Optimum dimensioning of a flicker compensator in three-phase electric-arc furnaces supply systems

Similar documents
A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

Long lasting transients in power filter circuits

POWER QUALITY ENHANCEMENT IN ARC FURNACE ENVIRONMENT Nupur Laxman Mali,

Chapter 10: Compensation of Power Transmission Systems

Compensation of Reactive Power Case Study

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Application of SVCs to Satisfy Reactive Power Needs of Power Systems

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs

Investigation of D-Statcom Operation in Electric Distribution System

Power Quality Requirements for Connection to the Transmission System

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

Power Quality enhancement of a distribution line with DSTATCOM

CERN - ST Division THE NEW 150 MVAR, 18 KV STATIC VAR COMPENSATOR FOR SPS: BACKGROUND, DESIGN AND COMMISSIONING

Curso de Transmissão em Corrente Continua Rio de Janeiro, de Junho, 2007

POWER QUALITY REPORT

Journal of Electrical and Electronic Engineering

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

Implementing Re-Active Power Compensation Technique in Long Transmission System (750 Km) By Using Shunt Facts Control Device with Mat Lab Simlink Tool

VOLTAGE CRITERIA IN STEEL MILL NETWORKS

Transients impact on power filter circuit sizing

II. RESEARCH METHODOLOGY

ACTIVE COMPENSATION OF HARMONICS IN INDUSTRIAL APPLICATIONS. Sergej Kalaschnikow, Steffan Hansen, Lucian Asiminoaei, Henrik Gedde Moos

Design and Simulation of Passive Filter

Recommendations for Harmonic and Power Measurements in Electrical Networks

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk.

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online):

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation

Voltage-Current and Harmonic Characteristic Analysis of Different FC-TCR Based SVC

MV Network Operation Issues and Elimination of Phase Voltage Unbalance

Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM

High Voltage DC Transmission 2

Harmonic Requirements

p. 1 p. 6 p. 22 p. 46 p. 58

Brief Study on TSCS, SSSC, SVC Facts Device

Study on Voltage Controller of Self-Excited Induction Generator Using Controlled Shunt Capacitor, SVC Magnetic Energy Recovery Switch

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

High voltage shunt capacitor banks HIGH VOLTAGE COMPENSATION AND HARMONIC FILTERING PRODUCTS

Power Quality Analysis in Power System with Non Linear Load

SRI VIDYA COLLEGE OF ENGG AND TECH

Application of a thyristor-controlled series reactor to reduce arc furnace flicker

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Grid Converters for Photovoltaic

CONCLUSIONS AND SUGGESTIONS FOR FUTURE WORK

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

ELEMENTS OF FACTS CONTROLLERS

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

STATCOM, an efficient means for flicker mitigation

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation

High-Voltage Capacitive Compensation Unit for Transformer and Shunt Reactor Testing, Type HVCC

UNBALANCED CURRENT BASED TARRIF

EH2741 Communication and Control in Electric Power Systems Lecture 2

Results of earth fault measurements in an earth fault compensated 110-kV-system. P. Märtel H.-J. Radtke P. Schegner O. Seifert

Analysis the Modeling and Control of Integrated STATCOM System to Improve Power System

Harmonic distortion from induction furnace loads in a steel production plant

STUDY OF THE EFFECTS OF HARMONICS IN THE DESIGN OF TRANSMISSION NETWORK SHUNT COMPENSATORS: NETWORK SIMULATION AND ANALYSIS METHODS

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS

Fundamental Concepts of Dynamic Reactive Compensation. Outline

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

LV Compensation & Filtering Products

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS

Study on Reactive Automatic Compensation System Design

Modeling of Statcom. P.M. Sarma and Dr. S.V. Jaya Ram Kumar. Department of Electrical & Electronics Engineering GRIET, Hyderabad, India

A Review on Mid-point Compensation of a Two-machine System Using STATCOM

Power Converters and Power Quality

1. Introduction to Power Quality

Enhancement of Power System Voltage Stability Using SVC and TCSC

Impact of Thyristor Controlled Series Capacitor on Voltage Profile of Transmission Lines using PSAT

Performance Improvement of Power System Using Static Synchronous Compensator (STATCOM) Priya Naikwad, Mayuri Kalmegh, Poonam Bhonge

Short Tutorial on Quartz Crystals and Oscillators

VOLTAGE DIPS AND SENSITIVITY OF CONSUMERS IN LOW VOLTAGE NETWORKS

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

Power Factor Improvement Using Static VAR Compensator

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

FAQ for SIMOREG 6RA70 and Control Module

Determination of Optimal Account and Location of Series Compensation and SVS for an AC Transmission System

