RE22R2MYMR Multi-function Timing Relay s 300h V AC/DC - 2C/O

RENF22R2MMW Zelio Timer Relay - Modular

RE22R2MMU Multifunction Timer Relay - 24VDC/ V AC - 2 C/O

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RMMW time delay relay 10 functions - 1 s..100 h V AC/DC - 1 OC

RE17RMMW time delay relay 10 functions - 1 s..100 h V AC/DC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RMMW time delay relay 10 functions - 1 s..100 h V AC/DC - 1 OC

RE11RMMU time delay relay 10 functions - 1 s..100 h V AC - 1 OC

RE17RMMU time delay relay 10 functions - 1 s..100 h V AC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

RE17LLBM asymmetrical flashing relay s V AC - solid state output

RE7MY13MW time delay relay 8 functions s V AC DC - 2OC

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC

RE7CP13BU adjustable symmetrical flashing relay s - 24 V AC DC - 2OC

RE7RL13BU off-delay timing relay with control contact s - 24 V AC DC - 2OC

RE7TP13BU adjustable on-delay timing relay s - 24 V AC DC - 2OC

ZBRRA Programmable receiver - 2 relays V AC/ DC - 2 pusbuttons - 6 LEDs

RXG21BD interface plug-in relay - Zelio RXG - 2 C/O standard - 24V DC - 5A - with LTB

RE Product data sheet Characteristics. universal plug-in timing relay V AC - 1 C/O. Main. Complementary. Discrete output type

08/07/2015

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

LC2D09BD. Main. Device short name. Utilisation category. Poles description Pole contact composition

08/07/2015

ATS01N206QN soft starter for asynchronous motor - ATS01-6 A V KW

02/11/2015

22/10/2012

LC2D09BL REVERSING CONTACTOR 575VAC 9A IEC

05/09/2012

LC1D25BL TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 24 V DC coil

PART NUMBERING SYSTEM

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

Electronic timer CT-MFS.21

RXG12BD interface plug-in relay - Zelio RXG - 1C/O standard - 24VDC-10A-with LTB and LED

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

Electronic timer CT-SDD.22

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

02/11/2015

02/11/2015

PART NUMBERING SYSTEM

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

LC1D12BL TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V DC coil

ATS01N125FT soft starter for asynchronous motor - ATS01-25 A V KW

ATS01N112FT soft starter for asynchronous motor - ATS01-12 A V KW

Electronic timer CT-SDS.22

27/04/2015

02/11/2015

LC1D12BD TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V DC coil

Multi-voltage Multi-function. Wiring diagram (without control signal)

LC1D32BD TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 24 V DC coil

Zelio Control Measurement Relays

02/11/2015

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

LC1D32ED TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 48 V DC coil

Electronic timer CT-MBS.22 Multifunctional with 2 c/o (SPDT) contacts

ATS01N103FT soft starter for asynchronous motor - ATS01-3 A V KW

Electronic timer CT-TGD.22

Electronic timer CT-MFS.21 Multifunctional with 2 c/o (SPDT) contacts

83 Series - Modular timers 16 A. Features

Electronic timer CT-MFS.21 Multifunctional with 2 c/o (SPDT) contacts

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

24/07/2012

Electronic timer CT-SDE Star-delta change-over with 1 n/c + 1 n/o contact

Electronic timer CT-WBS.22 Impulse generating and flashing with 2 c/o (SPDT) contacts

11/03/2013

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

Electronic timer CT-MVS.12 Multifunctional with 1 c/o (SPDT) contact

83 SERIES. 83 Series - Modular timers A. Features

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

Multi-voltage Multi-function. BE: Off-delay with control signal BE: Off-delay with control signal CE: On- and off-delay with control signal

ATS01N206QN soft starter for asynchronous motor - ATS01-6 A V KW

ATS01N222LU soft starter for asynchronous motor - ATS01-22 A V KW

ZBRT2 double actions (up/down) transmitter for wireless and battery less pushbutton

Electronic timer CT-EBE Flasher starting with OFF, 1 c/o (SPDT) contact

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

Current monitoring relays CM-SRS.M1 For single-phase AC/DC currents

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

ATSU01N232LT soft starter for asynchronous motor - ATSU01-32 A V KW

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

ATSU01N222LT soft starter for asynchronous motor - ATSU01-22 A V KW

Modular timers A

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

Type CP-S, CP-C & CP-A Switch mode


CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

Multi-function (MI, ME, M2, M1) 2 NO (2 SPST-NO) 12 / / 400 3,000 1, / 0.3 / (5 / 5) AgNi

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Multi-function 11 pin Plug-in for use with 90 series sockets

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

ATS22C21Q soft starter-ats22-control 220V-power 230V(55kW)/ V(110kW)

