An Experimental Study of the Effect of Current THD to kwh Meter s Energy Measurement

Similar documents
World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

Power Factor and Power Factor Correction

HARMONIC contamination, due to the increment of nonlinear

Determination of Transformer Rating Based on Total Harmonic Distortion Under Balanced Conditions

Low Pass Harmonic Filters

Harmonics White Paper

DSP-BASED CURRENT SHARING OF AVERAGE CURRENT CONTROLLED TWO-CELL INTERLEAVED BOOST POWER FACTOR CORRECTION CONVERTER

Single Phase Bridgeless SEPIC Converter with High Power Factor

THE ANALYSIS OF MAGNIFICATION OF NEUTRAL CURRENT IN THE PRESENCE OF POWER QUALITY PROBLEMS

THE third-harmonic current injection is a method to reduce

A Novel Ultra High Fidelity Power Quality and Energy Management Software Using NI LabVIEW

Harmonic Distortion Evaluations

IDENTIFICATION OF POWER QUALITY PROBLEMS IN IEEE BUS SYSTEM BY USING NEURAL NETWORKS

Comparison between Conventional and Modified Cascaded H-Bridge Multilevel Inverter-Fed Drive

Development of a Single-Phase PWM AC Controller

Improving Passive Filter Compensation Performance With Active Techniques

ECE 528 Understanding Power Quality

A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits

Study of Power Factor Correction in Single Phase AC-DC Converter

A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards

ISSN: International Journal of Science, Engineering and Technology Research (IJSETR) Volume 1, Issue 5, November 2012

ISSN Vol.03,Issue.07, August-2015, Pages:

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

The Effect of High Switching Frequency on Inverter Against Measurements of kwh-meter

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Study of Harmonics and THD of Nine Phase PWM Inverter Drive with CLC Filter for motor drive applications

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk.

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

Harmonic Analysis to Improve Power Quality

Project acronym: Multi-island

Reduced PWM Harmonic Distortion for a New Topology of Multilevel Inverters

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

Comparison of SPWM,THIPWM and PDPWM Technique Based Voltage Source Inverters for Application in Renewable Energy

Design of Single-Stage Transformer less Grid Connected Photovoltaic System

Power Quality Evaluation of Electrical Distribution Networks

Modeling of Nonlinear Loads and Analysis of Harmonics in a Small Scale IT Park

ANALYSING PERFORMANCE OF SUPER-CAPACITOR AND BATTERY IN LOW VOLTAGE ELECTRICAL DISTRIBUTION SYSTEMS

International Journal of Electrical Engineering and Technology (IJEET), ISSN (Print), INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING &

ECE 2006 University of Minnesota Duluth Lab 11. AC Circuits

CHAPTER 4 MULTI-LEVEL INVERTER BASED DVR SYSTEM

Development of Mathematical Models for Various PQ Signals and Its Validation for Power Quality Analysis

Indirect Current Control of LCL Based Shunt Active Power Filter

What does Power Factor mean?

ECET Modern Power

CHAPTER 4 HARMONICS AND POWER FACTOR

Harmonic Requirements

Power Quality Measurements the Importance of Traceable Calibration

Proposed test procedure for the laboratory characterisation of gridconnected

Analysis of Harmonic Distortion in Non-linear Loads

Power Quality Notes 2-1 (MT)

Systematical measurement errors

ELECTRICITY tariff structures in Egypt are fairly complex,

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

POWER FACTOR CORRECTION USING BOOST CONVERTER

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Investigation of Passive Filter for LED Lamp

Application of Wavelet Transform for the Detection and Minimization of Harmonics using Shunt Active Filter

Active Elimination of Low-Frequency Harmonics of Traction Current-Source Active Rectifier

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

A Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

SWITCHING FREQUENCY HARMONIC SELECTION FOR SINGLE PHASE MULTILEVEL CASCADED H-BRIDGE INVERTERS

Improving the Power Factor Correction in the Presence of Harmonics by Reducing the Effect of Resonance and Harmonics

3D Intermodulation Distortion Measurement AN 8

Emicon Engineering Consultants L.L.C.

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Harmonics Elimination Using Shunt Active Filter

Fuzzy Logic Control of APF for Harmonic Voltage Suppression in Distribution System

Industrial Electricity. Answer questions and/or record measurements in the spaces provided.

