Manholes Table of Contents

Similar documents
MH Table of Contents Standard Title/Scope Page Table of Contents SCE Public

DISTRIBUTION VAULT 8' x 14' x 9'-4" DEEP TRAFFIC FLAT WALL WITH 5' x 8' OPENING

Utility Structures. Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles

2' x 3' Polymer Pull Box Cover 4'-0" 7'-0" 24" x 76" Access Opening 3'-6"

5/16" Flange nut. Bolt Keeper Plate (8" Sq. SYS.) (3) 1/2" x 3" Hex head connector zinc plated bolt w/ washers and nut. Anchor 3" sq. 7 Ga.

SECTION PRECAST CONCRETE SECTIONAL MANHOLES

SECTION MANHOLES

Pipe Product Catalog Table of Contents

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes

Anti-Trust Statement

Floor Boxes. Concealed Service Floor Boxes. Engineering Data 663 Series. Faces Plates for 663 Floor Box. 663 Series Floor Box

SECTION UNDERGROUND POWER DUCT AND SUB-STRUCTURES. A. Section : Trenching, Backfilling, and Compacting

StormTrap Guide Specification. StormTrap 2 SingleTrap on Aggregate Foundation Groundwater BELOW Invert Revised 11/30/17

CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION

Manhole or Catch Basin Type A & B Cone Sections Precast - Design F Manhole or Catch Basin Cover (Reducer Cone Section Precast) Design D

Standard Specifications

SECTION 39 - MANHOLES TABLE OF CONTENTS

F-5-1a. Concrete Bollards (Detail 1 of 2) WEIGHT: 166kg. WEIGHT: 227kg. WEIGHT: 113kg. WEIGHT: 212kg

PART MATERIALS. Section Fencing Materials. Description

D. Thermally Sprayed Metallic Coating (Flame Spray): STD SPEC

CONCRETE MANHOLES.

SECTION MANHOLES

StormTrap Guide Specification. StormTrap SingleTrap on Pad Foundation Groundwater BELOW Invert Revised 11/21/18

SECTION SAND CUSHION TERRAZZO FLOORING

Midwest Roadside Safety Facility

1.1 RELATED DOCUMENTS

10x12 FOUNDATION GUIDE 10x12 TRICO AND FLORA SHEDS

Proposal PROJECT MANUAL P R O P E R T Y M A N A G E M E N T F A L L O N C O U N T Y. Baker, MT P.O. Box 846

GENERAL ISOMETRIC LAYOUT

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP

SECTION PUBLIC UTILITY MANHOLES AND STRUCTURES. 2. Modular precast concrete pump wetwell. 5. Manhole bedding and cover materials.

A. Extent of structural precast concrete work is shown on drawings and in schedules.

STANDARD BID ITEM NUMBERS

Current Standard Plates including Transmittal Letters are available on the web at:

This specification describes the minimum requirements for piping systems for the following service:

INSTALLATION INSTRUCTIONS. March 2016 FOR FURTHER QUESTIONS, PLEASE CALL

Plastibeton Trench System. Installation Packet

2. Remove from the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates (August 31, 2012)

SUBJECT: Standard Plate Turf Establishment Areas (at Pipe Culvert Ends)

APPENDIX FENCE GENERAL NOTES

MAINTENANCE HOLES, CATCH BASINS AND DITCH INLETS - MTC FORM 407 INDEX

SECTION 58 PRECAST CONCRETE BOX CULVERT. This work consists of furnishing and installing Pre-cast Concrete Box Culverts.

Digitally Signed 06/02/2015

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION

Plastibeton Trench System. Installation Packet

VILLAGE OF VILLA PARK CENTRAL BOULEVARD IMPROVEMENTS LOCATION MAP (NOT TO SCALE) CORTESI AVE. MYRTLE AVE. CENTRAL BLVD.

DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA

Thru Wall Floor Seals For New Installation

GENERAL ELEVATION SECTION A-A

AMENDMENTS Manual of STANDARD SPECIFICATIONS. Adopted by Standard Specifications Committee. Amendment. No. 6. Published by

SECTION METAL FABRICATIONS

24" B B Joint X501 Joint See MARKINGS Note PCB-RXX-350-TL3 " X501 Y301 (Typ.) " A PLAN (reinforced casting option shown) A " dia. Hinge Bar (Typ.) NOT

1. INTRODUCTION 2. REFERENCE SPECIFICATIONS. Page -1- Bonding and Grouting

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence

Current Standard Plates including Transmittal Letters are available on the web at:

General Information...SA1-SA4

Installation Instructions

Installation Guide. Capped Cellular PVC Fencing. Table of Contents. Storage and Handling Tools Needed Fence Layout and Locating Posts

