Integration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201

Similar documents
Technical catalogue. Emax Low voltage air circuit-breakers. Hotline:

Distribution systems and protection against indirect contact and earth fault

Directional protection and directional zone selectivity

Mould circ. Moulded case circuit-breakers

MV/LV transformer substations: theory and examples of short-circuit calculation

3-phase short-circuit current (Isc) at any point within a LV installation

MV network design & devices selection EXERCISE BOOK

Protection of Electrical Networks. Christophe Prévé

1960 Research Drive, Suite 100, Troy, Michigan with. REVISION: December 10, 2007 (Supersedes previous versions) Prepared by:

Circuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

02/11/2015

Maintenance/Connection/Installation Service life C/O cyclesx1000

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

Stabilized Differential Relay SPAD 346. Product Guide

presentation contents application advantages

VI 3 - i TABLE OF CONTENTS

02/11/2015

Multimeter 500CVD21 RTU500 series

Medium Voltage Products. KECA 80 C85 Indoor current sensor

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Protective Relays Digitrip 3000

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

Panorama Molded case circuit breakers Power circuit breakers

02/11/2015

White paper. Protection against electric arc Integration between Arc Guard System TM (TVOC-2) and Emax air-circuit breakers

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

White paper. Generators protection: Ekip G trip unit for SACE Emax 2

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly

Electrical Protection System Design and Operation

Residual Current Operated Circuit-Breakers (RCCBs)

Transformer Protection

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

Powered by technology...driven by service CURRENT TRANSFORMERS. Multifunction Meters. Transducers & Isolators. Temperature Controllers

2015 Relay School Bus Protection Mike Kockott March, 2015

Impedance protection on power transformer.

Power System Protection Manual

Technical catalogue. Emax. Low voltage air circuit-breakers 1SDC200006D0205

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

8V General information. 2 Order data 8V

SPAD 346 C Stabilized differential relay

Grounding Recommendations for On Site Power Systems

REF 610 Feeder Protection Relay. Technical Reference Manual

Earth Fault Protection

Line protection with transformer in the protection zone

Low Voltage. Residual-current protection relays

QUINT-PS/ 3AC/24DC/10

Electrical Description

N. TEST TEST DESCRIPTION

02/11/2015

ELECTRICAL POWER TRANSMISSION TRAINER

TN, TT & IT Earthing Arrangements

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

KENYA ELECTRICITY GENERATING COMPANY LTD

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

"Modular" versions designed for application-specific functions LCD with 4 lines of 18 characters and configurable backlighting

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Custom "Compact" range with display CD20 Custom Part number

Ariadna CI MV & LV cable identifier

Complex Solution for the Distribution Substation REF 542plus. Application and Setting Guide

GUIDELINES FOR SELECTIVE OVERCURRENT PROTECTION FOR ELECTRICAL SYSTEMS OF SHIPS

Transformer protection IED RET 670

Transformer Fault Categories

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

Substation Preventive Maintenance

QUINT-PS/ 3AC/24DC/40

Excitation Systems. Service Generators SIPOL. Transistorized Excitation Systems for Synchronous Generators. Power Generation

Installation / Monitoring Technique

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

SPAD 346 C. Stabilized Differential Relay. User s manual and Technical description SPAD 346 C V ~ V. f n SPCD 3D53 SPCJ 4D28

Zone Selective Interlocking (ZSI)

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

Electronic Circuit Breaker ESS1 for System SVS1

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

QUINT-PS/ 1AC/24DC/20

Distribution/Substation Transformer

Page 13-2 Page Page 13-7

Series P. Applications

Impact Assessment Generator Form

ISOLATING TRANSFORMERS FOR TLC PLANTS

Busbars and lines are important elements

technical information

XD1-T Transformer differential protection relay. Manual XD1-T (Revision A)

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

SPAA 341 C. Feeder Protection Relay. User s manual and Technical description SPAA 341 C. U aux V ~ V. f n. t 2 > [ s ] 0 I 0 >> Trip

