Improving Rural Power Quality in New Zealand. EEA Conference & Exhibition 2010, June 2010, Christchurch

Similar documents
Power Quality implications of new residential appliances. EEA Conference & Exhibition 2010, June 2010, Christchurch

Harmonic Planning Levels for Australian Distribution Systems

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

Power Quality Management

Harmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems

A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits

Harmonic Filters for Single Phase Equipment

Power Quality Survey in a Distribution System, Standard Procedures and Limitations. H. Mokhtari S. Hasani and M. Masoudi

Tuningintobetter power quality

Overvoltage Protection of Light Railway Transportation Systems

Power Quality Improvement by Input Current Harmonic Reduction Using Three-Phase Multi-Pulse AC-DC Converter

ON-SITE TESTING OF SPECIAL TRANSFORMERS

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

Electromagnetic Harmonic Filters Technical Guide

Harmonic Reduction using Thyristor 12-Pulse Converters

Harmonic Distortion Evaluations

Open-Delta Systems Affect Variable Frequency Drives

Alternative Designs to Support Electronic Loads in Extensive UPS Distribution Systems

Power Transmission of AC-DC Supply in a Single Composite Conductor

HARMONIC REDUCTION DUE TO MIXING SINGLE-PHASE AND THREE-PHAS E LOAD CURRENT UNDER NON-IDEAL SUPPLY CONDITION. M. Ashari * S. Islam** S.S.

Economical Solutions to Meet Harmonic Distortion Limits[4]

MAINS SIGNAL PROPAGATION THROUGH DISTRIBUTION SYSTEMS. J. Stones*, S. Perera*, V. Gosbell* and N. Browne**

Aggregated Rooftop PV Sizing in Distribution Feeder Considering Harmonic Distortion Limit

NJWA - Harmonics and Drives Proper System Design

III CHAPTER. Analysis Methodology. regarding data sampling, benchmarking indices and overall program layouts.

Network Monitoring and Visibility Summary

Power Quality Issues in Traction Power Systems

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

HARMONIC MITIGATIONCASE STUDY

MODELING THE EFFECTIVENESS OF POWER ELECTRONICS BASED VOLTAGE REGULATORS ON DISTRIBUTION VOLTAGE DISTURBANCES

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP

Heat pump Performance: Voltage dip/sag, Under voltage and Over voltage

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

PULSE MULTIPLICATION IN FORCED- COMMUTATED CURRENT SOURCE CONVERTERS BY DC RIPPLE REINJECTION

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Emicon Engineering Consultants L.L.C.

Induction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Assessing network compliance for power quality performance

Power Quality Summary

Harmonics and Flicker Levels at a Sub- Transmission Substation: A Measurement Experience

Understanding Input Harmonics and Techniques to Mitigate Them

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

New 24-Pulse Diode Rectifier Systems for Utility Interface of High-Power AC Motor Drives

Fundamentals of Power Quality

Some European experiences with renewable installations

Alternators Reactance for Nonlinear Loads

Southern Company Power Quality Policy

Reducing Total Harmonic Distortion with Variable Frequency Drives

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

ZENER ELECTRIC PTY LTD

IMPLEMENTATION OF PERFORMANCE ANALYSIS OF 18-PULSE AC-DC CONVERTER FED SWITCHED RELUCTANCE MOTOR DRIVES TO ROBOTICS

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, VARIATION OF HARMONICS AND RIPPLE WITH PULSE NUMBER Pulse Number

Handling System Harmonic Propagation in a Diesel-Electric Ship with an Active Filter

Power Quality Overview

MV network design & devices selection EXERCISE BOOK

ENERGISING INRUSH CURRENT TRANSIENTS IN PARALLEL-CONNECTED TRANSFORMERS

The Value of Frequency Keeping and Governor Response to New Zealand

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

ISSN Vol.03,Issue.07, August-2015, Pages:

Characteristics of power quality disturbances in Australia: voltage harmonics

Design and Simulation of Passive Filter

HARMONICS ANALYSIS USING SEQUENTIAL-TIME SIMULATION FOR ADDRESSING SMART GRID CHALLENGES

Generator Advanced Concepts

SIMULATION STUDIES ON AUTOTRANSFORMER RECTIFIER UNIT FOR AIRCRAFT APPLICATIONS

The Confusion Surrounding Stray Voltage

International Journal of Electrical Engineering and Technology (IJEET), ISSN (Print), INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING &

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

International Journal of Advance Engineering and Research Development. 18 Pulse Uncontrolled Rectifier

22.0 Harmonics in Industrial Power Systems

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

Harmonic Survey of an MV Distribution System. V. Gosbell, D. Mannix, D. Robinson & S. Perera University of Wollongong

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

Problems connected with Commissioning of Power Transformers

An Active Interphase Transformer for 12-Pulse Rectifier System to Get the Performance Like 24- Pulse Rectifier System

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

TECHNICAL BULLETIN 004a Ferroresonance

Technical Paper. Harmonic Distortion in Data Centers

CHAPTER-III MODELING AND IMPLEMENTATION OF PMBLDC MOTOR DRIVE

International Journal of Research Available at

Power quality report. A Manufacturing Plant

Power System Neutral/Ground Voltages Causes, Safety Concerns and Mitigation

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

Harmonic Filtering in Variable Speed Drives

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

CHAPTER 3 DEVELOPMENT OF DISTRIBUTION SIMULATION PACKAGE FOR LOAD ANALYSIS OF LV NETWORK

The Advantages and Application of Three Winding Transformers

TAMING THE POWER ABB Review series

Bridgeless Cuk Power Factor Corrector with Regulated Output Voltage

Understanding Power Quality

Solving Customer Power Quality Problems Due to Voltage Magnification

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

M.Tech in Industrial Electronics, SJCE, Mysore, 2 Associate Professor, Dept. of ECE, SJCE, Mysore

INVESTIGATION INTO THE HARMONIC BEHAVIOUR OF MULTIPULSE CONVERTER SYSTEMS IN AN ALUMINIUM SMELTER

Transcription:

Improving Rural Power Quality in New Zealand Neville Watson 1, Stewart Hardie, Tas Scott 3 and Stephen Hirsch 3 1 University of Canterbury, Christchurch, New Zealand EPECentre, Christchurch, New Zealand 3 Orion N.Z. Ltd, Christchurch, New Zealand Presenters: Neville Watson & Stephen Hirsch EEA Conference & Exhibition 010, 17-18 June 010, Christchurch 1

Improving Rural Power Quality in New Zealand Neville Watson 1, Stewart Hardie, Tas Scott 3 and Stephen Hirsch 3 1 University of Canterbury, Christchurch, New Zealand EPECentre, Christchurch, New Zealand 3 Orion N.Z. Ltd, Christchurch, New Zealand Abstract Power Quality (or more accurately Voltage Quality) has become a significant issue in New Zealand with the changing nature of the loads. In the rural sector high prices for dairy products has resulted in many farms converting to dairy farming. Often these farms are situated in dry areas where intensive irrigation is required to maintain adequate grass growth for the herds. These irrigators use submersible pumps that are often fed from variable speed drives (VSD). This has caused harmonic problems in the rural network, particularly in control and protection equipment. Field measurements have been made to understand and quantify the problem and these have shown harmonic levels above N.Z. regulatory limits. To retrofit harmonic filters to the existing VSDs was impractical due to the lack of space in pumping sheds and the inability to retrospectively require farmers to install them. Hence an alternative method of harmonic cancellation was investigated. In order to achieve harmonic cancellation, strategic Dyn11 transformers were replaced with Dzn0 transformers. This investigation involved computer simulations followed by testing on a trial installation before more widespread deployment was adopted. This paper overviews the development of this technique for controlling rural harmonic levels and shows the results from implementing this on the Orion N.Z. network. 1. Introduction Large variable speed drives (VSDs) are increasingly being used to drive irrigation pumps in the rural areas and the effect of these is clearly seen in the harmonic levels on rural electrical networks. It is better to fix the harmonic problem at the source and the VSD drive manufacturers have standard harmonic filters as optional extras, as well as some offering low-distortion drives as another option. Therefore it is desirable to consider harmonic distortion levels when planning a new installation and these options can be implemented. To retrofit harmonic filters to the existing VSDs was impractical due to the lack of space in pumping sheds and the inability to retrospectively require farmers to install them. An earlier study looked at providing harmonic filters at the district substation [1]. This has the advantage of adequate space and one filter to cover many VSD drives, however the simulations showed it was a poor solution due to the size of the filter required for adequate reduction in harmonic levels. The study also indicated a substantial improvement could be achieved by phase shifting the harmonics in order to obtain harmonic current cancellation.. Harmonic Assessment.1 VSD Harmonic Current Injection To verify the harmonic currents injected by an irrigation pump driven by a VSD, measurements were made on one such pump on 18 May 008. The waveform and harmonic currents measured using a Fluke41 when the 160 kw drive was at approximately 65% of full power are displayed in Fig. 1. This clearly shows a large 5 th harmonic component. The manufacturer of this drive also provides Harmonic Calculation Toolbox (MCT31) which is based on the solution of the basic six-pulse

