Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Similar documents
Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

2020 P a g e. Figure.2: Line diagram of series active power filter.

A Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Power Quality improvement of a three phase four wire system using UPQC

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Enhancement of Power Quality using D-Statcom Fed Induction Motor Drive

Simulation Study of PWM Techniques for Voltage Source Converters

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

Chapter 2 Shunt Active Power Filter

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Key terms: Voltage, Phase Angle, FACTS, Multilevel Converter, Power Quality, STATCOM.

Control Of Shunt Active Filter Based On Instantaneous Power Theory

A NOVEL APPROACH TO ENHANCE THE POWER QUALITY USING CMLI BASED CUSTOM POWER DEVICES

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

Power Quality enhancement of a distribution line with DSTATCOM

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Indirect Current Control of LCL Based Shunt Active Power Filter

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

SHUNT ACTIVE POWER FILTER

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

FFT Analysis of THD in Distribution System with Grid Connected RES

Review on Shunt Active Power Filter for Three Phase Four Wire System

Application of Fuzzy Logic Controller in Shunt Active Power Filter

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

A Comparative Study of Different Topologies of Multilevel Inverters

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Modeling of Statcom. P.M. Sarma and Dr. S.V. Jaya Ram Kumar. Department of Electrical & Electronics Engineering GRIET, Hyderabad, India

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

CHAPTER 3 H BRIDGE BASED DVR SYSTEM

Comparison of Reference Current Extraction Methods for Shunt Active Power Filters

Literature Review for Shunt Active Power Filters

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Harmonic Reduction in Five Level Inverter Based Dynamic Voltage Restorer

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Mitigation of Voltage Sag, Swell and Load Hamonics by the Combined Opertation of Series APF and Solar System

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Analysis & Function of Unified Power Quality Conditioner for Power Quality Improvement of Distributed Network

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Mitigation of Flicker Sources & Power Quality Improvement by Using Cascaded Multi-Level Converter Based DSTATCOM

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Power Quality Improvement using Active shunt Power filter using PI Controller

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

Shunt active filter algorithms for a three phase system fed to adjustable speed drive

ENHANCEMENT OF POWER QUALITY USING 9-LEVEL CASCADED H-BRIDGE BASED D-STATCOM WITH IRP THEORY SK. Meeravali* 1, Dr. K.

A Hybrid Cascaded Multilevel Inverter for Interfacing with Renewable Energy Resources

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

ISSN Vol.02,Issue.19, December-2013, Pages:

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Bhanutej Jawabu Naveez Assistant Professor, Vignana Bharathi Institute of Technology, Aushapur, Ghatkesar, Hyderabad.

Development of Multilevel Inverters for Control Applications

Svpwm Technique to Eliminate Harmonics and Power Factor Improvement Using Hybrid Power Filter and By Using Dsp Tms 320lf2407

Power Control Scheme of D-Statcom

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Power Quality Improvement using Shunt Passive Filter

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

Reduction In Total Harmonic Distortion Using Active Power Filters

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

Protection from Voltage Sags and Swells by Using FACTS Controller

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

TRANSFORMER LESS H6-BRIDGE CASCADED STATCOM WITH STAR CONFIGURATION FOR REAL AND REACTIVE POWER COMPENSATION

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

Modeling and Simulation of STATCOM

MATLAB Implementation of a Various Topologies of Multilevel Inverter with Improved THD

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

A Five Level DSTATCOM for Compensation of Reactive Power and Harmonics

Lecture Note. DC-AC PWM Inverters. Prepared by Dr. Oday A Ahmed Website:

A Review on Improvement of Power Quality using D-STATCOM

Level Shifted Pulse Width Modulation in Three Phase Multilevel Inverter for Power Quality Improvement

B.Tech Academic Projects EEE (Simulation)

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

Analysis the Modeling and Control of Integrated STATCOM System to Improve Power System

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Transcription:

Multi Level Inverter Based Active Power Filter for Harmonic Reduction K Siva Gopi Raju Department of Electrical and Electronics Engineering, Andhra University, Visakhapatnam, Andhra Pradesh 530003, India. Abstract A shunt active power filter reduces the harmonic content due to non linear loads to a percentage below 5. But due to inverter configuration of filter the harmonic reduction is limited to some value. In this project the harmonic content is further reduced by modifying the inverter configuration. Multi level inverter provides sine wave by increasing the level at the output. The general configuration is 3 level which is modified to 5 level inverter. The results will be analyzed by using matlab simulink software. Index Terms multi level inverter, active power filter, total harmonic distortion. I. Introduction With the advent of power semiconductor switching devices like SCRs, GTO's, IGBT's (Insulated Gate Bipolar Transistors) and many more devices, control of electric power has become a reality. Such power electronic controllers are widely used to feed electric power to electrical loads, such as adjustable speed drives (ASD's), furnaces, computer power supplies, HVDC systems etc [1]. The power electronic devices due to their inherent nonlinearity draw harmonic and reactive power from the supply. In three phase systems, they could also cause unbalance and draw excessive neutral currents. The injected harmonics, reactive power burden, unbalance, and excessive neutral currents cause low system efficiency and poor power factor [2-4]. K Padma Department of Electrical and Electronics Engineering, Andhra University, Visakhapatnam, Andhra Pradesh 530003, India. In addition to this, the power system is subjected to various transients like voltage sags, swells, flickers etc. These transients would affect the voltage at distribution levels. Excessive reactive power of loads would increase the generating capacity of generating stations and increase the transmission losses in lines. Hence supply of reactive power at the load ends becomes essential. Power Quality (PQ) has become an important issue since many loads at various distribution ends like adjustable speed drives, process Industries, Printers, domestic Utilities, computers, microprocessor based equipments etc. have become intolerant to voltage fluctuations, harmonic content and interruptions [3]. Power Quality (PQ) mainly deals with issues like maintaining a fixed voltage at the Point of Common Coupling (PCC) for various distribution voltage levels irrespective of voltage fluctuations, maintaining near unity power factor power drawn from the supply, blocking of voltage and current unbalance from passing upwards from various distribution levels, reduction of voltage and current harmonics in the system and suppression of excessive supply neutral current [4]. Conventionally, passive LC filters and fixed compensating devices with some degree of variation like SCR switched capacitors, SCR switched reactors were employed to improve the power factor of ac loads. Such Cite this article as: K Siva Gopi Raju & K Padma, "Multi Level Inverter Based Active Power Filter for Harmonic Reduction", International Journal & Magazine of Engineering, Technology, Management and Research, Volume 5 Issue 9, 2018, Page 102-108. Page 102

devices have the demerits of fixed compensation, large size, ageing and resonance. Nowadays equipments using power semiconductor devices, generally known as active power filters (APF's), Active Power Line Conditioners (APLC's) etc. are used for the power quality issues due to their dynamic and adjustable solutions. Flexible AC Transmission Systems (FACTS) and Custom Power products like STATCOM (Static synchronous compensator), DVR (Dynamic Voltage Restorer), etc, [5] deal with the issues related to power quality using similar control strategies and concepts. Basically, they are different only in the location in a power system where they are deployed and the objectives for which they are deployed z. II. ACTIVE POWER FILTERS Current Source Inverter (CSI) Active Power Filter [Fig 2.1.1(a)] and Voltage Source Inverter (VSI) Active Power Filter [Fig 2.1.1(b)] are two classifications in this category. Current Source Inverter behaves as a nonsinusoidal current source to meet the harmonic current requirement of the nonlinear loads. A diode is used in series with the self-commutating device (IGBT) for reverse voltage blocking. However, GTO-based configurations do not need the series diode, but they have restricted frequency of switching. They are considered sufficiently reliable, but have higher losses and require higher values of parallel ac power capacitors. Moreover, they cannot be used in multilevel or multistep modes to improve performance in higher ratings. The other converter used as an AF is a voltage-fed PWM inverter structure, as shown in Fig 2.1.1(b).It has a self-supporting dc voltage bus with a large dc capacitor. It has become more dominant, since it is lighter, cheaper, and expandable to multilevel and multistep versions, to enhance the performance with lower switching frequencies. It is more popular in UPSbased applications, because in the presence of mains, the same Inverter Bridge can be used as an AF to eliminate harmonics of critical nonlinear loads [6]. Fig 2.1.1(a) Current fed type AF Fig 2.1.1(b) Voltage fed type AF 3 DSTATCOM compensating AC and DC loads: Due to the simplicity, the absence of the unbalance in the dc link voltage and independent current tracking with respect to other phases, a three phase H-Bridge VSI topology is chosen. The following figure 3.3: shows a three phase-four-wire-compensated system using H- bridge VSI topology-based DSTATCOM compensating unbalanced and nonlinear ac load. Figure 3.3: showing a three phase-four wire compensated system using the H-bridge VSI topology-based DSTATCOM Page 103

