Manhole or Catch Basin Type A & B Cone Sections Precast - Design F Manhole or Catch Basin Cover (Reducer Cone Section Precast) Design D

Similar documents
SUBJECT: Standard Plate 9102 Turf Establishment Areas At Pipe Culvert Ends

SUBJECT: Standard Plate Turf Establishment Areas (at Pipe Culvert Ends)

Standard Plate 7036 is discontinued. It is replaced by Standard Plan Pedestrian Curb Ramp Details.

2. Remove from the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates (August 31, 2012)

INSTRUCTIONS: 1. Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual.

SUBJECT: Standard Plates 4132, 4155, Drainage Structures and Castings Info

Current Standard Plates including Transmittal Letters are available on the web at:

Current Standard Plates including Transmittal Letters are available on the web at:

Standard Plate Sheer Reinforcement for Precast Drainage Structures has been updated upon recommendation of the Bridge Office.

Plate 8132A - Preformed Rigid PVC Conduit Loop Detector, is a new plate requested by OTST.

DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA

STANDARD DRAWINGS INDEX MODIFIED FOR CENTRAL REGION Revised August 6, 2018

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION

Government Of Newfoundland & Labrador Municipal Water, Sewer And Roads Master Construction Specifications

MSD STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY

STANDARD BID ITEM NUMBERS

Pipe Product Catalog Table of Contents

Miscellaneous. Demolition

STORM M ANHOLE FOR 42" PIPE AND SM ALLER JOB NO. SHEET NO. DATE MARCH 2015 OF MIN OF 3 CRSES MAX OF 5 CRSES 30"MAX 3 OR 3.5 PRECAST ECCENTIC CONC

CITY OF VISTA STANDARD DRAWINGS

CITY OF DANA POINT DEVELOPMENT REVIEW

CITY OF VISTA STANDARD DRAWINGS

LETTING : CALL : 029 COUNTIES : GOODHUE

STANDARD CATCH BASIN GUTTER LINE CB INLET FRAME & GRATE, GROUTED TO GRADE RINGS AS REQ'D CONCRETE CURB FINISHED GRADE ASPHALT MAX 50 MIN

MAINTENANCE HOLES, CATCH BASINS AND DITCH INLETS - MTC FORM 407 INDEX

50.24 Type, Size and Location Plans for Culverts, Bridges and Culvert Bridges

SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS

City of Regina Standard Construction Specification SECTION 2999 LISTING OF ROADWAY STANDARD DRAWINGS

City of Vaughan Engineering Department DESIGN STANDARD DRAWINGS

TYPE 4-C TYPE 6 TYPE 7 TYPE 8

MINIMUM C/L RADII OF CURVATURE OF LOCAL ROADS IN SUBDIVISIONS

Ohio Department of Transportation Office of Roadway Engineering January 18, 2013

UTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1

CITY OF SAN MARCOS ENGINEERING DIVISION

STANDARD DETAILS Crow Canyon Road San Ramon, CA Telephone: (925) Fax: (925)

5/16" Flange nut. Bolt Keeper Plate (8" Sq. SYS.) (3) 1/2" x 3" Hex head connector zinc plated bolt w/ washers and nut. Anchor 3" sq. 7 Ga.

RAIL PANEL AT TRANSITION SECTION PLAN - POST DETAIL PLAN - TUBE SPLICE. Colorado Department of Transportation. Staff Bridge Branch

SUPPLEMENTARY STANDARD DETAIL DRAWINGS

E:\Wilmot\DGN\14018pp.dgn 3/11/2015 6:49:16 AM

Existing and proposed contours at 1-foot intervals. The fill and/or excavation quantities in cubic yards.

VILLAGE OF VILLA PARK CENTRAL BOULEVARD IMPROVEMENTS LOCATION MAP (NOT TO SCALE) CORTESI AVE. MYRTLE AVE. CENTRAL BLVD.