Hardened Structures Hardened Shelters, LLC. Explosion Resistant Pre-hung Sealed Blast Door

STORM M ANHOLE FOR 42" PIPE AND SM ALLER JOB NO. SHEET NO. DATE MARCH 2015 OF MIN OF 3 CRSES MAX OF 5 CRSES 30"MAX 3 OR 3.5 PRECAST ECCENTIC CONC

ACORNWIRE.COM MESH PARTITIONS DIVISION 10 - SPECIALTIES WIRE MESH PARTITION FOLDING GATE

STRUCTURES FOR SANITARY AND STORM SEWERS

SPECIFICATIONS FOR THE MANUFACTURE AND DESIGN OF PRECAST THREE SIDED ARCH STRUCTURES, WINGWALLS AND HEADWALLS

Section 914. JOINT AND WATERPROOFING MATERIALS

Customer Requirements Commercial Secondary Service

MEDIUM DUTY CAST IRON SLIDE GATES SERIES 20-10C

This specification describes the minimum requirements for piping systems for the following service:

Thread protection accessories are installed at the MODIX production factory and delivered with couplers.

CS3 represents manufacturers of products for use in the municipal waterworks industry.

American Safe Room. Explosion Resistant Blast Hatch with Integrated Riser

TOLL FREE:(888) FAX:(941) ASSEMBLY of ProTEC CONCRETE STRUCTURAL INSULATED PANEL

AUXILIARY FRAMING AND ACCESSORIES

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 8

Concealed Thru-Roof Assemblies

W 869 SN 303 S. Paterson Street, Ste. 1 Madison, WI ph Structural Engineering: /Users/paulcuta/Desktop/1603 Finals/1603

RAIL PANEL AT TRANSITION SECTION PLAN - POST DETAIL PLAN - TUBE SPLICE. Colorado Department of Transportation. Staff Bridge Branch

NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH

Foundation Specifications for 5.6-Meter Modular Earth Station Antennas

ADJUSTABLE BASKETBALL SYSTEM ASSEMBLY INSTRUCTIONS AND OWNER'S MANUAL

UNIVERSAL BASES. #60UB - Universal Mounting Base. Same as above for 1/2 inside threads.

Foundation Specifications for 7.6-Meter Modular Earth Station Antennas

INSTRUCTIONS: 1. Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual.

14000 I/O Series Flush Glaze. Fabrication and Installation Instructions

Appendix C Construction Details

STEEL PIPE GUIDERAIL 01/01/

PCCP Preservation Steps to Take to Extend Pavement Life and Performance of Your Concrete Pavements

Storefront Installation Guide

ALL SEASON PATIO COVER

CITY OF VISTA STANDARD DRAWINGS

Dry Toilet, Version 2.0 June 17, 2015

Flange Dimensions Class 125 Bronze Flange Dimensions Class 300 Bronze Flange Dimensions Class 150 Bronze Flange Dimensions

Item 550 Chain Link Fence

FOR SERVICE BOXES IN CONCRETE DRIVEWAYS, SEE NOTE Min. COVER UNDER DITCHES. 600 Min. COVER

EXTERIOR BUILDING, ROOFING, AND SITE IMPROVEMENTS

1 PREPARATIONS. T2000 INSTALLATION GUIDE

24" Dia. 36" Dia. WE BUILD CONFIDENCE

SHADOWBOX INSTALLATION FOR: Standard 6 H x 8 W Shadowbox Fence 5 x 5 Routed Posts Dog Ear or Straight-Edge Pickets 1.75 x 3.5 Rail

Safe and secure Dero

Model CB Embedded References

This specification describes the minimum requirements for service water piping systems (ie: cooling water, process water, etc.), located on surface.

Transcription:

Standard MH 300 Title Manholes Requirements MH 300.1 Manholes Requirements Manholes Table of Contents Underground Structures Standards MH 310 MH 318 MH 320 MH 325 MH 330 MH 335 MH 340 MH 350 Precast Tub-Type Manholes MH 310.1 Precast Tub-Type Manholes Precast Manhole Neck Detail MH 318.1 Precast Manhole Neck Detail 4' x 6' x 7' Manhole Traffic Loading MH 320.1 4' x 6' x 7' Manhole Traffic Loading 4' x 8' x 7' Manhole Traffic Loading MH 325.1 4' x 8' x 7' Manhole Traffic Loading 6' x 8' x 7' Manhole Traffic Loading MH 330.1 6' x 8' x 7' Manhole Traffic Loading 7' x 7' x 7' Manhole Traffic Loading MH 335.1 7' x 7' x 7' Manhole Traffic Loading 6' x 10' x 7' Manhole Traffic Heavy Loading MH 340.1 6' x 10' x 7' Manhole Traffic Heavy Loading Manhole Neck Details 27" Opening MH 350.1 Manhole Neck Details 27" Opening Effective Date: 07-15-2011 Manholes Table of Contents MH i SCE Internal

This page intentionally left blank.

