Company Replaces previous document Document ID Issue E.ON Energidistribution AB Ny engelsk utgåva D

Similar documents
Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

Onsite Mobile AC High Voltage Test System

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

Miniature circuit breakers. Residential current circuit breakers. Busbar systems. Comfort functions/energy control. Residential enclosures

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Electronic circuit breaker ESS30-Sxxx-DC24V

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

INTERNATIONAL STANDARD

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

Electronic Circuit Breaker ESS20-0..

PHOENIX CONTACT

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC

Capacitor Switching Contactors

page 2 of 86 Report reference No:

MINISTRY OF ELECTRICITY

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

Series P. Applications

11/0 IZM circuit-breakers, IN switch-disconnectors

Technical catalogue. Emax Low voltage air circuit-breakers. Hotline:

3 - Protection components Circuit-breakers

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

LYRA 501 USER S MANUAL

Miniature circuit-breakers S 280 UC series. System pro M. Technical data

Distribution/Substation Transformer

INTERPLANT STANDARD - STEEL INDUSTRY

EH2741 Communication and Control in Electric Power Systems Lecture 2

NEMA Contactor and Starter Specifications

Substation Preventive Maintenance

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

Electronic Circuit Breaker with reset input ESS20-1..

CB Testing Laboratory...:EZÚ Address...:Pod Lisem Praha71-Trója Testing location/ procedure...: CBTL RMT SMT WMT TMP IEC60947_2C

DIGITAL DUAL DISPLAY AC/DC CLAMP METER MODEL-860A OPERATION MANUAL

Documents and Addresses

C 1. SPECTRONIC SP - Air circuit breakers. Summary. C.3 General characteristics. C.4 Fixed circuit breaker. C.5 Withdrawable circuit breakers

For Immediate Delivery call KMParts.com at (866)

Type VDG 13 Undervoltage Relay

Open Type Without Enclosure

NZ7. NZ7 Automatic Transfer Switching Equipment. 2. Type designation. 1. General. 3. Operation conditions N Z 7- /

SIRCO M UL98 Load break switches standards UL and CSA 30 to 100 A

PHOENIX CONTACT

Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12

(1,5 modules per pole)

Electronic Circuit Breaker ESS1 for System SVS1

Harmonic restraint earth fault or single-phase overcurrent protection

Protection relays and transformers

8PK-ST1520 Digital Earth Resistance Tester

FL ballasts Electronic dimming. PCA T8 ECO lp Y II, W ECO T8

Time over/underfrequency relay with protection assemblies

TORKEL 900-series Battery Load Unit

EC centrifugal fan - RadiCal

Arc Suppression Coils

SECTION AUTOMATIC TRANSFER SWITCH

TORKEL 900-series Battery Load Unit

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

SPTO 1D2. Control module SPAC 3 C. User s manual and Technical description. U aux V _ V _. f n SPTO 1D2. I n = 1 / 5 A( I o)

Phase and neutral overcurrent protection

TVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active

1% Switchgear and Substations

AC axial compact fan

Modeion OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS

ET 40 - Electrician Theory Examination Marking Schedule

EC centrifugal fan - RadiCal

FL ballasts Electronic dimming. PCA T8 ECO lp Y, 3x18 W and 4x18 W ECO T8

NIPSCO Energy Symposium

Switchgear Type SIMOSEC up to 24 kv, Air-insulated, Extendable

Medium voltage circuit breaker technical guide

Smart Power Relay E I...

X-band Magnetron. Cooling (note 5) Water Output coupling (note 6) UG51/U Magnet (note 7) Integral, Permanent

OPTOTRONIC Intelligent

EC centrifugal fan - RadiCal

TS RES - OUTSTANDING ISSUES

ELE-CMOS-E-2001 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

AC axial compact fan

Power Distribution System SVS18

PCA ECO lp Y, W T8 fluorescent lamps

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads)

General Technical Specifications of Frequency Converters for Tokyo-Chubu Interconnection Project

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

EC centrifugal fan - RadiCal

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

AC centrifugal fan. R2E180-AS backward curved, single inlet. Nominal data

DRIVIA cabinets LIMOGES Cedex France 1. DESCRIPTION, USE 3. DIMENSIONS 2. RANGE, CAT. NO. EQUIVALENCE TABLE

Room Temperature Controllers. for heating and cooling systems

Auxiliary Contact (10 600V) Auxiliary Contact (10 5V DC)

MG6090 Tunable S-Band Magnetron

EARTH RESISTANCE TESTER

TECHNICAL SPECIFICATIONS for 300KV CONSTANT POTENTIAL X RAY EQUIPMENT (for industrial applications) S. No. PARTICULARS BHEL SPECIFICATIONS

X band Magnetron. Water: Anode cavity Forced-air: Input ceramics and terminals Output coupling (note 6) UG51/U Magnet (note 7) Integral, Permanent

VI 3 - i TABLE OF CONTENTS

Power Processor - Series 700F 10KVA to 150KVA

Portable equipment for insulation fault location for unearthed and earthed systems (IT and TN systems) to be used in conjunction with or without an

ELECTRICAL POWER TRANSMISSION TRAINER

Transcription:

Document type Page Verksamhetsstyrande 1 (9) Company Replaces previous document Document ID Issue E.ON Energidistribution AB Ny engelsk utgåva D17-0008995 3.0 Organisation Valid from Valid until Regionnätsaffärer 2018-08-08 Responsible for the document Secrecy class Approved by Claes Ahlrot Öppen Roger Appelberg Title Technical requirements Circuit breakers and disconnectors 1 General...3 1.1 Scope...3 1.2 Standards...3 1.3 Labelling...3 2 Changes relative to previous issue...3 3 Electrical and mechanical requirements...4 3.1 Insulation levels...4 3.2 Mechanical design...4 3.3 Connections...4 3.4 Breaking and insulation medium...4 3.5 Composite Insulators...5 4 Functional requirements...5 4.1 General...5 4.2 Circuit-breakers...5 4.2.1 Monitoring...5 4.2.2 Indication...5 4.2.3 Operating mechanism...6 4.2.4 Connection of capacitor banks...6 4.2.5 Connection of reactors...6 4.2.6 Controlled connection...6 4.3 Disconnectors...7 4.3.1 Control...7 4.3.2 Indication...7 4.3.3 Operating mechanism...7 4.4 Earthing switches...7 4.4.1 Control...7 4.4.2 Operating mechanism...7 4.4.3 Indication...7 4.5 Common...8 4.5.1 Auxiliary voltages...8 4.5.2 Indication...8 4.5.3 Operating mechanism...8 4.5.4 Interlocking...8 4.5.5 Operating functions for disconnectors and earthing switches...8

E.ON Energidistribution AB Verksamhetsstyrande 2 (9) 4.5.6 Operating functions for circuit-breakers and disconnecting circuitbreakers....9 5 Testing...9 6 Documentation...9 7 Appendices...9 Terminals...1

E.ON Energidistribution AB Verksamhetsstyrande 3 (9) 1 General 1.1 Scope These requirements cover the general demands of E.ON Energidistribution AB in respect of circuit-breakers, disconnecting circuit breaker, disconnectors and earthing switches. The requirement apply to the voltage for equipment of 12-145 kv, rated frequency 50 Hz for indoor or outdoor designs. These requirements are complement to the requirements set out in the Facility Directive Regional Network. These requirements are a translation from the Swedish requirements D10-0015671. If the content of this document differs from the Swedish version, the Swedish requirements shall prevail. 1.2 Standards The apparatuses shall be designed, manufactured and tested in accordance with the most recent edition of applicable Swedish standards. In the absence of such standards, the European Standard (EN) and IEC publications apply. In the event of disparities between this document and the relevant standard, these Technical Regulations shall apply. 1.3 Labelling For terminal blocks, the manufacturer s labelling must be located on the equipment side. The cable side shall be free of labelling; intended for E.ON s own labels. Cables and cable parts in the operating mechanism, between the operating mechanism and other components, shall be labelled at both ends. Earthing switches shall be fitted with yellow/black warning labels on earthing blades and manoeuvre tubes. 2 Changes relative to previous issue Changes relative to the previous issue are shown with a vertical line in the right-hand margin. Updated Appendix for connections.

E.ON Energidistribution AB Verksamhetsstyrande 4 (9) 3 Electrical and mechanical requirements 3.1 Insulation levels For insulation level phase-earth and the phase distance refer to Facility Directive Regional network. Requirements for the insulation level over the disconnecting distance for disconnectors and disconnecting circuit breakers are presented below. Highest Voltage Insulation level [kv] for equipment 12 kv LI85 AC32 24 kv LI145 AC60 36 kv LI195 AC80 52 kv LI290 AC110 72.5 kv LI325 AC140 72.5 kv LI375 AC160 DCB 82.5 kv LI440 AC175 145 kv LI650 AC275 145 kv LI750 AC315 DCB 3.2 Mechanical design The apparatus shall be dimensioned for the static and dynamic forces in the most unfavourable direction. Earthing switches that extend other apparatus shall have at least the same short circuit strength as this. 3.3 Connections High voltage connections for outdoor circuit breakers and disconnectors 12-52 kv shall be made of copper/copperalloy or aluminium. See Appendix 1. High voltage connections for outdoor circuit breakers and disconnectors over 52 kv shall be made of aluminium or silver-plated copper/copper alloy. See Appendix 1. Cable shields and any reinforcement shall be earthed at both ends. Terminal blocks according to Facility directive Regional Networks. 3.4 Breaking and insulation medium Circuit breakers with SF6 gas for isolation and arc quenching shall only be used unless there are no other acceptable alternatives, for environmental reasons. If SF6-gas are used, mixed gas is only permitted for stations with a minimum temperature lower than -40 C.