Appendix C Construction Details

MDOTProjectwise\Documents\Reference Documents\Traffic Reference\Statewide Special Details\Develop

STANDARD AND EXAMPLE DRAWINGS

SECTION 8: DRAINAGE, SEWER AND WATER SUPPLY NETWORKS

Manholes Table of Contents

3. DESIGN SPECIFICATIONS

MH Table of Contents Standard Title/Scope Page Table of Contents SCE Public

24" B B Joint X501 Joint See MARKINGS Note PCB-RXX-350-TL3 " X501 Y301 (Typ.) " A PLAN (reinforced casting option shown) A " dia. Hinge Bar (Typ.) NOT

CONCRETE MANHOLES.

SECTION MANHOLES

Standard Details Index NWTP Improvements and MF System Installation

Revised BRIDGE REPORT AND LAYOUT PAVEMENT STRUCTURE DESIGN CHAPTER VII UTILITIES CHAPTER VIII TRAFFIC CONTROL DEVICES

RECORD DRAWINGS REVISED TO CONFORM TO CONSTRUCTION RECORDS PROVIDED BY CONTRACTOR GMG BY DATE 11/13 CRS NO.

M I N N E S O T A D O T BID TABULATION SUMMARY JOB PAGE 1 ON 01/14/97 MINNESOTA PROJECT NO.S: DPI 015-8(021) DPI 015-8(022)

CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA (360)

Utility Structures. Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles

1. MATERIALS SHALL CONFORM TO THE FOLLOWING: a) STEEL REINFORCING - WIRE FABRIC (4x4) GALVANIZED - G G REINFORCING EARS TO BE EPOXY CO

ROUTES: 65 SECTIONS: miles in length. THE FOLLOWING ITEMS AND APPROXIMATE QUANTITIES ARE INVOLVED:

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes

SECTION MANHOLES

C-M TMR Products Index

FOR SERVICE BOXES IN CONCRETE DRIVEWAYS, SEE NOTE Min. COVER UNDER DITCHES. 600 Min. COVER

F-4 FURNITURE. Contents

CITY OF REEDLEY NEW DEVELOPMENT PLAN REVIEW CHECK LIST

City of Massillon Site Plan Checklist

PART MATERIALS. Section Fencing Materials. Description

SECTION G ESTIMATE OF QUANTITIES

Anti-Trust Statement

CITY OF MUSKEGO DRAFTING STANDARDS

MAY J. Collins Engineering Associates, LLC San Jose Blvd. Jacksonville, Florida 32223

SIGN MOUNTED BEACON SIG-027-A SINGLE SIGN MOUNTED FLASHING BEACON INSTALLED ON ONE WOOD POST DETAIL "A-1"

Plan Preparation Checklist

CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION

Item 550 Chain Link Fence

DELINEATOR REFERENCE POINT 200' TYPICAL SPACING (YELLOW DELINEATORS) END OF MERGE LANE TAPER DELINEATOR REFERENCE POINT

City of Beaumont. Public Works Engineering. Street Improvement Plan Checklist REV 4/18/16

INSTALLATION GUIDE PermaTrak. Patented Product: U.S. Patent #5,906,084 #8,302,362 #8,522,505 #8,839,588 #9,096,975

Survey Requirements. Design Guidelines and Standards. June Office of the University Architect

Survey Control Point Observations

SIGNALS AND LIGHTING FIELD GUIDE

F-5-1a. Concrete Bollards (Detail 1 of 2) WEIGHT: 166kg. WEIGHT: 227kg. WEIGHT: 113kg. WEIGHT: 212kg

LONCY LEAKE BASEBALL FIELD RENOVATION MESQUITE, TX PROJECT NO ISSUED FOR PROPOSALS

SECTION 9.00 AS-BUILT DRAWING REQUIREMENTS SUB-INDEX

STEEL PIPE GUIDERAIL 01/01/

REVISIONS INDEX 2016 ROAD & BRIDGE STANDARDS. September 2017 Revision Letter August 2017 Revision Letter February 2017 Revision Letter

