FURTHER STATIC TENSION TESTS OF BOLTED JOINTS. A B S T RAe T

Similar documents
What happens to bolt tension in large joints?, Fasteners, Vol. 20, No. 3, 1965, Publication No. 286

Strength of a440 steel joints connected with a325 bolts, Publication IABSE, Vol. 23, 1963, Reprint 245 (63-24)

Large shingle splices that simulate bridge joints, December 1968 (70-24)

Behavior of large shingle splices that simulate bridge joints, M.S. thesis (70-24)

NYIT Instructors : Alfred Sanabria and Rodrigo Suarez

Copyright. Michael Joseph Gilroy. May 1997

Bolts and Set Screws Are they interchangeable?

Fasteners. Fastener. Chapter 18

ERECTION & CONSTRUCTION

Tex-452-A, Rotational Capacity Testing of Fasteners Using a Tension Measuring Device

Slip and yield resistance of friction type of high strength bolted connections with over-sized holes

BEHAVIOR OF LARGE BOLTED JOINTS. Geoffrey L. Kulak. Lynn S. Beedle

1/2/2016. Lecture Slides. Screws, Fasteners, and the Design of Nonpermanent Joints. Reasons for Non-permanent Fasteners

Connection and Tension Member Design

Bolt Material Types and Grades 1- Bolts made of carbon steel and alloy steel: 4.6, 4.8, 5.6, 5.8, 6.8, 8.8, 10.9 Nuts made of carbon steel and alloy

Procedure for Wrench Calibration and Snug Tightening

Bolted Joint Types Grip Washer

Structural Bolting. Notice the Grade 5 has a much smaller head configuration and a shorter shank then the grade A325 structural bolt.

Behavior of bolted joints with oversize or slotted holes, August 1967

Mechanical joints. Major diameter Mean diameter Minor diameter Pitch p chamfer. Root Crest. Thread angle 2a. Dr. Salah Gasim Ahmed YIC 1

Tightening of Structural Joints

Procedure for Testing Direct Tension Indicators (DTI) Assemblies

ODOT ITB Group 4 Item 33 Qty. 1

Instruction Manual for installing

AN, MS, NAS Bolts. AN3 20 bolts are identified by a multi-part code:

Copyright. Yavor Cvetanov Cekov

Effect of Washer Placement on Performance of Direct Tension Indicators

A5l4 STEEL JOINTS FASTENED BY A490 BOLTS. Geoffrey L. Kulak

AN, MS, NAS Bolts. AN3 20 bolts are identified by a multi-part code:

Instruction Manual for installing

FASTENER CHARACTERIZATION

CH # 8. Two rectangular metal pieces, the aim is to join them

A training course delivered at a company s facility by Matrix Engineering, an approved provider of Bolt Science Training

A Tale of Tearouts: Web Supplement

Subject Index. Bearing damage, in bolted, composite-metal

Design of Machine Elements I Prof. G. Chakraborty Department of Mechanical Engineering Indian Institute of Technology Kharagpur

HEICO FASTENING SYSTEMS. Simple Fast Reliable HEICO-TEC TENSION NUT

Bolted Joint Design. Mechanical Properties of Steel Fasteners in Service

Riveted Joints : Types and Uses

A training course delivered at a company s facility by Matrix Engineering, an approved provider of Bolt Science Training

Bolt Tensioning. This document is a summary of...

Welded connections Welded connections are basically the same design in AISI as in AISC. Minor differences are present and outlined below.

712 - STRUCTURAL STEEL CONSTRUCTION SECTION 712 STRUCTURAL STEEL CONSTRUCTION

Proposed changes on NZS 3404 specified part-turn method of tensioning high strength friction grip (HSFG) property class 8.8 bolts

Shear strength of high-strength bolts

UNIVERSITY OF THESSALY

Skewed connections result when members frame to each

Anti-check bolts as means of repair for damaged split ring connections

Disclaimer. Socket Products Socket depth limits maximum torque. Torque figures are based on 80% of maximum torque for a given key size.

Load partition and ultimate strength of shingle joints, April 1970.

