Simulation of Synchronous Machine in Stability Study for Power System: Garri Station as a Case Study

Similar documents
Performance Analysis of Fuzzy Logic And PID Controller for PM DC Motor Drive Khalid Al-Mutib 1, N. M. Adamali Shah 2, Ebrahim Mattar 3

Modeling & Simulation of PMSM Drives with Fuzzy Logic Controller

Comparison of Adaptive Neuro-Fuzzy based PSS and SSSC Controllers for Enhancing Power System Oscillation Damping

1. Governor with dynamics: Gg(s)= 1 2. Turbine with dynamics: Gt(s) = 1 3. Load and machine with dynamics: Gp(s) = 1

Automatic Voltage Control For Power System Stability Using Pid And Fuzzy Logic Controller

Development of a Fuzzy Logic Controller for Industrial Conveyor Systems

DC Motor Speed Control: A Case between PID Controller and Fuzzy Logic Controller

Automatic Generation Control of Two Area using Fuzzy Logic Controller

Tuning Of Conventional Pid And Fuzzy Logic Controller Using Different Defuzzification Techniques

CHAPTER 4 FUZZY LOGIC CONTROLLER

Fuzzy Controllers for Boost DC-DC Converters

SPEED CONTROL OF BRUSHLESS DC MOTOR USING FUZZY BASED CONTROLLERS

Improvement in Dynamic Response of Interconnected Hydrothermal System Using Fuzzy Controller

Design of an Intelligent Pressure Control System Based on the Fuzzy Self-tuning PID Controller

ISSN: [IDSTM-18] Impact Factor: 5.164

TWO AREA CONTROL OF AGC USING PI & PID CONTROL BY FUZZY LOGIC

DESIGNING POWER SYSTEM STABILIZER FOR MULTIMACHINE POWER SYSTEM USING NEURO-FUZZY ALGORITHM

Simulation of Optimal Speed Control for a DC Motor Using Conventional PID Controller and Fuzzy Logic Controller

Intelligent Fuzzy-PID Hybrid Control for Temperature of NH3 in Atomization Furnace

CHAPTER 4 AN EFFICIENT ANFIS BASED SELF TUNING OF PI CONTROLLER FOR CURRENT HARMONIC MITIGATION

High Frequency Soft Switching Boost Converter with Fuzzy Logic Controller

Investigations of Fuzzy Logic Controller for Sensorless Switched Reluctance Motor Drive

The Effect of Fuzzy Logic Controller on Power System Stability; a Comparison between Fuzzy Logic Gain Scheduling PID and Conventional PID Controller

High Efficiency DC/DC Buck-Boost Converters for High Power DC System Using Adaptive Control

CHAPTER 1 INTRODUCTION

Comparative Study of PID and Fuzzy Controllers for Speed Control of DC Motor

Comparison of Fuzzy Logic Based and Conventional Power System Stabilizer for Damping of Power System Oscillations

Study on Synchronous Generator Excitation Control Based on FLC

ARTIFICIAL INTELLIGENCE IN POWER SYSTEMS

Comparative Analysis of Room Temperature Controller Using Fuzzy Logic & PID

A Novel Fuzzy Variable-Band Hysteresis Current Controller For Shunt Active Power Filters

Development of a Fuzzy Logic based Photovoltaic Maximum Power Point Tracking Control System using Boost Converter

Single Phase Shunt Active Filter Simulation Based On P-Q Technique Using PID and Fuzzy Logic Controllers for THD Reduction

FUZZY AND NEURO-FUZZY MODELLING AND CONTROL OF NONLINEAR SYSTEMS

CHAPTER 4 LOAD FREQUENCY CONTROL OF INTERCONNECTED HYDRO-THERMAL SYSTEM

Digital Control of MS-150 Modular Position Servo System

Fundamentals of Industrial Control

TRANSIENT STABILITY ENHANCEMENT OF POWER SYSTEM USING INTELLIGENT TECHNIQUE

STABILITY IMPROVEMENT OF POWER SYSTEM BY USING PSS WITH PID AVR CONTROLLER IN THE HIGH DAM POWER STATION ASWAN EGYPT

Fuzzy Logic Based Speed Control System Comparative Study

Application of Soft Computing Techniques in Water Resources Engineering

A Fuzzy Knowledge-Based Controller to Tune PID Parameters

A new fuzzy self-tuning PD load frequency controller for micro-hydropower system

Fuzzy Based Control Using Lab view For Temperature Process

6545(Print), ISSN (Online) Volume 4, Issue 1, January- February (2013), IAEME & TECHNOLOGY (IJEET)