Midwest Roadside Safety Facility

BRIDGE RAILING, 4 TUBE B-26-F POST DETAILS MICHIGAN DEPARTMENT OF TRANSPORTATION

"A" "A" SECTION "A-A" X-SECTION VERTICAL CURB (TYPE B) Village STREET & PAVEMENT STR-05. Engineering Department

PLAN RATINGS & COMMON ERRORS TO WATCH FOR IN PLANS

Midwest Roadside Safety Facility

Anne Arundel County Dept. of Inspections and Permits Storm Drain Checklist

STRUCTURES FOR SANITARY AND STORM SEWERS

Porter County Plan Commission

Survey Data and TOPO Checklist

EXTERIOR BUILDING, ROOFING, AND SITE IMPROVEMENTS

Project Name: County File No.: Checked by: For: Date:

CHAPTER 11. Plan Standards

SKT-SP Tangent Terminal

SECTION 39 - MANHOLES TABLE OF CONTENTS

Transcription:

MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (14-02) MANUAL: Standard Plates DATED: April 21, 2014 SUBJECT: Standard Plates 4005 and 4018 Manhole or Catch Basin The following Standard Plate has been updated: 4005 - Manhole or Catch Basin Type A & B Cone Sections Precast - Design F 4018 - Manhole or Catch Basin Cover (Reducer Cone Section Precast) Design D See the associated Summary of Change documents for specifics. INSTRUCTIONS: Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual. The previous Transmittal Letter No. issued for this manual was 14-01 dated March 11, 2014. Remove from the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates Standard Plate 4005L, Manhole or Catch Basin Type A & B Cone Sections Precast - Design F Standard Plate 4018A, Manhole or Catch Basin Cover (Reducer Cone Section Precast) Design D Insert into the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates (April 16, 2014) Standard Plate 4005M, Manhole or Catch Basin Type A & B Cone Sections Precast - Design F (April 16, 2014) (Backside 4006L) Standard Plate 4017C (Backside 4018B, Manhole or Catch Basin Cover (Reducer Cone Section Precast) Design D) (April 16, 2014) Current Standard Plates including Transmittal Letters are available on the web at: http://standardplates.dot.state.mn.us/stdplate.aspx Direct any technical questions regarding this transmittal to Ron Reemer, Design Standards Unit at (651) 366-4707. Michael Elle, P.E. Design Standards Engineer

THIS PAGE INTENTIONALLY LEFT BLANK

Summary of Changes Standard Plate 4005M Manhole or Catch Basin (Type A & B cone sections) Transmittal Letter No. (14-02) General: 1. Plate number incremented from 4005L to 4005M Notes: The following sentence added to the end of numbered note 5: NO PIPE OR STRUCTURE ALLOWED ABOVE TOP OF CONE.

Summary of Changes Standard Plate 4018B Manhole or Catch Basin (Reducer cone section) Transmittal Letter No. (14-02) General: 1. Plate number incremented from 4018A to 4018B Section A-A: A dimension was added for depth. Notes: The following numbered note 4 was added: THE MAXIMUM DEPTH FROM THE TOP OF THE CASTING TO THE TOP OF THE REDUCER CONE IS 10-0.

