Comparative Analysis of Grid Power Quality using DVR, DSTATcom, Open UPQC and SVC Light In Grid Wind Energy System

Similar documents
Protection from Voltage Sags and Swells by Using FACTS Controller

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Analysis & Function of Unified Power Quality Conditioner for Power Quality Improvement of Distributed Network

Series Active Power Filter for Power Quality Improvement Based on Distributed Generation

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Application of Dynamic Voltage Restorer for Voltage Balancing with ASD Load Using DQO Transformation

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Power Quality enhancement of a distribution line with DSTATCOM

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

ISSN Vol.07,Issue.21, December-2015, Pages:

A Voltage Controlled Dstatcom for Power Quality Improvement

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

FUZZY LOGIC CONTROLLER BASED UPQC FOR POWER QUALITY MITIGATION IN GRID CONNECTED WIND ENERGY CONVERSION SYSTEM

ISSN Vol.03,Issue.11, December-2015, Pages:

Power Quality and the Need for Compensation

Harmonics Reduction using 4-Leg Shunt Active Power Filters

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

Mitigation of Voltage sag and Harmonics in Grid connected Wind Energy System using STATCOM

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

World Journal of Engineering Research and Technology WJERT

Voltage Sag and Swell compensation using DVR to enhance Power Quality

Power Quality Improvement of Grid Connected Wind Energy System by Statcom for Balanced and Unbalanced Linear and Nonlinear Loads

Performance of DVR under various Fault conditions in Electrical Distribution System

Power Quality improvement of a three phase four wire system using UPQC

B.Tech Academic Projects EEE (Simulation)

A CONTROL TECHNIQUE FOR INSTANT MITIGATION OF VOLTAGE SAG/SWELL BY DYNAMIC VOLTAGE RESTORER

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

A Power Control Scheme for UPQC for Power Quality Improvement

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

Power Quality Improvement using Hysteresis Voltage Control of DVR

Mitigation of Voltage Sag/Swell by Using Battery Energy Storage DVR for Induction Motor Drive Applications

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Design of a Unified Power Quality Conditioner (UPQC)

Mitigation of Voltage Sag and Swell using D-STATCOM to improve Power Quality

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

FUZZY LOGIC CONTROL BASED DYNAMIC VOLTAGE RESTORER FOR POWER QUALITY IMPROVEMENT IN DISTRIBUTION SYSTEM

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Voltage Sag Mitigation of DVR using Matlab Simulation

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Enhancement of Voltage Stability & reactive Power Control of Distribution System Using Facts Devices

UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY

Voltage Correction Methods in Distribution System Using DVR

STATCOM BASED ON REDUCTION OF PQ ISSUES IN MICRO GRID APPLICATION SYSTEMS

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Mitigation of Voltage Sag/Swell Using UPQC

MODELING AND SIMULATION OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

SIMULATION VERIFICATION OF DYNAMIC VOLTAGE RESTORER USING HYSTERESIS BAND VOLTAGE CONTROL

Implementation of UPQC for Voltage Sag Mitigation

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3

Design and Simulation of Dynamic Voltage Restorer (DVR) Using Sinusoidal Pulse Width Modulation (SPWM)

Control of Power Flow with Multi Bus Three-Feeder Distribution System using GUPQC

STUDY OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT RAJIV KUMAR SINKU

Simulation and Implementation of DVR for Voltage Sag Compensation

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

A VOLTAGE SAG/SWELL ALONG WITH LOAD REACTIVE POWER COMPENSATION BY USING SERIES INVERTER of UPQC-S

Synchronous Reference Frame Theory (SRF) along with PI Controller Based Dynamic Voltage Restorer

Power Quality Improvement in Distribution System Using D-STATCOM

DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK

A Novel Approach to Simultaneous Voltage Sag/Swell and Load Reactive Power Compensations Using UPQC

OVERVIEW OF DVR FOR POWER QUALITY IMPROVEMENT

Power Quality Analysis in Power System with Non Linear Load

II. RESEARCH METHODOLOGY

Enhancement of Power Quality Using Advanced Series Active Power Filters

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review

Design and Development of DVR model Using Fuzzy Logic Controller for Voltage Sag Mitigation

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Power Quality Compensation by using UPFC

Improve Power Factor and Reduce the Harmonics Distortion of the System

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Control of Shunt Active Power Filter for Improvement of Power Quality

UPQC (Unified Power Quality Conditioner)

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement

ROLE of DC-MLI based D-STATCOM in Distribution Network with FOC Induction Motor Drive

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

CHAPTER 3 ELECTRIC POWER QUALITY

p. 1 p. 6 p. 22 p. 46 p. 58

Power Quality Study of Electrical Installation in Academic Institute Case Study

IJESR/Nov 2012/ Volume-2/Issue-11/Article No-21/ ISSN International Journal of Engineering & Science Research

Modelling And Analysis of DVR With SEPIC Converter And Supercapacitor

Introduction to Harmonics and Power Quality

Transcription:

International OPEN ACCESS Journal Of Modern Engineering Research (IJMER) Comparative Analysis of Grid Power Quality using DVR, DSTATcom, Open UPQC and SVC Light In Grid Wind Energy System Mrs. Lubna Ismatulla Shaikh 1, Dr. Chandrashekhar Thorat 2 1 Department of Electrical Engineering, Govt. Polytechinc, Jalna (MS) India 2 Govt. Polytechnic, Nagpur (MS), India ABSTRACT: Wind power injection into an electric grid affects power quality due to fluctuating nature of wind. The power arising out of the wind turbine connected to grid concerning power quality measurements are active power, reactive power, voltage sag, voltage swell, flicker and harmonics. Dynamic Voltage Restorer (DVR) is a series compensator that can compensate power quality problems for instance voltage harmonics, voltage sags, voltage swells, voltage flickers, voltage unbalance. Distribution Static Compensator (DSTATCOM) is a shunt compensator that can compensate power quality problems like harmonics in current, reactive current, unbalancing of current and so on. SVC Light is a flicker mitigating device that attacks the root of the problem, i.e., the erratic flow of reactive power through the supply grid to the furnace. It does this by measuring the reactive power consumption and generating a corresponding amount for injection into the system, thereby reducing the net reactive power flow to an absolute minimum. As an immediate consequence, voltage flicker is also minimized. Unified Power Quality Conditioner (UPQC) is a device that consists of series and shunt converters which are in back to back connection and deals with the defects of supply voltage and load current. Open UPQC consists of DVR and DSTATCOM without common DC link. The key objective of this paper is to build up models of DVR, DSTATCOM, SVC Light and OPEN-UPQC for development of power quality under a variety of operating conditions. An open UPQC to compensate for high power load consisting of non linear load is used. It is then simulated to lessen voltage sag/swells and harmonic currents. In order to examine the performance of compensators such as series, shunt and combination of series-shunt the traditional dq-theory is used with PI controller. The open UPQC separates the utility from problems in current quality of load and simultaneously separates the load from problems in voltage quality of utility. The THD of DVR, DSTATCOM, SVC light and Open UPQC are compared in this paper for a 3-phase wind connected distribution network with nonlinear load using Matlab Simulink in power system block set. Keywords: DSTATCOM, DVR, Power quality, SVC LIGHT, OPEN UPQC I. INTRODUCTION The main purpose of a utility system is to deliver electric power in sinusoidal form, currents with proper magnitudes and frequency to the customers at the point of common coupling (PCC). Even though the voltage generated by synchronous machines are nearly sinusoidal in power plants, a few unsighted conditions like lightning and short circuit faults, also non linear loads account steady state error or else transient current and voltage disturbances. For example, electric arc furnaces results in voltage fluctuations whereas harmonics in current and distort voltage waveforms are generated by power electronic converters, and short circuits faults cause voltage sags/swells [1-4]. Alternatively the majority of customer loads like computers, microcontrollers, hospital equipment etc are sensitive to power quality conflicts and their appropriate operation is dependent on the supplied voltage quality. This is achievable only if the continuous power flow is ensured at proper levels of voltage and frequency. Thus FACTS devices and Custom power devices came into existence in electrical system to enhance the quality of the electrical power by reducing the problems associated with power quality. The different types of Custom Power devices are Active Power Filters (APF), Battery Energy Storage Systems (BESS), Surge Arresters (SA), Static Electronic Tap Changers (SETC), Super conducting Magnetic Energy Systems (SMES), Solid State Fault Current Limiter (SSFCL), Static VAR Compensator (SVC), Solid-State Transfer Switches (SSTS), Distribution Series Capacitors (DSC), Distribution Static synchronous Compensators IJMER ISSN: 2249 6645 www.ijmer.com Vol. 6 Iss. 6 June 2016 59