Simple and Advanced Models for Calculating Single-Phase Diode Rectifier Line-Side Harmonics

Voltage and Current Waveforms Enhancement using Harmonic Filters

RECENTLY, the harmonics current in a power grid can

Distributed Active Filter Systems (DAFS): A new approach to power system harmonics

Electrical Motor Power Measurement & Analysis

A New Active Power Factor Correction Controller Using Boost Converter

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

Control of buck-boost chopper type AC voltage regulator

Abstract. Keywords: Electric vehicle; Modelling; Pulse Width Modulation (PWM) inverters; MOSFET circuits.

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

VOLTAGE MULTISTABILITY FOR DISTRIBUTION SYSTEM

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

Testing Power Factor Correction Circuits For Stability

Improvement of Power Quality Using a Hybrid Interline UPQC

Power Quality Notes 3-2 (MT)

1C.4.1 Harmonic Distortion

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

1. Introduction to Power Quality

IEEE Transactions On Circuits And Systems Ii: Express Briefs, 2007, v. 54 n. 12, p

Power Factor Pre-regulator Using Constant Tolerance Band Control Scheme

Page 2 A 42% B 50% C 84% D 100% (Total 1 mark)

Simulation and Experimental Validation of AC to AC Converter Waveform and Power Consumption using the Integral Cycle PWM Technique

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Converters with Power Factor Correction

TO LIMIT degradation in power quality caused by nonlinear

Power Quality Survey in a Distribution System, Standard Procedures and Limitations. H. Mokhtari S. Hasani and M. Masoudi

II. SINGLE PHASE BOOST TYPE APFC CONVERTER

Reactive Power Compensation of LC Coupling Hybrid Active Power Filters by DC Link Voltage Controls

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Transcription:

An Experimental Study of the Effect of Current THD to kwh Meter s Energy Measurement Syafrudin Masri 1, M.N. Mamat 2, M.Y. Yahya 3 Associate Professor, PPKEE, Universiti Sains Malaysia, Penang, Malaysia 1 Senior Research Officer, PPKEE, Universiti Sains Malaysia, Penang, Malaysia 2 Research Assistant, PPKEE, Universiti Sains Malaysia, Penang, Malaysia 3 Abstract: An experimental study of the effect of constant rms current with different THD to the single phase digital kwh meter is presented in this paper. The study focused on how harmonics from non-linear load with constant voltage supply and constant rms current affect the energy measurement of single phase digital watt-hour meter. Traditionally, analog electromechanical meter is using the rms current as its main measurement parameter. In digital meter, different techniques and sampling are used to measure the power consumed by the consumers. Although different techniques and sampling are used, the rms current parameter is still the dominant parameter used to measure and calculate the energy measurement. Both electromechanical and digital meter show good measurements under linear load condition. On the other hand, under non-linear load, harmonics are often neglected in energy measurement. In addition, harmonics in heavily distorted current originated from non-linear load and contributed to lot of losses and it will not be recorded in the billing. To make the situation worse, harmonics can propagate through the transformer and they will be affected the power network either if the harmonics are injected from the source or load side. Analysis from the measurement data clearly showed the effect of the harmonics to the energy measurement. In consequence, either utility company or consumer shall be affected if the harmonics parameter is neglected in the energy measurement purpose. The results showed that no significant difference when the actual digital watt-hour meter energy reading is compared to the calculated energy consumption based on rms current value. Therefore, either harmonics are taken or not taken into account during the energy measurement, the consumer is not affected and still paying the same prices. However, the utility company will be burdened by some losses if harmonics are not taken into consideration. Keywords: Non linear load, THD current, Real power, Energy, Billing and kwh meter-eds2560. I. INTRODUCTION In modern electrical distribution system, there have been sudden increases of non-linear loads such as power supply rectified equipments, new switched mode power supply appliances, domestic appliances and adjustable speed drive control equipments. Non-linear load in a power system is characterized by the introduction of a switching action and consequently current interruptions. This behaviour provides current with different components that are multiples of the fundamental frequency of the system. These components are called harmonics. These are the loads which have non-linear characteristics and result in harmonic distortion of both voltage and current waveforms. As more non-linear loads are introduced within a facility, these waveforms get more distorted [1-6]. Higher distortion levels can affect the performance of electrical energy metering equipment and therefore impact the billing charges of the utility company. In addition, harmonics result in extra losses in power distribution system such as transformers and capacitors bank [2]. Moreover, the changes in the operating condition and the rapid growth of advanced power conversion devices, electronic equipments, computers, office automation, airconditioning systems, adjustable speed heating ventilation also lead to more distortions in the power network. According to the Electric Power Research (EPR), in 2012 an estimated of 85% of all electric power flows through electronic converters. All these devices are named as nonlinear loads and become sources of harmonics [2]. The amplitude and phase angle of a harmonic is dependent on the circuit and on the load it drives. The harmonic currents flow toward the power source through the path of the least impedance and presented by this equation. I s (t) = I m1 sinωt + I m2 sin2ωt + I m3 sin3ωt +... +I mnsinnωt where (t) = Instantaneous current I m1 = First max harmonic current n = Order of harmonic Total harmonic distortion (THD) is an amplifier or preamplifier specification that compares the output signal of the amplifier with the input signal and measures the level differences in harmonic frequencies between the two. The difference is called total harmonic distortion. THD applies to both current and voltage and is defined as the root mean square (rms) summation value of harmonics divided by the Copyright to IJIREEICE DOI 10.17148/IJIREEICE.2017.5218 98