Selected Problems of Induction Motor Drives with Voltage Inverter and Inverter Output Filters

Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions

Interharmonic Task Force Working Document

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

Var Compensators. 1. Introduction. 2. Technical Trends of SVCs. Shigeo Konishi Kenji Baba Mitsuru Daiguji

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 08, 2015 ISSN (online):

Design of Static var Compensators using a General Reactive Energy Definition

Reactors for filtering

Emission Limits for Customer Facilities Connected to the Hydro-Québec Transmission System

MAVOWATT 4 Multifunction Power Meter

International Journal of Emerging Technology in Computer Science & Electronics (IJETCSE) ISSN: Volume 8 Issue 1 APRIL 2014.

Transcription:

Optimum dimensioning of a flicker compensator in three-phase electric-arc furnaces supply systems Abstract Three-phase electric arc furnaces, the design power ratings of which are in many cases above 100 MVA, primarily cause voltage fluctuations (flicker) in their hightension feed systems, in addition to harmonics and unbalance. Static VAr compensators (SVCs) are used to smooth out these mains effects, The example of the dimensioning of an SVC is used to illustrate how effective flicker reduction can be achieved with al relatively low SVC design power rating by means of numerical process simulation and optimization of the compensator control system, saving investment costs of around 1.8m. Introduction The smelting of steel is carried out worldwide in high-performance electric arc furnaces operating with either AC or DC current and at a rated power of over 100 MVA. In the case of three-phase AC electric arc furnaces, particularly, feedback affects the high voltage supplying grid because there are uneven changes in the active net load and reactive load in the wiring of the AC system and because the physics entailed in a high current arc (the graph of current against voltage is non linear). The feedback impairs the quality of supply voltage and may disturb the operation of the whole grid. Compensators must, in many cases, be used to avoid impermissible distortion, asymmetry and rapid changes to the voltage in the network within very short periods. Their task is: - to have ready a basic load so that variations in the supply voltage are restricted, - to keep within permitted limits the distortion in the network voltage by means of filters and - to make available variable, asymmetrical reactive power so as to avoid any undesired voltage changes and fluctuations (causing flicker phenomena) and any major variations in the asymmetry over time. Compensators help to steady the electric arc, to raise the efficiency of the melting process, to lower the demand for reactive power from the supply network, to reduce electrical losses and to improve performance generally in steel production. If the compensator needs power of more than 100 MVAr, the SVC type is, as has long been the case, an economical option. It has a mechanism to provide the necessary basic load using a filter circuit, which will also do the job of restricting voltage distortion. A thyristor-controlled reactor (TCR) is used as a choke to produce the necessary, variable, asymmetrical reactive power. The sum of the reactive power from the furnace, the TCR and the filter, whether positive or negative, corresponds, on average, to one of the ideal values prescribed for the supply network. 1

The compensation principle in static VAr compensators (SVCs) The principle of reactive power compensation is illustrated in Fig. 1. Fig. 1: Simplified mains supply system diagram and reactive load flow (indirect compensation principle) The SVC filter circuit draws from the grid constant, capacitive reactive power and filters the harmonics of the furnace network voltage arising from the operation of the electric arc furnace. The TCR acting as a choke takes inductive reactive power in varying amounts over time from the network, with the aim of keeping constant the reactive power remaining in the particular branch of the network from the combined work of the electric arc furnace, the filter circuit and the TCR itself at an ideal figure Q soll = Q N = Q Ofen Q F + Q TCR The purpose of the mechanism is to ensure a constant longitudinal voltage drop and to limit any flicker, any voltage asymmetry, and the voltage fluctuations caused by the operation of the furnace to an acceptable level. The TCR as a regulation mechanism must be capable of remedying any deviations from the control values within 1 to 2 wave periods of the network. 2