STANDARD PLATES BLANK... 0000 SERIES PAVEMENT... 1000 SERIES BLANK... 2000 SERIES CULVERTS AND APPURTENANCES... 3000 SERIES SEWER APPURTENANCES... 4000 SERIES EROSION CONTROL STRUCTURES... 5000 SERIES BLANK... 6000 SERIES CURB, CURB AND GUTTER, SIDEWALK... 7000 SERIES BARRICADES, SIGNALS, MARKERS, ETC.... 8000 SERIES MISCELLANEOUS... 9000 SERIES PLATE NO. 0000 SERIES BLANK 1000 SERIES PAVEMENT 1070M 1103K 1150R 1210G Supplemental Pavement Reinforcement Typical Dowel Bar Assembly Concrete Header Joints Concrete Pavement Adjacent to Railway Crossing 2000 SERIES BLANK 3000 SERIES CULVERTS AND APPURTENANCES 3000L Reinforced Concrete Pipe (5 Sheets) 3001B Reinforced Concrete Reducer Pipe 3002B Reinforced Concrete Increaser Pipe 3006G Gasket Joint for R.C. Pipe (2 Sheets) 3007E Shear Reinforcement for Precast Drainage Structures 3014J Reinforced Concrete Pipe Arch (2 Sheets) 3020F Reinforced Precast Concrete Cattle Pass (60" & 72") 3022C Precast Concrete Safety Apron (3 Sheets) 3030A Precast Cattle Pass Transition Section 3031B Connection between Existing 4 Ft. X 6 Ft. Cattle Pass and New Precast Transition Section 3040F Corrugated Metal Pipe Culvert (Standard 2-2/3" x 1/2" Corrugation) 3041D Corrugated Metal Pipe (3" x 1" Corrugation) 3050B Design Data Structural Plate Structures (18" Corner Radius) 3051B Design Data Structural Plate Structures (31" Corner Radius) 3065C Connection between Existing Culv. & New "C" Culv. Barrel (2 Sheets) 3066A C.M. Extension for Box Culvert 3100G Concrete Apron for Reinforced Concrete Pipe 3110G Concrete Apron for Reinforced Concrete Pipe-Arch 3114H Sectional Concrete Apron for Reinforced Concrete Pipe-Arch 3122K Metal Apron for C.M. Pipe-Arch Culvert 3123J Metal Apron for C.S. Pipe 3124B Metal Apron Connection 3125A Inlet Protection for Metal Culverts (90" dia. to 96" dia.) 3126B Inlet Protection for Structural Plate Pipe (60" thru 96" dia. or span) 3127A Inlet Protection for Structural Plate Pipe (102" thru 180" dia. or span) MINNESOTA DEPARTMENT OF TRANSPORTATION NUMERICAL INDEX OF STANDARD PLATES (Sheet 1 of 4) April 16, 2014

PLATE NO. 3128H 3129A 3131C 3132A 3133D 3134D 3135A 3136B 3137B 3138B 3139B 3142A 3143C 3145G 3146C 3148A 3221C Metal Safety Apron & Grate (2 Sheets) Metal Apron for Corrugated Polyethylene Pipe (Use at Entrances and Driveways) Precast Concrete Headwall for Subsurface Drains Grate for 1:4 Precast Concrete Aprons Riprap at RCP Outlets Riprap at CSP Outlets Hand-Placed Riprap at Precast Concrete Cattle Pass Slotted Vane Drain for P.V.C. Pipe Slotted Drain for 12" thru 30" Dia. C.M. Pipe (Stackable) Slotted Drain for 12" thru 30" Dia. C.M. Pipe (Not Stackable) Riprap at Precast Concrete End Sections Outlet Screen for C.M. & S.C. Pipes Inspection Tees Concrete Pipe or Precast Culvert Ties Anti-Seepage Diaphragm (For CMP and CMP-A) Safety Slope Metal End Section for Circular & Arched Pipes (2 Sheets) Corrugated Steel Pipe Coupling Band (3 Sheets) 4000 SERIES--SEWER APPURTENANCES Drainage Structure and Castings (4 Sheets) Structure and Casting Combinations Standard Casting Assemblies List of Castings List of Drainage Structures 4000J Manhole or Catch Basin (Masonry, Field Constructed) - Design A 4002F Manhole or Catch Basin (Masonry, Field Construction) - Design C 4003B 30" Precast Catch Basin Design N 4005M Manhole or Catch Basin Type A & B Cone Sections Precast - Design F 4006L Manhole or Catch Basin Precast - Designs G and H 4007C Precast Mechanical Joint Sewer Manhole 4008E Catch Basin (Sectional Concrete Pipe) - Design I 4009H Manhole or Catch Basin (Sectional Concrete Pipe) - Design J 4010H Concrete Short Cone & Adjusting Ring (Sectional Concrete) 4011E Precast Concrete Base 4017C Catch Basin (Concrete Pipe and Metal Pipe) - Designs PC and PM 4018B Manhole or Catch Basin (Reducer Cone Section Precast) Design D 4020J Manhole or Catch Basin (For Use With or Without Traffic Loads) (2 sheets) 4021F Precast Curb Opening Catch Basin 4022A Manhole or Catch Basin Cover (3 ft. X 2 ft. Opening) 4024A 48" Dia. Precast Shallow Depth Catch Basin - Design SD 4025B Drop Inlets or Catch Basins - Design DI (Concrete & Metal) 4026A Concrete Encased Concrete Adjusting Rings 4101D Ring Casting For Manhole or Catch Basin 4108F Adjusting Rings for Catch Basins and Manholes 4110F Cover Casting for Manhole (For Use in all Traffic Areas) Casting No. 715 and 716 4125D Catch Basin Frame Casting (For Square Grate) Casting No. 806 4126F Catch Basin Frame Casting Casting No. 801 4129G Catch Basin Frame Casting (For Square Grate) - Casting No. 802A 4132F Catch Basin Frame Casting (For Square Grate) Casting No. 805 4133A Curb Box Casting for Catch Basin - Casting No. 824 4134A Curb Box Casting for Catch Basin (For Design B Curbs) - Casting No. 825 4140D Special Grate Castings for Catch Basin (Convex and Concave) - Casting No. 720 and 721 4143E Stool Grate & Concrete Frame (Median Drains) - Casting No. 731 4149C Grate Casting for Catch Basin - Casting No. 810 MINNESOTA DEPARTMENT OF TRANSPORTATION NUMERICAL INDEX OF STANDARD PLATES (Sheet 2 of 4) April 16, 2014