E.ON Energidistribution AB Verksamhetsstyrande 5 (9) 3.5 Composite Insulators Shall be performed and tested according to applicable standards and SS- EN 61462. 4 Functional requirements 4.1 General Disconnecting circuit breakers shall always be equipped with added earthing switches. 4.2 Circuit-breakers 4.2.1 Monitoring Circuit-breakers with gas shall be equipped with a density monitor for gas monitoring in each two steps according to the following: 12-36 kv: Level 1: ALARM 52-145 kv: Level 1: ALARM Level 2: BLOCKING There shall be manometers for direct reading of the gas pressure. Signal contact for Level 1: ALARM shall be a free contact that makes at a low gas pressure. Circuit-breakers shall be prepared for monitoring of tripping circuits. 4.2.2 Indication The circuit-breaker s position shall be mechanically indicated with the signs TILL or 1 and FRÅN or 0. For circuit-breakers the operating mechanism s standby position is shown with the mechanical position indication of the closing springs stated with the text SPÄND and EJ SPÄND. Circuit-breakers shall be equipped with a mechanical counter for the number of executed operating cycles (Closed/Open). The counter shall be at least 4-digit and shall not be possible to reset. Motor operated apparatus shall be equipped with the following free auxiliary contacts: 4 connected in closed position 4 connected in open position 2 connected when the motor is running

E.ON Energidistribution AB Verksamhetsstyrande 6 (9) 4.2.3 Operating mechanism There shall be a device for manual charging of the closing springs for the circuit-breaker. The device shall be so designed that it releases if the motor starts or a two-way breaking of the motor circuit take place automatically when the device is used. There shall be a device that prevents pumping after tripping with remaining closing pulses. Operating mechanism for circuit-breakers shall be equipped with double electrically tripping magnets that work independently of each other. Normally only one closing magnet is required but it shall be possible to supply the circuit breaker with an additional magnet. 4.2.4 Connection of capacitor banks Circuit breakers for capacitor banks should be capable to connecting both single and parallel capacitor banks. The circuit breakers shall meet the requirements SS-EN 62271-100 4.107 Table 9 or higher value of the current required in the application. Data for the inrush current can be calculated using SS-EN 62271-100 Annex H. In order to reduce the inrush current, controlled switching or/and current limiting reactor can be used. If controlled switching is used, the circuit breaker shall be dimensioned for non-controlled switching. Capacitor bank circuit breakers shall be designed for controlled switching, as per chapter 4.2.6. 4.2.5 Connection of reactors Circuit breakers for reactor shall meet the requirements of SS-EN 62271-110. Reactor circuit breakers shall be designed for controlled switching, as per chapter 4.2.6 4.2.6 Controlled connection Objects who should be provided with a controlled connection are capacitor banks, reactors and in some special cases also power transformers. Circuit-breakers intended for controlled connection shall have been tested and approved for at least 10,000 operating cycles. If the voltage-setting circuit breaker for transformers is to be controlled, the controlled connection shall be done by measuring the transformer's remedy. Controlled disconnection of shunt reactors shall provide non-reignition breakings, in accordance with the requirements of SS-EN 62271-110.

E.ON Energidistribution AB Verksamhetsstyrande 7 (9) Deviations in operating-time due to mechanical spreading shall be lower than: Closing time: ± 1 ms Opening time: ± 1 ms Deviations in operating-time at resting period less than 64 hours shall be lower than: Closing time: ± 1 ms Opening time: ± 2 ms 4.3 Disconnectors 4.3.1 Control Disconnectors equipped with hand operated or motor drive according to the technical specification. 4.3.2 Indication The disconnector s position shall be mechanically indicated with the signs SLUTEN or 1 and ÖPPEN or 0. 4.3.3 Operating mechanism Disconnectors equipped with hand operated or motor drive according to the technical specification. The grip part of the operating device shall be insulated or of an insulating material. At least one operating device of each type shall be supplied. 4.4 Earthing switches 4.4.1 Control Earthing switches are always designed with three/way operation. 4.4.2 Operating mechanism Earthing switches to be equipped with hand operated or motor drive according to the technical specification. Earthing switches added to disconnecting circuit breakers are always equipped with a motor drive. The grip part of the operating device shall be insulated or of an insulating material. At least one operating device of each type shall be supplied. 4.4.3 Indication The earthing switch s position shall be mechanically indicated with the signs 1 and 0 or Earth symbol and 0.