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

N. TEST TEST DESCRIPTION

Transcription:

1SDC007402G0201

Index 1. Introduction... 2 2. Theoretical outline 2.1 Restricted earth fault... 3 2.2 Selectivity between medium and low voltage... 4 3. Application examples and wiring logic 3.1 Restricted earth fault... 5 3.2 Selectivity between medium and low voltage... 8 3.2.1 Description of the plant... 8 3.2.2 The solution using PR120/K signaling unit: wiring logic... 12 4. Analysis of the necessary equipment 4.1 Signaling unit for the interlock between low and medium voltage... 15 4.1.1 PR021/K unit... 15 4.1.2 PR120/K unit... 17 4.2 Homopolar toroid for the star centre of the transformer... 18 4.3 Wiring between MV and LV circuit-breakers... 19 5. Bibliography... 20 1

1. Introduction 1. Introduction This White Paper describes the possibilities of integration between ABB medium and low voltage protection trip units, paying particular attention to the protection and control unit type REF542 (for MV) and the protection trip unit PR123 (for LV). Two different application fields are taken into consideration: coordination with the medium voltage for an earth fault upstream the relevant protection on the low voltage side selectivity between two MV and LV protection units A fault between the windings of a transformer secondary or in the section immediately on the supply side of the LV circuit-breaker (also called restricted earth fault ) cannot be easily detected by the protections on the primary of the MV/LV transformer. As a consequence, it could be necessary to provide for a dedicated protection against this kind of fault, so that fire hazard is limited as much as possible and people s safety is guaranteed. Achieving correct MV/LV selectivity may sometimes be complicated. The difficulties can be solved by means of suitable coordination strategies. 2

2. Theoretical outline 2.1 Restricted Earth Fault Restricted earth fault protection (also known as Restricted Earth Fault, acronym REF) is applied in order to detect earth faults occurring both on the secondary winding of the distribution transformers as well as on the connection cable between the transformer and the LV circuit-breaker, faults which could be unlikely detected by the protections placed on the primary winding (e.g. by the transformer residual current protections against internal faults), because of their modest intensity. A possible solution to detect and eliminate this type of fault, is using an external toroid connected to the star centre of the transformer and using the signal coming from this device to open the MV circuit-breaker and disconnect the fault. Figure 1 (REF Protection) C N a N b C B B A A 0 f 1 I -x,a I -x,b I d > I -A I -B I -C { } I Y - I d,g > Figure 1 shows a principle diagram comprising a MV/LV earthed delta-star transformer, where the symbol I d,g > identifies the protection REF (restricted earth fault) whereas I d > indicates the residual current protection of the transformer. The distribution system on the LV side is type TN-S. Taking into consideration an earth fault on the secondary windings of the transformer, it is evident that the single-phase earth fault on the LV side is seen from the MV side as a two-phase fault. By means of some simple calculations, it is possible to demonstrate how, while the REF protection is able to detect the whole fault current, the residual current protection of the transformer sees only a percentage (even if very small) of the fault current. 3

2. Theoretical outline For example, for a 20 kv / 400 V earthed delta-star transformer, if the fault occurs at halfway of a winding, the residual current protection of the transformer shall detect a current which is 0.6% of the effective earth fault current. This could make it impossible to set the residual current protection of the transformer so that it can trip with such a low threshold. It is necessary to point out that the toroid connected on the star centre detects also every current deriving from an earth fault on the supply side (non-restricted earth fault): therefore it is necessary to provide a protection able to discriminate (time selectivity) between the two fault typologies. The solution offered by the protection trip units by ABB is defined Double G. For further information on the Double G function, it is possible to consult the technical documentation given by ABB. 2.2 Selectivity between medium and low voltage With protection selectivity it is meant the capability of the trip unit (or, more generally, of the protection) to distinguish the type of fault and its location and to trip only in case of faults occurring in the area for which the protection is provided. To carry out a selectivity study between MV and LV circuit-breakers, it is necessary to insert in a logarithmic diagram (referred to a defined voltage) the main parameters, that is: 1. for the transformer: magnetizing curve; rated current; short-circuit current of the busbars on the LV side; short-time current of the transformer. 2. for the upstream network: time-current characteristic of the protection device owned by the distri bution Authority. Once these information have been traced out, the protection curve on the LV side can be drawn, taking into account the following limitations: the transformer must be protected against overload; the protection must be selective in comparison with other LV protections. Once the curve of the LV protection is known, the limits of the MV protection can be defined keeping into account that: it must protect the transformer against overload (if this protection is not already guaranteed by the protection on the LV side); it must not trip during the inrush phase of the transformer; it must not interfere with the MV protection owned by the distribution Authority. 4