MH 300 Manholes Requirements Scope MH 300.1 Manholes Requirements 1.0 General 1.1 Manholes that have acceptable precast counterparts are shown on the working drawings (List of Materials) by item number and the types of manholes approved for each item number are listed below. Other manholes are listed by drawing number. Unless otherwise noted on the working drawings, any of the structures covered by a particular item number are acceptable. 1.2 All manhole installations will be watertight. Standard manhole cover/frame size is 30 inches. Manhole covers to be cast-iron for traffic loading, and Reinforced Polymer Material (RPM) for parkway loading. Manhole entry covers will be bolted closed and any lift holes sealed. 2.0 Poured Manholes Each manhole will include accessories and facilities in conformance with the requirements set forth in the drawings, specifications, schedules, and tabulations referred to below: 2.1 Concrete and reinforcement as shown on the drawing and in conformance with GI 020; 2.2 Opening cover as shown on structure drawing or as modified on the working drawing (shown in the List of Materials); 2.3 Conduit entrance (CD 130); 2.4 Inserts (AC 720 and AC 722); 2.5 Sump (AC 710); 2.6 Ground wires (AC 700); 2.7 Neck (MH 350; see MH 318 for precast concrete]); 2.8 Ladders (when required) (AC 740). 3.0 Precast Manholes Each precast manhole will be manufactured in conformance with the requirements as referred to below: 3.1 Manholes will be manufactured and installed to the requirements as set forth in GI 030; 3.2 Each manhole will include accessories and facilities as required in poured manholes. (Some small construction variations have been allowed the precast concrete manufacturers.); 3.3 Manholes will be placed on a 6-inch minimum thickness of mechanically compacted crushed aggregate base (3/4-inch maximum). 3.4 All walls and ceilings to be painted white. Manholes Requirements Effective Date: What s Changed? 1 of 2 07-15-2011 MH 300

3.5 Maximum placement depth is 4 feet, measured from grade to the top outside surface of the manhole and under conditions assumed in GI 030. Contact Division Underground Planning Supervisor if greater depth is required. Item No. M-1 b/ Nominal Size Table MH 300 1: Manholes Field Construction Drawings Precast Concrete Manufacturers a/ Jensen Precast Utility Vault Co. a/ Standard style enclosures are listed. For intercept part numbers add "-INT" to the end of the standard part number. b/ Not approved for use on new construction. 4' x 6'-6" x 5'-6" K466-DM66-11 M-3 4' x 6'-6" x 7' K466-DM84-11 ED466-84MH M-2 4' x 6' x 7' MH 320 M-4 4' x 8' x 7' MH 325 M-5 4'-6" x 8'-6" x 7' K4686-DM84-11 ED4686-84MH M-6 6' x 8' x 7' MH 330 K68-DM84-11 ED68-84MH M-7 6' x 10' x 7' K610-DM84-11P ED610-84MH M-8 6' x 10' x 7' (T) MH 340 K610-DM84-11T ED610-84MH-Traffic M-9 7' x 7' x 7' MH 335 Special Order M-10 c/ c/ Tub Style 5' x 10'-6" x 7' K5106-FM84-11 ED5106-84MH M-11 c/ 6' x 12' x 7' K612-FM84-11 ED612-84MH = For Reference Only Table MH 300 2: Manhole SAP Numbers Nominal Size Type SAP Number 4' x 6'-6" x 5'-6" a/ Standard 10117536 4' x 6'-6" x 7' Standard 10117282 4' x 6'-6" x 7' Intercept 10117537 5' x 10'-6" x 7' Standard 10117539 5' x 10'-6" x 7' Intercept 10117540 6' x 12' x 7' Standard 10117541 6' x 12' x 7' Intercept 10117542 a/ Not approved for use on new construction. MH 300 2 of 2 Manholes Requirements What s Changed? Table MH 300 1 and MH 300 2 were updated to reflect appropriate structures not approved for new construction. Effective Date: 07-15-2011

