MICROFUSION SINGLE PHASE SCR POWER CONTROLLERS

Similar documents
MICROFUSION SINGLE PHASE SCR POWER CONTROLLERS

MICROFUSION FEATURES OPTIONS CERTIFICATIONS THREE PHASE SCR POWER CONTROLLERS

MICROFUSION THREE PHASE SCR POWER CONTROLLERS

MICROFUSION THREE PHASE SCR POWER CONTROLLERS

Process Control HPP-25

Frame through-beam sensors

Process-Controller HPP-25

Through-beam ring sensors

MICROFUSION SCR POWER CONTROLLERS USER S MANUAL MicroFUSION Operator s Manual Rev 2.37

The compact test- disconnect terminal interface system for protection and secondary technology

OPERATING INSTRUCTIONS AND SPECIFICATIONS. NI 9207E 16-Channel, ±20 ma/±10 V, 24-Bit Analog Input Module

30 A AC/DC Current Probe TCP0030A Datasheet

Programmable DC Electronic Loads. Series Programmable DC Electronic Loads. Programmable DC electronic loads DC POWER SUPPLIES

AC/DC Current Probe TCP0150 Datasheet

To be automatically connected to the nearest North American Technical Sales Office:

Programmable Pulse Generators PSPL10050A, PSPL10060A, PSPL10070A Datasheet

Don t Let EMI/EMC Compliance Certification Slow You Down TUTORIAL

OPERATING INSTRUCTIONS AND SPECIFICATIONS. NI 9853E 2-Port, High-Speed CAN Module

PARAMETER LIST MICROFUSION

Automated Frequency Response Measurement with AFG31000, MDO3000 and TekBench Instrument Control Software APPLICATION NOTE

Data Sheet. Agilent M9185A PXI Isolated D/A Converter. DISCOVER the Alternatives... Agilent MODULAR Products. 8/16-Channel 16-bit, ±16 V

FP-DO-400 and cfp-do-400

KickStart Instrument Control Software Datasheet

Keysight Technologies 87405C 100 MHz to 18 GHz Preamplifier. Technical Overview

FP-RLY-420. Features. Installing the FP-RLY-420. FieldPoint Operating Instructions. Eight-Channel SPST Relay Module

OPERATING INSTRUCTIONS AND SPECIFICATIONS. NI 9211E 4-Channel Thermocouple Input Module

1204 Reflected Wave Reduction Device

Agilent 87222C/D/E Coaxial Transfer Switches dc to 26.5, 40, 50 GHz

Keysight Technologies N9398C/F/G and N9399C/F DC Block. Technical Overview

AC/DC Current Measurement Systems TCPA300, TCP312A, TCP305A, TCP303, TCPA400, TCP404XL Datasheet

Keysight Technologies N9398C/F/G and N9399C/F DC Block. Technical Overview

Verifying Power Supply Sequencing with an 8-Channel Oscilloscope APPLICATION NOTE

AC/DC Current Measurement Systems TCPA300, TCP312A, TCP305A, TCP303, TCPA400, TCP404XL Datasheet

AC/DC Current Measurement Systems

AC/DC Current Measurement Systems

Who Reads and Who Follows? What analytics tell us about the audience of academic blogging Chris Prosser Politics in

Using the Model 4225-RPM Remote Amplifier/ Switch to Automate Switching Between DC I-V, C-V, and Pulsed I-V Measurements APPLICATION NOTE

Keysight Technologies 87405C 100 MHz to 18 GHz Preamplifier. Technical Overview

SCXI High-Voltage Terminal Block

Simplifying FET Testing with 2600B System SourceMeter SMU Instruments APPLICATION NOTE

BenchTop Extraction Arms with unbeatable flexibility

BenchTop Extraction Arms with unbeatable flexibility

Simplifying DC-DC Converter Characterization using a 2600B System SourceMeter SMU Instrument and MSO/DPO5000 or DPO7000 Series Scope APPLICATION NOTE

12.5 Gb/s Driver Amplifier LABware Module PSPL8001 Datasheet

Keysight E5063A ENA Series Network Analyzer

Cisco ONS Metropolitan Dense Wavelength Division Multiplexing 100-GHz FlexLayer Filter Solution