3. Applications examples and wiring logic 3. Application examples and wiring logic 3.1 Restricted Earth Fault The example of Figure 3 shows a plant, comprising: - a protection circuit-breaker on the MV side, equipped with REF542 protection and control unit; - a MV/LV distribution transformer (with a TN-S distribution system on the LV side); - a main LV circuit-breaker type Emax equipped with PR123 LSIG trip unit; - different moulded-case circuit-breakers to protect the outgoing feeders towards the loads. In order to guarantee proper coordination and protection against the earth faults which can occur in the plant of the figure, it is necessary that: - in case of earth fault in the part of the plant between the transformer and the Emax circuit-breaker (that is in case of restricted earth fault), the MV circuitbreaker opens (afterwards it is possible to choose whether to keep the LV circuit-breaker closed or to open it); - in case of earth fault in the area between the opened circuit-breaker and the moulded-case circuit-breakers, only the main LV circuit-breaker opens; - in case of earth fault in the load area, only the moulded case circuit-breaker immediately on the supply side opens. In order to make the MV circuit-breaker open, it is sufficient to send a signal to its opening coil. As an example, here is given a single line wiring diagram for the control of the opening coil of the MV release using a signaling contact (K51/p1) of the remote signaling module PR120/K: Figure 2 K10 K10 K10 XK6 7 K51 p1 -AR (803) X21/d10 X21/d12 XK6 8 K9 K9 K9 -XX 11 -XB 9 -XB 7-08 -XB12 -XB11 1 Caption AR: REF 542 Protection Unit BB1, BB3: Auxiliary contacts TR1: AC/DC converters MO1: Opening coil K51/p1: Contact of PR120/K module -TR1 -XB 8 -BB3 + -BB1 2 -XB11 2 -MO1 5

3. Applications examples and wiring logic The circuit-breaker opening, commanded by the REF542 protection unit following up the trip of any of the protections, occurs through the closing of AR contact. Then the opening signal is transmitted to the coil MO1 through the rectifier TR1. The auxiliary contacts BB1 and BB3 (able to report the circuit-breaker status) can be used, for example, to prevent the opening coil from being supplied when the circuit-breaker is open or to create interlocks. To command the opening through a circuit-breaker type EMAX, it is possible to use one contact of the signaling modules PR120/K (internal) or PR021/K (external) controlled by PR123 LSIG trip unit. These signaling modules are able to signal from remote the alarms and the trips of the circuit-breaker and can be programmed according to the events to be signaled. Figure 3 Homopolar toroid MV CB MV-LV TRAFO ACB PR123 LSIG MCCB LSIG MCCB LSIG MCCB LSIG M L L 6