converter shown in Fig. [,3]. Application of this toolbox gives the predicted harmonic current levels which are shown in Table 1. The measured harmonic current levels (Table ) agree very well with the predicted levels. The small discrepancies can be attributed to the pre-existing harmonic distortion levels and imbalance in the phases. 300 00 Current (Amperes) 100 0-100 -00-300 0 0.00 0.004 0.006 0.008 0.01 0.01 0.014 0.016 0.018 0.0 Time (S) 100 Current drawn by VSD (Farm 1) Current (%Fundamental) 80 60 40 33.0 0 8.5 8.0 3.7 3.9.3.4 1.3 0 0 5 10 15 0 5 30 Harmonic Order Figure 1. Current waveform drawn and harmonics injected a VSD. Table 1. Predicted Harmonic Currents Units 1 5 7 11 13 17 19 3 5 9 31 [%] 100 30 9.8 7.0 4.0 3.0.3 1.5 1.3 0.8 0.7 [A] 164 50 16. 11.5 6.6 5.0 3.7.4.1 1.3 1. Table. Measured Harmonic Currents (Phase a) Units 1 5 7 11 13 17 19 3 5 9 31 [%] 94. 31.1 8 7.5 3.5 3.7.. 1.3 1.3 0.8 [A] 163 53.9 13.9 13.1 6.1 6.4 3.8 3.9.. 1.3 Figure. Basic Circuit Layout. 3