Fuzzy Control Scheme for Damping of Oscillations in Multi Machine. Power System with UPFC

Governor with dynamics: Gg(s)= 1 Turbine with dynamics: Gt(s) = 1 Load and machine with dynamics: Gp(s) = 1

Fuzzy Logic Based Handoff Controller for Microcellular Mobile Networks

Load Frequency and Voltage Control of Two Area Interconnected Power System using PID Controller. Kavita Goswami 1 and Lata Mishra 2

Design Of PID Controller In Automatic Voltage Regulator (AVR) System Using PSO Technique

EXPERIMENTAL INVESTIGATION OF THE ROLE OF STABILIZERS IN THE ENHANCEMENT OF AUTOMATIC VOLTAGE REGULATORS PERFORMANCE

Modeling and simulation of feed system design of CNC machine tool based on. Matlab/simulink

INTEGRATED PID BASED INTELLIGENT CONTROL FOR THREE TANK SYSTEM

A GENERALIZED DIRECT APPROACH FOR DESIGNING FUZZY LOGIC CONTROLLERS IN MATLAB/SIMULINK GUI ENVIRONMENT

COMPUTATONAL INTELLIGENCE

Energy-Based Damping Evaluation for Exciter Control in Power Systems

International Journal of Advance Engineering and Research Development. Aircraft Pitch Control System Using LQR and Fuzzy Logic Controller

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Fuzzy auto-tuning for a PID controller

Speed Control of Brushless DC Motor Using Fuzzy Based Controllers

Abstract: PWM Inverters need an internal current feedback loop to maintain desired

Performance Analysis of Boost Converter Using Fuzzy Logic and PID Controller

CHAPTER 4 FUZZY BASED DYNAMIC PWM CONTROL

Fuzzy Logic Controller on DC/DC Boost Converter

ADVANCES in NATURAL and APPLIED SCIENCES

ISSN: [Appana* et al., 5(10): October, 2016] Impact Factor: 4.116

A CONTROL STRATEGY TO STABILIZE PWM DC-DC BUCK CONVERTER WITH INPUT FILTER USING FUZZY-PI AND ITS COMPARISON USING PI AND FUZZY CONTROLLERS

USED OF FUZZY TOOL OR PID FOR SPEED CONTROL OF SEPRATELY EXCITED DC MOTOR

DC motor position control using fuzzy proportional-derivative controllers with different defuzzification methods

Design and Development of an Optimized Fuzzy Proportional-Integral-Derivative Controller using Genetic Algorithm

DSPACE BASED FUZZY LOGIC CONTROLLED BOOST CONVERTER

CHAPTER 6. CALCULATION OF TUNING PARAMETERS FOR VIBRATION CONTROL USING LabVIEW

PID Controller Optimization By Soft Computing Techniques-A Review

Speed control of a DC motor using Controllers

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

OPTIMAL DESIGN OF POWER SYSTEM STABILIZERS CONTROL FOR MONOMACHINE AND MULTIMACHINE USING INTELLIGENT CONTROL TECHNIQUES -FUZZY LOGIC-

Fuzzy cooking control based on sound pressure

CHAPTER 6 ANFIS BASED NEURO-FUZZY CONTROLLER

International Journal of Scientific Research Engineering & Technology (IJSRET), ISSN Volume 3, Issue 7, October 2014

Some Tuning Methods of PID Controller For Different Processes

Performance Improvement Of AGC By ANFIS

Time Response Analysis of a DC Motor Speed Control with PI and Fuzzy Logic Using LAB View Compact RIO

Load Frequency Control of Multi Area Hybrid Power System Using Intelligent Controller Based on Fuzzy Logic

Incipient Fault Detection in Power Transformer Using Fuzzy Technique K. Ramesh 1, M.Sushama 2

International Journal of Advance Engineering and Research Development. Fuzzy Logic Based Automatic Generation Control of Interconnected Power System

A.V.Sudhakara Reddy 1, M. Ramasekhara Reddy 2, Dr. M. Vijaya Kumar 3

Comparative Analysis Between Fuzzy and PID Control for Load Frequency Controlled Power

