VEGAFLEX 80 two-wire 4 20 ma/hart

Similar documents
Operating Instructions. Indication and adjustment module PLICSCOM

Operating Instructions 09/2013

Guided Wave Radar SITRANS LG250. Operating Instructions 03/2014. Profibus PA Coax probe

Guided Wave Radar SITRANS LG250. Operating Instructions 03/2014. Foundation Fieldbus Coax probe

Operating Instructions VEGAFLEX 81. TDR sensor for continuous level and interface measurement of liquids ma/hart two-wire. Document ID: 41824

Please enter the identity code of your device here!

Calibration Instruction Manual Emerson 475 Field Communicator. Manual Revision FC.2

Technologies, Solutions, and Applications. Guided Wave Radar for Level

Operating Instructions 11/2013

Operating Instructions

Instruction Manual ABM HART Gateway Software. Instruction Manual Revision A.1

Please enter the identity code of your device here!

Operating Instructions

Please enter the identity code of your device here!

Please enter the identity code of your device here!

Operating instructions Electronic level sensor LK / / 2008

Guided Wave Radar SITRANS LG240. Operating Instructions 03/2014. Foundation Fieldbus PFA coated rod and cable probe

Operating Instructions VEGAFLEX 81. TDR sensor for continuous level and interface measurement of liquids ma/hart - four-wire Coax probe

Operating Instructions

Description of Device Parameters Levelflex FMP5x HART

d = c 10/20/2017 Level Measurement Transmitters Applying Level Measurement p C T 273K Ultrasonic The Principle Time of Flight (TOF)

Application and Engineering Guide Levelflex FMP51, FMP52, FMP54, FMP55

User manual. paper moisture meter RH5.1 with sword-sensor

Level Measurement. Continuous level measurement - Capacitance transmitters SITRANS LC300 5/271. Overview. Configuration

Please completely read through operating instructions! Do not discard! The warranty shall be invalidated by damage caused by operating errors!

Product information. Guided Wave Radar. Level and interface measurement in liquids VEGAFLEX 81 VEGAFLEX 83 VEGAFLEX 86. Document ID: 46597

Ultrasonic level transmitter, non-contact

Xperience The Future in Level Measurements

Description of Device Parameters Levelflex FMP50, FMP51, FMP52, FMP53, FMP54, FMP55, FMP56, FMP57 FOUNDATION Fieldbus

Please enter the identity code of your device here!

Technologies, Solutions, and Applications. Magnetic Level Indication and Bridle Measurements

815LT Submersible Smart Level Transmitter

Description of Device Parameters Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56, FMR57 FOUNDATION Fieldbus

Instruction Manual. Ultrasonic and Radar

Level Measurement. Continuous level measurement Capacitance transmitters SITRANS LC300. icenta Controls Ltd

HARTR FIELD COMMUNICATION PROTOCOL

MBA PULS 400. Document ID: 36823

levelflex M FMP 40, FMP 41 C, FMP 45 with HART, PROFIBUS-PA and Foundation Fieldbus Guided Level-Radar

Operating Instructions VEGAFLEX 86. TDR sensor for continuous level and interface measurement of liquids ma/hart - two-wire. Document ID: 41844

Quick setup guide VEGAPULS 62. Radar sensor for continuous level measurement of liquids ma/hart - four-wire. Document ID: 51873

MSO Supplied with a full SDK including example programs Software compatible with Windows XP, Windows Vista and Windows 7 Free Technical Support

TEK-TROL HART GATEWAY SOFTWARE. Operating Instruction Manual.

HP 33120A Function Generator / Arbitrary Waveform Generator

Operating Instruction

Operating Instructions VEGAPULS 66

Operating Instructions VEGAPULS 61

LST400 Ultrasonic level / open channel flow transmitter

1800 Series Attachable Loop-Powered Digital Indicators Operating Manual

INSTRUCTION MANUAL FOR ULTRASONIC/MICROWAVE SENSORS

Description of Instrument Functions. Prosonic T FMU30. Ultrasonic Level Measurement BA00388F/00/EN/

Operating Instructions VEGAPULS 61

LVTX-10 Series Ultrasonic Sensor Installation and Operation Guide

Guided Wave Radar SITRANS LG270. Foundation Fieldbus Rod and cable probe C. Operating Instructions 09/2017. Siemens Parts