MH 310 Precast Tub-Type Manholes Scope MH 310.1 Precast Tub-Type Manholes Figure MH 310 1: Precast Tub-Type Manholes 36" Manhole Clear Opening Approved Joint Sealer See Note 1. Conduit Terminators See Note 2. (Typical All Manufacturers) Sump 1. See GI 030. 2. See CD 142. 1.0 Excavation Size: Precast Tub-Type Manholes Effective Date: What s Changed? 1 of 2 Consult manufacturer s installation guides for exact excavation dimensions for each structure size. 2.0 Reference: GI 031............................................ General Specification for Precast Structures GI 035..................................... Allowable Tolerances for Installed Precast Structures CD 142................................................................Conduit Entrance MH 318............................................(page MH 5) Precast Manhole Neck Detail AC 711............................................................Sump Drain and Detail AC 740....................................................................... Ladders MH 310

1. Conduit terminators to be generally located as shown on CD 142. Standard conduit entrance will be a flatwall design. Slight variations by manufacturers may be allowable with Company approval. 2. Tub-type structures will be furnished with 1/2" threaded bronze grounding inserts, as shown on VA 411. 3. Inside walls and ceiling to be painted white MH 310 2 of 2 What s Changed? Precast Tub-Type Manholes Effective Date:

MH 318 Precast Manhole Neck Detail Scope MH 318.1 Precast Manhole Neck Detail Figure MH 318 1: Precast Manhole Neck Detail See Note 6. See Note 7. Dry pack grout under frame and cover after ring is set to grade. Adjustable Anchors (4 required) 30" Clear Opening 36" 12" Approved Joint Sealant Roof Line Grade Ring See Note 2. 1. See AC 740 for ladder installation (when required). 2. Various size grade rings available (3", 6", 12", and so on). SeeTable MH 318 2 ( 2). 3. Reinforcement designed for H-20 bridge loading. 4. Standard manhole cover/frame size is 30". 5. RPM cover is to be used when in nonvehicular traffic conditions. 6. Bonding adhesive per GI 030. 7. Cover and frame per FC 621. Table MH 318 1: Replacement 30-Inch Diameter Manhole Neck and Cover Cast Iron Traffic Manufacturer Part Number Material Code Jensen Precast K36-MN14-11T 655-02700 Utility Vault A-1106 Frame and Cover 655-02700 Precast Manhole Neck Detail Effective Date: What s Changed? 1 of 2 MH 318

Table MH 318 2: Manhole Grade Rings Manufacturers Numbers Item Number Extension Height Jensen Precast a/ Utility Vault Co. Material Code MX-1 3 inch MN36-R3 ED-3603-GR 655-02726 MX-2 6 inch MN36-R6 ED-3606-GR 655-02734 MX-3 12 inch MN36-R12 ED-3612-GR 655-02742 a/ Jensen Precast (formerly Brooks Products, Inc.) MH 318 2 of 2 What s Changed? Precast Manhole Neck Detail Effective Date:

MH 320 4' x 6' x 7' Manhole Traffic Loading Scope MH 320.1 4' x 6' x 7' Manhole Traffic Loading Figure MH 320 1: 4' x 6' x 7' Manhole Traffic Loading Cover N1 T5 T4 T6 T1 T5 T2 T1 T6 T6 Section A-A A T5 1. See MH 300 for reference drawings giving installation details, schedules, and general requirements for manhole structures and accessories. See working drawings for additional details of neck, conduit bank, and so on. B B 2" T1 12" T2 See Note 2. Neck Detail 4 Spaces O.C. 16" 6'-0" 7'- Roof Plan T4 T6 2 Spaces O.C. A 5 Spaces O.C. 4'-0" 5'- Section B-B T2 T6 Excavation: 14.2 Cu. Yds. Concrete: 7.06 Cu. Yds. Total Rebar: 781 Lbs. 2. See MH 350. 4' x 6' x 7' Manhole Traffic Loading Effective Date: What s Changed? 1 of 4 MH 320

Table MH 320 1: Reinforcing Schedule 4' x 6' x 7' Manhole Traffic Loading Cover Mark Quantity Length Long Leg Size Wt. Lbs. T1 16 4'-10" 29" V. #5 81 T2 24 3'- 23" H. #5 92 10 4'-0" Straight #5 42 T4 6 3'- 29" V. #5 21 T5 8 4'-5" 29" V. #5 37 T6 4 6'-0" Straight #5 25 6" 4 Spaces 1 O.C. C N1 1 110" Welded Wire Fabric 2" x 2" 12 Ga. Min. 3 Figure MH 320 2: 4' x 6' x 7' Manhole Traffic Loading Wall Section C-C 7'- 6'-0" 8 Spaces O.C. 12" 7' 0" 8' 10" C D Section D-D 5'- 4'-0" 5 Spaces O.C. Vent When Req'd. D 6" 10" Side Wall End Wall MH 320 2 of 4 What s Changed? 4' x 6' x 7' Manhole Traffic Loading Effective Date:

1. All side steel clear from outside surface. Table MH 320 2: Reinforcing Schedule 4' x 6' x 7' Manhole Traffic Loading Wall 5'- Mark Quantity Length Long Leg Size Wt. Lbs. 30 7'-0" Straight #3 79 10 6'-0" Straight #3 23 10 4'-0" Straight #3 15 20 2'-10" 17" H. #3 22 F B5 See Note 2. Sump Detail E E Figure MH 320 3: 4' x 6' x 7' Manhole Traffic Loading Floor 4 Spaces @ O.C. 6'-0" 7'- B4 Floor Plan B4 B4 B4 2 Spaces @ O.C. F Section E-E 10" 2" B4 B4 Section F-F 1. All floor and roof steel 2" minimum clear from outside surfaces. All side steel minimum clear from outside surfaces. 2. See AC 710. 4' x 6' x 7' Manhole Traffic Loading Effective Date: What s Changed? 3 of 4 MH 320

Table MH 320 3: Reinforcing Schedule 4' x 6' x 7' Manhole Traffic Loading Floor Mark Quantity Length Long Leg Size Wt. Lbs. 28 4'- 29" H. #5 126 30 3'- 23" H. #5 115 11 4'-0" Straight #5 46 B4 8 6'-0" Straight #5 50 B5 4 1'-9" Straight #5 7 MH 320 4 of 4 What s Changed? 4' x 6' x 7' Manhole Traffic Loading Effective Date:

MH 325 4' x 8' x 7' Manhole Traffic Loading Scope MH 325.1 4' x 8' x 7' Manhole Traffic Loading Figure MH 325 1: 4' x 8' x 7' Manhole Traffic Loading Roof T1 T1 T5 T1 T6 A B 9'- 8'-0" 5 Spaces O.C. 2 T6 T4 T6 B T4 See Note 2. 2" Section A-A T6 Roof Plan N1 3 Spaces O.C. T6 T4 T6 T2 1. See MH 300 for reference drawings giving installation details, schedules, and general requirements for manhole structures and accessories. See working drawings for additional details of neck, conduit banks, and so on. T2 12" Clear A T1 5 Spaces O.C. 4'-0" 5'- T2 T6 Section B-B T5 T6 T2 T2 Excavation: 18.11 Cu. Yds. Concrete: 8.4 Cu. Yds. Total Rebar: 975 Lbs. 2. See MH 350. 4' x 8' x 7' Manhole Traffic Loading MH 325 Effective Date: What s Changed? This type of poured in place manhole is no longer valid for new construction. 1 of 5 7-25-2008 The standard was made for reference only for rebuilding or expanding existing structures.

Table MH 325 1: Reinforcing Schedule 4' x 8' x 7' Manhole Traffic Loading Roof Mark Quantity Length Long Leg Size Wt. Lbs. T1 20 4'-10" 29" V. #5 101 T2 28 3'- 23" H. #5 110 12 4'-0" Straight #5 51 C 6" 4 Spaces 1 O.C. T4 8 3'- 29" V. #5 28 T5 8 5'-3" 3 H. #5 45 T6 4 8'-0" Straight #5 34 N1 1 110" Welded Wire Fabric 2" x 2" 12 Ga. Min. 3 Figure MH 325 2: 4' x 8' x 7' Manhole Traffic Loading Wall Section C-C 9'- 8'-0" 11 Spaces O.C. Typ. C 12" D Section D-D 5'- 4'-0" 5 Spaces O.C. Vent When Req'd. 9' 0" D 6" 12" Side Wall End Wall MH 325 2 of 5 4' x 8' x 7' Manhole Traffic Loading What s Changed? This type of poured in place manhole is no longer valid for new construction. The standard was made for reference only for rebuilding or expanding existing structures. Effective Date: 7-25-2008

Table MH 325 2: Reinforcing Schedule 4' x 8' x 7' Manhole Traffic Loading Wall Mark Quantity Length Long Leg Size Wt. Lbs. 36 7'-0" Straight #3 95 10 8'-0" Straight #3 31 10 4'-0" Straight #3 15 20 2'-10" 17" H. #3 22 1. All side steel clear from outside surface. 4' x 8' x 7' Manhole Traffic Loading MH 325 Effective Date: What s Changed? This type of poured in place manhole is no longer valid for new construction. 3 of 5 7-25-2008 The standard was made for reference only for rebuilding or expanding existing structures.

