OPTIMIZING MAINS IMPEDANCE: REAL WORLD EXAMPLES by Judith M. Russell Consulting Electrical Engineer PowerLines

Similar documents
Short Circuit Current Calculations

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

3Ø Short-Circuit Calculations

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Short-Circuit Current Calculations

Power Quality Monitoring and Power Metering Tutorial

Strategies for design 600V large modular UPS for critical power applications

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

Harmonic Mitigating Transformer - Technical Guide

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

Transformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

TABLE OF CONTENT

Power Quality Basics. Presented by. Scott Peele PE

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Fluke 40/41 Power Harmonics Analysers

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV

22.0 Harmonics in Industrial Power Systems

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Preface...x Chapter 1 Electrical Fundamentals

Industrial Electrician Level 3

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

TOSHIBA International Corp

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

User's Guide. AC Circuit Load Tester. Model CT70

INTEGRATED CIRCUITS. AN120 An overview of switched-mode power supplies Dec

(2) New Standard IEEE P (3) Core : (4) Windings :

Power Processor - Series 700F 10KVA to 150KVA

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

SINGLE-PHASE VSV SWITCH

TECHNICAL BULLETIN 004a Ferroresonance

All in all, a very interesting project; the PQube appears to be a handy tool in the power quality kit!

Phoenix DX Clean Power (18 Pulse) AC Drive

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES

TRANSFORMERS INTRODUCTION

Primary Metering. What is Primary Metering?

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

Power-Sure 700. Technical Data TD158001EN. Contents

EPG. by Chris C. Kleronomos

GESS Industrial UPS System. Overview

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

~=E.i!=h. Pre-certification Transformers

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

Electrical Protection System Design and Operation

Open-Delta Systems Affect Variable Frequency Drives

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)

Low Pass Harmonic Filters

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Conventional Paper-II-2011 Part-1A

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

How adjustable speed drives affect power distribution

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

TEACHER ASSESSMENT BLUEPRINT ELECTRICAL CONSTRUCTION TECHNOLOGY. Test Code: 5171 Version: 01

T-68 Protecting Your Equipment through Power Quality Solutions

Electromagnetic Harmonic Filters Technical Guide

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

Back to the Basics Current Transformer (CT) Testing

SINGLE-PHASE VSV SWITCH

Calculating AC Line Voltage Drop for M215 Microinverters with Engage Cables

Electric Power Quality: Voltage Sags Momentary Interruptions

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

INTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet...

Construction Electrician/Industrial Electrician/Power Electrician Common Core Level 2

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

1C.6.1 Voltage Disturbances

Thermal Imaging, Power Quality and Harmonics

Utility Interconnection and System Protection

Feed Line Currents for Neophytes.

Est Static Frequency Converter. SFX 10kVA - 10MVA

DC Solid State Power Controller Module

Effects of Harmonic Distortion I

Economical Solutions to Meet Harmonic Distortion Limits[4]

Chapter 1 Electrical Theory and Part C Series Parallel and Code Questions Multiwire Branch Circuits Unit 1 Electrician s Math

Consulting Report Breaker Trip / Fuse Blowing Investigation MCC / Blower Motors

Power Protection and Conditioning

PRODUCT FEATURES TYPICAL APPLICATIONS

Transformer Protection

Rev.8.8 SSRMAN-1P SERIES USERS MANUAL SSR INTELLIGENT PHASE ANGLE CONTROL MODULE COPYRIGHT 2015 NUWAVE TECHNOLOGIES, INC.

2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS

NJWA - Harmonics and Drives Proper System Design

Grounding for Power Quality

Thyristorised Automatic Power Factor

Final Exam Fall 2018

ULTRA-K Series 600K - he

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Wisconsin Contractors Institute Continuing Education