LXM32CD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

ATV212HU22M3X variable speed drive ATV kW - 3hp - 240V - 3ph - wo EMC - IP21

Transcription:

Product datasheet Characteristics RE22R2MYMR Multi-function Timing Relay - 0.05s 300h - 24 240V AC/DC - 2C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Zelio Time Modular timing relay Relay RE22 8 A Complementary Contacts type and composition Time delay type Time delay range Control type [Us] rated supply voltage Input voltage Voltage range 1 C/O timed or instantaneous contact, cadmium free 1 C/O timed or instantaneous contact, cadmium free 2 C/O timed contact, cadmium free A At Aw C D Di H Ht Qg Qt W Ct Dw Hw Wt Dt Dit Diw Qgt Qtt Qgw Qtw 0.3...3 s 1...10 s 0.05...1 s 3...30 s 10...100 s 30...300 s 3...30 min 30...300 min 3...30 h 30...300 h Rotary knob Diagnostic button External potentiometer 24...240 V AC/DC at 50/60 Hz <= 2.4 V 0.85...1.1 Us Supply frequency 50...60 Hz (+/- 5 %) Connections - terminals Screw terminals : 1 x 0.5...1 x 3.3 mm², AWG 20...AWG 12 solid cable without cable end Screw terminals : 2 x 0.5...2 x 2.5 mm², AWG 20...AWG 14 solid cable without cable end Screw terminals : 1 x 0.2...1 x 2.5 mm², AWG 24...AWG 14 flexible cable with cable The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. 1 / 12

Tightening torque 0.6...1 N.m conforming to IEC 60947-1 Housing material end Screw terminals : 2 x 0.2...2 x 1.5 mm², AWG 24...AWG 16 flexible cable with cable end Self-extinguishing Repeat accuracy +/- 0.5 % conforming to IEC 61812-1 Temperature drift Voltage drift +/- 0.05 %/ C +/- 0.2 %/V Setting accuracy of time delay +/- 10 % of full scale at 25 C conforming to IEC 61812-1 Minimum pulse duration 30 ms 100 ms (with load in parallel) Insulation resistance 100 MOhm at 500 V DC conforming to IEC 60664-1 Reset time Immunity to microbreaks Power consumption in VA Power consumption in W Switching capacity in VA Minimum switching current Maximum switching current Maximum switching voltage Electrical durability Mechanical durability 120 ms (on de-energisation) <= 10 ms 3 VA at 240 V AC 1.5 W at 240 V DC 2000 VA 10 ma 5 V DC 8 A 250 V AC 100000 cycles for 8 A at 250 V AC-1 100000 cycles for 2 A at 24 V DC-1 10000000 cycles [Uimp] rated impulse withstand voltage 5 kv for 1.2...50 µs conforming to IEC 60664-1 Delay response < 100 ms Creepage distance 4 kv/3 conforming to IEC 60664-1 Overvoltage category III conforming to IEC 60664-1 Safety reliability data Mounting position MTTFd = 171.2 years B10d = 160000 Any position Mounting support 35 mm DIN rail conforming to EN/IEC 60715 Status LED Width Product weight Green LED backlight (steady) for dial pointer indication Yellow LED (steady) for output relay energised Yellow LED (fast flashing) for timing in progress and output relay de-energised Yellow LED (slow flashing) for timing in progress and output relay energised 22.5 mm 0.105 kg Environment dielectric strength standards IEC 61812-1 UL 508 directives product certifications 2.5 kv for 1 ma/1 minute at 50 Hz between relay output and power supply with basic insulation conforming to IEC 61812-1 2004/108/EC - electromagnetic compatibility 2006/95/EC - low voltage directive CCC CE CSA GL UL RCM EAC China RoHS ambient air temperature for operation -20...60 C ambient air temperature for storage -40...70 C IP degree of protection IP20 (terminals) conforming to IEC 60529 IP40 (housing) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529 pollution degree 3 conforming to IEC 60664-1 vibration resistance 20 m/s² (f = 10...150 Hz) conforming to IEC 60068-2-6 shock resistance 15 gn (not operating) (duration = 11 ms) conforming to IEC 60068-2-27 2 / 12