E.ON Energidistribution AB Verksamhetsstyrande 8 (9) 4.5 Common 4.5.1 Auxiliary voltages Operating and motor equipment shall be designed for 110 V DC. Heating equipment shall be designed for 230 V DC. 4.5.2 Indication Operating push/buttons shall be equipped with signs with the text MANÖVER and the operating device shall have the symbols 0 and 1. 4.5.3 Operating mechanism Operating mechanisms for outdoor use shall be equipped with heating to prevent condensation. The heating element and all parts of the 230 V AC circuits shall be touch protected design. Monitoring of the heating via potential-free contacts shall be installed. Motors shall be fully disconnected in rest position. The motor shall be protected against overload by means of a direct-online starter that shall be possible to operate on/off by hand. The directon-line starter shall be equipped with a sign with the text MOTOR. The operating device shall have the symbols 0 and 1. A direct-on-line starter or switch are not required for indoor circuit/breakers with the highest voltage for equipment 12-36 kv. Motor circuits shall be galvanic separated from other circuits. 4.5.4 Interlocking There shall be a mechanical interlocking between added earthing switches and disconnectors. There shall be mechanical and electrical interlocking between added earthing switches and disconnecting circuit breakers. 4.5.5 Operating functions for disconnectors and earthing switches Electric operation shall be prevented at locking by blocking the control circuits. BLOCKED It shall be possible lock the operating mechanism in both end positions. The locking device must be approved by E.ON. Locking shall be performed using padlocks with a shackle, diameter 9 mm. Locking shall be on the outside of the operating mechanism. Two-way opening shall be performed automatically by motor and control circuits. DISTANCE Electric, two-way distance operation shall be possible.

E.ON Energidistribution AB Verksamhetsstyrande 9 (9) MANUAL Mechanical operation shall be possible using a crank or handle. Two-way opening shall be performed automatically by motor and control circuits. 4.5.6 Operating functions for circuit-breakers and disconnecting circuitbreakers. No push-buttons or knobs for electric local operation are to be found on the operating mechanism. Mechanical disconnection shall be possible and well described in the user's manual, if single-pole operated cicuit breakers are used, electric push button are allowed in common cabinet. Emergency mechanical disconnection shall be well marked and with a sign (Nödfrånslag). Also the outside of the door shall be fitted with a sign, (Nödfrånslag bakom denna dörr). Signs should be red with white text. Electric operation shall be prevented when locking by blocking the control circuits. BLOCKED (only disconnecting circuit breaker) The circuit-breaker shall be possible to block and lock in the open position. The locking device must be approved by the client. Locking shall be performed using padlocks with a shackle, diameter 9 mm. Locking shall be on the outside. DISTANCE Electrical distance operation shall be possible. MANUAL Mechanical spring charging shall be possible using a crank or handle. Mechanical opening shall be possible via a push-button or knob. 5 Testing Unless otherwise specified, testing must conform to the scope and requirements for test results set down in applicable standards. 6 Documentation The documentation shall include information about the capacitive breaking capacity of the apparatus. Any changes from previous versions of the same design shall be evident at procurement and in the documentation. 7 Appendices Appendix 1 Primary connections

E.ON Energidistribution AB Bilaga 1 1 (1) Al Cu Terminals For max Cylindrical Flat current diam length Hole Sizes (mm) (A) (mm) (mm) numbers a b c d e fig Notes 400 30 125 2 75 19 40 14 10 1 1250 30 125 4 75 17,5 40 14 15 2 1600 40 125 - - - - - - - 2500 60 125 - - - - - - - 3150-9 125 22,5 40 14 35 3 4000A when double sided 4000-12 125 22,5 40 14 35 4 5000A when double sided 1600 30 125 - - - - - - - 2500 40 125 4 75 17,5 40 14 10 2 4000 60 125 - - - - - - - 6300 - - 4 100 25 50 18 15 2 double sided 8000 - - 4 125 30 65 18 18 2 double sided Note! The current value above refers to the maximum load current including the overload capacity of the apparatus.