A DUAL FUZZY LOGIC CONTROL METHOD FOR DIRECT TORQUE CONTROL OF AN INDUCTION MOTOR

ANALYSIS OF V/f CONTROL OF INDUCTION MOTOR USING CONVENTIONAL CONTROLLERS AND FUZZY LOGIC CONTROLLER

A PLC-based Self-tuning PI-Fuzzy Controller for Linear and Non-linear Drives Control

Fuzzy Based Control Using Lab view For Temperature Process

Fuzzy PID Speed Control of Two Phase Ultrasonic Motor

LOW FREQUENCY OSCILLATION DAMPING BY DISTRIBUTED POWER FLOW CONTROLLER WITH A ROBUST FUZZY SUPPLEMENTARY CONTROLLER

Temperature Control of Water Tank Level System by

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

Smart Home System for Energy Saving using Genetic- Fuzzy-Neural Networks Approach

Automation of Domestic Flour Mill Using Fuzzy Logic Control

Fuzzy Expert Systems Lecture 9 (Fuzzy Systems Applications) (Fuzzy Control)

Performance Analysis of PSO Optimized Fuzzy PI/PID Controller for a Interconnected Power System

Path Following and Obstacle Avoidance Fuzzy Controller for Mobile Indoor Robots

Transcription:

Simulation of Synchronous Machine in Stability Study for Power System: Garri Station as a Case Study Bahar A. Elmahi. Industrial Research & Consultancy Center, baharelmahi@yahoo.com Abstract- This paper aimed to investigate the effectiveness of an adaptive artificial intelligence on enhancing the stability of gas turbine-garri Power Station, which is designed to generate about 38MW. Fuzzy logic method controller was proposed based on stabilizer to enhance the power system stability. Linguistic rules and fuzzy inference mechanism are utilized to tune the controller parameters in different operating states. The proposed controller was applied to a single machine infinite bus system, represented by Gas Turbine-Garri Power Station (GPS). Simulation studies have been carried out using TILLSHELL software. The simulation results demonstrated that the proposed control scheme performs well and strongly control the power system under different loading conditions, disturbances and system parameter variations. The proposed controller is robust and more suitable for damping of low frequency oscillation and more effective in improving dynamic stability and voltage profile than the conventional systems. Keywords: Gas Turbine, synchronous machine, fuzzy controller. % %!" "# $ *+ ", -. / ". # + 0 1 2 3 )&'( =4%> 56+ "+7 '% 6 +( ""8 % " 9%' %: ;< ") 4. A" % 2' " ' 5+ 5, 5> ='% ;-?,. 2+ @ 6%+ "%+CA% "!# '+ "+!"' A" 2' B: +".) =4 "+ % % +. )5"+ 5"+ 5 5"" 5> 5> 7 D ' > )G.+B7, "+. + 2' 8 "# C" 3+E F+ > ' Introduction Power system oscillations affect system stability and they may lead to failure if the system is not properly controlled. Most of power system stability in electric power systems employs the classical linear control theory approach based on a linear model of a fixed configuration of the power system. Uncertainty in the form of ambiguity makes the real world a complex place. Humans have been able to address this problem of ambiguity with their ability to think and adapt to an ever changing environment. Fuzzy logic, as one of the principal elements of artificial intelligence is playing a key role in dealing with uncertain and imprecise information (1). It was designed mathematically to represent the vagueness and uncertainty of linguistic problems; thereby obtaining formal tools to work with intrinsic imprecision in different type of problems. It is considered as a generalization 21

of the classic set theory. The main motivation behind fuzzy logic was the provision of a framework to represent human knowledge in which imprecision is a common feature. Artificial intelligent system based fuzzy method has an active research topic in automation and control theory. It provides a systematic method to incorporate human experience and implement nonlinear algorithms characterized by a series of linguistic statements into the controller (2, 3). In power system studies, there are three principal control systems that directly affect a synchronous generator: the boiler, governor, and exciter controller. These factors should be addressed before proceeding to design any simulation program for power system.a schematic diagram of the necessary components that affected on the simulation procedure are shown in Figure 1. Most of Power System Stabilizers (PSS) in use in electric power systems employ the classical linear control theory approach based on linear models of fixed configuration of the power system. Such a fixed-parameter controller, called a conventional PSS (CPSS), is widely used in existing power systems and has made a great contribution in enhancing power system dynamics stability (4) which shown in Figure 1. The parameters of CPSS are determined based on a nominal operating point where they can provide good performance. Since power systems are highly non-linear, with configurations and parameters that change with time, the CPSS design based on the linearised model of the power system cannot guarantee its performance in a practical operation environment (5, 6). The common structures of PSS are: Figure 1: Basic controls of a generator a. Lead-lag structure or conventional PSS (CPSS) b. Proportional Integral Derivative (PID) structure. c. Other structure based on optimal, adaptive, variable structure, intelligent...etc. The common input signals used are the speed, frequency, voltage, electric and accelerating power deviations. However, PSS can be either conventional PSS (one-band PSS, Figure 2) which is (analog or digital) or multiband PSS as shown in Figure 3. To improve the performance of CPSS, numerous techniques have been proposed for their design such as using intelligence optimization methods (fuzzy, neural networks, genetic algorithm and other nonlinear techniques). 22

Figure 2: PSS structure Power System Stabilizer Conventional PSS Multi-band PSS Analog Digital Using Linear Method of Design Using Nonlinear Method of Design Figure 3: Multi types of PSS Fuzzy logic Technological innovations in soft computing techniques have brought automation capabilities to new levels of applications. Conventional control theory is based on mathematical models that describe the dynamic behavior of process control systems. Fuzzy logic is a flexible approach to conventional controllers. This logic was developed based on Lofti Zadeh's 1960s fuzzy set theory (5), which was motivated mainly by the conviction that the traditional analysis methods were inadequate to describe phenomena whose constraints were not related by differential equations. This theory provides a way of representing the vague notions through the element and its membership. This method dealing on what the system should do rather than trying to model how it works. So fuzzy logic is the logic on which fuzzy controller is based, dealing with concept of completely truth and they are called the Zadeh operators, usually uses IF/THEN rules (3). The major concept in fuzzy logic is the linguistic variable and membership functions. Where a linguistic variable was introduced to process the natural language.the concept of membership function is to describe these linguistic values in terms of numerals. So controllers based on the fuzzy logic give the linguistic strategies control conversion from expert knowledge in automatic control strategies. So the fuzzy logic controllers are rule-based controllers. The basic configuration of the FLC can be simply represented in four parts, as shown in Figure 4. Fuzzification Fuzzification is a process in which the inputs are classified to corresponding linguistic terms to get degree of fulfillment. It means adding uncertainty by design to crisp sets or to sets that are already fuzzy. A triangular membership function was used which could be compressed or expanded, but not when rule re-insertion was used. 23

Knowledge base The main tasks of designing control knowledge base are: a. Database: The database provides necessary definitions to define linguistic control rules and fuzzy data manipulation in an FLC. b. Linguistic (fuzzy) control rule base The rule base characterizes the control goals and control policy of the domain experts by means of a set of linguistic control rules. Decision-Making Logic (DML) The Decision-Making Logic is the kernel of an FLC It has the capability of simulating human decision-making based on fuzzy concepts, implication and the rules of inference in fuzzy logic. Decision-making logic determines how the fuzzy logic operations are performed and together with the knowledge base determine the outputs of each fuzzy IF- THEN rules. Hence the main part of the fuzzy controller for design is the rule base, in which it represents a human expert "in the - loop". Therefore information's that loaded into the rules in the rule base may come from an actual human expert, who spent a long time learning how to control the process. Defuzzification Last step, as the name suggests, the defuzzifier s task is the reverse operation to the fuzzifier. Which covers the inferred decision forms the linguistic variables back the numerical values, or it convert the FLC inferred control actions from fuzzy values to crisp values. This process depends on the output fuzzy set, which is generated from the fired rules. The performance of the FLC depends very much on the defuzzification process. This is because the overall performance of the system under control is determined by the controlling signal that the system universe. Defuzzifier types are: centroid defuzzifier, center average defuzzifier and min-maximum defuzzifier. Fuzzy-Logic Based Power System Stabilizer A FLC is a kind of a state variable controller governed by a family of rule and a fuzzy inference mechanism. The FLC algorithm can be implementation using heuristic strategies, defined by linguistically describe statements. The fuzzy logic control algorithm reflects the mechanism of control implemented by people, without using a mathematical model the controlled object, and without an analytical description of the control algorithm. Figure 5, shows block diagram of synchronous generator and FLC loops. The fuzzy logic controllers apply to maintain the signals in order to keep them constant according to pre-established values. The fuzzy controller used in power system stabilizer is normally a two-input and a single-output component. It is usually a Multi- Inputs and Single Outputs (MISO) system (9, 10). As shown in Figure 6 it consists of the following units: 1. Synchronous machine (AC-generator) 2. Governor controls the steam/gas power amount admitted to the turbine. 3. The excitation system controls the generated EMF of the generator and therefore controls not only the output voltage but the power factor and current magnitude as well. Fuzzy Logic Controller The fuzzy controller is the heart of the system, it makes logic decisions depending on the input and output behavior of the generating unit (11, 12). The online system consists or needs a transformer to step-down signals and measurement circuits. The generator output passes though measurement circuits into the computer, for controlling, to control circuits. Therefore FLC is software program that interacts with the generator such that the output of the generator is maintained at specific values. 24

Fuzzy Knowledge base Fuzzy Defuzzification Interface Decision making logic Fuzzification Interface Control signal (non-fuzzy) Controlled System (process) Output signal Figure 4: Principle Design Fuzzy logic Figure 5: Block diagram of synchronous generator and FLC loops DC Motor AC Generator Control Circuit Control Circuit Transformer DAC Control program ADC Voltage measurement circuit DAC Fuzzy Knowledge base ADC Frequency measurement circuit Fuzzy Controller Figure 6: Block diagram of FLC connected with system 25

After modifying or maintaining the signal through the computer, control circuit that interfacing the FLC with the machines. Signals convert form digital to analogue (DAC) should be understood by the machine, in order to complete the loop of controlling operation. In the design of fuzzy-logic controllers shown in Figure 6 unlike most conventional methods, a mathematic model is not required to describe the system under study. It is based on the implementation of fuzzy logic technique to power system stabilizer (PSS) to improve system damping. The effectiveness of the fuzzy logic PSS in a single machine infinite bus is demonstrated by the TILL Shell Software. The performance of fuzzy logic PSS is compared with the conventional power system stabilizer (CPSS). The time-domain simulation performed on the test system will be used to study the nonlinear response following the steady state operation and large disturbance [8]. Case study: synchronous generator-garri Power Station: Considering a single machine connected by a transmission line to an infinite bus power system as the Figure 5. The purpose of this work is the development of a fuzzy controller (software) to simulate the automatic voltage and frequency behavior. The proposed approach was single machine infinite bus system designed to generate 38MW. One type of this system is used in gas plant Garri-station.The simulation was performed using TIL Shell software in fuzzy system environment; the data of the system are given in Appendix A. The controller has been incorporated with 25 rules, a triangular membership function was used which could be compressed or expanded and the system simulated with different values of the parameter considered, then compared with the nominal value (real value). The simulation results were obtained as shown in Table 1. Table 1: The outputs for both controllers (CPP&FLC) TIME MW FLC TIME MW FLC TIME MW FLC TIME MW FLC 1:00 24.3 24.84 4:00 24.9 28.00 7:00 23.2 28.00 10:00 35.5 30 1:15 27.7 26 4:15 26.9 28.00 7:15 25.6 28.00 10:15 31.8 30 1:30 29.8 26.53 4:30 28.9 28.00 7:30 28.6 28.00 10:30 28.7 30 1:45 22.0 26.90 4:45 25.9 28.00 7:45 36.4 28.00 10:45 25.3 28 2:00 25.4 28.00 5:00 22.8 28.00 8:00 35.3 30.00 11:00 22 28 2:15 25.3 28.16 5:15 22.8 28.00 8:15 35.3 30.00 11:15 22.1 28 2:30 25.2 28.00 5:30 22.8 28.00 8:30 35.3 30.00 11:30 22.3 28 2:45 25.1 28.00 5:45 22.9 28.00 8:45 35.3 30.00 11:45 22.4 28 3:00 25 28.00 6:00 22.9 28.00 9:00 35.4 30.00 12:00 22.6 28 3:15 24.5 28.00 6:15 22.9 28.00 9:15 35.4 30.00 12:15 22.6 28 3:30 24.9 28.00 6:30 23.8 28.00 9:30 35.4 30.00 12:30 22.6 28 3:45 24.9 28.00 6:45 23.5 28.00 9:45 35.4 30.00 12:45 22.4 28 26

Figure 7: Slip Response of CPSS & FPSS. Time interval is 0:15 (1:00 3:45) Figure 8: Slip Response of CPSS & FPSS. Time interval is 0:15 (4:00 6:45) 27

