B 520 ELECTRONIC AMBIENT TEMPERATURE CONTROLLERS. RTB C2 Eng. COSTER BUS. B RTB C2 Eng MC REV 01

Similar documents
By means of C-Bus connection DTT 318 can be inserted in a telemanagement system.

B 556. LOCAL BUILT-IN OR WALL-MOUNTED UNIT WITH Volt RELAY OUTPUT "MULTIZONE" SYSTEM. RTL 120 Eng. = built-in unit

D 151 TEMPERATURE CONTROLLER. RTF 31.. C1 Eng. COSTER. D RTF 31.. C1 Eng DA REV. 01

COSTER. Adjustment of desired value by means of remote set point adjuster.

Room Temperature Controllers. for heating and cooling systems

Room Temperature Controllers. for heating and cooling systems

NRT 105: Electronic fan-coil controller, equiflex

Room Temperature Controllers. for heating and cooling systems

ELECTRONIC THERMOSTAT: T920

Electro Controls. Input-Output Modules WattsIndustries.co.uk

Room Temperature Controllers. for heating and cooling systems

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION

Room Temperature Controllers. for heating and cooling systems

The appliance is fitted with a 3-digit display in order to show the room temperature and the 2 + and - key parameters for the programming functions.

Control solutions Biofloor

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77

ELECTRONIC THERMOSTAT: T951

TLC3-BCR-U Series Thermostat

CM927 WIRELESS PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

Application Sheet Active chilled beam with variable fan, cooling coil and hot water radiator on triac output

PRODUCT CATALOGUE TEMPERATURE CONTROL Grässlin products for individual control of temperature

Relay (R1) 003. Balancing Valve. Slab Pump (P1) Max. 4 pipe diameters apart. Injection Pump (P2) 150 No 24V only. Power. Off.

Fan Coil Actuator FCA 2

Microprocessor Based Multistage Temperature Controller & Two Channel 365 Day Time Switch. Made in Australia 100% Australian Owned Company

Application Sheet Fan coil unit with staged fan, heating/cooling coil (2 pipe) on triac output and electric reheater

Application Sheet Fan coil unit with variable fan, heating/cooling coil (2 pipe) on triac output and electric reheater

Room Temperature Controller with Built-in Room Sensor 1 Feb 2002

WIREFREE CHRONOTHERM FEATURES PRODUCT SPECIFICATION SHEET. CM67RF can be used with Automatic Time Setting module (Q6667B1007)

Universal Controller

Device connection and commissioning can only be carried out by qualified professionals. Always make the connections while the power is switched off.

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Sauter Components

ALPTEC POWER FACTOR CONTROLLER

NRT 300: Electronic air-conditioning controller, heating/cooling, equiflex

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition

Thermostat P. Thermostats Electronic room thermostat with clock for thermal actuators

Intelligent Compact Controller

Control module 2 circuits AD290. Installation and Service Manual

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

Temperature Controller

Application Programs Descriptions

R7426A. MicroniK 200 TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

P5201 Universal Programmable Transmitters with Galvanic Isolation

TEC Controller Constant Volume with Hot Water Reheat, Application Application Note Building Technologies

K3P ENG.qxd 23/10/ Pagina 1

MULTIFUNCTION GRAPHICAL UNIT MGU 800

Technical Information

INFOCAL 8 Energy calculator

B 265 OPTIMISING COMPENSATOR SLAVE. DSE 600 Eng. C2 COSTER C BUS C RING. B DSE 600 Eng. C LB

Communicative heating controller

DIN rail mounting temperature controller with current transformer input deltadue series D1 line

T 1000 PLUS Secondary Injection Relay Test Set

Wireless Room Thermostat Installation and Operation Y6630D1007

Owner s Manual S10 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

SONOMETER TM 1100 Ultrasonic compact energy meter

INSTAT 868 Radio Frequency Single-Room Controls

LOW VOLTAGE CONVERTER WITH THREE POINT GALVANIC INSULATION

1 Safety instructions. 2 Device components. 3 Function. KNX Heating actuator 6gang RMD 230 V. Order-No. :

Intelligent Installation Systems. ABB i-bus KNX Room Thermostat Fan Coil with Display 6138/11-xx-500 Product Manual

Analogue temperature controllers

43.019/1. NRT 300: Electronic controller for air-conditioning (heating/cooling) Sauter Components

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting

Digital Meters With A Multicolour Bargraph LEL-NA3 one-channel LEL-NA5 one-channel LEL-NA6 two-channel

RX-100. Drahtloser Programmierbarber Thermostat Betriebs-, Reinigungsund Wartungsanleitung für den INSTALLATEUR und den BENUTZER

DESCRIPTION DIMENSIONS HOW TO ORDER

R7420B. MicroniK 100 HONEYWELL TEMPERATURE CONTROLLER PRODUCT DATA GENERAL FEATURES

P o w e r. C O N T R O L S A N D a t h e n a c o n t r o l s. c o m. ATHENA CONTROLS, INC Campus Drive Plymouth Meeting, PA U.S.A.

FCU-503 FAN COIL CONTROLLER WITH RDU-TOUCH INTERFACE

AK48 SPECIFICATIONS APPLICATIONS GENERALS FEATURES. 1/16 DIN Process controller

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

Radiocontrol F. Floor Heating Controller Radio control system for floor heating

KNX Room temperature controller

43.030/1. NRT 101: Electronic room-temperature controller with time program. Sauter Components

SRC-110 Series Zone Controllers with Modbus RTU

SAT.. Electromotoric actuators for valves ACVATIX. with a 5.5 mm stroke and 300 N positioning force

OVEN INDUSTRIES, INC. Model 5C7-362

Electromotoric actuators for stroke valves

Instruction Notes for 108A L Sensor Input

CS-200. PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL

Level Limit Switch nivotester FTL 370, FTL 372

April 1994 UCM-420A. Setpoint Controller. Operating and Installation Instructions

R&D TECHNICAL SPECIFI

RS /E-EV BLU SERIES

User Instructions For TopTronic RS-10

SONOMETER TM 1100 Ultrasonic compact energy meter

Electromotoric actuators

About AB Industrietechnik

PRODUCT MANUAL. ABB i-bus KNX VC/S 4.x.1 Valve Drive Controller

Owner s Manual S5 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL

H7625A, H7635A, H7626A, H7636A Series 2000 Humidity/Temperature Sensors

SERVICE-MANUAL ROOM TEMPERATURE CONTROLLER NEA 230V / 24V. Construction Automotive Industry

REH FC-BMS3 Modbus Manual

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

SAV.. ACVATIX Electromotoric actuators for valves. with a 20/40 mm stroke

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

Transcription:

ELECTRONIC AMBIENT TEMPERATURE CONTROLLERS C BUS C2 Eng. B 520 - C2 Eng. 25.09.07 MC REV 01 B 520 25.09.07 MC REV 01 1 On-Off output or 1 modulating & 1 On-Off 2 modulating outputs with Pl control action Can be connected to central display unit via C-Bus interface NTC 10 kω temperature sensing element incorporated Remote detector option as alternative to above Choice of adjusting temperature by incorporated or remote setpoint adjuster Individual or centralized season switching 1. APPLICATION temperature controllers are designed for control of ambient temperature in heating and air-conditioning plants in, for example : hotels and guest houses residential complexes commercial centers and office blocks schools and public buildings. 2. FUNCTIONS Their main uses are: as independent controllers without timed programming; as controllers in a multizone system with independent timed programming if connected via CosterBus to a central display unit (CDU). They are suitable for control of: 040/140 Electric load 230 or 24 V~,. 5(1) A, for control of fans, pumps, burners or air-conditioning units. 040, if connected to a central unit, can be used also as a timeswitch by disactivating the internal detector (remove jumper 12-13). 041/141 One modulating valve with three-wire electric control and one electric load 230 or 24 V~. (1)A (Heating or Cooling). 042/142 Two modulating valves with three-wire electric control ( 50 W for one); (Heating and Cooling). 045/145 Up to four 24 V~ electrothermal valves. ( 50 W for one) 3. MODELS Model Outputs Type of load Season switch Setpoint adjuster 040 1 On-Off relay (Heat. or Cool.) 24 V or 230 V,. 5(1) A Local or centralized No 140 1 On-Off a relay (Heat. or Cool.) 24 V or 230 V,. 5(1) A Local or centralized Yes 041 1 triac modul. & 1 On-Off relay 3-wire valve 24 V. Local or centralised No (Heat. or Cool) & 24 V or 230 V. 5 (1)A 141 1 triac modul. & 1 On-Off relay 3-wire valve 24 V. Local or centralised Yes (Heat. or Cool) & 24 V or 230 V.5 (1) A 042 2 triac modul. (Heat. & Cool.) 3-wire valve 24 V. Not applicable No 142 2 triac modul. (Heat. & Cool.) 3-wire valve 24 V. Not applicable Yes 045 4 triac On-Off (Heat. or Cool.) 24 V thermal valves. Local or centralised No 145 4 triac On-Off (Heat. or Cool.) 24 V thermal valves. Local or centralised Yes 4. ACCESSORIES Model Description + 1 hour key Sensing element Setpoint adjuster SAB 010 Ambient temperature detector NTC 10 kω No SAB 210 Ambient temperature detector Yes NTC 10 kω No SCB 110 Ambient temperature detector NTC 10 kω Yes SCB 210 Ambient temperature detector Yes NTC 10 kω Yes STT 010 Temp. detector for heating/cooling coils NTC 10 kω No STA 010 Air duct temperature detector NTC 10 kω No AIC 240 Window switch cable 1

A B B 520 - C2 Eng. 25.09.07 MC REV 01 5. TECHNICAL DATA Electrical Power supply 24 V~ ± 10% Frequency 50... 60 Hz Consumption 4 VA Electromagnetic compatibility CEE 93/68 On-Off SPDT output (.40): imum switching voltage 250 V~ imum switching current 5 (1) A Auxiliary On-Off output (.41): imum switching voltage 250 V~ imum switching current 5(1)A Triac outputs powered by 24 V~ (. 41-.42-.45): output voltage 24 V~ imum switching current 2 A Measurement range ambient detector: heating 5... 25 C cooling 5... 30 C Construction standards Italian Electrotech. Comm. (CEI) NOTE: The consumption data refers only to (41, 42, 45); In order to have complete data it is essential to know the consumptions of all the devices connected to each of the Triac outputs. Factory settings desired Day Heating temp. 20 C desired Night Heating temp. 16 C desired Frost Protection Heating temp. 6 C desired Day Cooling temp. 25 C desired Night Cooling temp. excluded actuator run time (.41-.42) 150 s half-load cycle (.40 -.45) ± 8 min. proportional band - Heating ± 2 C proportional band - Cooling ± 1 C integral time - Heating 20 min. integral time - Cooling 20 min. Setting ranges (from CDU): desired (Day-Night) Heating temp. (excluded)... 25 C desired (Day-Night) Cooling temp. (excluded)... 30 C limits of local setpoint adjuster - Heating 0... + 5 C limits of local setpoint adjuster - Cooling 0... 5 C actuator run time (.41-.42) 10... 510 s half-load cycle (.40 -.45) 10... 510 s proportional band ± 0.5... ± 10 C integral time 1... 99 min. Ambient temperature: operation 0... 45 C storage 20... + 60 C Protection IP 30 Dimensions 130 x 80 x 35 mm Weight 170 g 6. OPERATIONAL DIAGRAMS TYPICAL APPLICATIONS On-Off control thermal valve (hot or cold) On-Off control fan (hot or cold) 140 140 CDZ 064 VDM 3.. 230 V. Modulating control one 3-wire valve and one On-Off fan (hot or cold) 141 141 Modulating control 3-wire valve (hot) 230 V. CDZ 064 HMM 4.. CDR 064 HGT 2.. Modulating control two 3-wire valves (hot & cold) On-Off control. 4 thermal valves (hot) 142 CDZ 064 VDM 4.. CosterBus Sum. - Win. 145 7. CHOICE IN RELATION TO TYPE OF PLANT Radiators with: 2-port valve + 230 V~ electrothermal actuator 2-port valve + 24 V~ electrothermal actuator 2-port valve + 24 V~ three-wire actuator Fan coil with : Control fan at 230 V~ 4-port valve + 230 V~ electrotherm. actuator (. 500 W) 2-port valve + 24 V~ electrotherm. actuator 4-port valve + 24 V three-wire actuat. + fan (. 500 W) Two 4-port valves + 24 V~ three-wire actuator 230 V~ circulation pumps Burners or independent boilers (230 V ) Independent air-conditioning unit (230 V ).40 On-Off one or more valves in parallel (. 20).45 On-Off one or more valves (. 4).41 modulating one valve.40 On-Off one or more fans in parallel (. 500 W).40 On-Off one or more valves in parallel (. 20).45 On-Off one or more valves (. 4).41 modulating one valve & On-Off one fan (hot or cold).42 modulating 2 valves (hot and cold).40 On-Off (. 500 W)..40 On-Off (. 500 W)..40 On-Off (. 500 W) 2

B 520 - C2 Eng. 25.09.07 MC REV 01 8. PLANTS controllers, from the plant point of view, can be used: As individual controllers: Those with one output can switch the Heating-Cooling operation by means of their incorporated season switch. As individual controllers with centralized season switching: By connecting to all the controllers with one output a parallel 24 V~ voltage to terminals 10-11. With centralized control: by connecting all the controllers (. 239) to a CDU, via C-Bus interface, it is possible to adjust all the parameters, including season switching, of each single controller. 9. OPERATION are a range of electronic temperature controllers incorporating microprocessors with all the setting data already entered. The setting data for heating and cooling are separate and the controllers use one or the other according to the season switching. When they are connected to a supervisory system via the C-Bus parallel interface, 24-hour and 7-day timed event programmes can be used. 9.1 Temperature monitoring Ambient temperature is measured by an incorporated NTC 10 kω sensing element or by a remote detector; if the latter is connected it is necessary to remove jumper 12-13 in order to exclude the internal detector. In event of use as remote sensor of an analogue output of another controller, it is necessary to respect the polarity. The output B is connected to terminal 13 and output M to terminal 14. The value of the desired temperature (Heating and Cooling) can be adjusted, in models 14., using the incorporated setpoint adjuster, or by means of the setpoint adjuster on the SCB 110-210 ambient detector. On the controllers it is possible to limit the adjustment range mechanically by means of two stops, or electronically if the controller is connected to a CDU. 9.2 OP E RATI N G FE ATU RE S Modulating outputs with PI control action: The controller compares the actual temperature value t, measured by the detector, with the desired value T. If there is a difference, the controller calculates the output value (valve opening 0... 100%) according to the amount of the difference and the proportional band Pb. If the difference persists, it is corrected by the integral function which adjusts, over time, the calculated position of the valve, in relation to the integral time It. To position the valve at the calculated value, the controller sends opening or closing signals to the valve (threewire control), modulated over time, in relation to the actuator speed (150 s). Proportional band Pb, Integral time It and actuator speed are all adjustable. On-Off outputs with PI control action: The controller calculates the output value using the same criteria as modulating controllers (PI control action) and converts it into On and Off output signals. When the output is 0% the signal is always Off; when it is 100% the signal is always On; when it is 50% the duration of the On signal is equal to the duration of the Off signal and the total time is the half-load operating cycle (e.g.16 min. = 8 min. On and 8 min.off). With this system the effective hysterisis proves to be much narrower than the proportional band Pb set and the ambient temperature much more stable. Auxiliary On-Off output (only RTS 041-141): Voltage-free contact suitable for control of fan coil fans or circulation pumps. When the output is 0% the signal is always Off; when it is 100% it is always On. The response of the contact is not immediate but there is a delay of four minutes between the On and Off status. 9.3 SE AS ON S W I TCH I N G In controllers with one output it is possible to invert the output action, in order to pass from winter to summer operation, in three different ways: Single switching by means of the incorporated season switch. Centralized switching using a central switch which energises in parallel at 24 V~ the terminals 10-11 of all the controllers. Without power it is Heating and with power Cooling. With this type of switching all the controllers must remain in the Winter position. Centralized switching from the CDU. 9.4 OP E N W I N D OW S W I TCH An electric switch, of the burglar alarm type, installed on the window of the space controlled and connected to terminals 15-16, permits switching the heating to Frost Protection mode and excluding Cooling, when the window is opened. 9.5 + 1 H OU R KE Y Ambient detectors SAB 210 and SCB 210 incorporate a key which allows user in a zone to prolong by one hour the heating period at the desired Day temperature. It does not function in Cooling periods. 9.6 TI M E D E V E N TS S W I TCH 040 controller, if connected via CosterBus to a CDU, can operate as a switch for running a timed events programme. The ambient detector must be disabled by removing the jumper between terminals 12 and 13. 3

B 520 - C2 Eng. 25.09.07 MC REV 01 10. OPERATING DIAGRAMS 041-141 1 modulating output & 1 On-Off with season switching Winter Summer 042-142 2 modulating outputs in sequence Heating Cooling 041-141 On-Off output with season switching Winter Summer 11. OVERALL DIMENSIONS 1 Cover 2 Base 3 Output LEDs 4 Setpopint adjuster ± 15 C 5 Sum.-Win. switch ( 1 output) 6 Cover/base securing elements 12. INSTALLATION Controllers 04. and 14., if using the incorporated ambient detector, must be installed at a height of 1.5... 1.6 meters from the floor, on an internal wall of the space and at a point which represents the average temperature. They must be as far as possible from windows, doors and sources of heat and corners and curtains must be avoided. If a remote detector is used the controller can be installed anywhere convenient. Separate base and cover by releasing the cover/ securing elements. Fix the base to the wall or to the panel-mounting patress using the pre-drilled holes. Make the electrical connections strictly in accordance with the wiring diagram (14) and in observance of the safety regulations in force. Replace the cover on the base and close the two parts carefully until they snap into place. Warning: If the controller is installed on a panel-mounting patress it could happen that the sensing element becomes cooled by cold air from the cable ducting. In this event the rear of the base must be thermally insulated. 13. WIRING DIAGRAMS It is advisable not to insert more than two cables in a single terminal of the controller and if necessary to use external junction boxes. Power supply 24 V~ : Cables with 1.5 mm 2 cross section Power supply actuators: Cables with 1.5 mm 2 cross section. Detectors: Cables with min. 1mm 2 cross section. C-Bus wiring: Cables, of different colours, with 1.5 mm 2 cross section; imum length five km. Bus polarity must be strictly observed. 4

B 520 - C2 Eng. 25.09.07 MC REV 01 14. WIRING DIAGRAMS General (fig. A) Centralized power supply (fig. B) Outputs (fig.f) Sum-Win Detector & remote Local centralized setpoint adjuster Coster Bus Alternate connections so as not (fig. C) (fig. E) (fig. D) to overload the power transformer Centralized Sum. - Win. switching (fig. C) Bus connection with CDU (fig. D) It is not indispensable to respect the polarity of the connections Make sure the polarities of the BUS connections are correct DETECTORS & REMOTE SETPOINT ADJUSTER (fig. E) Ambient detector Detector fan coil extract air Ambient detector or fan coil extract air & remote setpoint adjuster & remote setpoint adjuster To use internal detector leave jumper 12-13 With remote sensor remove jumper 12-13 (Terminal 14 = M = 0 V) c1= AIC 240 window switch reversal cable Warning: For electrical connection see Techincal Data Sheet D 615 - AIC 240 OUTPUTS (fig. F) s1 = Window switch Window open = switch open controller on frost protection..40..45..41..42 1 2 6 7 8 7 8 9 2 5 9 2 6 ~ 24 V~ M 5(1) L N 230 V~ ~ 24 V~ Y1 Y1 Y1 Y1 ~ 24 V~ Op Co Cl Y2 L N 230 V~ M 5(1)A ~ 24 V~ Op Co Cl Y+ Op Co Cl Y B1 SAB 010 ambient detector B2 STT 010 fan coil extract air detector or SCB 110 air duct detector B3 Ambient detector with SCB 110 setpoint adjuster M Fan coil fan N... controllers P Central display unit (CDU) c1 AIC 240 window switch inversion cable s1 Window switch Y1 Electrothermal valve Y2 Valve with 3-wire control Y+ Heating valve with 3-wire control Y Cooling valve with 3-wire control 5

B 520 - C2 Eng. 25.09.07 MC REV 01 6

B 520 - C2 Eng. 25.09.07 MC REV 01 7

B 520 - C2 Eng. 25.09.07 MC REV 01 Amendments to data sheet Date Revision No. Page Section Details of amendments Firmware version Software Version 30.03.06 MZ Variuos Various Updated switching current 13.07.06 MZ 3 9.1 Temperature monitoring Note included regarding use of remote sensor. 16.10.06 MC 2 5 5. Technical Data 14. Functional diagrams (fig. E) Amended consumption with insertion of explanatory note for with Triac output Added note: for connection window switch cable (AIC 240) 25.09.07 MC 01 5 14 Wiring diagram (fig. F) The numbers of the terminals shown in the actuators have been eliminated 07 0.98.2295 CONTROLLI TEMPERATURA ENERGIA TECNOLOGIE ELETTRONICHE S.p.A. Sede Legale: 20132 Milano - Via San G.B. De La Salle, 4/a Head Office & Sales Via San G.B. De La Salle, 4/a Tel. +39 022722121 20132 - Milano Fax +39 022593645 Orders Fax +39 0227221239 Reg. Off. Central & Southern Via S. Longanesi, 14 Tel. +39 065573330 00146 - Roma Fax +39 065566517 Shipping Via Gen. Treboldi, 190/192 Tel. +39 0364773200 25048 - Edolo (BS) Tel. +39 0364773202 E-mail: info@coster.eu Web: www.coster.eu ISO 9001:2000 THE INTERNATIONAL CERTIFICATION NETWORK Registration Number: IT - 34674 CSQ - Certificate N. 9115.COEE D 33150 8