High Voltage DC Transmission 2

Alternator winding pitch and power system design

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

WHR Series STABILINE Voltage Regulators

CONTENTS. 1. Introduction Generating Stations 9 40

Busbars and lines are important elements

HARMONICS CAUSES AND EFFECTS

Practical Tricks with Transformers. Larry Weinstein K0NA

POWER QUALITY AND SAFETY

Transcription:

by Judith M. Russell Consulting Electrical Engineer PowerLines Introduction Power Quality has historically been quantified in terms of voltage. Metering equipment measures RMS voltage level, voltage sags and swells, voltage harmonics, or voltage transients. Current, if measured, becomes a secondary parameter useful in diagnosing problems (line generated vs. load generated, or assessing the impact of voltage disturbances on a particular load) or sizing solutions. While current is usually not the first thing reviewed, it has become standard to measure both voltage and current when investigating power quality. Impedance, however, is rarely measured directly, and only occasionally assessed indirectly, in the diagnosis and resolution of power quality issues. Impedance is an important issue for almost any piece of sensitive electronic equipment, but it is of particular importance in the following cases: There is an intermittent, cycling, or pulsing characteristic to the load There is a high inrush current to the sensitive load or a sub-system of the sensitive load The sensitive equipment requires high power / high current, or an allied or connected piece of equipment requires high power The load current is non-sinusoidal perhaps a single-phase rectified load, or a three-phase power converter with minimal input filtering. These loads, drawing current with relatively high harmonic currents, often team up with high impedance to cause significant voltage problems. While considering, measuring, and understanding impedance are often important factors in resolving power quality problems, the concept is not well understood outside of power quality engineering. One problem is that impedance is not something that can be easily marketed or sold. Few pieces of test equipment consider impedance either directly or indirectly. A handful of manufacturers have marketed impedance-optimized devices (usually isolation transformers) over the years, but often at a premium price that limits their appeal. The copper industry has a power quality group that spends a lot of time talking about impedance - admittedly, to promote the use of copper. For the most part, however, impedance is a poor cousin to more exciting products such as transient suppressors or uninterruptible power supplies, or more dramatic power quality topics such as grounding, voltage sags, or harmonics.

Optimizing vs. Minimizing Readers will note that I have used the word optimizing in the title of this paper, as opposed to the word minimizing. While the majority of impedance related power quality issues are indeed related to excessive impedance, occasionally the reverse is true. The tools and techniques discussed herein to measure and to correct impedance problems are equally valid. Three cases of real world low impedance problems are brought to mind: 1. A wire manufacturing facility, where a 480 VAC inductive pre-heating unit experienced serious cable slapping at switch-on, related to high inrush currents. This was both disconcerting to the user, as well as potentially damaging to the cable and conduit. The device had recently been moved from a soft source (high impedance, 208 VAC, via a small step up transformer) to a low impedance source (480 VAC bus). The solution: add some impedance to limit the inrush currents. 2. A medical X-Ray system was experiencing component failures during tube arcs. Such arcs are a normal, end-of-life behavior of an X-Ray tube, but the X-Ray generator should not fail during tube arcs. In this case, a particularly low impedance source was able to supply high fault currents during this sort of fault, exceeding the maximum current ratings of the devices, and resulting in power semiconductor failure. The solution: adding impedance (in the form of a 1:1 isolation transformer) limited the available fault current, and prevented component damage during tube arcs.

3. A press brake (metal bender) in an industrial facility was spuriously tripping a circuit breaker during operation (specifically, when the brake cycles off). A high current related to the hydraulic system power off cycling, was drawing excessive current for the installed overcurrent protection. Unexpectedly low source impedance at the facility permitted the high currents to flow. The solution: installation of a circuit breaker with a higher magnetic trip characteristic was required to permit system operation from the low impedance source. These three cases demonstrate that minimizing mains impedance is not always the goal. However, these three cases are truly aberrations far outnumbered by the other impedance problems. Most of the time, a power quality impedance problem is related to excessive impedance, and optimizing mains impedance means minimizing mains impedance.