The rated power of the TCR Q TCRr will normally be set to exceed the rated power of the filter circuits by 10 % to 15 %. This will ensure that the targeted control level Q N = Q soll will also be achieved for any electric arc furnaces currently out of operation and for an ideal control value of Q soll > 0. Computational simulation of the process facilitates optimum configuration of SVC The computer model of the energy sources in the supply grid (the transformers, the wiring, the chokes and the condensers) necessary for the simulation of the electrical behaviour of the three-phase AC electric arc furnace plus grid plus compensator is created on the basis of known alternative circuits consisting of R, L, C and switch elements. These substitute circuits are linked together by differential equations which apply to the grid structure. A similar procedure is used for the electrical equipment of the AC arc furnaces. The substitute elements R EAF and X EAF represent the sum of the leakage reactance and the resistance of the furnace transformers, the furnace chokes and the highcurrent circuit (see Fig. 2). Fig. 2: Equivalent circuit diagram and calculation model The electric arcs of the furnace are represented in the data by a voltage source which changes over time u arc (t) and are described during the creation of the model by a mean value Ū arc (t) which changes over time, which may be positive or negative and 3

which is formed in any half period of the actual electric arc voltage wave u arc (t). In this way the statistically probable arcing behaviour of the three-phase AC arc is simulated in dependence on its operational phase [1]. There will be a statistically probable degree of fluctuation in the electric arc voltage as a result of the electromagnetic phenomena (shift in position or change in length) in the arc. The fluctuations are stronger during the burn-in phase of every melt process because the scrap metal surface is hard and uneven and the scrap itself shifts or collapses. Since the arc voltage varies over time, there are constant adaptations going on within the furnace current. The time constants are in the upper range of µs. To rate the SVC, electrical conditions in the supply network for this operational stage of the electric arc furnace has to be used which have been obtained from reference measurements and are available in the form of statistical distribution curves for Ū arc (t). In the case of the filter circuits with the different frequencies to which they are tuned, and of the TCRs of the SVC, the substitution elements R F, X LF, X CF, R TCR and X TCR are taken into account for the calculation of the electrical network parameters (see Fig. 2). The switching behaviour of the power converter valves is simulated by ideal switches with the actual time of switching set to depend on the valve voltage u V, the valve current i V, the phase position of the vector depicting supply voltage ϕ(u N ), and the angles α 12, α 23 and α 31 which control the TCR. To fulfil the purposes of the investigation, it is necessary to integrate the method of operation of the TCR control system into the calculation of the network, thus ensuring economical configuration of the compensator. This regulation instance provide a servo control through the input currents of the three-phase AC electric arc with superposed reactive power control. The method provides on the one hand a short delay in composing the control variable and on the other hand it gains a great stationary accuracy. Differential equations are used for the discrete mathematical description of the transfer elements for the control mechanism [2]. An example of rating The compensator of an electric furnace steelworks, composed of filters and the regulated, choked condenser, was not capable of bringing the flickering due to the operation of the electric arc furnace down to a permissible level, particularly in the 110-kV network of urban consumers (Fig. 3). 4

Fig. 3: Simplified overview diagram of the power supply for an iron and steel works Measurements were taken and computer simulation were carried out for the network section shown in Fig. 3. These all confirmed that the compensation equipment in use did limit the voltage displacement at the PCC adequately, so that EN 50160 is observed, but revealed a need for measures to reduce the amount of reactive power drawn by the steelworks and to reduce flicker effectively. Determination of the rated power of the compensator The first thing was to measure the reactive power required over time by the electric arc furnaces in order to discover the rated power necessary for the new (SVC) compensator equipment. Fig. 4 shows an example, that of the 120-MVA furnace LBO2 during the melt and its 1-second mean values for effective and reactive power drawn. The operational conditions at the "restless" stage of the melt are marked separately. Fig. 4: Plots of the LBO2 s active power and reactive load against time 5

The reactive power drawn fluctuates strongly. The maximum reactive power value Q max exceeds twice the mean reactive power value Q mitt in the course of the restless stage of the melt. When both of the three-phase AC electric arc furnaces are in operation at the same time under these conditions, a maximum reactive power of 180 MVAr can be drawn as part of the power supplied. For this reason, the rated power of the compensator was established as Q CΣ = 180 MVAr (shown as version V2). As maximum values always arise for only very short times where reactive power is concerned, the next smaller version of a compensator, this time with rated power of Q CΣ = 150 MVAr (version V1), was also investigated. Two filters were added to the filter circuit (F1 and F4, see Fig. 5) and this also lessened the voltage displacement, predominantly in the range above 350 Hz. For this filter system design, the required rated power of the TCR was found to be 165 MVAr (version V1) or 200 MVAr (version V2). Fig. 5: Results of comparative assessment of several variants In order to prove the flicker-reducing effect of the SVC, simulation and computation based on the one-minute short-term flicker due to both furnaces being used at once for the melt at the "restless" stage were carried out. The contribution of the crucible furnace to the flicker is negligible and was therefore not taken into account for the computation. Fig. 5 shows a comparison between the results of simulation for the versions investigated and actual measurements obtained when a TSC was used as the compensator. 6

The results show that the use of an SVC with Q r = 180 MVAr will achieve the necessary flicker reduction in the 110-kV network. On the other hand it is clear that adequate flicker reduction is not yet possible with the 150-MVAr type of compensator. However, on closer analysis of the dynamic responsiveness of the 150-MVAr compensator as designed, it was seen that the windup arising under the given load in the PI regulator of the TCR was significantly impairing the electrical behaviour. Windup arises when the range in which adaptation on the part of the control element should take place is not big enough to allow the actual value which is being regulated to reach the ideal value as set. This means that a control error will continue to be present which will result in a continuing rise in the mathematically integrated part of the regulator. In consequence, the control mechanism will have a delayed response when the polarity of the variation from the reference values changes, i.e. the control response time will be impaired. The windup effect is particularly apparent in the 150- MVAr SVC because complete compensation of the reactive power for the furnace(s) requires capacitive reactive power up to a level of 180 MVAr and the SVC is not capable of providing this. The following diagrams show how it is possible to improve the electrical responsiveness of the less powerful compensator version (V1) by an anti-windup extension of the regulator to such an extent that flicker reduction which will meet the requirements is achieved. Optimising control of compensator To avoid the wind-up effect, the PI regulator (SVC) was extended by an additional mechanism. The use of an additional limiter avoids mathematical integration of the control error (the windup effect) which arises when the range set for the compensation is not big enough fully to accommodate the necessary regulation of the furnace reactive power at certain times. To illustrate the effectiveness of the anti-windup extension, Fig. 6 depicts a comparison of the network reactive power and how it changes over time in the branch supplying the network (on the 220-kV side) when there is a sudden change in the total reactive power of both furnaces: - from Q N = 120 MVAr to Q N = 180 MVAr at t 0.1 s (in the case of LBO1) - from Q N = 180 MVAr to Q N = 120 MVAr at t 0.2 s (in the case of LBO2) between the picture with and the picture without an anti-windup extension of the regulator. The load variation investigated represents the "worst case scenario for power change resulting from an overlap of the two electric arc furnaces, both operating at the restless stage of the melt 7

Fig. 6: Plot of supply reactive load against time (simulation result) Fig. 7 shows the effective voltage values in the 110-kV grid for an urban area and how they change over time, firstly without and then with anti-windup extension of the PI regulator. The modifications as described improve the dynamic behaviour of the compensator to such an extent that flickering can be reduced in the 110-kV grid to P stmax = 1.5 which corresponds to a (10 min) short-term flicker value of P st = 0.8. The steelworks is still certain to function reliably. Also on a reliable basis, flickering is limited to permissible values in the downstream low-voltage networks serving the public. The compensation effect produced by the 150-MVAr SVC thus corresponds to that offered by 180-MVAr versions without anti-windup extension (cf. Fig. 7). Fig. 7: Plot of supply voltage r.m.s. value in the 110kV system (see Figure 3) On the basis of the investigations here presented, the SVC with Q r = 150 MVAr can be considered the most technically and economically viable compensatory solution for the steelworks network. Using this type of compensator instead of the 180-MVAr type offers potential savings in investment costs to an amount of 1.8 million. 8

BIBLIOGRAPHY [1] Krämer, S.; Stade, D. Modellierung des elektrischen Betriebsverhaltens von Drehstromlichtbogenöfen, Tagungsband des 43. Internationalen Wissenschaftlichen Kolloquiums der Technischen Universität Ilmenau, 21. to 24.9.1998, p. 59 63 [2] Prinz, S. Bewertung der Elektroenergiequalität in Netzen mit leistungsstarken Stromrichteranlagen unter Beachtung des Einflusses ihrer Regelung und Steuerung Technische Universität Ilmenau 2004 Details of Author Prof. Dr.-Ing. habil. Dietrich Stade, VDE, is the Consulting Engineer at H. Kleinknecht GmbH & Co. KG in Ilmenau Email: dietrich.stade@kleinknecht.de Dr.-Ing. Helge Schäfer, VDE, is the Business Unit Manager at H. Kleinknecht GmbH & Co. KG in Ilmenau Email: helge.schaefer@kleinknecht.de Postal contact: H. Kleinknecht GmbH & Co. KG Weimarer Straße 1 b 98693 Ilmenau, Germany Tel.: ++ 49 3677 / 46969-0 Fax: ++ 49 3677 / 46969-10 Email: vertrieb@kleinknecht.de http://www.kleinknecht.de 9