American Institute of Timber Construction 7012 South Revere Parkway Suite 140 Centennial, CO Phone: 303/ Fax: 303/

Effects of tightening speed on torque coefficient in lag screw timber joints with steel side plates

Effect of Bolt Layout on the Mechanical Behavior of Four Bolted Shear Joint

Fasteners Table of Contents

Experimental Evaluation of Metal Composite Multi Bolt Radial Joint on Laminate Level, under uni Axial Tensile Loading

Comparative Evaluation of Resistance Made Simple Shear Connection with Bolts and With Welding

Instruction Manual for Installing HIGH-STRENGTH BOLTS

4-Bolt Wood-to-Steel Connections

Hazlan Abdul Hamid* & Mohammad Iqbal Shah Harsad

ISO INTERNATIONAL STANDARD. Fasteners Torque/clamp force testing. Éléments de fixation Essais couple/tension. First edition

Power Threads. Shigley s Mechanical Engineering Design

Lawrence A. Soltis, M. and Robert J. Ross, M. 1

DTFACT 16 C IN PAVEMENT LIGHT FIXTURE TESTING AND ANALYSIS FINAL SUMMARY PRESENTATION

Structural Strength of Lapped Cold-Formed Steel Z-Shaped Purlin Connections with Vertical Slotted Holes

INSTALLATION CHARACTERISTICS OF ASTM F1852 TWIST-OFF TYPE TENSION CONTROL STRUCTURAL BOLT/NUT/WASHER ASSEMBLIES

DTI s. Direct Tension Indicators. Hardened Steel Washers. Leading provider of bolt loading & removal solutions

Dowel connections in laminated strand lumber

THE GATE COACHAll Rights Reserved 28, Jia Sarai N.Delhi ,-9998

Innovation in mechanical fastening technology for maintenance free joints

MECH 344/M Machine Element Design

HEICO-LOCK WEDGE LOCK WASHERS

ENGINEERING FUNDAMENTALS

USER MANUAL Nord-Lock X-series washers

LOCTITE WEBINAR SERIES Threadlocking & the Torque-Tension Relationship

A training course delivered to Engineers and Designers, at a company s premises, on the technical aspects of bolting.

INSTALLATION MANUAL IOWA MOLD TOOLING CO., INC. BOX 189, GARNER, IA MANUAL PART NUMBER:

Big Bolts Better? Choices for Performance and Economy

Tightening Strategies for Bolted Joints Methods for Controlling and Analyzing Tightening

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

Threaded Fasteners 2. Shigley s Mechanical Engineering Design

RlGIDITY AND STRENGTH OF WALL FRAMES BRACED WlTH METAL STRAPPING

FIRE STATION NO TH STREET NORTH ST. PETERSBURG, FL M-1 SCOPE OF WORK SYMBOL DESCRIPTION SYMBOL DESCRIPTION HVAC SYMBOL LEGEND

Connection Philosophy. p NDS Chapter-by-chapter description Changes from previous editions Examples. Part 1: Member Design Webinar.

STUDY AND ANALYSIS OF ANGULAR TORQUING OF ENGINE CYLINDER-HEAD BOLTS USING TORQUE-TO-YIELD BOLTS: A CASE STUDY

S. Ramhormozian 1, G.C. Clifton 2 and H. Nguyen 3

ISO INTERNATIONAL STANDARD. Fasteners Torque/clamp force testing. Éléments de fixation Essais couple/tension. First edition

DEFORMATION CAPACITY OF large DIAMETER mgh STRENGTH BOLTS wrru WAISTED SHANK SUBJECTED TO AXIAL TENSIlE FORCE. (Received October 15, 2001)

FASTENERS, MEASUREMENTS AND CONVERSIONS

The Wood Products Council is a Registered Provider with. . Credit(s) earned on completion of this program will be

General Specification

low or medium carbon steel, fully or partially annealed

SECTION 3. BOLTS. bolt is a standard AN-type or a special-purpose bolt, and sometimes include the manufacturer.