3. Applications examples and wiring logic In detail, to realize what described above, it is necessary to use: - a SACE Emax air circuit-breaker equipped with an electronic trip unit PR123/P LSIG; - a PR120/K module (or PR021/K) mounted on the trip unit; - a homopolar toroid to be mounted on the earthing of the star center of the transformer and connected to the electronic trip unit. As pointed out, in case of an earth fault occurring in the area of the plant between the transformer and the main LV circuit-breaker, it is necessary that the MV circuit-breaker opens so that the fault can be disconnected. To command the opening of the MV circuit-breaker, it is necessary that the contact K51/p1 of PR120/K module is set as followed: - reference event: Gext alarm (blocked trip) - status: NO (normally open) - latching function: not selected - time-delay upon closing: selected (To prevent the LV circuit-breaker from being opened by the protection, it is possible to set to Off the trip enable of Gext function). The reference event is chosen as Gext alarm (blocked trip) so that such signal is maintained for all the duration time of the fault up to its extinction; besides, the contact shall be duly delayed to give the internal protection G (Gint) the time to trip, in case the fault occurs on the load side of the main LV circuit-breaker. To guarantee the correct setting of K51/p1 contact, it is possible to use PR010/T test and signaling unit or the software SD-Pocket (for PDA) and SD-TestBus (for PC). As an example, the following Figure shows the main window of PR120/K module as it appears in the program SD-TestBus: Figure 4 7

3. Applications examples and wiring logic For further information on the function double G, available on the trip units type PR123/LSIG and PR333/LSIG, reference must be made to other ABB technical documents. The programmable contact shall be put in series with the opening coil of the MV circuit-breaker as previously pointed out. As a consequence, the correct sequence of the events is the following: a fault occurs on the supply side of the main LV circuit-breaker; - the Gext protection is activated by the fault current flowing through the toroid; - the K51/p1 contact changes its status moving to closed position; - the opening coil of the MV circuit-breaker is energized, thus being opened; a fault occurs on the load side of the main LV circuit-breaker: - the Gext protection is activated by the fault current flowing through the toroid; - also the Gint protection is activated by the fault current equal to the resultant of the currents flowing through the active conductors (phases plus neutral); - the Gint protection, being set so as to be faster than the Gext protection, causes the opening of the main LV circuit-breaker; - the K51/p1 contact does not change status and consequently does not energize the opening coil of the MV circuit-breaker, which remains in closed position. 3.2 Selectivity between medium and low voltage 3.2.1 Description of the plant The study of selectivity between medium voltage and low voltage for the plant of Figure 5 is here briefly illustrated. Here are the characteristic parameters of the plant: characteristics of the supply side network: - rated voltage Un = 20 kv - three-phase symmetrical short-circuit current Ik3 = 12.5 ka - protection against overcurrents IEEE 51: - first threshold: I> 250 A, t 0.5 s - second threshold: I>> 790 A, t 0.12 s 8

3. Applications examples and wiring logic 20/0.4 kv cast resin transformer: - apparent rated power Sn = 1600 kva - short-circuit voltage Uk = 5,7 % - rated current at the primary It1 = 46 A - rated current at the secondary It2 = 2309 A - three-phase short-circuit current referred to the secondary Ik3LV2 = 40.5 ka - three-phase short-circuit current referred to the primary Ik3LV1 = 810 A - short-time current: 770 A for 2 s main MV circuit-breaker: - QF1: HD4/R equipped with REF542 PLUS connected LV circuit-breakers: - QF2: SACE Emax E3N 2500 PR122/P-LSI - QF3: SACE Emax X1N 1600 PR332/P-LSI - QF6: SACE Tmax T7S 1000 PR232/P-LSI Figure 5 -QF1 -TM1 Vn2 = 400 V Sn = 1600 kva -QF2 E3N 2500 PR122-LSI 2500 A -B1 V = 388.0 V Ib = 2105.0 A cosphi = 0.92 Icc nax = 40.5 ka -QF3 X1N 1600 PR332 LSI 1600 A -B2 V = 388.0 V Ib = 1500.0 A cosphi = 0.92 Icc nax = 40.4 ka -QF6 T7S 1000 PR232-LSI 1000 A 9

3. Applications examples and wiring logic Figure 6 shows the data relevant to the transformer (in black) and to the MV protection (in orange) at 20 kv reference voltage: Figure 6 Time current curve 1E4s 1E3s 100s 10s 1s 0.1s 0.2s 0.3s 1E-3kA 1E-2kA 0.1kA 1kA 10kA 100kA 1E3kA The main LV circuit-breaker must be selective with the circuit-breakers on the load side. 10