rms value of the fundamental, and then multiplied by 100% and defined as: THD = A dis A 1 100% where; A dis = rms summation of current or voltage distortion A 1 = rms value of the fundamental current or voltage THD of voltage (THDs) is usually less than 5%. THDs below 5% are widely considered to be acceptable, but values above 10% are definitely unacceptable and will cause problems for sensitive equipment and loads [4]. THD of current (THDi) is the total harmonic distortion of the load current. THDi varies from a few percent to more than 100%. It deteriorates the power factor of the system, which is the ratio between the average power of a certain load and the average power calculated for a pure resistive load with equal voltage amplitude. II. MEASUREMENT SETUP Measurements were conducted to an adjustable non-linear load powered by an adjustable low distorted voltage power supply. Power supply was set to 240V single phase, 50Hz. It was assumed that this power supply will not contributed any harmonics into the measurement setup. The non-linear load consisted of one set of variable capacitors, one set of high power variable resistors and a full bridge rectifier to perform the AC-DC conversion. Variable capacitors were used to set different THDi during measurement while variable resistors were used to set the constant rms current. The rms current was set to a constant value of 9.60A. Data were measured using Fluke 43B Power Quality Analyzer at the non-linear load to record all prominent parameters. The parameters were used to measure and calculate the total electrical energy consumption from the load side. EDS2560 single phase digital watt-hour meter was used to measure the real-time energy consumption. It was placed directly after the incoming mains connection. Fig. 1 shows the measurement setup. Fig. 1 Measurement Setup Fluke 43B Analyzer was used to record the rms current, fundamental current, power factor, THDi and individual harmonics. EDS2560 digital meter was used to record the actual meter reading during measurement setup. A series audit of measurement and monitoring for all parameters above were carried out for eight different THDi. For each THDi, EDS2560 measured the energy usage within 24 hours, E p (kwh). The energy consumed for 24 hours from Fluke 43B can be divided into three types namely energy consumed based on rms current, E rms (kwh), energy consumed based on fundamental current, E f (kwh) and energy consumed based on effective harmonic current, E e (kwh). All parameters measured and calculated were labeled as follows: E p = EDS2560 energy measurement for 24 hours in kwh E rms = Fluke 43B energy usage for 24 hours using rms current in kwh E f = Fluke 43B energy usage for 24 hours using fundamental current in kwh E e = Fluke 43B energy usage for 24 hours using effective harmonic current in kwh PF = power factor of the non-linear load I rms = rms current in Ampere I e = total effective harmonic current in Ampere I 1 = fundamental harmonic current in Ampere An easy way to comply with the conference paper formatting requirements is to use this document as a template and simply type your text into it. III. RESULTS AND ANALYSIS Table 1 shows the measurement results when the nonlinear load is subjected to different current total harmonic distortion, THDi(%). As stated earlier, power supply, V s (V) is set at 240V, 50Hz while rms current, I rms (A) is set at 9.6A. EDS2560 measures the energy consumed within 24 hours. Other parameters recorded are fundamental harmonic current, I 1 (A), power factor (PF). From the Table 1, PF is affected by the THDi. Clearly, PF is decreased when the THDi is increased. Table 1 Parameters for constant rms current for energy consumed measured using EDS2560 THDi I 1 PF E p 0.9 9.60 1.00 53.89 9.6 9.57 0.96 52.66 11.5 9.53 0.95 51.77 14.2 9.50 0.94 51.02 17.7 9.43 0.92 50.68 20.7 9.40 0.90 50.55 26.5 9.23 0.87 49.14 36.5 8.95 0.81 44.56 Fig. 2 shows the current and voltage waveforms when the non-linear load is subjected to different THDi. In this setup, the power supply voltage retains the pure sinusoidal shape even under heavy distortion whereas current waveform shows a distorted sinusoidal shape. Table 2 shows the harmonic spectrums when different THDi is applied to the non-linear load. Heavier THDi leads to lower fundamental current and higher value to the other harmonics current. Copyright to IJIREEICE DOI 10.17148/IJIREEICE.2017.5218 99