SCXI High-Voltage Terminal Block

S540 Power Semiconductor Test System Datasheet

2018/2019 HCT Transition Period OFFICIAL COMPETITION RULES

Debugging SENT Automotive Buses with an Oscilloscope APPLICATION NOTE

Agilent 4294A Precision Impedance Analyzer, 40 Hz to 110 MHz. Configuration Guide

stripax The professional stripping tool

CISCO ONS /100-GHZ INTERLEAVER/DE-INTERLEAVER FOR THE CISCO ONS MULTISERVICE TRANSPORT PLATFORM

MBR10xCT Series TO-220AB

SX (400 V) System configuration

FP-RTD-124 AND CFP-RTD-124. Features. FieldPoint Operating Instructions. Eight-Channel Four-Wire RTD and Resistance Input Modules

SX (690 V) System configuration

Keysight Technologies USB Preamplifiers

1.5 GHz Active Probe TAP1500 Datasheet

Isolation Addresses Common Sources of Differential Measurement Error

WOODWORKING TECHNOLOGY IN EUROPE: HIGHLIGHTS European Federation of Woodworking Technology Manufacturers

Inclinometer Selection Guide

Agilent U1700 Series Handheld LCR Meters

NI 6624 Calibration Procedure

GENERAL PURPOSE POWER SUPPLIES, SPECIAL PURPOSE POWER SUPPLIES, AND ELECTRONIC LOADS SELECTOR GUIDE

MV1000 MEDIUM VOLTAGE AC DRIVE 175 HP TO 16,000 HP

Welcome to the IFR Press Conference 30 August 2012, Taipei

Keysight Technologies P9400A/C Solid State PIN Diode Transfer Switches

NI Channel, Universal Digital Input Module

NI Channel SPST Electromechanical Relay Module

FP-DO-401 and cfp-do-401

Keysight Technologies

Process Control Calibration Made Easy with Agilent U1401A

BNC-2121 Connector Accessory for 660X Devices

S540 Power Semiconductor Test System Datasheet

The Keysight Technologies, Inc. U1730C Series handheld LCR meters allow you to measure at frequencies as high as 100 khz a capability typically found

AC Current Probes CT1 CT2 CT6 Data Sheet

Keysight Technologies Resistance Measurements Using the B2900A Series of SMUs

NI sbrio-9632/9642 Verification Procedure

QuickSpecs. VIVE Pro VR System with Advantage+ Service Pack. Overview

20X Low Capacitance Probe P6158 Datasheet

FP-DO-403 and cfp-do-403

Regulatory status for using RFID in the UHF spectrum 3 May 2006

50MHz arbitrary waveform/function generator

OPERATING INSTRUCTIONS NI Port DeviceNet Module

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters.

10 GHz Linear Amplifier PSPL5866 Datasheet

Agilent N8973A, N8974A, N8975A NFA Series Noise Figure Analyzers. Data Sheet

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

Tire Pressure Monitoring Systems and Remote/Passive Keyless Entry

DATAMAN 470 SERIES BARCODE READERS. Premium fixed-mount barcode readers for the most challenging applications

Table of Contents Executive Summary 29

Performing Safe Operating Area Analysis on MOSFETs and Other Switching Devices with an Oscilloscope APPLICATION NOTE

Keysight Technologies U1730C Series Handheld LCR Meters Take your expectations higher with the latest LCR meters. Data Sheet

NGR. Guided Wave Radar Level Transmitter

General Purpose Drives

Keysight Technologies

Switching Between C-V and I-V Measurements Using the 4200A-CVIV Multi-Switch and 4200A-SCS Parameter Analyzer APPLICATION NOTE

FP-SG-140 AND CFP-SG-140

Keysight Technologies Migrating Balanced Measurements from the

Transcription:

CONTROL CONCEPTS MICROFUSION SINGLE PHASE SCR POWER CONTROLLERS FEATURES Auto-Ranging Input Voltage UL: 24-600 Vac, 45-65 Hz CE: 24-690 Vac, 45-65 Hz AC Output 8, 16, 32, 50, 80, 100, 130, 160, 200, 240, 320, 400 A (@ 6000 ft [1829 m], 122 F [50 C]) Control Features Microprocessor-based controller, phase lock loop timing Firing modes: Zero Cross, Phase Angle, Zero Cross Transformer (ZCT) Mode, HiPER Mode, and Fast Zero Cross Mode Feedback: Voltage, Current, True Power, External Adjustable Soft Start: Phase Angle Output Limits: Voltage, Current, Power Missing Cycle Detection SYNC-GUARD : Power-level multiple Zero-Cross controllers TRANS-GUARD : Prevent upstream transformer heating Dedicated Input Bit for Run/Stop kwh Meter Heater Bakeout Resistance Measurement Analog Interface (Up to Two Analog Inputs) Standard setpoint ranges: 0-5 Vdc, 4-20 ma Field Scalable: 0-10 Vdc, 0-20 ma, or Potentiometer Available Fieldbus Interfaces EtherNet/IP EtherCAT PROFINET Modbus TCP (Ethernet) Easy Setup via Plug-n-Play USB Load / Save Controller Configurations Chart Diagnostics and Log Operations Two Year Warranty OPTIONAL FEATURES General Purpose Input Second Analog Input Channel Additional Setpoint, Potentiometer Input, External Feedback, or Pulse Width Modulation (PWM) Alarm Relay Form C Relay Output 2 x 16 Bit Analog Retransmits Standard Setpoint Ranges: 0-5 Vdc, 4-20 ma Field Scalable: 0-10 Vdc, 0-20 ma, or Potentiometer Limit Control Current, Power, and Voltage Remote Display Handheld 2 line, 16 character text display 1/4 Din Mount MADE IN THE USA High Performance True RMS Power, Load Voltage Feedback, Load Current Feedback, High Resolution Control Loop Isolated I/O 500 Vac isolation from 24 Vdc control power to Analog Inputs, General Purpose Input, Run/Stop, and Retransmits External, Touchsafe Class T Fusing 1 Control Concepts, Inc., 2018 www.ccipower.com 1-800-765-2799 MicroFUSION 1ø Brochure Rev. 5.06

DESCRIPTION MicroFUSION is an ultra-compact high-performance microprocessor-based power controller to assist with control of AC loads. Resistive or transformer-connected loads can be controlled in either Phase Angle, Zero Cross, Zero Cross Transformer (ZCT), Fast Zero Cross (FZC), or HiPER Mode. Output is controlled linearly with respect to command signal and can be set to the average or RMS value of the voltage and current, as well as true instantaneous power or external feedback. MicroFUSION Series power controllers are available in current ratings from 8-400 A AC. Auto-ranging voltage circuitry enables main supply voltage from 24-600 Vac for UL/cUL or 24-690 Vac for CE, (45-65 Hz) eliminating the need for hardware jumpers or stocking multiple controllers for international voltages. A separate 24 Vdc power source supplies the control electronics and maintains critical communications to your control system when the mains are absent. Status LEDs and a LED bar graph make operation and troubleshooting simple. A plug-n-play USB interface and free Control Panel software for your PC further simplifies installing and configuring the controller to its designated application. For multiple controllers, controller settings can be duplicated by simply loading a configuration file saved from a previous unit. Setpoints can be controlled through the standard analog or optional digital fieldbus interface. The factory-configured analog setpoint signal ranges are 0-5 Vdc and 4-20 ma, both of which are field scalable from 0-10 Vdc or 0-20 ma. The Connect Gateway Module is a fieldbus interface option that includes EtherNet/IP, EtherCAT, PROFINET, PROFIBUS, or Modbus TCP. These can be used to communicate with a PLC or factory control system. PROFINET, Modbus TCP, and EtherNet/IP are also available as internal fieldbus options. A single external Connect Module can also control up to ten zones, which assists in reducing system installation costs. The robust design of MicroFUSION allows for continuous full-frame current operation, without derating, up to 122 F [50 C], 6000 ft [1829 m] altitude. Cooling is accomplished through natural convection, forced air, or optional external panel mount. The optional IP65 Remote Display provides a clear readout of key parameters and alarm status. Setpoints, limits and alarms are touchpad accessible and easily customized. For additional convenience, a panel mounting kit is available, eliminating the need for external meters, indicators, switches and the associated costs of wiring and labor. MicroFUSION 1ø Brochure Rev. 5.06 www.ccipower.com 1-800-765-2799 Control Concepts, Inc. 2018 2