(DSTATCOM) Dynamic Voltage Restorer (DVR), Uninterruptible Power Supplies (UPS), and Unified power quality conditioner (UPQC). The main focus of this paper is on DVR, DSTATCOM,OPEN UPQC and SVC light.. Wind Energy Generating System Wind generations are based on constant speed topologies with pitch control turbine. The induction generator is used in the proposed scheme because of its simplicity, it does not require a separate field circuit, it can accept constant and variable loads, and has natural protection against short circuit. The available power of wind energy system is presented as under in (2.1). where (kg/m 3 ) is the air density and A (m 2 ) is the area swept out by turbine blade, V wind is the wind speed in m/s. It is not possible to extract all kinetic energy of wind, thus it extract a fraction of power in wind, called power coefficient Cp of the wind turbine, and is given in (2.2). (2.2) where Cp is the power coefficient, depends on type and operating condition of wind turbine. This coefficient can be expressed as a function of tip speed ratio λ and pitch angle θ. The mechanical power produce by wind turbine is given in (2.3) where R is the radius of the blade (m). II. POWER QUALITY PROBLEMS Power quality has various meanings to different people. According to the IEEE Std. 1100, the power quality is defined as Power quality is the concept of powering and grounding sensitive equipment in a matter that is suitable to the operation of that equipment. The most commonly occurring power quality problems are current harmonics, voltage sags and voltage swells as shown in Figure-2.1. Altogether they comprise high proportion of the power quality disorders affecting the most commercial and industrial customers. 2.1. Voltage Sag Voltage sag is considered as a decrease in rms voltage between 0.1 and 0.9 per unit (pu) at the power frequency for the durations from 0.5 cycle to 1 min. The term sag is described as decrease in voltage. The occurrence of voltage sags is generally by system faults but the energization of heavy loads, overloaded wiring and starting of large motors can also cause voltage sag. (2.1) (2.3) 2.2. Voltage Swells Figure-2.1 Most Common Types of Power Quality Problems IJMER ISSN: 2249 6645 www.ijmer.com Vol. 6 Iss. 6 June 2016 60