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks

Technologies, Solutions, and Applications. Level Switching

Temperature Measurement

ORCA-50 Handheld Data Terminal UHF Demo Manual V1.0

Proline Promass 100 HART Coriolis Flowmeter

Temperature Measurement

Operating Instructions VEGAPULS WL 61. Radar sensor for continuous level measurement of water and wastewater ma/hart - two-wire

Operating Instructions VEGAPULS 66. Radar sensor for continuous level measurement of liquids ma/hart two-wire. Document ID: 36519

Operating Instructions VEGAPULS 62

Instruction Manual Ultrasonic Level Meter Model: NUS

WCS-D5100 Programming Software for the Icom ID-5100 Data

Nico 15/30. Radar sensor for the continuous level measurement of solids. Operating Instructions. SWR engineering Messtechnik GmbH

Georg Fischer Piping Systems Point, Ultrasonic & Radar Level Products

Берг АБ Тел. (495) , факс (495) Initial operation and diagnosis

OEM radar transmitter, for aggressive media level measurement

Various Technics of Liquids and Solids Level Measurements (Part 4)

Operating Instructions VEGAPULS 68

Operating Instructions 09/2017

ABB MEASUREMENT & ANALYTICS DATA SHEET. Ultrasonic level LST400 Open channel flow transmitter

Operating Instructions

Continuous level measurement. The radar sensor for bulk solids VEGAPULS 69

TECHNICAL DOCUMENT EPC SERVO AMPLIFIER MODULE Part Number L xx EPC. 100 Series (1xx) User Manual

PhenoMaster / LabMaster Phenotyping Research Platform

LV-Link 3.0 Software Interface for LabVIEW

HZJF-9007 Fully Functional Partial Discharge Inspector USER MANUAL. Huazheng Electric Manufacturing(Baoding) Co.,Ltd

815PT Smart Pressure Transmitter

Temperature Measurement Transmitters for mounting in sensor head

Micro Motion Model 2700 Transmitters with Configurable Input/Outputs 2700***B 2700***C. Configuration and Use Manual Supplement

Operating Instructions 09/2017

Operating Instructions VEGAPULS 68

Ultrasonic level measuring device, non-contact

Please enter the identity code of your device here!

Echotel Model 338 Non-Contact Ultrasonic Two-Wire Transmitter for Level, Volume, or Open Channel Flow

The keypad is used to set the flowmeter. The function of the keys are as follows: This key selects the figures to be changed.

FlatPack Ultrasonic Sensors

Servo Indexer Reference Guide

FAST SAMPLING CONVERTER

Technologies, Solutions and Applications. Magnetic Level Indication and Bridle Measurements

Safe and reliable. Level and pressure instrumentation for the process industry

PROGRAMMING MANUAL For SCA-3!!-4 models with HART

WHITE PAPER HOW TO SELECT A CONTINUOUS LEVEL SENSOR BINVENTORY. Jenny Christensen Todd Peterson. BinMaster

Network Analyzer for Low-, Medium- and High-Voltage Networks

Micro IRHD Laser revolution

1000TR. Instructions

PHG 70 TD PD / PHG 80 TD PD

Ultrasonic Level Sensor LUC-M** with HART/4 ma ma and PROFIBUS PA

Operating Instructions

Transcription:

VEGAFLEX 80 two-wire 4 20 ma/hart.3.0 2/206 Function extensions New functions and modifications: Bulk solids applications Standard deactivation of the automatic false signal suppression Standard deactivation of the measurement via probe end with Medium/Dielectric constant "Granules, powder, cement/.5 3 and "Dusts, powder, wood chips/ <.5 Sensitivity increased at 5 mv with Medium/Dielectric constant "Granulates, powder, cement/.5 3 in the close range Optimizations for applications with short measuring ranges/probes 0.4 m New option "False signal suppression with uncovered probe Optimization of the measuring cycle time Reduction of the track number Optimization of the overfill recognition so that overfillings above the sensor reference point are apparent To avoid errors during the setup of an interface application, the possibility of a common adjustment or scaling was removed Instrument function in general: Optimization of the start behaviour PLICSCOM: During the sensor start and with operating sensor, the sensor TAG and the version information are no longer displayed on PLICSCOM. Due to this, the measured value is displayed approx. 0 s earlier. The version information is in the menu item "Info" The current output is set by default to "Fix current(4 ma) if HART address 0 is selected Adaptation of the adjustment structure to the standardized VEGA adjustment structure variable positions after the decimal point for the display value Introduction of additional Common Practice Commands CMD 33 Write Variable CMD 36 Set Primary Variable Upper Range Value CMD 37 Set Primary Variable Lower Range Value CMD 40 Enter/Exit Fixed Current Mode CMD 42 Perform Reset CMD 45 Trim Loop Current Zero CMD 46 Trim Loop Current Gain CDM 47 Write Primary Variable Transfer Function CMD 50 Read Dynamic Variable Assignements CMD 5 Write Dynamic Variable Assignements CMD 53 Write Variable Units CMD 54 Read Variable Information CMD 79 Write Variable 3 VEGAFLEX 80_2L HART_Gerätesoftware_Versionshistorie_629_EN_SW009.docx Page of 9