DIMENSIONS Dimensions in Inches [mm]. MicroFUSION can be DIN rail mounted (up to 80 A) or panel mounted. 100-160 A 8-32 A 5.10 [129.54] 6.28 [159.51] 2.00 [50.80] 2.43 [61.72] 6.00 [152.40] 8.87 [225.30] 0.80 [20.32] Weight: 1.8 lb [0.816 kg] 50 A (without fan) to 80 A (with fan) Weight: 4.0 lb [1.81 kg] 200-400 A 5.10 [129.54] 8.80 [223.52] 3.25 [82.55] 4.48 [113.79] 6.00 [152.40] 11.43 [290.32] 0.80 [20.32] Weight: 3.0 lb [1.36 kg] Weight: 7.5 lb [3.40 kg] 3 Control Concepts, Inc., 2018 www.ccipower.com 1-800-765-2799 MicroFUSION 1ø Brochure Rev. 5.06

P1/P2 CONNECTOR P1 Command Connector P2 Command Connector + * Retransmit 1 - Output * Retransmit 2 + Output - No Connection NO * Relay (250 Vac Form C) C NC SINGLE PHASE LINE/LOAD CONNECTIONS SINGLE PHASE 8-80 AMP PE GND B1 A1 FUSES L O A D REF* A1 B1 A2 P2 P1 See manual for recommended wire sizes. *Note: 0.60 ma maximum through B1 connection at 600 Vac MicroFUSION 1ø Brochure Rev. 5.06 www.ccipower.com 1-800-765-2799 Control Concepts, Inc. 2018 4

SINGLE PHASE 100-160 AMP SINGLE PHASE 200-400 AMP P1 P1 P2 P2 See manual for recommended wire sizes. *Note: 0.60 ma maximum through B1 connection at 600 Vac 5 Control Concepts, Inc., 2018 www.ccipower.com 1-800-765-2799 MicroFUSION 1ø Brochure Rev. 5.06

FEATURE COMPARISON MicroFUSION is available with one of four performance options: SX-S (Standard board), SX-L (Standard board with Current features), HX-L (High Performance board with Current and Voltage features) and HX-P (Fully populated High Performance board) = Included = Field Upgradable Option = Option Available at Manufacturing Time - = Not available FEATURE LIST SX-S SX-L HX-L HX-P Auto-Ranging Input: 24-600 Vac for UL/cUL, 690 Vac for CE Phase Angle and Zero Cross Firing Modes Adjustable Phase Angle Soft-Start Heater Bake Out Touchsafe Design UL Listed, CE, 100kA SCCR, and RoHS certifications Micro USB Connection (USB Plug-N-Play) Free Control Panel Software DIN Rail Mountable (Up to 80A) Panel Mount Run/Stop Overcurrent Trip Analog Input (0-10 Vdc, 0/4-20 ma or potentiometer) CCI Link Connectivity TRANS-GUARD - Prevents upstream transformer heating LED Bar Graph Fixed Current Limit - 105% of Frame - - - Adjustable Current Limit Alarm Relay Current Control Load Voltage Control - - Voltage Limit - - Monitor Load Current - Provides load current data via software, display, or fieldbus Isolated I/O 2 Analog Input Channel (0-10 Vdc, 0/4-20 ma or potentiometer) General Purpose Input Pulse Width Modulation Input (PWM) Accessory Option: Remote Display SYNC-GUARD Connectivity - Power level multiple Zero-Cross controllers External Fieldbus Options: Modbus TCP, EtherNet/IP, PROFINET, PROFIBUS, or EtherCAT Internal Fieldbus Options: PROFINET, Modbus TCP, and EtherNet/IP External Panel Mount Heatsink (Up to 50 A) FEATURE COMPARISON LIST, continues on next page MicroFUSION 1ø Brochure Rev. 5.06 www.ccipower.com 1-800-765-2799 Control Concepts, Inc. 2018 6

FEATURE COMPARISON, CONTINUED FEATURE LIST, CONTINUED SX-S SX-L HX-L HX-P Water Cooled Heatsink (Contact factory) Zero Cross Transformer Firing Mode - - Retransmit (RTX): 2x High Resolution Analog Outputs 0-10 Vdc or 0/4-20 ma - - Power Limit - - True Power Control - - Monitor True RMS Power - Provides true power data via software, display, or fieldbus - - High Resolution Control Loop - - Kwh Meter - - HiPer Mode - High performance low conduction angle firing mode - - Resistance Measurement - - SPECIFICATIONS POWER Line Voltage (Auto Ranging) Line Frequency (Auto Ranging) UL/cUL: 24-600 Vac (Nominal) (+10% / -15%) (Contact CCI for other options) CE: 24-690 Vac (Nominal) (+10% / -15%) (Contact CCI for other options) 45-65 Hz Frame Current Ratings (Amps) Continuous RMS (AC) 8 16 32 50 80 100 130 160 200 240 320 400 Current Rating - Peak Surge 20x frame rating for 10 ms Minimum Hold/Latch Current 500 ma up to 160 A 1 A at 200-400 A Max Leakage Current SCR Rating (PIV) Fusing Thermal Current Limit Current Trip Power Dissipation Control Power / Operates Internal Control Electronics 10.6 ma @ 600 Vac 50/60 Hz 1600 V peak forward & reverse Optional external Class T, branch-rated, touch-safe fusing Integrated heat sink thermal sensor 105% (SX-S), 20-105% (SX-L, HX) of continuous rating of Frame Amp Rating 50-450% of continuous rating 1.3 W per A of load current per phase 24 Vdc (+10 / -15%) ENVIRONMENTAL Surrounding Air Operating Temp 32 F [0 C] to 122 F [50 C] with derating for 140 F [60 C] Humidity 20% to 90% RH Non-Condensing Rated Operating Altitude Up to 6000 ft [1829 m] at full rated current Contaminates RoHS Compliant, CE Pollution Degree 2 Storage Temperature -4 F [-20 C] to 176 F [80 C] 7 Control Concepts, Inc., 2018 www.ccipower.com 1-800-765-2799 MicroFUSION 1ø Brochure Rev. 5.06

SPECIFICATIONS, CONTINUED RELIABILITY Mean Time Between Failure (MTBF) Designed for 50,000 Hours TEMPERTURE DERATING Surrounding Air Temperature effect on the Controller 100% 75% Frame Current (%) 0% 0 Surrounding Air Temperature ( F [ C] ) 122 [50 ] 140 [60 ] PERFORMANCE Standard Setpoint Resolution 10k 10k or 64k Internal Control Loop Resolution 16k 64k High Performance Option Output Resolution 12k @ 50 Hz, 10k @ 60 Hz 50k @ 50 Hz, 42k @ 60 Hz Response Time Adjustable from 50 ms to 2 s Adjustable from 50 ms to 2 s Accuracy (Full Conduction) Voltage 3.0% of frame rating 0.5% of frame rating Current 3.0% of frame rating 0.5% of frame rating Power 3.0% of frame rating 1.0% of frame rating Output Linearity 4.0% from (5-100%) output range 1.0% from (5-100%) output range Accuracy Temperature Drift (+10% / -15%) line voltage change will result in a max output change of 0.5% from (5-100%) output range Output shall not change greater than 0.5% per degree C max over the operating temperature range from (5-100%) output range +10% to -15% line voltage change will result in a max output change of 0.05% from (5-100%) output range Output shall not change greater than 0.2% per degree C max over the operating temperature range from (5-100%) output range MicroFUSION 1ø Brochure Rev. 5.06 www.ccipower.com 1-800-765-2799 Control Concepts, Inc. 2018 8

SPECIFICATIONS, CONTINUED COOLING Din Rail/Panel Mount External Panel Mount Forced Air / Natural Convection Natural Convection DC POWER CONSUMPTION 8-50 A Single Phase 7 W 45 A Single Phase DC 9 W 80 A Single Phase 9 W 100-160 A Single Phase 7 W 200-240 A Single Phase 11 W 320-400 A Single Phase 17 W Onboard Fieldbus Module CCI Connect Module ENCLOSURE PROTECTIVE RATING International IP 20 Add 0.7 W Add 6 W Remote Display IP 65, UL Type 1 & 12 External Panel Mount IP 65, UL Type 4 I 2 t DATA (8.3-10 msec) Frame Size Conditions I 2 t Data 0-80 Junction Temp 125 C 16200 A 2 s 100-160 Junction Temp 125 C 80000 A 2 s 200-240 Junction Temp 125 C 125000 A 2 s 320-400 Junction Temp 125 C 320000 A 2 s ISOLATION Signal to Line/Load Line/Load to Ground Signal to Ground Network USB Signal to Processor Remote Display 3750 Vac minimum 2500 Vac minimum 1500 Vac minimum 1500 Vac minimum 2500 Vac minimum 1500 Vac minimum 2500 Vac minimum SCCR - TYPE 1 COORDINATION Frame 1Ø / 3Ø ANALOG SETPOINT INPUTS Voltage Voltage Impedance Max Voltage Current Mode Current Impedance Max Current Pulse Width- Modulation Required Fusing * 0-10 Vdc (0 to 65535) 200 kω +/- 15 Vdc 0-20 ma (0 to 32767) 249 Ω +/- 31 ma or +/- 7.8 Vdc SCCR Rating** 8 A 10 A Fast Acting J or T 100 ka 16 A 20 A Fast Acting J or T 100 ka 32 A 40 A Fast Acting J or T 100 ka 50 A 60 A Fast Acting J or T 100 ka 80 A 100 A Fast Acting J or T 100 ka 100 A 125 A Fast Acting J or T 100 ka 130 A 175 A Fast Acting J or T 100 ka 160 A 200 A Fast Acting J or T 100 ka 200 A 250 A Fast Acting J or T 100 ka 240 A 300 A Fast Acting J or T 100 ka 320 A 400 A Fast Acting J or T 100 ka 400 A 500 A Fast Acting J or T 100 ka * Maximum fuse A shown above, fuses with lower A rating can also be used. ** To meet SCCR rating Fast acting J or T fusing must be used. Update period: 6 ms 0-100% Frequency range: 20 Hz to 2 khz max 9 Control Concepts, Inc., 2018 www.ccipower.com 1-800-765-2799 MicroFUSION 1ø Brochure Rev. 5.06

ACCESSORIES CCI LINK MicroFUSION features CCI Link, a proprietary deterministic digital bus that enables multiple CONTROL CONCEPTS devices to communicate with each other. CCI Link is currently used to enable SYNC-GUARD over a digital bus. 0.5 ft [0.15m] cable 0058003-0050 - 005 1 ft [0.30 m] cable 0058003-0050 - 01 3 ft [0.91 m] cable 0058003-0050 - 03 5 ft [1.52 m] cable: 0058003-0050 - 05 15 ft [4.57 m] cable: 0058003-0050 - 15 25 ft [7.62 m] cable: 00580003-0050 - 25 FIELDBUS INTERFACE Modbus TCP (Ethernet), EtherNet/IP, EtherCAT, PROFINET, or PROFIBUS. Simplify your cabling, eliminate A/D conversion error, and gain access to monitor information. Internal interface option: Modbus TCP, EtherNet/IP, or PROFINET. External interface option: All fieldbus interfaces are available. Controls up to ten zones. REMOTE HAND TERMINAL This handheld display can be plugged into any MicroFUSION device to view and change parameters on the display list. Part Number: SMADISPLAY-RTK. Cables may be purchased to connect the Remote Hand Terminal to MicroFUSION devices. MicroFUSION 5 ft [1.52 m] cable: 0058007-0050 - 05 15 ft [4.57 m] cable: 0058007-0050 - 15 25 ft [7.62 m] cable: 0058007-0050 - 25 REMOTE DISPLAY When the Remote Display is panel mounted it s easy to view and customize limits, setpoints, and alarm conditions via the 2-Line, 16-character text display. UL-type 1 & 12 ratings, IP65 5 ft [1.52 m] cable: SMAUFUSION - RDK5 15 ft [4.57 m] cable: SMAUFUSION - RDK15 25 ft [7.62 m] cable: SMAUFUSION - RDK25 DIN RAIL POWER SUPPLIES USB CABLE 24 W 0091011-0024 - 1 60 W 0091011-0060 - 1 96 W 0091011-0096 - 1 120 W 0091011-0120 - 1 15 ft [4.92 m], Micro USB cable: 0058006-0000-15 OTHER ACCESSORIES Control Concepts, Inc. will be as accomodating as possible for fuse sizing and other accessory needs, please contact Control Concepts, Inc. via website, email, or phone. MicroFUSION 1ø Brochure Rev. 5.06 www.ccipower.com 1-800-765-2799 Control Concepts, Inc. 2018 10

MODEL NUMBERS uf1 - - Board Type SX = Standard HX = High performance Terminal L = Lug (100-400 A) T = Pluggable terminal block (8-80 A) R = Ring terminal 1 (8-80 A) Frame Style A = 16-32 A (Panel Mount / DIN Rail) B = 50-80 A (Panel Mount / DIN Rail) E = 8 A (Panel Mount / DIN Rail) G = 100-160 A (Panel Mount) H = 200-240 A (Panel Mount) I = 320-400 A (Panel Mount) Option Board 0 = None E = Modbus TCP I = EtherNet/IP N = PROFINET Amp Size 8 = 8 A 2 130 = 130 A 16 = 16 A 160 = 160 A 32 = 32 A 200 = 200 A 50 = 50 A 240 = 240 A 80 = 80 A 320 = 320 A 100 = 100 A 400 = 400 A Performance Available with SX: S = Standard L = Adjustable Current Limit and Current Feedback Available with HX: L = Adjustable Current Limit, Current Feedback, Load Voltage Feedback, & Voltage Limit P = High Performance (Includes Load Voltage Feedback, True RMS Power Control, Current Limit, Power Limit, High Resolution Control Loop) *DC only available in HX I/O 0 = None 3 1 = Alarm Relay (1x Form C) 2 = General Purpose Input, Analog Input Channel 2, Pulse Width Modulation Input 3 3 = Alarm Relay and General Purpose Input, Analog Input Channel 2, Pulse Width Modulation 4 = Isolated I/O 3 5 = Isolated I/O with Alarm Relay 6 = Isolated I/O with Gen. Purpose Input, Analog Input Channel 2, Pulse Width Modulation 3 7 = Isolated I/O with Alarm Relay and Gen. Purpose Input, Analog Input Channel 2 / Pulse Width Modulation Retransmits 0 = None R = Retransmits 2 (Two 16-bit analog retransmits for voltage, load resistance, current, power) Sync 0 = None S = Digital SYNC-GUARD Zero Cross Transformer Mode (ZCT) 0 = None Z = Zero Cross Transformer Mode 2 1 Contact factory for availability 2 Only available with HX type board 3 Only applicable for SX; Alarm relay is standard for HX 11 Control Concepts, Inc., 2018 www.ccipower.com 1-800-765-2799 MicroFUSION 1ø Brochure Rev. 5.06

CONTROL CONCEPTS has a worldwide presence in more than 51 countries Algeria Finland Japan Portugal Taiwan Australia France Latvia Romania Thailand Austria Germany Lithuania Russia Turkey Belgium Greece Malaysia Singapore United Kingdom Bulgaria Hong Kong Mexico Slovakia United States Canada Hungary Morocco Slovenia Ukraine China India The Netherlands South Korea Vietnam Czech Rep. Indonesia New Zealand South Africa Denmark Irelande Norway Spain Egypt Israel Philippines Sweden Estonia Italy Poland Switzerland CONTROL CONCEPTS EUROPE celduc relais NORTH AMERICA PMA Controls ASIA SOUTH AMERICA AFRICA PACIFIC Sales department for North & South America: Tel. +1(952) 474-6200 or +1(800) 765-2799 Web: www.ccipower.com Email: info@ccipower.com Sales department for Europe: Tel. +33 4 77 53 90 21 for Africa / Asia / Pacific : Tel. +33 4 77 53 90 19 Web: www.celduc-relais.com Email: cci@celduc.com Sales department for India : Tel. + 091-44249 60315 Web: www.pmacontrols.in Email: info@pmacontrols.in 18760 Lake Drive East Chanhassen, MN 55317 USA www.ccipower.com Information furnished by CONTROL CONCEPTS INC. is believed to be accurate and reliable. However, no responsibility is assumed by CONTROL CONCEPTS INC. for its use. CONTROL CONCEPTS INC. Reserves the right to change the design or operation of the equipment described herein and any associated controller products without notice. CONTROL CONCEPTS INC. also assumes no responsibility for any errors that may appear in this document. Information in this document is subject to change without notice. MicroFUSION 1ø Brochure Rev. 5.06 www.ccipower.com 1-800-765-2799 Control Concepts, Inc. 2018 12