PLATE NO. 4150C Grate Casting for All Pipe Drainage Structures 4151B Grate Casting for Catch Basin (Square Type) - Casting No. 811 4152C Catch Basin Grate Casting - Casting No. 814A 4153A Catch Basin Grate Casting - Casting No. 815 4154B Catch Basin Grate Casting - Casting No. 816 4160D Curb Box Casting for Catch Basin - Casting No. 823A and 833A 4161F Curb Box Casting for Catch Basin - Casting No. 821B, 822 and 831A 4180J Manhole or Catch Basin Step 5000 SERIES--EROSION CONTROL STRUCTURES 5010A Reinforced Concrete Pipe Energy Dissipater 6000 SERIES -- Blank 7000 SERIES--CURB, CURB AND GUTTER, SIDEWALK 7000E Integrant Curbs (Design B, Design V and Design D) 7020K Concrete Curb (Design B, Design V, Design S, Design DR and Design BR) (2 Sheets) 7035N Concrete Walk & Curb Returns at Entrances 7038A Detectable Warning Surface Truncated Domes 7065C Bituminous Curb 7100H Concrete Curb and Gutter (Design B and Design V) 7102J Concrete Curb and Gutter (Designs D, S, B4, B5 and D3) (2 Sheets) 7105C Concrete Median (Mountable Type) 7107I Entrance Nose (Urban Design) 7108G Exit Nose (Urban Design) 7109C Median Nose and Island (Undivided to Divided Roadway) 7111J Installation of Catch Basin Castings (Concrete Curb and Gutter) 7112C Installation & Reinforcement of Catch Basin & Manhole Castings (Concrete Integrant Curbs) 7113A Concrete Approach Nose Detail 8000 SERIES -- BARRICADES, SIGNALS, MARKERS, ETC. 8000I 8002G 8105B 8106B 8110E 8111E 8112G 8114A 8117F 8118D 8119C 8120P 8121H 8122F 8123G 8126K 8127C 8128C Standard Barricades Permanent Barricade Equipment Pad A (Cast-in-Place or Precast) Equipment Pad B (Cast-in-Place or Precast) Traffic Signal Bracketing (Pole Mounted) Traffic Signal Bracketing (Pedestal Mounted) (3 Sheets) Pedestal Foundation (Traffic Control Signals) P.V.C. Handhole/Pullbox (No Vehicle Load) (2 Sheets) Precast Concrete Hand Hole (Or Pullbox) (2 Sheets) Service Equipment & Pole Traffic Control Signals Ground Mounted Cabinet Foundation Pole Foundation (PA85) Transformer Base and Pole Base Plate (PA85, PA90 and PA100) (2 Sheets) Pedestal and Pedestal Base (For Traffic Control Signals Support) (2 Sheets) Pole and Mast Arm Luminaires and Traffic Lights Assembly (For All Pole Types) (2 Sheets) Pole Foundation (PA90 and PA100) Light Foundation - Design E (40 ft. Pole or Less) (2 Sheets) Light Foundation - Design H (49 ft. Pole) (2 Sheets) MINNESOTA DEPARTMENT OF TRANSPORTATION NUMERICAL INDEX OF STANDARD PLATES (Sheet 3 of 4) April 16, 2014