Optimizing Impedance via Nominal Voltage Level One way to optimize mains impedance is to select an appropriate nominal voltage level and system type for the power of the load to be applied. In 1997, PowerLines was retained to look at an image quality problem on a large video sign possibly related to power quality. We traced the problem to voltage waveform distortion, caused by the load current waveform (phase controlled SCR) and the mains impedance, but a primary contributor was the nominal voltage level. This particular sign was a behemoth fed via a dedicated 12.5 KV / 1500 KVA service. But the sign design, and the power distribution for it, had been scaled up from smaller designs that were successfully run from 208 VAC power. Thus the power feed had hundreds of feet of distribution at 208 VAC. Had the sign manufacturer transitioned to 480 VAC internal distribution, the current levels in the distribution would have been halved, and impedance would have been much easier to minimize / control. Optimizing Impedance via System Type In the mid-90 s, there was a lot of buzz in the medical imaging world about a Single-phase X- Ray Generator. Such a device might find a niche in small clinics and offices where three-phase power was not available. However, the sales and marketing folks in the industry were equating single-phase with low-cost, and were not considering the impact that moving to a singlephase power converter would have on the installation costs (conductor sizing, transformers, etc.), nor the impact of what a large, single phase pulsed load would have on a typical three-phase electrical system. The low-cost product (from a device cost stand-point) had a much higher installation cost, and as a result, did not have the expected sales success. Optimizing Impedance at the System Level Increase source voltage (for example, 120 VAC to 240 VAC, or 208 VAC to 480 VAC) as equipment power levels rise Migrate to three-phase power as equipment power levels rise

Conductor Size / Run Length Engineers must consider the impact of conductor size and run length on mains impedance. In most cases, conductor sizes are selected based on thermal performance and safety. Oftentimes, these are derived directly from the National Electric Code or other safety standards related to the specified equipment circuit rating or overcurrent protection. And in most cases such sizing is both safe and appropriate. However, in some cases conductors sized only based on thermal requirements or overcurrent protection may cause problems. If run lengths are long, consider increasing the conductor size to minimize impedance. Similarly, if equipment has specific characteristics that make impedance important, consider increasing conductor sizes (even if the run length does not appear to be excessive. For example: If the load is known to be intermittent or pulsing If the load has a high inrush current or a large current swell during some operating conditions If conductor or source derating (related to duty cycle) is permissible by the electrical code(s) a good example is medical imaging equipment, where a 50% derating from maximum current is allowed. Whenever impedance is a potential problem, conductor sizes should be chosen based on thermal requirements, as well as impedance / voltage drop requirements. However, manufacturers may not clearly indicate the importance of impedance and the need for increased conductor sizing. The following clues can indicate the potential for impedance problems: If the manufacturer publishes an impedance specification (ohms or percent drop) If the manufacturer publishes a conductor size chart (size vs. run length) If the manufacturer specifies particular overcurrent protection (adjustable magnetic trip, or time-delay fuses) If the manufacturer specifies a separate / dedicated circuit or warns to keep a particular load separate from other loads

Two typical design and construction situations can cause problems from an impedance perspective. Contractors often bid a project based on overcurrent protection ratings, and might even go so far as to rough-in conduit before the electrical design has been completed. As a result, increasing conductor sizes (to minimize impedance) might not be included in the cost of the project, or require significant changes. Right: Conduits are often sized based on circuit breaker size, and may not accommodate impedance-driven increases in conductor size If step changes in voltage are required (up or down), placement of transformers is critical. Position transformers so as to minimize the length of lower voltage runs (208Y/120 VAC, for example) in favor of higher voltage runs. (Potential Impedance Problem) 480 VAC Source Step-down Transformer Increase conductor sizes for long runs Sensitive 208 VAC 200 Ft. (Preferred) 480 VAC Source Run long runs at higher voltage if possible Step-down Transformer 208 VAC Sensitive Optimizing Impedance Related to Conductors Consider increasing conductor sizes for long runs If you have the option, design long conductor runs at the highest available system voltage Be on the lookout for code-minimum electrical designs, and conductors sized solely on the basis of thermal loads, with no consideration of impedance When conductors need to be increased in size, get that information out early in the design / construction process to avoid extra costs and project delays

Isolation Transformers Isolation transformers are invariably the highest impedance devices in an electrical system. In most cases where high impedance has evolved into a power quality issue, an isolation transformer (or two!) is often involved. Typical problems include: Isolation transformers sized for demand (KW) but with high impedance Heavily loaded isolation transformers (transformer impedance typically rises with temperature) Multiple isolation transformers, combined to step voltage up and down to match equipment requirements 112 KVA Step-down Transformer 75 KVA Step-up Transformer 480 VAC Source 208 VAC 380 VAC Sensitive Two Transformers = High Impedance Transformers complicate impedance discussions. Transformer impedance is typically specified at a high (maximum) temperature, and actual impedance is often significantly lower. This is especially true if the transformer is oversized (e.g., harmonics) or if the load has a low duty cycle. Special low impedance transformers are available, often at a premium price. These may be simply derated and oversized (to reduce impedance at the fundamental frequency), or may incorporate advanced materials and construction techniques intended to reduce impedance at higher frequencies. Right: This 30 KVA transformer has a specified impedance of 6.5% at 170 C but the actual operating impedance may be much lower, depending upon the applied load and resultant transformer operating temperature.