relative humidity 95 % at 25...55 C electromagnetic compatibility 5 gn (in operation) (duration = 11 ms) conforming to IEC 60068-2-27 Fast transients immunity test (test level: 1 kv, level 3 - capacitive connecting clip) conforming to IEC 61000-4-4 Surge immunity test (test level: 1 kv, level 3 - differential mode) conforming to IEC 61000-4-5 Surge immunity test (test level: 2 kv, level 3 - common mode) conforming to IEC 61000-4-5 Electrostatic discharge (test level: 6 kv, level 3 - contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge (test level: 8 kv, level 3 - air discharge) conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test (test level: 10 V/m, level 3-80 MHz...1 GHz) conforming to IEC 61000-4-3 Conducted RF disturbances (test level: 10 V, level 3-0.15...80 MHz) conforming to IEC 61000-4-6 Fast transient bursts (test level: 2 kv, level 3 - direct contact) conforming to IEC 61000-4-4 Immunity to microbreaks and voltage drops (test level: 30 % - 500 ms) conforming to IEC 61000-4-11 Immunity to microbreaks and voltage drops (test level: 100 % - 20 ms) conforming to IEC 61000-4-11 Offer Sustainability Sustainable offer status RoHS (date code: YYWW) REACh Product environmental profile Product end of life instructions Green Premium product Compliant - since 1520 - Schneider Electric declaration of conformity Reference not containing SVHC above the threshold Available Available Contractual warranty Warranty period 18 months Dimensions Wiring Diagram Function A: Power On-Delay 3 / 12

On energisation of power supply, the timing period T starts. After timing, the output(s) R close(s).the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function At: Power On-Delay with Pause / Summation Control On energisation of power supply, the timing period T starts.timing can be interrupted / paused each time X1 energizes.except for RE17*, RE22R2AMU, RE22R2MMW, RE22R2MMU, RE22R2MJU, timing can be interrupted / paused each time Y1 energizes.when the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R close(s).the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). with Pause / Summation Control with Pause / Summation Control with Retrigger / Restart Control with Retrigger / Restart Control Function Aw : Power On-Delay With Retrigger / Restart Control 4 / 12

On energisation of power supply, the timing period T starts.at the end of the timing period T, the output(s) R close(s).energization of Y1 makes the output(s) R open(s).deenergization of Y1 restarts timing period T.At the end of timing period T, the output(s) R close(s).the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST") Function C: Off-Delay Relay with Control Signal After energisation of power supply and energization of Y1 causes output(s) R close(s). When Y1 deenergizes, timing T starts.at the end of this timing period T,the output(s) R revert(s) to its/their initial position.the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function Ct: Off-Delay Relay with Control Signal & With Pause / Summation Control After energisation of power supply and energization of Y1 cause output(s) R close(s).when Y1 deenergizes, timing starts and the timing can be interrupted / paused each time X1 energizes. When the cumulative total of time periods elapsedreaches the pre-set value T, the output(s) R revert(s) to its/their initial state.the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). 5 / 12

Function D: Symmetrical Flashing Relay (Starting Pulse Off) On energisation of power supply, output(s) R starts at its/their initial state for timing duration T then change(s) to output(s) R close(s) for the same timing duration T.This cycle is repeated indefintely until power supply removal.specially for RE17*, RE22R2AMU, RE22R2MMW, RE22R2MMU, RE22R2MJU,this D function can only be initiated by energizing Y1 permanently.the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). with Retrigger / Restart Control Function: 2 Output with Retrigger / Restart Control Function Dt: Symmetrical Flashing Relay (Starting Pulse Off) & With Pause / Summation Control On energisation of power supply, output(s) R starts at its/their initial state for timing duration T and the timing can be interrupted / paused each time X1 energizes.when the cumulative total of time periods elapsed reaches the pre-set value T, then changes to output (s) R close(s).the output(s) R close state will remain for the same timing duration T and the timing can be interrupted / paused each time X1 energizes.when the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R revert(s) to its/their initial state.this cycle is repeated indefintely until power supply removal.the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). 6 / 12

t'1 + t'2 + t'1 + t'2 + Function DW: Symmetrical Flashing Relay (Starting Pulse Off) & With Retrigger / Restart Control On energisation of power supply, output(s) R starts at its/their initial state for timing duration T then change(s) to output(s) R close(s) for the same timing duration T.This cycle is repeated indefintely until power supply removal.specially for RE17*, RE22R2AMU, RE22R2MMW, RE22R2MMU, RE22R2MJU,this D function can only be initiated by energizing Y1 permanently.the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function Di: Symmetrical Flashing Relay (Starting Pulse On) On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T then revert(s) to its/their initial state for the same timing duration T.This cycle is repeated indefintely until power supply removal.the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function Dit: Symmetrical Flashing Relay (Starting Pulse On) & With Pause / Summation Control 7 / 12

On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T and the timing can be interrupted / paused each time X1 energizes.when the cumulative total of time periods elapsed reaches the pre-set value T, then revert(s) to its/their initial state.the output(s) R at initial state will remain for the same timing duration T and the timing can be interrupted / paused each time X1 energizes.when the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R change(s) to close state.this cycle is repeated indefintely until power supply removal.the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). t'1 + t'2 + t'1 + t'2 + Function Diw: Symmetrical Flashing Relay (Starting Pulse On) & With Retrigger / Restart Control On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T then revert(s) to its/their initial state for the same timing duration T.This cycle is repeated indefintely until power supply removal.at any state of the output(s) R when Y1 energizes, the output(s) R will revert to its/their initial state and followed by Y1 deenergizes then restarts the same operation as described at the beginning.the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function H: Interval Relay On energisation of power supply, output(s) R close(s) and timing period T starts.at the end of the timing period T, the output(s) R revert (s) to its/their initial state.the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). 8 / 12