3. Applications examples and wiring logic By supposing to set at 2100 A (I1=0.84 x In) the threshold I1 of the Emax circuitbreaker, it is possible to trace the curves of the circuit-breakers on the LV side. A possible solution is shown in the following graph Figure 7 Time current curve 1E4s 1E3s 100s 10s 1s 0.1s 0.2s 0.3s 1E-3kA 1E-2kA 0.1kA 1kA 10kA 100kA 1E3kA It can be noticed that total selectivity is guaranteed between X1 and T7 circuitbreakers through an effective setting of S protection. By analyzing the graph, please observe that, to get a good selectivity level with the circuit-breakers X1 and T7 positioned on the load side, Emax air circuit-breaker cannot be selective with the MV protection due to a fault on the LV busbar B1. In fact, if such a fault occurred, both QF2 and QF1 would open. In order to avoid this event, the most simple solution would be implementing logic or zone selectivity by sending a signal to block the MV release through the zone selectivity outputs present on the Emax trip unit PR123, thus integrating into a single selectivity chain also the MV circuit-breaker. Nevertheless, this is not directly possible, because the voltage of the physical signal used for the zone selectivity on REF542 PLUS shall be comprised between 48 and 240V DC, whereas the zone selectivity connection used on the trip units PR123 (as well as PR122), using a voltage of 24V DC (auxiliary voltage more often used in LV plants). To solve this problem it is possible to use as block signal a signal coming from the modules PR120/K or PR021/K, set to the event S timing. 11

3. Applications examples and wiring logic 3.2.2 The solution using PR120/K signaling unit: wiring logic REF542 PLUS unit has many input and output contacts. In particular, BI14 binary input and B07 binary output can be used to block the protection functions between interlocked REF542 PLUS (Figure 8). The input is used to receive the block signal, and the output to send the signal. The wiring diagram of the inputs/outputs is shown in the scheme below, where with AR1 and AR2 two REF542 PLUS releases are indicated: Figure 8 (Wiring of REF542 Plus for the management of the Zone Selectivity) + -AR1 -AR2 X21 X20 B07 z24 z26 d24 -XI -XC/-XI -XC/-XI -XI d28 z28 B14 BI14 X20 d28 z28 -XI -XC/-XI -XC/-XI -XI X21 z24 z26 B07 d24 + 12

3. Applications examples and wiring logic As already pointed out, the binary inputs can be used for voltages in the range from 48 to 240V DC. By analyzing the direct current performances (reported in the table of Figure 9) of the contacts of PR120/K module (also valid for PR021/K) it is possible to verify that the module is suitable as interblock of REF542 PLUS. Figure 9 Type of contact Max switching voltage Max switching current Max switching power SPST 130 VDC 5 A 175 W Breaking capacity at 35 VDC 5 A Breaking capacity at 120 VDC 0.2 A Breaking capacity at 250 VAC - Breaking capacity at 380 VAC - Contact/coil insulation Contact/contact insulation Here is an example of wiring using the contact K51/P1 of PR120/K module at a voltage of 48 V DC (this can be obtained analogously also with PR021/K module). Figure 10 (example of interblock obtained by wiring a PR120/K module with REF542 Plus) REF452 X21 PR120/K K10 B07 z24 K10 z26 K10 d24 X20 XK6 7 BI14 d28 z28 -XI -XC/-XI -XC/-XI -XI K51 p1 + XK6 8 K9 K9 K9 13

3. Applications examples and wiring logic To set properly K51/p1 contact, it is possible to use the test and signaling unit PR010/T or the programs SD-Pocket (for PDA) or SD-TestBus (for PC); to send the block signal to the MV product, it is necessary that the contact K51/p1 is set as follows: - reference event: S timing - status: NO (normally open) - latching function: not selected - time-delay upon closing: 0.0 To guarantee a correct functioning of the zone selectivity with a MV device, it is necessary that the minimum opening time of the MV circuit-breaker is not lower than 120 ms (for the protection against phase faults) or 150 ms (for the protection against earth faults). 14