Optimizing Impedance at Isolation Transformers Never combine or daisy chain similarly sizes isolation transformers Consider worst case loading (maximum load, inrush currents) when sizing transformers Include impedance in your transformer selection criteria Derate transformers or consider premium transformer designs Power Conditioners Power conditioning devices can be a wild card in terms of impedance. Some devices, such as a double conversion UPS or rotary power conditioner, provide an output that is for the most part independent of the input voltage. So for all intents and purposes, the impedance of these devices cannot be calculated or analyzed using conventional calculations. It s important to understand the step load response, the device response to non-linear load currents, and the output regulation characteristics to ensure device compatibility with the load. Assuming that compatibility is established, the devices should be effective over a wide range of source impedance. Other devices, such as transformer or autotransformer-based regulators, can correct for voltage changes at the fundamental frequency. However, these devices often are not fast enough to compensate for inrush currents or pulsing loads, nor do they correct for sub-cycle issues, related to non-linear loads and impedance. High harmonic load currents can cause voltage distortion if source impedance is high. In general, any time that active power conditioning or voltage regulation is employed, traditional impedance measurements (whether in ohms or in percent) are less likely to be meaningful, and special care should be taken to ensure that the output characteristics of the power-conditioning device are compatible with the load requirements. Optimizing Impedance at Power Conditioners Double conversion technologies can overcome impedance problems Transformer based technologies can not correct impedance problems Power conditioner compatibility with the load is critical

Unbalanced Impedance Mains impedance is typically balanced across the three phases. The voltage drop on any phase should be similar to that across other phases. When this is not the case, it s a certain sign of problems. Most likely, an impedance imbalance points to a problem on one phase. Check for things like loose connections, corrosion, or conductors or devices damaged by overload or heating. In one noteworthy site visit, PowerLines found a loose transformer tap connection that was sure to cause a catastrophic failure (had it not been discovered and corrected) the smoking gun that led to this problem being discovered was a measurement of the mains impedance. Right: Mains impedance imbalance pointed the way to finding this loose transformer tap connection the adjacent wire showing heat damage is a different phase, with 480 VAC potential to the tap it is touching. One other situation can cause mains impedance imbalance. Unbalanced transformer secondary configurations (such as an Open Delta, a 240 VAC Delta connection with the center point of one leg grounded, or the exotic Scott-Tee transformer connection) will all produce imbalanced impedance measurements. Once these are identified, a careful study of the source characteristics and load requirements can help to determine if the unusual transformer connection is compatible with the load requirements. Above: A Scott Tee transformer connection, used to connect a three-phase load to a twophase source. Left: A 240 VAC Delta transformer connection, with one phase center tapped to feed 240/120 VAC single-phase loads.

Dedicated Lines Specifying a dedicated line, kept separate from other loads, is often a technique used to optimize power quality. One way to consider a dedicated line is as an attempt to reduce or minimize shared impedance. In the drawing below voltage changes related to operation of the high power, or pulsing loads, could impact the power quality to the sensitive load. Z(service) Z(transformer) Z(feeder) Z (branch) High Power Pulsing Sensitive Shared Impedance By powering each device via a separate, or dedicated line, the shared impedance is reduced to only that of the service, and the likelihood of load-to-load interference is reduced. Z(servic Z(transform Z(feede Z High Loa Pulsin Loa Shared Sensitiv Loa Dedicated Lines: A Caveat When working with dedicate lines, it is possible that impedance to a given load is actually increased. As an example, if a 30 Amp circuit is run 200 feet via a 200 Amp feeder to a distribution panel, and then an additional 50 feet (30 amp circuit), the impedance will be much lower than if the 30 Amp circuit were run the full 250 feet back to the service. In this case the power quality benefits of the dedicated line must be weighed against the higher mains impedance. Acknowledgement: The author wishes to thank Alixe Cielo for proofreading and grammar checking this document.