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

Development of a New-Generation Dowel and Screw Combination 2014 International Crosstie and Fastening System Symposium Urbana, IL, USA 3 June 2014

c. Pins, bolts, and retaining rings b. Washers, locking nuts, and rivets

SuperMount Series Installation instructions for SuperMount 46, 68 & 80 wall structures Bill Of Materials

Structural and Thermal Analysis of Bolted joint of Coiler Drum in Steckel Mill using Finite Element Method

REVIEW OF THREADED FASTENERS LOOSENING AND ITS EFFECTS

S-BT screw-in stainless steel and carbon steel threaded studs

Stress Analysis Of Bolted Joint

Transcription:

December, 1958-1 FURTHER STATIC TENSION TESTS OF BOLTED JOINTS 1. Introduction A B S T RAe T Tests of two joints using I" and 1 1/8" bolts confirm the findings of previous tests using 7/8" high strength bolts. Balanced design can be achieved by using a T/S ratio of 1.00/1.10. Fritz Engineering Laboratory Report No. 271.1, "Static Tension Tests of Bolted Joints" reports on the strength of joints fastened with 7/8" high strength bolts. The most important information gained from those tests is that for a balanced design the Tension/Shear ratio should be about 1.00/1.10. To verify this finding two additional joints have been.tested using It! and 1 1/8t! bolts at the above T/S ratio. II. Description of Test.Joints The additional joints were similar in construction to those of the B series (7/8t! bolts) in that they were half butt joints with the main plate made up of two 18" x It! steel plates and the lap plates each an 18" X I" plate. Joint A3 used 16-1" bolts arranged in a compact pattern of 4 longitudinal lines at a gage of 4 1/2" and 4 transverse rows at a pitch of 4". Thus, gld and p/d were ina range comparable to those of the B joints. The T/S equaled 1.00/1.10. Joint Gl had 12-1 1/8" bolts in 4 lines'and 3 rows. The gage and pitch dimensions were th.e same as for A3 hence g/d and p/d were slightly different but still within practice. TheT/S equaled 1.00/1.11.

-2 III. Material Properties The plate used wa.s AS'IM-A7 structural steel as described in the report of the B-series. that report under A3B3 The properties may be formed in Table II of and G1B2. The bolts used were AS'IM-A325 high strength bolts (5 1/2" under head for 1" bolts and 6" for 1 1/8") These bolts were not as close to minimum strength as the 7/8" bolts used in the B-series. Load-e1ongation calibration curves determined by direct tension for 5 bolts of each lot showed that the bolts possessed the required minimum proof loads and the following ultimate loads. Direct Tension Tests of Bolts Ultimate Ultimate Bolt No. Load, lbs Bolt No. Load, lbs. A128 72,000.G15 88,750 A129 74,000 G24 93,750 A155 73,750 G28 90,000 A156 74,500 G29 91,500 A157 74,000 G30 92,000 Avg. 74,100 Avg. 91,200 Specs. 69,700 Specs. 80,100 Shear tests on individual bolts and mill scale faying surfaces have shown that the ultimate effective shear stress of the high strength bolt is about 70% of the ultimate tensile stress on the stress area. On that basis the e'ffective shear strength of the A and G bolts would be 85.6 ksi and 83.7 ksi respectively.

-3 IV. Fabrication of Test Joints The shop fabrication of joint A3 was identical to that for the B series, the corner holes being subdrilled and reamed while all other holes were drilled thru 4 plies. The procedure forgl differed because that joint was made by altering jointa2(20-1" Bolts) which had been. fabricated before it was decided that testing of it would be unnecessa.ry. Thus, to produce Gl, two rows of holes were burned off of A2 and the remaining 1 1/16" holes were reamed to 1 3/16". Faying surfaces were mill scale. An erection crew of Bethlehem Steel Company bolted both joints using their current field procedure which in this case meant turning the nut 1/2 turn from the snug position using the impa.ct wrench. Bolt lengths were measured before and after tightening and the elongations were converted to tension by means of a direct tension vs. elongation calibration urve. In Joint A3 bolt elongations varied from 0.0107" to 0.0395" with an average of 0.0317", or a clamping force per bolt of 60,500 lbs. In JointGl the range was from 0.390" to 0.715", and an average of 0.0519: converts to 78,000 lbs per bolt. V.lnstrumentation The instrumentation was similar to that used on Joint B6 and consisted of SR4 gages, slide bar extensometer to measure pitch elongation, and dial gages to measure the total elongation of the bolt pattern.