A voltage swell is defined as an enhance in rms voltage or current between 1.1 and 1.8 pu at the power frequency for the durations from 0.5 cycle to 1 min. Voltage swells are generally connected with system error conditions, however they do not occur as frequent as voltage sags. The voltage swell can be caused by energizing a large capacitor bank, sudden load reduction, switching off a large load, open neutral connection and insulation breakdown. Voltage swells show negative effect on the performance of sensitive electronic equipment causing data errors, equipment shutdowns, and equipment damage and may lessen equipment life. It causes annoyance tripping and deprivation of electrical contacts. 2.3. Current Harmonic Distortion The harmonic voltage distortion and harmonic current distortion are robustly linked with each other since harmonic voltage distortion is mostly due to non-sinusoidal load currents whereas current harmonic distortion needs over-rating of series components such as transformers and cables. Distorted current causes more losses compared to a sinusoidal current with the same rms value because of the increase in the series resistance with frequency. The equipment that causes current harmonics is switched mode power supplies, single-phase loads, small Uninterruptible Power Supply (UPS) units, electronic fluorescent lighting ballasts and variable speed drives. The following are the problems caused by current harmonics such as overloading of neutrals, circuit breakers nuisance tripping, overheating of transformers, over-stressing of capacitors used for power factor correction and skin effect. The calculation of total harmonic distortion (THD) describes the harmonic distortion levels that measure the complete harmonic spectrum of every individual harmonic component with magnitudes and phase angles. THD is described as the square-root of sum of squares of each individual harmonic. The following is the Voltage THD where V1 represents the rms magnitude of the fundamental component and V n is the rms magnitude of component n, where n = 2,3,..., 2.4. Voltage Fluctuations / Flickers Voltage fluctuations/flickers are relatively small (less than 5 percent) changes in the rms line voltage. The main contributors of these changes/variations are arc furnaces, cyclo converters and other systems. They draw current with no synchronization with the line frequency. The voltage flicker results in an unnecessary pulsating torque because of the fluctuation in the speed of electric drives. Figure-2.2.: Voltage Fluctuations or Flicker III. CUSTOM POWER DEVICES N.G.Hingorani [6] introduced the custom power concept that means the usage of power electronics controllers in distribution systems. The quality and also the reliability of the power delivered to the customers are increased by the custom power. There are two categories of custom power devices, network configuring type and compensating type. The former type is used for current transferring, current limiting and current breaking. The later type is used for load balancing, active filtering, voltage regulation and power factor correction. The family of compensating devices includes DSTATCOM (Distribution Static compensator), DVR (Dynamic voltage restorer) and Unified power quality conditioner (UPQC). IJMER ISSN: 2249 6645 www.ijmer.com Vol. 6 Iss. 6 June 2016 61

Figure-3.1: DSTATCOM 3.1. Distribution Statcom (DSTATCOM) Fig. 2(3.1) shows the key components of a DSTATCOM. It comprises a dc capacitor, an ac filter, one or more inverter modules, a transformer that matches the output of the inverter to the line voltage and finally a PWM control strategy. The purpose of the DSTATCOM is to terminate load harmonics provided to the supply. DSTATCOM work as current sources and connected to the nonlinear load in parallel. It generates the harmonic currents required by the load and balances them besides providing the reactive power [6]. The current is injected by the DSTATCOM into the point of common coupling, to compensate unwanted components of the load current. The power factor and also unbalanced loads can be corrected through an appropriated control strategy. Shunt Active Power Filter in current control mode is also called as DSTATCOM. 3.2. Dynamic Voltage Restorer (DVR) In order to compensate the voltage sags/swells at the load side, a voltage component is injected by DVR in series with the supply voltage which is shown in figure-3.2. The capability of active power transfer via dc link is implied by injecting voltage in arbitrary phase with regard to the load current. The sources for the supply of active power can be a diode bridge linked to the ac network, a shunt connected PWM converter and an energy storage device. DVR works as a harmonic isolator that prevents the harmonics in the source voltage additionally balancing and regulating the voltages. Figure-3.2: Dynamic Voltage Restorer 3.3 SVC Light SVC Light is a flicker mitigating device that attacks the root of the problem, ie the erratic flow of reactive power through the supply grid to the furnace. It does this by measuring the reactive power consumption and generating a corresponding amount for injection into the system, thereby reducing the net reactive power IJMER ISSN: 2249 6645 www.ijmer.com Vol. 6 Iss. 6 June 2016 62