4. Analysis of the necessry equipment 4. Analysis of the necessary equipment 4.1 Signaling unit for the interlock between low and medium voltage To realize an interlock between medium voltage and low voltage, as seen in the previous clauses, it is necessary to use one of the signaling units compatible with SACE Emax circuit-breakers. These units allow remote signaling of circuit-breaker alarms and trips and can be set by the user by means of the test and signaling unit PR010/T or the programs SD-Pocket (for PDA) or SD-TestBus (for PC). Reference must be made to the previous clauses for the setting of the contacts. 4.1.1 PR021/K module Figure 11 (PR021/K module) PR021/K signaling module converts the digital signals of the protection units into electrical signals via 8 normally open contacts. For the proper functioning a 24V DC supply is needed: since an earth-insulated auxiliary voltage is required, it is necessary to use galvanically insulated converters complying with the Standards IEC 60950 (UL1950) or any equivalent device. 15

4. Analysis of the necessry equipment Figure 12 PR021/K module shall be connected to the internal bus of the trip unit, through the slots W3 and W4 of the terminal box (the figure shows the terminal box of a withdrawable circuit-breaker type Emax). PR021/K module shall be mounted on a 35 mm standard DIN rail. For the removable front connectors of the module, the cables to be used shall have a cross section in the following range: - 0.5 and 1.5 mm2 (AWG 22 14) for the connection to the clamps 1 10; (left side of the module); - 0.5 and 2.5 mm2 (AWG 22...12) for the connections to the terminals 11 26 (on the right side of the unit). 16

4. Analysis of the necessry equipment 4.1.2 PR120/K module Figure 13 (PR120/K module) The internal signaling module PR120/K (mounted on the back part of the release) is supplied by trip units (in case the auxiliary supply is provided on it) or by PR120/V voltage module. PR120/K is equipped with four trip units, whose contacts are called K51/p1, K51/ p2, K51/p3 and K51/p4. These contacts can signal different events which can be selected by the user among those included in the standard list; however, the user can associate to the 4 contacts customized events by selecting Custom from the menu and setting the required signal through PDA, SD-Testbus or PR010/T. The outputs on the contact terminal box are identified by the terminals K4,K6,K8,K10. 17

4. Analysis of the necessry equipment Figure 14 (installation of PR120/K module) WL COM SIGNALLING MEASURING COM 4.2 Homopolar toroid for the star center of the transformer The rated current of the toroid can be set to 100A, 250A, 400A or 800A by using different combinations of connections. The connection between the homopolar toroid and the terminals T7 and T8 of the terminal box shall be realized using a corded shielded two-wire cable (BELDEN type 8762/8772) with length not exceeding 15 m. Shielding shall be earthed on the CB side and on the current sensor side. Figure 15 (the homopolar toroid) 18

4. Analysis of the necessry equipment 4.3 Wiring between MV and LV circuit-breakers Wiring between LV and MV circuit-breakers can be realized by means of a two-pole shielded cable to obtain selectivity between MV and LV as shown in clause 3.3. Due to the very low currents absorbed by the inputs of ABB MV releases, it is possible to reach wiring distance up to 800 meters. Figure 16 A suitable cable for this application is Belden 82841 (nominal characteristic impedance 120 Ohms, nominal conductor DC resistance @ 20 C 24 Ohms/1000 ft., max. recommend current 4 Amps per conductor @ 25 C). 19

5. Bibliography 5. Bibliography Installation and service instruction, Installation, service and maintenance instructions for low voltage air circuit-breakers Emax (code 1SDH000460R0002-L2778) Instruction Manual, SACE PR021/K signaling unit (code 1SDH000559R0002-L3016) 20

Due to possible developments of standards as well as of materials, the characteristics and dimensions specified in this document may only be considered binding after confirmation by. 1SDC007402G0201 December 08 A division of ABB S.p.A. L.V. Breakers Via Baioni, 35 24123 Bergamo - Italy Tel.: +39 035.395.111 - Telefax: +39 035.395.306-433 http://www.abb.com