Figure MH 325 3: 4' x 8' x 7' Manhole Traffic Loading Floor 9'- 8'-0" E 5 Spaces O.C. F B4 B4 Section E-E 5' 4' 0" B4 B4 2" CL. Section F-F CL. 2" CL. E B4 5 Spaces O.C. F B4 Floor Plan All floor and roof steel 2" min. clear from outside surfaces. All side steel minimum clear from outside surfaces. MH 325 4 of 5 4' x 8' x 7' Manhole Traffic Loading What s Changed? This type of poured in place manhole is no longer valid for new construction. The standard was made for reference only for rebuilding or expanding existing structures. Effective Date: 7-25-2008

Table MH 325 3: Reinforcing Schedule 4' x 8' x 7' Manhole Traffic Loading Floor Mark Quantity Length Long Leg Size Wt. Lbs. 36 4'- 29" H. #5 176 36 3'- 23" H. #5 138 14 4'-0" Straight #5 59 B4 8 8'-0" Straight #5 67 4' x 8' x 7' Manhole Traffic Loading MH 325 Effective Date: What s Changed? This type of poured in place manhole is no longer valid for new construction. 5 of 5 7-25-2008 The standard was made for reference only for rebuilding or expanding existing structures.

This page intentionally left blank.

MH 330 6' x 8' x 7' Manhole Traffic Loading Scope MH 330.1 6' x 8' x 7' Manhole Traffic Loading Figure MH 330 1: 6' x 8' x 7' Manhole Traffic Loading Roof N1 T1 T4 T2 T6 T2 T1 A T5 T1 1. See MH 300 for reference drawings giving installation details, schedules, and general requirements for manhole structures and accessories. See working drawings for additional details of neck, conduit bank, and so on. Excavation: 25.3 Cu. Yds. Concrete: 11.3 Cu. Yds. Total Rebar: 1,857 Lbs. 2. See MH 350. B B T6 T6 T6 Section A-A See Note 2. 12" 4 Spaces O.C. 8'-0" 9'- Roof Plan T4 T6 T6 12" 12" T2 A T2 T2 8 Spaces O.C. 6'-0" 7'- Section B-B T1 T5 T6 6' x 8' x 7' Manhole Traffic Loading Effective Date: What s Changed? 1 of 4 MH 330

Table MH 330 1: Reinforcing Schedule 6' x 8' x 7' Manhole Traffic Loading Roof Mark Quantity Length Long Leg Size Wt. Lbs. C T1 20 5'-6" 33" V. #6 166 T2 38 4'- 27" H. #6 247 12 6'-0" Straight #6 109 T4 8 4'- 33" V. #6 57 T5 14 5'-9" 33" H. #6 121 T6 8 8'-0" Straight #6 97 N1 1 12" x 110" Welded Wire Fabric 2" x 2" 12 Ga. Min. 3 1. All side steel clear from outside surface. Figure MH 330 2: 6' x 8' x 7' Manhole Traffic Loading Wall Section C-C 9'- 8'-0" 11 Spaces O.C. 6" 4 Spaces 1 O.C. 7'-0" 9'-0" 6" 12" 12" C D Section D-D Side Wall End Wall 7'- 6'-0" 8 Spaces O.C. Vent When Req'd. D MH 330 2 of 4 What s Changed? 6' x 8' x 7' Manhole Traffic Loading Effective Date:

Table MH 330 2: Reinforcing Schedule 6' x 8' x 7' Manhole Traffic Loading Wall Mark Quantity Length Long Leg Size Wt. Lbs. 42 7'-0" Straight #3 111 10 8'-0" Straight #3 31 10 6'-0" Straight #3 23 20 2'-10" 17" #3 22 Figure MH 330 3: 6' x 8' x 7' Manhole Traffic Loading Floor B4 E 7'- 6'-0" 8 Spaces O.C. F Section E-E B4 See Note 2. B4 5 Spaces O.C. 8'-0" 9'- F Floor Plan B4 E Section F-F B4 12" 1. All floor and roof steel 2" minimum clear from outside surfaces. All side steel minimum clear from outside surfaces 2. See AC 710.. 6' x 8' x 7' Manhole Traffic Loading Effective Date: What s Changed? 3 of 4 MH 330

Table MH 330 3: Reinforcing Schedule 6' x 8' x 7' Manhole Traffic Loading Floor Mark Quantity Length Long Leg Size Wt. Lbs. 42 5'- 29" H. #6 337 42 4'- 23" H. #6 273 14 6'-0" Straight #6 127 B4 11 8'-0" Straight #6 133 MH 330 4 of 4 What s Changed? 6' x 8' x 7' Manhole Traffic Loading Effective Date:

MH 335 7' x 7' x 7' Manhole Traffic Loading Scope MH 335.1 7' x 7' x 7' Manhole Traffic Loading Figure MH 335 1: 7' x 7' x 7' Manhole Traffic Loading Roof 1. See MH 300 for reference drawings giving installation details, schedules, and general requirements for manhole structures and accessories. See working drawings for additional details of neck, conduit bank, and so on. Excavation: 25.7 Cu. Yds. Concrete: 10.5 Cu. Yds. Total Rebar: 2,468 Lbs. 2. See MH 350. 3. 8'- 7'-0" 12" A T4 T1 T1 T1 T4 T4 Section A-A Roof Plan T2 T1 T4 T2 T2 See Note 2. N1 A T2 3" 13 Spaces 6" O.C. 3" 7' x 7' x 7' Manhole Traffic Loading Effective Date: What s Changed? 1 of 4 MH 335

Table MH 335 1: Reinforcing Schedule 7' x 7' x 7' Manhole Traffic Loading Roof Mark Quantity Length Long Leg Size Wt. Lbs. T1 40 5'-3" 33" V. #6 316 T2 56 4'- 27" H. #6 364 28 7'-0" Straight #6 295 T4 16 4'-5" 33" V. #6 107 N1 1 110" Welded Wire Fabric 2" x 2" 12 Ga. Min. 3 Figure MH 335 2: 7' x 7' x 7' Manhole Traffic Loading Wall B 3" Section B-B 8'- 7'-0" 13 Spaces 6" O.C. Vent When Required 6" 4 Spaces 1 O.C. 7'-0" 8'-10" 3" 12" 6" B Wall 1. All side steel clear from outside surface. MH 335 2 of 4 What s Changed? 7' x 7' x 7' Manhole Traffic Loading Effective Date:

Table MH 335 2: Reinforcing Schedule 7' x 7' x 7' Manhole Traffic Loading Wall Mark Quantity Length Long Leg Size Wt. Lbs. 56 7'-0" Straight #3 148 20 7'-0" Straight #3 53 20 2'-10" 17" H. #3 22 Figure MH 335 3: 7' x 7' x 7' Manhole Traffic Loading Floor 10" C 3" 6 Spaces 6" O.C. Section C-C 8'- 7'-0" 3" 3" Floor Plan C 13 Spaces 6" O.C. 3" 7' x 7' x 7' Manhole Traffic Loading Effective Date: What s Changed? 3 of 4 MH 335

Table MH 335 3: Reinforcing Schedule 7' x 7' x 7' Manhole Traffic Loading Floor Mark Quantity Length Long Leg Size Wt. Lbs. 56 5'- 33" H. #6 449 56 4'- 27" H. #6 364 32 7'-0" Straight #6 337 1. All floor and roof steel 2" minimum clear from outside surfaces. All side steel minimum clear from outside surfaces. MH 335 4 of 4 What s Changed? 7' x 7' x 7' Manhole Traffic Loading Effective Date:

MH 340 6' x 10' x 7' Manhole Traffic Heavy Loading Scope MH 340.1 6' x 10' x 7' Manhole Traffic Heavy Loading Figure MH 340 1: 6' x 10' x 7' Manhole Traffic Heavy Loading B 2'-7" 2'-0" 6" 6" T1 A 15" 15" 2" 15" 15" 2" T14 T5 T4 T2 T6 T10 T11 2" 4 Spaces 10" 15" 10 Spaces 6" Bottom Steel Top Steel 11'- 10'-0" Plan See Note 4. T9 T8 C Sump 45 B 2'0" T12 6'-3" 5'- 11 Spaces 6" 6" 12" 6" 2'-0" 2'-11" Neck Welded Wire Fabric - N1 2 30" MIN T14 3 Spaces 15" 7'-0" 12" 2 Spaces 12" T13 T14 A T13 1 MIN 8'-10" 6" 10" Excavation 9'-10" MIN C 9" 9" Section A-A Figure MH 340 1.1: Plan and Section A-A 6' x 10' x 7' Manhole Traffic Heavy Loading Effective Date: What s Changed? 1 of 3 MH 340

9" 9" N1 1" CL T10, 11, 12, 13, and 14 3-1/2" CL Slope Floor to Sump Sump Section B-B 45 Figure MH 340 1.2: Section B-B and Section C-C 1. See MH 300 (page MH-1) for reference drawing giving installation details, schedules, and general requirements for structures and accessories. 2. For total quantities of steel, castings, and related foundry items, see Summary for each set of working drawings. 3. See working drawings for additional neck, conduit bank, and so on. 4. See MH 350. Table MH 340 1: List of Materials 6' x 10' x 7' Manhole Traffic Heavy Loading Quantity T13, 14 3 Spaces 15" 25 Spaces 12" 6" Sump Reinforcing Symm. Abt. 11'- Description 1 Only 26 Manhole Casting 9.8 Cu. Yds. Concrete As Detailed Pull Eyes B9 3 0 2'-0" Section C-C B4 B5 B7 2 B8 8 Spaces 7" 1 B6 2 Spaces 1 7' 9" 9" MH 340 2 of 3 What s Changed? 6' x 10' x 7' Manhole Traffic Heavy Loading Effective Date:

Table MH 340 2: Reinforcing Schedule 6' x 10' x 7' Manhole Traffic Heavy Loading Mark Quantity Type Size Total Length Wt. Lbs. T1 4 Straight 5/ Dia. 6'- 26.4 T2 2 Straight 5/ Dia. 5'-6" 11.5 2 Straight 5/ Dia. 4'-3" 3.7 T4 2 Straight 5/ Dia. 3'-10" 8.0 T5 2 Straight 5/ Dia. 3'-0" 6.3 T6 2 Straight 1/2" Dia. 10'- 14.3 T7 2 Straight 1/2" Dia. 8'- 11.1 T8 1 Straight 1/2" Dia. 5'-6" 3.7 T9 1 Straight 1/2" Dia. 3'-2" 2.1 T10 1 1/2" Dia. 3'-6" 2.4 T11 2 3'-0" 3/ Dia. 4'-2" 12.5 T12 2 1/2" Dia. 4'-0" 5.4 T13 18 3'-0" 3/ Dia. 5'-6" 148.8 T14 26 2'-5" 1/2" Dia. 5'-0" 85.6 N1 1 1'-0" 1'-2" Welded Wire Fabric 12 G.A. 2" x 2" Mesh (Min.) 1' x 13' Normal 12 45 6'-0" 1/2" Dia. 10'- 85.5 45 7 10'- 1/2" Dia. 15'- 71.5 2'- 1'-6" 29 Straight 1/2" Dia. 8'-1" 152.0 1 1/2" Dia. 4'- 2.9 4 6'- 1/2" Dia. 11'- 31.2 2 6'-0" 1/2" Dia. 11'-0" 14.7 B4 2 5'-5" 1/2" Dia. 10'-5" 13.2 2'- B5 2 4'-10" 1/2" Dia. 9'-10" 13.1 1'-10" B6 2 4'-3" 1/2" Dia. 9'-3" 12.4 B7 2 3'- 1/2" Dia. 8'- 11.6 B8 2 3'-1" 1/2" Dia. 8'-1" 10.7 B9 1 3'-5" 1/2" Dia. 8'-5" 5.6 0 1 6'-5" 1/2" Dia. 11'-5" 7.6 1 1 9'-5" 1/2" Dia. 14'-5" 9.6 2 1 10'- 1/2" Dia. 15'- 10.5 3 1 4'-0" 1/2" Dia. 6'-6" 4.6 4.7 1. 23.12 Cu. Yds. Excavation 2. 820.9 Lbs. Reinforcing Steel 6' x 10' x 7' Manhole Traffic Heavy Loading Effective Date: What s Changed? 3 of 3 MH 340

This page intentionally left blank.

MH 350 Manhole Neck Details 27" Opening Scope MH 350.1 Manhole Neck Details 27" Opening Figure MH 350 1: Manhole Neck Details 27" Opening Color top surface to match surrounding pavement Drop thru clean out holes below each cover bolt 1" 2" See Note 5. In non-traffic installations neck may be bevelled to allow matching of existing pavement 12" MIN below flow line of gutter 13-1/2" 10" 12" 2" MIN Varies 13-1/2" 15-1/2" See Note 6. Half Elevation Normal Neck (Height 2 or Less) For cold joint use 2" x key and two coats of Sika Seal Half Elevation Extended Neck (Height in Excess of 2) 6" Overlap of Reinforcing Cover Bolts (With Drop Thru Holes) 4 Required 43" Sq. 47" Sq. Anchor Bolts 4 Required Half Plan Normal Neck (Height 2 or Less) Half Plan Extended Neck (Height in Excess of 2) 1. Reinforcing: No. 3 rebar on 12" centers or 4 x 4-10/10 WWF minimum concrete coverage will be 2". 2. Concrete: per GI 020. Manhole Neck Details 27" Opening Effective Date: What s Changed? 1 of 2 MH 350

3. Approved variations may be allowed precasters to accommodate manufacturing processes. 4. Use 30" round opening if specified on substructure drawing. 5. See FC 620 for manhole cover. 6. See AC 740 for ladder installation. MH 350 2 of 2 What s Changed? Manhole Neck Details 27" Opening Effective Date: