOHN GODSK NIELSEN, MICHAEL NEWMAN, HANS NIELSEN, AND FREDE BLAABJERG Control and Testing of a Dynamic Voltage Restorer (DVR) at Medium Voltage Level IEEE Transactions On Power Electronics, Vol. 19, No. 3, MAY 2004. [8]. P. DAEHLER,TURGI, SWITZERFAND R. MOLTER Requirements And Solutions For Dynamic Voltage Restorer, A Case Study IEEE 2000. @IJAERD-2018, All rights Reserved 408