flow to an absolute minimum. As an immediate consequence, voltage flicker is also minimized. Important added benefits are a high and constant power factor, regardless of the load fluctuations over furnace cycles, as well as a high and stable bus rms voltage. These benefits translate into improved furnace productivity as well as lower operating costs due to lower specific electrode and energy consumption and reduced refractory wear. To balance the rapidly fluctuating consumption of reactive power, an equally rapid compensating device is required. 3.4 Unified Power Quality Controller (UPQC) Unified power quality conditioner (UPQC) is in shunt series connection and research efforts have been ended towards utilizing UPQC in solving nearly all power quality problems such as voltage sag, voltage outage, voltage swell, over correction of power factor and unacceptable levels of harmonics in the voltage and current. Figure-3.3 illustrates the configuration of UPQC. The main principle of UPQC is to compensate for supply voltage flicker/imbalance, reactive power, negative-sequence current, and harmonics. That is, the UPQC is capable of improving power quality at the installation point on power distribution systems or industrial power systems. Thus the UPQC, considered as one of the most powerful solutions for large capacity sensitive loads to voltage flicker/imbalance. The UPQC comprises two three phase inverters which are connected in cascade that is inverter I is connected with the supply voltage in series via a transformer and inverter II is connected in parallel with the load. The shunt compensator mainly compensates for the reactive power that is demanded by the load, eliminates the harmonics and regulates the common dc link voltage. The operation of the series compensator is in PWM voltage controlled mode. The voltage is injected by it in quadrature advance to the supply voltage (current) in a way that the voltage at load end is maintained at the desired value at all times. The two inverters function in a coordinated manner. Figure-3.3: Unified Power Quality Controller 3.5. Superiority of UPQC over Other Devices The custom power devices have their own benefits and limitations. Among various devices, UPQC is considered as one of the most powerful solutions to loads of large capacity which are sensitive to supply voltage and load current disturbances. It is more flexible than any single inverter based device. UPQC can correct the unbalance and distortion at the same time in both the source voltage and load current while all other devices either correct current or voltage distortion. Thus the function of two devices is served by UPQC alone. IV. SIMULATION RESULTS The simulations of the D-STATCOM, DVR,Open UPQC and SVC Light for current harmonics, voltage harmonics and both current and voltage harmonics respectively are done in this work using Matlab. i) DSTATCOM DSTATCOM is used for the reduction of harmonics in source current. Fig 4.1 source current without and with compensation IJMER ISSN: 2249 6645 www.ijmer.com Vol. 6 Iss. 6 June 2016 63

Output waveform of the source current without compensation and with compensation is shown in Fig 4.1. In the figure the source without DSTATCOM is from 0 to 0.5 sec and after 0.5 sec the waveform with DSTATCOM is shown in which current harmonics is reduced. Fig 4.2 shows the THD analysis of the current at the source side without compensation. The THD analysis of the current at the source side after compensation is shown in fig 4.3. In this the THD is reduced from 28.31% to 0.49% as shown indicating the reduction in the current harmonics. Fig 4.2 without compensation FFT analysis of source current Fig 4.3 without compensation FFT analysis of source current ii) DVR The load voltage harmonics are reduced by using DVR. IJMER ISSN: 2249 6645 www.ijmer.com Vol. 6 Iss. 6 June 2016 64

Fig 4.4 load voltage without and with compensation In fig 4.4 the output waveform of the voltage at load side without and with compensation is shown. The figure shows the reduction in the voltage harmonics after 0.5 sec which is done by using DVR. Fig 4.5 without compensation FFT analysis load voltage Figures 4.5 and 4.6 shows the THD analysis of load voltage in which voltage harmonics are reduced from 20.62% (as in fig 4.5) to 1.99%.(as in fig 4.6) Fig 4.6 with compensation FFT analysis load voltage IJMER ISSN: 2249 6645 www.ijmer.com Vol. 6 Iss. 6 June 2016 65

iii) OPEN UPQC Using OPEN UPQC both the current harmonics and voltage harmonics are reduced thus it is more preferable device compared to DVR and DSTATCOM. Fig 4.7 Source current without and with compensation Fig 4.7 shows the waveform in which the current harmonics at source side without and with compensation is shown. Fig 4.8 without compensation FFT analysis of source current Fig 4.9 with compensation FFT analysis of source current FIG 4.8 and FIG 4.9 shows the THD analysis in which the current harmonics is mitigated from 28.49% to 0.41%. IJMER ISSN: 2249 6645 www.ijmer.com Vol. 6 Iss. 6 June 2016 66

iv) SVC Light The SVC light is similar to DSTATCOM which reduces the harmonics in source current. Fig 4.10 source current without and with compensation The output waveform form fig 4.10 shows the source current without and with compensation. Fig 4.11 without compensation FFT analysis of source current From Fig 4.11 and Fig 4.12 respectively it is clear that the total harmonic distortion without compensation is 28.51%, which is reduced to 0.53% where SVC light is connected. IJMER ISSN: 2249 6645 www.ijmer.com Vol. 6 Iss. 6 June 2016 67