. Diversity in Harmonic Currents The next question is how much diversity is there in the harmonic currents injected by the various irrigation pumps. This was tested on 0 November 008 when simultaneous measurements were made on four different VSDs fed from the same substation (Bankside). Fig. 3 (a) shows a polar plot of the 5 th harmonic currents. The phase angles are relative to the terminal voltage waveform (no GPS synchronisation) and no adjustment has been made to the slight difference in voltage phase angle at the different farms. Even so this plot clearly shows a lack of diversity, which is exemplified when the phase a 5 th harmonic currents are added vectorially, as shown in Fig. 3(b). By introducing more diversity into the harmonic currents, harmonic cancellation can be achieved much in the same way two 6-pulse bridges can be connected to form a 1-pulse converter in HVDC applications. This is achieved by utilizing the phase-shift across transformers with different winding configurations. In HVDC Δ/Y and Δ/ Δ are often used [4,5,6]. At present the 11kV to 415V transformers at the farms are Dyn11 transformers. The obvious choices are Dd0 or Yyn0 transformers which have no phase shift between MV to LV, and hence are 30 degree phase shifted with respect to the Dyn11 transformer supply. These however do not satisfy the requirements of having a delta on the MV side to trap triplen harmonics or providing a neutral point on the LV side. The solution is to use the slightly more complicated Dzn0 transformer. Figure 4 displays the current waveforms at the 11 kv and 415V from an electromagnetic transient simulation (PSCAD/EMTDC) of a VSD with different transformer connections. 70 Amperes 306-SE6-54 60 Amperes 50 Amperes 40 Amperes 306-SE6-34 306-SE10-8 0 Amperes 306-SE9-74 (a) Polar plot of 5th Harmonic current Figure 3. 5 th Harmonic Current Phasors. (b) Summation of 5th harmonic current in phase a.3 Testing the Concept of Dzn0 Transformer at Bankside Before a more widespread use of Dzn0 transformer was adopted it was considered prudent to install one and to verify that harmonic cancellation would occur as expected. This test was performed on July 009. The transformer at Farm 1 was changed to a Dzn0 transformer while Farm s installation was not changed. Farm is on the same feeder as Farm 1 and is reasonably close. A PQ meter was installed at Bankside substation to measure the harmonic currents and voltage on the 11 kv feeder feeding these two farms. Measurements were also taken at each farm. The procedure was to start Farm s VSD and then after a delay start Farm 1 s VSD. Then 4

Farm s VSD was stopped and finally Farm 1 s VSD. This gave a period where each was running on its own and a period when both operated. Figure 5 shows a sample of the results obtained. When Farm s VSD turns ON there is a large increase in the 5 th harmonic current flowing in the 11 kv line. The 5 th harmonic voltage actually drops from approximately 1% to 0.6% as the VSD injection counters the background 5 th harmonic voltage. When Farm 1 s VSD starts the 5 th harmonic current flowing in the 11 kv line drops and the 5 th harmonic voltage rises to its background level. When Farm s VSD stops, while leaving Farm 1 s VSD running, the 5 th harmonic voltage jumps to approximately 1.7% and the 5 th harmonic current increases dramatically. This increase of 5 th harmonic voltage is because the 5 th harmonic current injection of this VSD is such as to reinforce the background harmonic voltage level. This test clearly demonstrated that the 5 th harmonic is cancelled by having two VSDs supplied from transformers with different phase shifts. Main : Graphs 0.0060 I_11kV (Dzn0) I_11kV (Dyn11) I_11kV (Yyn0) 0.0040 0.000 Current (ka) 0.0000-0.000-0.0040-0.0060 0.150 I_415 (Dzn0) I_415 (Dyn11) I_415 (Yyn0) 0.100 0.050 Current (ka) 0.000-0.050-0.100-0.150 Time... 0.4600 0.4650 0.4700 0.4750 0.4800 0.4850 0.4900 0.4950 0.5000 Figure 4. Time waveforms from PSCAD/EMTDC simulation..4 Rollout of Dzn0 Transformers at Darfield High levels of 5 th harmonic distortion on the 11 kv at Darfield substation has caused interference with equipment at Darfield substation. Recordings showed that during the summer of 008/09, the total voltage harmonic distortion (V THD ) appearing on the 11 kv supply from Darfield District Substation sometimes exceeded 8% while the regulatory limit is 5% (ECP36). Figure 6 displays the V THD for the phase-to-phase voltage between phases A & B (Red & Yellow) on the 11 kv busbar at Darfield during January 009. To perform a comparison of harmonic levels between years it is desirable to have a period when the irrigation load has been at its maximum for a consistent length of time. The weather during the summer of 008/09 was cold and damp and often not all the irrigators were running. Although the highest V THD for the 5