A dc load ( ) is connected across the dc link. The DSTATCOM consists of 12 insulated-gate bipolar transistor(igbt) switches each with an antiparallel diode, dc strorage capacitor, three isolation transformers and three interface conductors.the statr point of the isolation transformers( ) is connected to the neutral of load( ) and source (N). The H-bridge VSIs are connected to the PCC through interface inductors. The isolation transformers prevent a short circuit of the dc capacitor for various combinations of switching states of the VSI. The inductance and resistance of the isolation transformers are also included in and. The source voltages are assumed to be balanced and sinusoidal. With this supply being considered as a stiff source, the feeder impedance( - ) shown in the above figure.1: is negligible and hence it is not accounted in state-space modelling. To track the desired compensator currents, the VSIs operate under the hysterisis band current control mode due to their simplicity, fast response, and being independent of the load parameters. The DSTATCOM injects currents in to the PCC in such a way as to cancel unbalance and harmonics in the load currents. The VSI operation is supported by the dc storage capacitor with voltage across it. The dc bus voltage has two functions, that is, to support the compensator operationand to supply dc load. While compensating, the DSTATCOM mantains the balanced sinusoidal source currents with unity power factor and supplies the dc load through its dc bus. IV MULTI LEVEL INVERTERS The multilevel inverters have drawn tremendous interest in the power industry. They present a new set of features hat are well suited for use in reactive power compensation. It may be easier to produce a high-power, high-voltage inverter with the multilevel structure because of the way in which device stresses are controlled in the structure. Increasing the umber of voltage levels in the inverter without requiring higher ratings on individual devices can increase the power rating. The unique structure of multilevel voltage source inverters allows them to reach high voltages with low harmonics without the use of transformers or seriesconnected synchronized-switching devices. As the number of voltage levels increases, the harmonic content of the output voltage waveform decreases significantly. 5.1. Types of multilevel inverter The general structure of the multilevel converter is to synthesize a near sinusoidal voltage sources. As the number of level increases, the synthesized output waveform has more steps, which produce a staircase wave that approaches a desired waveform. Also, as more steps are added to the waveform, the harmonic distortion of the output wave decreases, approaching zero as the number of levels increases. As the number of levels increases, the voltage that can be spanned by summing multiple voltage levels also increases. The output voltage during the positive half-cycle can be found from..(5.1.) Where SFn is the switching or control function of nth node and it takes a value of 0 or 1. The multilevel inverters can be classified into three types. 1. Diode-clamped multilevel inverter; 2. Flying-capacitors multilevel inverter; 3. Cascaded multilevel inverter. 5.1.1 Diode-Clamped Multilevel Inverter Diode-clamped multilevel (m-level) inverter typically consists of (m-1) capacitors on the dc bus and produces m levels on the phase voltage. An m-level inverter leg 2(m-1) Switching devices and (m-1) (m-2) clamping diodes. The major advantages of the diode-clamped inverter can be summarized as follows: 1. When the number of level is high enough, the harmonic content is low enough to avoid the need for filters. 2. Inverter efficiency is high because all devices are switched at the fundamental frequency. Page 104

The major disadvantages of the diode-clamped inverter can be summarized as follows: 1. Excessive clamping diodes are require when the number of levels is high. 2. It is difficult to control the real power flow of the individual converter in multi-converter systems. 5.1.2 Flying-Capacitors Multilevel Inverter The dc bus needs (m-1) capacitors for an m-level converter. The number of capacitors required for each phase is.(5.2.) Thus for m=5, Nc=10. The major advantages of the Flying-Capacitors Multilevel inverter can be summarized as follows: 1. Phase redundancies are available for balancing the voltage levels of the capacitors. 2. Real and reactive power flow can be controlled. 3. The large number of capacitors enables the inverter to ride through short duration outages and deep voltage sags. The major disadvantages of the Flying-Capacitors Multilevel inverter can be summarized as follows: Control is complicated to track the voltage levels for all of the capacitors. Also, recharging all of the capacitors to the same voltage level and startup are complex. Switching utilization and efficiency are poor for real power transmission. The large numbers of capacitors are both more expensive and bulky than clamping diodes in multilevel diode-clamped converters. Packaging is also more difficult in inverters with a high number of levels. VOLTAGE SOURCE CONVERTER (VSC) A voltage-source converter is a power electronic device that connected in shunt or parallel to the system. It can generate a sinusoidal voltage with any required magnitude, frequency and phase angle. It also converts the DC voltage across storage devices into a set of three phase AC output voltages. It is also capable to generate or absorbs reactive power. If the output voltage of the VSC is greater than AC bus terminal voltages, is said to be in capacitive mode. So, it will compensate the reactive power through AC system. The type of power switch used is an IGBT in anti-parallel with a diode. The three phase four leg VSI is modeled in Simulink by using IGBT. Voltage source converters are preferred over current source converter because it is higher in efficiency and lower initial cost than the current source converters. They can be readily expanded in parallel to increase their combined rating and their switching rate can be increased if they are carefully controlled so that their individual switching times do not coincide. Therefore, higher-order harmonics can be eliminated by using converters without increasing individual converter switching rates. 5.3 CONTROL TECHNIQUE USED FOR INTERFACING INVERTER TO ACT AS SHUNT APF CASCADED H BRIDGE INVERTER Fig 4.3: Control scheme Page 105