Additional Variables are now supported by the following Common Practice Commands CMD 34 Write PV Damping Value CMD 43 Set PV Zero For level applications in which the dielectric constant cannot be determined and the HART diagnosis displays an err, this diagnosis can be deactivated via special parameter 23. Then the set dielectric constant is outputted When reset "Delivery status" is executed, the "Echo curve of the setup" was not deleted With instruments with customer-specific instrument setting it sometimes happened that after a reset "Delivery status" the parameters depending on the application setting were not disintegrated correctly and remained in a status as after a reset "Basic adjustment" When using the PLICSCOM function "Copy instrument settings, the special parameters 37 and 38 were not copied The selection of the time format 24/2 hours was not translated correctly in the Spanish language Wrong presentation of the sensor name in Russian language The first operation of the instrument via PLICSCOM caused the entry "Plicscom_VU8.FirstContactEnable in the parameter modification memory Brief deactivation of PLICSCOM with hardware version..0 corrected while starting the sensor Deactivation of the echo curve memory with a terminal voltage < 2 V, for a higher stability with lower supply voltage EMC optimization of the communication to PLICSCOM Error message F26/4004 is set during the sensor start when min. and max. adjustment are identical When allocating the scaled value for the current output, wrong values could be generated while converting distance units of the adjustment which caused a faulty loop current CMD0 returns now UpdateFailure as long as the previous changes have no effect in the sensor CMD 35 and CMD 44 generated entries in the parameter modification memory, even if there were no changes While executing the reset "Basic adjustment" not all HART enquiries were answered Faulty Global Status with active simulation/ Fixed Current Mode and parallel HART communication was corrected.2. /205 For the application "Interface without gas phase (vessel and 2 VEGAFLEX 80_2L HART_Gerätesoftware_Versionshistorie_629_EN_SW009.docx Page 2 of 9

bypass/standpipe)", a device offset was not taken into account which caused a wrong measured value while correcting through the dielectric constant. Linearization level measurement: When using the following linearizations: Cylindrical tank Spherical tank Venturi, trapezoidal weir, rectangular weir Palmer-Bowlus-Flume V-Notch User-programmable In combination with an adjustment from the basic settings, a measured value deviation iof the linearized percentage value is caused after a restart. Due to this, there is a wrong current if the linearized percentage value was assigned to the current output as output variable. Linearization interface: When using the following linearizations: Cylindrical tank Spherical tank Venturi, trapezoidal weir, rectangular weir Palmer-Bowlus-Flume V-Notch User-programmable In combination with two separate adjustments for level and interface, the linearized level value of the instrument is wrong after a restart, the lin. interface value is correct. During operation, always the output value is wrong which was not modified. Instrument software, in general: Error corrected when loading a corrupt delivery status HART communication: While enquiring unsupported Variables via HART Command 9, the sensor answered with error status "Invalid Selection instead delivering the special value "Not-A-Number. While reading out the dynamic variables via HART Command 9, the delivered codes of the measured values do not correspond to the dynamic variables but to the Variables.2.0, 04/205 Function extensions New functions and modifications: Optimization of the interface measurement Easier adaptation to the application Selection of the next, larger or last echo as interface Unit change of the reliability from % to unit mv Introduction of new probe types: 4 mm cable probe Coax probe 2 x 6 mm for 250 C applications Assistant to determine the dielectric value in bulk solids applications with dust/powder/wood chips 2 VEGAFLEX 80_2L HART_Gerätesoftware_Versionshistorie_629_EN_SW009.docx Page 3 of 9

Detection threshold for bypass/standpipe applications increased Treatment of the freely suspended gravity weight echo Sensor outputs probe length and not gravity weight begin Optimization of high temperature probes with reference Temperature offset reference to product cannot be configured Introduction of the sensor unit "inch" PLICSCOM operation: Adaptation of the adjustment structure to the standardized VEGA adjustment structure Additional menu languages: Turkish, Czech and Polish Lighting on as default setting Enquiry of the language setting when switching on the sensor for the first time Optimization of the transmission times (e.g. of echo curves) Introdcution of additional Common Practice Commands CMD 34 Write Primary Variable Damping Value CMD 35 Write Primary Variable Range Values CMD43 Set Primary Variable Zero CMD44 Write Primary Variable Units Introduction Burst Mode acc. to HART 5 Regulation device offset in case of moisture optimized on the coupling or deactivated in case of couplings with PEEK material Basic setting "Demonstration" adapted for tests and presentations Open focussing range Reduced noise suppression Focussing range interface on the probe end completely open backwards Calculation of the reference line adapted Threshold detection probe end with high temperature probes with reference reduced Error while storing switching off times removed Various fault rectifications:..5, 09/204 Error in the compensation of the spreading speed (concerns only instruments with reference distance). The error caused a considerable measurement error as well as an appropriate diagnosis message. Parameters which only depend on the probe length and probe type do not block the application. Hence these are newly written with a restart of the instrument when dissolving the probe dependence. A manual parameter adjustment will get lost. VEGAFLEX 80_2L HART_Gerätesoftware_Versionshistorie_629_EN_SW009.docx Page 4 of 9

In the quick setup assistant, the dielectric figure was enquired with level applications..3, 04/204 Optimization of the signal processing with: Level measurement statically and dynamically Adaptation of the detection thresholds for different probes and applications, for example interface Process SIL and non-sil measurement function standardized Improvement of the measurement accuracy of negative echoes Function first large echo with interface can be activated Determination of the dielectric figure value also possible without movement Safeties on the probe end with high temperature probes with reference optimized Reduction of the threshold for the cancellation of the limited decision range Automatic probe length determination Improved accuracy Probe length determination with positive probe end Fault signal echo loss was not effective with probe end tracking Sensor does not indicate empty with empty vessel and active probe end measurement Ceramic spacers with high temperature coax probes caused a slope error and the accuracy was not maintained, spacers are now compensated Empty signal with freely suspended cable Min. amplitude introduced for water sump Limitation of the measured value to the probe length Reduction of the safety when creating a gating out of false signals Dielectric figure value was not taken over into the sensor after calculation through the assistant Dielectric figure value could not be edited with locked aplication Adaptation of the application settings for probes with centering weight Simulation is now also possible when the instrument is in failure mode Message 8 "Automatic profile was updated filled the event memory during operation. Message will no longer be entered Output of the echo information for test certificates was provided in the unit "db" without positions after the comma, now in the unit mv Search range for cable breakage/probe loss could be invalid with short probes After the probe length determination, a previously activated measuring range limitation became inactive VEGAFLEX 80_2L HART_Gerätesoftware_Versionshistorie_629_EN_SW009.docx Page 5 of 9

Focussing range did not stop at the probe end and did not open backwards Total level could be behind the interface with interface measurement Probes with centering weight were only in the bypass When restarting with an integration time unequal 0 s, the current value corresponded to the level or interface value only after the integration time With electronics temperatures outside the limits (-40 C, +80 C), no message S600 was outputted Current value remained with an application change from interface to level when the interface value was assigned to the current output; now fault message F264 is outputted Interference current "> 2 ma increased from 2.5 ma to 2.7 ma With little energy, now the external enquiries are delayed so that the sensor does not crash Adjusted units were not taken into account for the configuration of the echo curve memory recordings After a rest Basic settings in the application Interface, the device identification remains on Interface (although the application was reset to Level); this caused problems in the PLICSCOM menu as well as with VEGAMET Various fault rectifications: After a restart when HART Secondary Value was assigned to the electronics temperature or the measurement reliability, the sensor switched the fault F26/207 The flag "Non PV Out of Limits" must only refer to the dynamic variables SV, TV and QV (instead to all variables)..2, 09/203 Reset could no longer be carried out successfully on instruments with longer operating time System time is only stored in the 0 minute time pattern.., 04/203 Rectification of device status F040/8000. Monitoring internal reference point of the electronics changes from 0.8 2.8 m to 0.25 2.8 m. Automatic false signal suppression with interface measurements and with probes smaller than 0.5 m deactivated..0, 03/203 Function extensions New functions and modifications: VEGAFLEX 80_2L HART_Gerätesoftware_Versionshistorie_629_EN_SW009.docx Page 6 of 9