summer 008/09 did not occur during January 009, it has been considered the best month to perform a comparison between years, as there were no significant dips in load due to rain. 600 Bankside Substation measurements Power (kw) 500 400 Farm running 300 Farm 1 running 00 11:04:0 11:11:00 11:17:40 11:4:0 11:31:00 11:37:40 11:44:0 11:51:00 11:57:40 1:04:0 1:11:00 Harmonic Voltage (%) Harmonic Current (A) 1.5 1 0.5 0 11:04:0 11:11:00 11:17:40 11:4:0 11:31:00 11:37:40 11:44:0 11:51:00 11:57:40 1:04:0 1:11:00 3 1 Phase A Phase B Phase C solid 5 th harmonic dotted 7 th harmonic 0 11:04:0 11:11:00 11:17:40 11:4:0 11:31:00 11:37:40 11:44:0 11:51:00 11:57:40 1:04:0 1:11:00 Time Figure 5. Recordings on a 11 kv feeder at Bankside substation. Figure 6. Voltage THD at Darfield 11 kv Busbar for January 009. The maximum value was 7.8% and the average 5.8% with a standard deviation of 0.77%. Figure 7 shows the same information in a different way. This shows as a histogram the proportion of time the V THD is within the specified bin (V THD level) and a Cumulative Probability (CP) distribution function which shows the percentage time 6

the V THD is below a given level. It shows that the V THD is below 5% only 18% of the time. Over the 009 winter there was an approximately 50% increase in the unfiltered VSD drive load connected to the Darfield network. This would have exasperated the harmonic distortion problems if some form of mitigation was not installed. Also during the winter of 009, 5 existing standard Dyn11 11kV/415 Volt distribution transformers supplying VSD pumps in the Darfield 11 kv network were changed to Dzn0 units. This represents approximately half the VSD load connected to the Darfield substation. The Dyn11 transformers were returned to stock and have been/will be installed elsewhere in the network. Figure 7. Voltage THD for January 009 at Darfield substation. Figure 8. Voltage THD at Darfield 11 kv Busbar for December 009/January 010. The V THD was recorded from 0 December 009 to 9 January 010 and is displayed in Fig. 8. The maximum value was 5.6% and the average level 3.9% (standard deviation of 0.5%). The histogram and cumulative probability are shown in 7

Fig. 9. Note that 98% of the time the V THD is below 5%. This is a dramatic reduction V THD and this is in spite of a 50% increase in VSD load. Figure 9. Voltage THD at Darfield 11 kv Busbar for December 009/January 010. 3. Conclusions The field experience of using Dzn0 transformers to create a phase-shift in harmonic current components and thereby cancel some of the harmonic orders has been very successful. This technique ideally cancels the following harmonic orders: 5,7, 17,19, 9,31 etc. For complete cancellation the VSD load connected by the Dyn11 and Dzn0 transformers need to be matched, however, even when not matched only the residual harmonic currents will flow in the 11 kv feeder. Having only some VSDs running is not a big issue because there is a strong correlation between the use of the VSDs in the rural sector. If the season is dry normally all the dairy farmers will be irrigating and if wet all irrigators will generally be turned OFF. 4. Acknowledgements The authors gratefully acknowledge the indispensible help provided by Bill Wilson (Orion N.Z. Ltd) in conducting the field measurements. References [1] Stewart Hardie, Neville Watson and Vic Gosbell, An investigation of excessive rural network harmonic levels caused by particular irrigation pumps, EEA Conference & Exhibition, 19-0 June 009, Christchurch [] L. Asiminoaei, F. Blaabjerg and S. Hansen, Harmonic calculation toolbox in industry application for adjustable speed drive, Applied Power Electronics Conference and Exposition, APEC '04, 004, Page(s): 168 1634, Vol.3 [3] L. Asiminoaei, S. Hansen and F. Blaabjerg, Development of calculation toolbox for harmonic estimation on multi-pulse drives, Industry Applications Conference, 39th IAS Annual Meeting, 004, Page(s): 878 885, Vol. [4] Derek A. Paice, Power Electronic Converter Harmonics: Multipulse Methods for Clean Power, IEEE Press, Piscataway (USA),1994 [5] Derek A. Paice, Clean Power Electronic Converters, Paice & Associates Inc., Florida (USA), 004 [6] Bin Wu, High-Power Converters and AC Drives, John Wiley & Sons, 006 8