PLATE NO. 8129A 8130E 8132B 8133A 8134B 8150C 8307S 8308A 8309A 8316C 8318C 8326D 8329I 8330G 8331B 8332C 8333B 8337C 8338D 8339A 8340A 8342A 8347A 8350A 8400E 8401C Shim and Washer (Traffic Control Signals and Roadway Lighting) Saw Cut Loop Detectors Preformed Rigid PVC Conduit Loop Detector (3 Sheets) Pole and Mast Arm - Type BA (9 Sheets) Pole Foundation - Type BA (4 Sheets) Installation of Culvert Markers W-Beam Guardrail & End Anchorages (Installation with Wood Posts) (4 Sheets) Reinforced Concrete Median Barrier Type F (Non-Glare Screen Type) Design 8308 (3 Sheets) Reinforced Concrete Median Barrier Type F & Glare Screen Design 8309 (3 Sheets) Post Seat for Anchorage on Footing or Box Culverts Guardrail Anchorage Plate for Bridges and BCT'S Flexible Plastic Glare Screen Eccentric Loader Breakaway Cable Terminal (ELT) (4 Sheets) 3-Cable Guardrail (With Wood Posts) (Assembly Details) (2 Sheets) 3-Cable Guardrail (With Steel Posts) (3 Sheets) Anchor Bolt Cluster for Light Poles 3-Cable Guardrail Anchor (Anchor Details) (4 Sheets) Temporary Portable Precast Concrete Barrier (Type F ) (3 Sheets) W-Beam Guardrail & End Anchorages (Installation with Steel Posts) (4 Sheets) 3-Cable (Steel Posts) to W Beam (Wood Posts) Guardrail Transition 3-Cable (Steel Posts) to W Beam (Steel Posts) Guardrail Transition High-Tension Cable Barrier Line Post Foundation Concrete Design Portable Precast Concrete Barrier Anchors Thrie Beam Anchorage Plate Pipe Railing At Grade Pipe Railing (Adjacent to Sidewalk) 9000 SERIES--MISCELLANEOUS 9000E 9101B 9102E 9303B 9308A 9309G 9320G 9321E 9322K 9323D 9324C 9350A Approaches and Entrances - Recommended Standards Shaping and Sodding of Slopes at Box Culvert Ends Turf Establishment Areas (At Pipe Culvert Ends) Geodetic Survey Disks (Aluminum) (2 Sheets) Survey Monument Cap (2 Sheets) PLS (Public Land Survey) Monument (2 Sheets) Woven Wire Fence (Wood Post) Woven Wire Fence (Steel Post) Chain Link Fence (2 Sheets) Barbed Wire Fence (Wood Post) Barbed Wire Fence (Steel Post) Mailbox Support (Swing-Away Type) MINNESOTA DEPARTMENT OF TRANSPORTATION NUMERICAL INDEX OF STANDARD PLATES (Sheet 4 of 4) April 16, 2014