Figure 9: Slip Response of CPSS & FPSS. Time interval is 0:15 (7:00 9:45) Figure 10: Slip Response of CPSS & FPSS. Time interval is 0:15 (10:00 12:45) 28

Figure 11: TILL Shell software results References 1. Leonid Reznik, (1997) "Fuzzy Controllers" Victoria University of Technology, Melbourne, Australia. 1'st edition. 2. Zadah, L, A.(1991)"Fuzzy Logic and the Calculus of Fuzzy If-Then Rules," Proceedings of SYNAPSE '91,Tokyo, Japan. 3. George J. Klir / Bo Yuan, (1995), "Fuzzy Set and Fuzzy Logic theory and Applications," Prentice Hall PTR-Upper Saddle River, New Jersey. Anderson P.M., and Fouad A.A., Power System Control and Stability, Ames, IA: Iowa State Univ. Press, 1977. 4. H.Cai, Z.Qu, D.Gan, J.F.Dorsey, (1997) A Robust Power System Stabilizer Design Based on Lyapunov's Approach, Proceedings of the American Control Conference Albuquerque, New Mexico. 5. J. He, O.P. Malik, (1997) An Adaptive Power System Stabilizer Based on Recurrent Neural Networks, IEEE Transactions on Energy Conversion, Vol. 12, No. 4. 6. K. E. Bollinger, and S. Z. Ao, (1996) PSS performance as affected by its output limiter, IEEE Trans. Energy Con., vol. 11, no. 1, pp. 118-124. 7. Hrahi Hassel (1998)"A Multiple-Input single-output (MISO) Fuzzy logic model for watershed soil conservation service (SCS) Curve Numbers". 8. Momah A. J., X. W. Ma, and K. Tomsovic,(1995)"Overview and 29

Literatures Survey of Fuzzy Set Theory in Power System, IEEE Transaction on Power Systems, vol. 10, No. 3,, pp. 1676-1690; 9. P. Hoang, K. Tomsovic, 1996 Design and analysis an adaptive fuzzy power system stabilizer. IEEE Transactions on Energy Conversion, Vol. 11, No. 2. 10. El-Hawary Mohamed E, (1988) Electric Power, Applications of fuzzy systems. 11. H. Toliyat (1996), Design of augmented fuzzy logic power system stabilizers to enhance power systems stability, IEEE Trans. Energy Con., vol. 11, no. 1, pp. 97-103. Appendix A Stability of power system over time Time Frequency Voltage MW Time Frequency Voltage MW 1:00 50.02 10.44 24.3 7:00 50.02 10.48 23.2 1:15 50.05 10.45 27.7 7:15 49.99 10.49 25.6 1:30 50.01 10.46 29.8 7:30 49.99 10.48 28.6 1:45 50.02 10.47 22.0 7:45 50.02 10.49 36.4 2:00 50. 03 10.49 25.4 8:00 50.05 10.54 35.3 2:15 50.1 10.47 25.3 8:15 50.06 10.54 35.3 2:30 50.02 10.48 25.2 8:30 50.08 10.52 35.3 2:45 50. 04 10.48 25.1 8:45 50.12 10.48 35.3 3:00 50.02 10.48 25 9:00 50.13 10.48 35.4 3:15 50.05 10.48 24.5 9:15 50.12 10.54 35.4 3:30 50.04 10.48 24.9 9:30 50.06 10.54 35.4 3:45 50.05 10.48 24.9 9:45 50.05 10.54 35.4 4:00 50.03 10.48 24.9 10:00 50.15 10.48 35.5 4:15 49.99 10.48 26.9 10:15 50.05 10.54 31.8 4:30 50.02 10.46 28.9 10:30 50.07 10.47 28.7 4:45 50.01 10.48 25.9 10:45 49.99 10.48 25.3 5:00 50.03 10.48 22.8 11:00 49.99 10.49 22 5:15 50.02 10.48 22.8 11:15 50.9 10.54 22.1 5:30 50.03 10.48 22.8 11:30 49.99 10.50 22.3 5:45 50.00 10.48 22.9 11:45 49.98 10.50 22.4 6:00 50.00 10.48 22.9 12:00 49.98 10.48 22.6 6:15 50.04 10.48 22.9 12:15 50.05 10.46 22.6 6:30 50.01 10.48 23.8 12:30 49.94 10.49 22.6 6:45 49.99 10.48 23.5 12:45 49.94 10.49 22.4 30