-4 VI. Test Procedure The test procedure was the same as that employed for the B-series. VII. Test Results A summary of the results of these tests is given in Table 1. The behavior of these specimens under load was similar to the behavior. of the B joi.nts. In the early stages - minor slips, then the major slip distingui.shed by a loud noise, and then further scraping and grating as additional minor slips brought the joint into full bearing. The failure of A3 took place in two stages which followed one another in a few seconds. At a load of l820 k (Nominal bolt shear stress = 75.2 ksi, average tensi.le str.'ess on.net section. ::: 66.2.ksi) the nut end of bolt 1ft 160 (top, south corner) sheared off and before the testing machine could be unloaded all the rema:i.ud.ngbolts sheared. Bolts in the upper three rows single sheared while. those of the bottom row double sheared. The final configuri::\tiol1. of t:b~ pla.tes was sim.ilar to that for B3, one lap plate being very mu.ch ber-t. The commercial length of thread on the 1" bolts placed the thread run out at the shearing plane so there Wa.s probably some reduced area effect. Each row of bolts show8d a. slightly different type of failure as follows: Top row (end of lap plates) Second row rupture plane cut diagonally across two threads rupture plane cut normal to bolt axis at thread run.out but two threads down a crack develpped at the root of the thread penetra.ting ha.lf way through the bolt

-5 Third row Bottom row rupture pla.ne cut normal to bolt axis at thread run out bolts double sheared on planes n.ormal to the axis During.the testin.g of Gl co.r!.siderable di.shing of the washer under top corner bolt fl9 was notic.ed at: a loa.d of 1200 kips. This was the first time that a marked deformation h.~.d beem rwti.ced at such a. low load. It was thought at the time that this portlf~nded :r:t weakness and possibly an early failure. How'ever, as th.e test turned out, there appeared to be no detrimental behavior of this b':jilt. The rupture of Gl occurred a.t a loa.d of l79s k when all of the bolts sheared. (Nominal boltshel'.:r stress:; 75.2 ksi, average tensile stress on net section = 67.8 ksi) Onc:e again the upper rows single sheared and three of the four bolts on the bottom ro...! double sheb:red. The holes showed large deforma.tions, pa,ttic.ularly the corner holes in the main plate which became ellipses wit:!:::. major axes of 1 1/2" inclined inward at the top at o about 10. The hei":ld end lap plat.(~ "Tas bent as i.n B3 and A3 indicating a momentary change to l1. L'3lp joint prior to c.omp1ete disengagement of the plates. The c.oielm~rcie.l thre.ad length place:;d thread run..outat the shearing plane and the bolt: sh(",ars occm:redl1lormal to the shank at this point. Several of the bolts 0:'2 dice top row showed signs of tearing at the root two threads dowti as repor.ted for A3. The ear1i.er. load-elongati.on curves for t,1:lese. joints are typical of those reported They show that in the elasti.c range the elongation that occurs is slightly less tha.n that predicted by PL/AE where A is the gross area. Each joi.nt showed a slip of about 0.08" and thereafter ea.ch curve proceeded upward at a.much flatter slope than tna:t of the elastic range.

-6 VIII. Summary and Conclusions The results of these two tests confirm the conclusions drawn from the tests on the 7/8" bolts. The T/S of 1.00/1.10 produced bolt failures but at the same time the tensile stress on the net section was above the average coupon strength thus indicating for all practical purposes a balanced design. Major slip occurred at nominal bolt shears well above the range of normal working loads. Joint elongation may be predicted satisfactorily by considering the joint as solid material equivalent to the main material. The average nominal bolt shear stress at failure in.a3 was of a single bolt value and ingl was 90%. \. 15.1 : g+.o

271. 2-7,, Pattern TABLE 1 RESULTS OF TESTS Units A3 G1 HE 1-'---- EEa f---- Number of A325 16 1" 12 1" - - 1'8" Bolts Nominal Gross Area sq in 36.0 36.0 Nominal Net Area sq in 27.5 26.5 Nominal Shear Area sq in 25.1 23.9 Tension: Shear Ratio. 1:1.10 1:1.11 Slip Load (Major) kips 843 920 Nomi.na1 Bolt Shear ksi 33.6 38.5 Tension on Net Section ksi 30.7 34.7 Average Extension of Bolts in.0317._0519 Initial Clamping Force kips 968 936 Coefficient of Friction 0.435 0.491. Ultimate Load kips 1820 1798 Nominal Bolt Shear ksi 72.5 75.2 Tension on Net Section ksi 66.2 67.8 Type of Failure Shear Shear of of bolts bolts