The turn on and turn off instants of inverter switches should be such that the load and the connected RES could appear as balanced load to the system. The dc link voltage, Vdc is sensed at a regular interval and is compared with its reference counterpart Vdc*. The error signal is processed in a PI-controller. The output of the pi controller is denoted as Im. The reference current templates (Ia*, Ib*, and Ic*) are obtained by multiplying this peak value (Im) by the three-unit sine vectors (Ua, Ub and Uc) in phase with the three source voltages. These unit sine vectors are obtained from the three sensed line to neutral voltages. The reference grid neutral current (In*) is set to zero, being the instantaneous sum of balanced grid currents. Multiplication of magnitude Im with phases (Ua, Ub, and Uc) results in the three phase reference supply currents (Ia*, Ib*, and Ic*). The grid synchronizing angle (Ѳ) obtained from phase locked loop (PLL) is used to generate unity vector template as {4.1} {4.3} {4.2} The instantaneous values of reference three phase grid currents are compute as {4.4} The neutral current is considered as {4.6} {4.7} {4.5} * The reference grid currents(i a *, I b, I * c and I * n ) are compared with actual grid currents(i a, I b, I c and I n ) to compute the current errors as {4.8} {4.10} {4.9} {4.11} These errors are given to hysteresis current controller then generate the switching pulses for six IGBTs of the grid interfacing inverter. 5.4 MATLAB /SIMULINK MODEL OF PI CONTROL Fig.4.6: MATLAB Simulink model of PI control 5.5 NON LINEAR LOAD: A three phase four leg diode rectifier feeding an RL load is considered as a non-linear load. The load is modeled in Simulink by using diodes. 5.6 MATLAB/SIMULINK MODEL OF THE PROPOSED SYSTEM Fig.4.7: MATLAB Simulink model of the proposed system Page 106

Mag (% of Fundamental) Fig.4.7: MATLAB Simulink model of the Using multi level inverter THD ANALYSIS FOR NON LINEAR LOAD Fig.5.3: THD of Source Current after Compensation 5 0-5 Selected signal: 17.5 cycles. FFT window (in red): 1 cycles Total Harmonic Distortion of Source Current after Compensation = 3.13% 0.05 0.1 0.15 0.2 0.25 0.3 0.35 Time (s) Fundamental (50Hz) = 9.472, THD= 30.13% 20 15 10 5 0 0 100 200 300 400 500 600 700 800 Frequency (Hz) Fig.5.2: THD of Source Current before Compensation Total Harmonic Distortion of Source Current before Compensation = 30.13% Source current using multi level inverter Page 107

Power Electron., vol. 19, no. 6, pp. 1586 1593,Nov. 2004 [3] Singh.B, Chandra.A, Al-Haddad.K, "A review of active filters for power quality improvement," IEEE Trans. Industrial Electronics, Vol. 46, pp. 960-971, Oct. 1999. [4] L Dinesh. M Divakar J uday venkatesh. DC Voltage Feedback Control to Active Power Filter for Harmonic Reduction. Journal of Energy Technologies and Policy. Iiste. [5] L. Gyugi and E. C. Strycula, Active AC Power Filters, IEEE-IAS Annual Meeting Record, 1976, pp. 529-535 Source current THD using multi level inverter vii. conclusions Multi level inverter based active harmonic filter is developed in which the total harmonic distortion is less when the controller is based on inverter configuration. A 5 level inverter based inverter is developed in which the pulse number is increased in which the harmonic content will be reduced. By using 3 level inverter the THD is 3.13 percentage. And by using 5 level inverter the THD is 0.99 percentage. The results are analyzed using matlab simulink software. [6] L. Dinesh, H. Sesham, and V. Manoj, Simulation of D-Statcom with Hysteresis Current Controller for Harmonic Reduction, International Conference on Emerging Trends in Electrical Engineering and Energy Management (ICETEEEM), Chennai, pp. 104-108, 2012. viii. References [1] J. M. Guerrero, L. G. de Vicuna, J. Matas, M. Castilla, and J. Miret, A wireless controller to enhance dynamic performance of parallel invertersin distributed generation systems, IEEE Trans. Power Electron.,vol. 19, no. 5, pp. 1205 1213, Sep. 2004. [2] J. H. R. Enslin and P. J. M. Heskes, Harmonic interaction betweena large number of distributed power inverters and the distribution network, IEEE Trans. Page 108