Fig 4.12 with compensation FFT analysis of source current V. CONCLUSION In this paper, work has been done to compare DSTATCOM, DVR, SVC LIGHT AND OPEN UPQC. Performance analysis has been done by comparing the power quality of each compensator in Matlab Simulink. DSTATCOM is proved to compensate current levels under faulty conditions. Current harmonics has been reduced considerably. Harmonics generated at source side has THD of 28.31% which has been compensated to 0.49% at PCC. DVR is proved to compensate voltage harmonics which has been reduced considerably. Harmonics generated at load side has THD of 20.62% which has been compensated to 0.92% at load end. Even the voltage sag during fault duration has also been compensated to a desired level. SVC LIGHT is proved to compensate current harmonics at source side. Current harmonics generated at source side has THD of 28.51% which has been compensated to 0.53% at PCC. OPEN UPQC is proved to compensate current and voltage harmonics which has been reduced considerably. Current harmonics generated at source side has THD of 28.49% which has been compensated to 0.41% at PCC. Voltage Harmonics generated at load side has THD of 26.8% which has been compensated to 0.50% at load end. Comparison Of Thd s Parameter DSTATCOM DVR OPEN UPQC SVC LIGHT without with without with without with without with Source voltage V S - - 20.62 20.62 26.80 26.80 - - Source current I S 28.31 0.66 - - 28.49 0.41 28.51 0.53 Load voltage V L - - 20.62 0.92 26.80 0.50 - - Load current I L 28.31 28.31 - - 28.49 28.49 26.23 26.23 REFERENCES [1]. K. R. Padiyar, Facts Controllers in Power Transmission and Distribution, New Age International Publishers, 2007. [2]. Roger C. Dugan, Mark F. McGranaghan, Surya Santoso, and H.Wayne Beaty, Electrical Power Systems Quality, The McGraw-Hill, Second Edition, 2004. [3]. Alexander Kusko, Sc.D. and Marc T.Thompson, Power Quality in Electrical Systems, McGraw-Hill, 2007. [4]. C. Sankaran, Power Quality, CRC Press LLC, 2002. IJMER ISSN: 2249 6645 www.ijmer.com Vol. 6 Iss. 6 June 2016 68

[5]. Toshifiimi Ise, Yusuke Hayashi and Kiichiro Tsuji, Definitions of Power Quality Levels and the Simplest Approach for Unbundled Power Quality Services, IEEE Proceedings of Ninth International Conference on Harmonics and Quality of Power, Vol.2 pp:385 390, 2000. [6]. Hingorani, Introducing Custom Power IEEE Spectrum, Vol.32, No.6, pp:41-48, June 1995. [7]. Arindam Ghosh and Gerard Ledwhich, Power Quality Enhancement Using Custom Power Devices, Kluwer Academic Publishers, 2002. [8]. Angelo Baggini, Handbook of Power Quality, John Wiley & Sons Ltd, 2008. [9]. T.A.Short, Distribution Reliability and Power Quality, Taylor & Francis Group, CRC Press, 2006. [10]. Afshin Lashkar Ara and Seyed Ali Nabavi Niaki, Comparison of The Facts Equipment Operation In Transmission and Distribution Systems, 17th International Conference on Electricity Distribution Barcelona, Session No.2, Paper No.44, pp:12-15 May 2003. [11]. Juan W. Dixon, Gustavo Venegas and Luis A. Mor an, A Series Active Power Filter Based on a Sinusoidal Current- Controlled Voltage-Source Inverter IEEE Transactions on Industrial Electronics, Vol. 44, No.5, pp:612-620, October 1997. [12]. T.Devaraju, V.C.Veera Reddy and M. Vijay Kumar, Modeling and Simulation of Custom Power Devices to Mitigate Power Quality Problems International Journal of Engineering Science and Technology, Vol.26, pp:1880-1885, 2012. IJMER ISSN: 2249 6645 www.ijmer.com Vol. 6 Iss. 6 June 2016 69