Compensation of the measurement error and occurring false echoes by condensation on the coupling Improvement of the accuracy by measurement without safety on the false signal suppression With coax probes cm safety on the factory false signal suppression With rod and cable probes cm safety on the manual or automatic false signal suppression Support of the second current output added PLICSCOM operation: Quick setup added Conversion of the menu level "Setup" Release special parameter for hour after entering the password Key query optimized The function water sump was active with interface measurement without superimposed gas phase. This could cause up measurement jumps With Application/Medium <.5 an empty signal was triggered with low level Pitch error with cable 4 mm liquid of -0.0 % removed After a waiting period, the measured value is now set to 0 m together with the status overfilling (previously the measured value was set to 0 m before the waiting time) Set measured value status for interface measured value to invalid if the application is set to Level Error correction with max. cable length with I²C connection Negative electronics temperature was displayed with wrong signs The sensor TAG could not be set correctly with HART command 8.0., 0/202 Error correction of the first production version New functions and modifications: Input filter of the concentric tube added to reduce EMC interferences Detection filter added to reduce the number of echoes in a search area. Filter only active with bulk solid In shipping status, the following measured values are now recorded in the measured value memory of the sensor: Distance, percentage value, VEGAFLEX 80_2L HART_Gerätesoftware_Versionshistorie_629_EN_SW009.docx Page 7 of 9

reliability, Electronics temperature, Dielectric constant Recording based on: Percentage value with measured value difference 5 % Time pattern 3 min. Error correction on the limits of the detection range. Echoes cut off too early Error correction when generating a reference line from a profile in the close range Incorrect course of the reference line in the first centimetres Steam pressure compensation/reference probe did not function Error correction of the compensation with reference probes and application interface and no superimposed gas phase Spreading correction for the coated probes was modified in such a way that the error was minized within the first 5 m Activation of the function st large echo, now a new decision to level is made Only probe lengths up to 74.3 m could be used. Now up to 75 m Measured value arrow in the echo curve presentation jumped to internal reference (in front of 0 m) With invalid echo and no valid dielectric figure The dielectric figure was outputted as measured value before it could be measured reliably Event 84/20700 is no longer stored in the event memory Parameter units were not displayed correctly in the parameter modification memory Echo curve memory based on events was incorrect With the partial transmission of the measured value memory, the dates of the measured values were not correct Italian translation was wrong Current output adjustment values were exchanged Dielectric figure had only one position after the comma. Now 3 Error correction for certification test DLL00.0.0, 07/202 First version New functions and modifications relating to VEGAFLEX 60: Increased accuracy Increased repetition rate Increased sensitivity by probe end tracking Extension with application parameter adjustment Automatic update of the false signal suppression Probe loss detection added Measured values can be configured for the current output VEGAFLEX 80_2L HART_Gerätesoftware_Versionshistorie_629_EN_SW009.docx Page 8 of 9

Running time correction with steam boiler application Determination of the dielectric figure added Lower supply voltages possible status according to NE 07 Event memory added Function extension for the measured value memory Real time clock added Modification of the menu structure Modification of the layout with value changes The following languages are : German English French Spanish Russian Italian Dutch Portuguese Japanese Chinese HART Revision 7 HART measured values can be configured Legend: Name Version Compatibility version.function extension version.error correction version Month/Year Version number of the instrument defined by HART. Consecutive integral number Will be increased if in the "Application Layer" modifications were carried out, e.g. new commands, modifications in the data structure in a command VEGAFLEX 80_2L HART_Gerätesoftware_Versionshistorie_629_EN_SW009.docx Page 9 of 9