3 5 2 FLOW 4 0 PIPE PIPE SECTION X-X 6 5 2 3-1/4 5 4 0 3 1 1 TYPE A CONE SECTION 3 VARIABLE - 4 0 5 3 2-3/4 6 TYPE B CONE SECTION 3 VARIES 5 7 7-1/4 7 6 4 X LINE A 4 X 1 5 LINE B 4 48 SECTION 4 0 PIPE 2 SECTIONAL VIEW PIPE TYPE B CONE SEE TYPE A CONE FOR ADDITIONAL INFORMATION 8 POURED CONCRETE BASE. BASE REINF. IS 0.12 SQ. IN. PER FT. IN EACH 5 MIN. 5 4 0 2 CLR. DIRECTION. FOR ALTERNATE PRECAST CONC. BASE, SEE STANDARD PLATE 4011. 5 4 SECTIONAL VIEW TYPE A CONE NOTES: REINFORCING: SINGLE LINE STEEL WIRE FABRIC HAVING AN AREA OF NOT LESS THAN 0.12 SQ. IN. PER FOOT OF HEIGHT. 1 2 3 NOMINAL OPENING. 2 PROVIDE MORTAR FILLETS TO FIT THE BOTTOM PORTION OF PIPE TO DIRECT FLOW TO OUTLET. 3 TYPE A CONE SECTION SHALL BE USED UNLESS OTHERWISE INDICATED IN THE PLANS. FOR SHORT CONE SECTION USE TYPE C. SEE STANDARD PLATE 4010. 4 THE ELEV. OF LINE A SHALL BE EQUAL TO OR ABOVE LINE B. 5 REFER TO PLAN FOR CASTINGS REQUIRED. USE ADJUSTING RINGS WHERE NECESSARY, SEE STANDARD PLATES INDEX. CASTING AND PRECAST CONC. ADJUSTING RINGS SHALL BE SET ON FULL MORTAR BEDS. NO PIPE OR STRUCTURE ALLOWED ABOVE TOP OF CONE. 6 REFER TO PLANS FOR ANY STEP REQUIREMENTS. 7 SEE STANDARD PLATES INDEX FOR OTHER APPROVED JOINTS. DESIGN F APPROVED APRIL 16, 2014 STATE OF MINNESOTA SPECIFICATION STANDARD DEPARTMENT OF TRANSPORTATION REFERENCE PLATE MANHOLE OR CATCH BASIN 2506 NO. STATE DESIGN ENGINEER TYPE A & B CONE SECTIONS PRECAST 4005M

A A TOP VIEW TOP OF CASTING 4-1/2 TYP. 48 DIA. 5 5-1/2 FOR 60 DIA. 6 FOR 72 DIA. 2 4 5 FOR 60 DIA. 6 FOR 72 DIA. 1 VARIABLE - 4 0 MAX. 3 5-1/2 FOR 60 DIA. 8 FOR 72 DIA. 60 DIA. 72 DIA. 6 7 SECTION A-A NOTES: REINFORCING: SINGLE LINE STEEL WIRE FABRIC HAVING AN AREA OF NOT LESS THAN 0.15 SQ. IN. PER FOOT OF HEIGHT FOR 60 DIA. AND NOT LESS THAN 0.18 SQ. IN. PER FOOT OF HEIGHT FOR 72 DIA.. 1 2 3 REFER TO PLANS FOR ANY STEP REQUIREMENTS. SEE STANDARD PLATES INDEX FOR OTHER APPROVED JOINTS. MANHOLE REDUCING SECTION 4 0 HIGH. WALL THICKNESS TAPERS TO PROVIDE A SMOOTH EXTERIOR. 4 THE MAXIMUM DEPTH FROM THE TOP OF THE CASTING TO THE TOP OF THE REDUCING CONE IS 10-0". DESIGN D APPROVED APRIL 16, 2014 STATE OF MINNESOTA DEPARTMENT OF TRANSPORTATION SPECIFICATION REFERENCE STANDARD PLATE MANHOLE OR CATCH BASIN NO. STATE DESIGN ENGINEER REDUCER CONE SECTION PRECAST 2506 4018B