Function Ht: Interval Relay & With Pause / Summation Control On energisation of power supply, output(s) R close(s) and timing period T starts.the timing can be interrupted / paused each time X1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R revert(s) to its/their initial statereenergization of X1 will also cause output(s) R close(s) if the time has elapsed and restart the same operation as described at the beginning.except for RE17*, RE22R2AMU, RE22R2MMW, RE22R2MMU, RE22R2MJU, timing can be interrupted / paused each time Y1 energizes.the second output (R2) can be either timed (when set to "TIMED" or instantaneous (when set to "INST"). with Retrigger / Restart Control Function: 2 Output with Retrigger / Restart Control Function Hw: Interval Relay & with Retrigger / Restart Control On energisation of power supply, output(s) R close(s) and timing period T starts.at the end of the timing period T, the output(s) R revert (s) to its/their initial state.at any state of the output(s) R when Y1 energizes followed by deenergizes, the output(s) R close(s) then restarts the same operation as described at the beginning.the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). 9 / 12

Function Qg: Star-Delta Relay (2 CO with same Common) On energisation of power supply, the output R3 closes such that energizes STAR CONTACTOR + MAIN CONTACTOR and the timing T starts (STAR connection time duration starts).at the end of the timing period T, the output R3 reverts to its initial state such that deenergizes STAR CONTACTOR and causes t transition time starts.at the end of the transition time, the output R4 closes such that energizes DELTA CONTACTOR. t : 20, 40, 60, 80, 100, 120, 140 ms Function Qgt: Star-Delta Relay (2 CO with same common) with Pause / Summation Control On energisation of power supply, the output R3 closes such that energizes STAR CONTACTOR + MAIN CONTACTOR and the timing T starts (STAR connection time duration starts).during STAR connection time, the timing can be interrupted / paused each time X1 energizes.when the cumulative total of time periods elapsed reaches the pre-set value T, R3 reverts to its initial state such that deenergizes STAR CONTACTOR and causes t transition time starts.at the end of the transition time, the output R4 closes such that energizes DELTA CONTACTOR. NOTE: RE22R2MYMR is with fixed transition time, t: 50ms Function Qt: Star-Delta Relay (2 CO with Split Common) On energisation of power supply, the output R3 & R4 initializes at its initial state such that energizes STAR CONTACTOR + MAIN CONTACTOR and the timing T starts (STAR connection time duration starts).at the end of the timing period T, the output R3 closes such that deenergizes STAR CONTACTOR and causes t transition time starts.at the end of the transition time, the output R4 closes such that energizes DELTA CONTACTOR. t : 20, 40, 60, 80, 100, 120, 140 ms 10 / 12

Function Qtt: Star-Delta Relay (2 CO with same common) with Pause / Summation Control On energisation of power supply, the output R3 & R4 initializes at its initial state such that energizes STAR CONTACTOR + MAIN CONTACTOR and the timing T starts (STAR connection time duration starts).during STAR connection time, the timing can be interrupted / paused each time X1 energizes.when the cumulative total of time periods elapsed reaches the pre-set value T, the output R3 closes such that deenergizes STAR CONTACTOR and causes t transition time starts.at the end of the transition time, the output R4 closes such that energizes DELTA CONTACTOR. NOTE: RE22R2MYMR is with fixed transition time, t: 50ms Function W: Interval Relay with Control Signal Off After energisation of power supply and on energization of Y1 following by denergization of Y1, the output(s) R close(s) and starts the timing T.At the end of the timing period, the output(s) R revert(s) to its/their initial state.the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function Wt: Interval Relay with Control Signal Off & with Pause / Summation Control After energisation of power supply and on energization of Y1 following by denergization of Y1, the output(s) R close(s) and starts the timing T.Timing can be interrupted / paused each time X1 energizes.when the cumulative total of time periods elapsed reaches the preset value T, the output(s) R revert(s) to its/their initial state.the second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). 11 / 12

Legend Relay de-energised Relay energised Output open Output closed U - Supply R1/R2 2 timed outputs - Ta - Adjustable On-delay Tr - Adjustable Off-delay X1 - Pause / Summation control Y1 - Retrigger / Restart control X2 - Function Selection R2 The second output is instantaneous if the right position is selected inst. - T - Timing period R4 - Delta contact output t - Delay to switch ON Delta contact output R3 - Star-Delta contact output 12 / 12