Current (A) ISSN (Online) 2321 2004 Fig. 2 (a) Voltage and rms current under linear load condition (b) Voltage and rms current under non-linear load with heavy THDi condition Table 2 The harmonic spectrum for different THDi for constant rms current THDi I 1 I 3 I 5 I 7 I 9 I 11 I 13 I 15 0.9 9.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.6 9.57 0.46 0.39 0.26 0.39 0.28 0.25 0.13 11.5 9.53 0.58 0.49 0.34 0.45 0.30 0.28 0.13 14.2 9.50 0.78 0.64 0.42 0.52 0.32 0.29 0.16 17.7 9.43 1.05 0.83 0.51 0.56 0.31 0.31 0.23 20.7 9.40 1.32 1.00 0.57 0.57 0.30 0.37 0.30 26.5 9.23 1.84 1.22 0.60 0.58 0.41 0.47 0.40 36.5 8.95 2.78 1.50 0.69 0.67 0.59 0.45 0.59 Table 3 shows the total effective harmonics current, I e compared to the constant rms current, I rms and fundamental harmonic current, I 1. In order to calculate I e, the harmonics sequences must be observed to get the correct effective value. The sequences are as follows. Zero sequence: 3,6,9,12,15... Positive sequence: 1,4,7,10,13... Negative sequence: 2,5,8,11,14... Hence, I e = I 1 -I 5 +I 7 -I 11 +I 13 Table 3 Total effective harmonics current of a constant rms current under different THDi Fig 3. shows the comparison for the rms, fundamental and total effective harmonics current under different THDi. From the graph, THDi contributes significant effect to the fundamental and effective harmonics current. Comparing rms value and the effective current, it is clear that the THDi affects the value of the effective current under nonlinear load. The heavier the THDi, the lower the effective current is. The same pattern also applies to the fundamental current. The heavier the THDi, the lower the fundamental current is. 10 THDi I rms I 1 I e 0.9 9.60 9.60 9.60 9.6 9.60 9.57 9.41 11.5 9.60 9.53 9.36 14.2 9.60 9.50 9.25 17.7 9.60 9.43 9.11 20.7 9.60 9.40 9.04 26.5 9.60 9.23 8.67 36.5 9.60 8.95 8.00 9 8 Irms I1 Ie 7 0.9 9.6 11.5 14.2 17.7 20.7 26.5 36.5 THDi (%) Fig. 3 Different current types under different THDi Copyright to IJIREEICE DOI 10.17148/IJIREEICE.2017.5218 100

Energy consumption (kwh) ISSN (Online) 2321 2004 Table 4 shows the comparison between the energy measurement from EDS2560 and the energy usage from Fluke 43B based on rms current, fundamental harmonic current and effective harmonic current. Relatively, E rms shows a quite similar value compared to the measured E p. Table 4 Energy consumption of the non-linear load with different current types THDi E p E rms E f E e 0.9 53.89 55.30 55.30 55.30 9.6 52.66 53.08 52.92 52.03 11.5 51.77 52.53 52.15 51.22 14.2 51.02 51.98 51.44 50.08 17.7 50.68 50.87 49.97 48.28 20.7 50.55 49.77 48.73 46.86 26.5 49.14 48.11 46.25 43.45 36.5 44.56 44.79 41.76 37.32 Fig. 4 shows the graphical energy consumption with different current types under different THDi. Comparing the actual reading based on EDS2560 to the other readings, clearly the most suitable parameter to be used in the digital watt-hour energy measurement is the rms current. No significant difference between the E p and the E rms value is spotted when comparing both parameters. However, fundamental and effective harmonic current show significant differences when they are compared to the measured EDS2560 values. From the consumer side, the non-linear load (even with heavy THDi) did not influence the customer s bill for single phase usage because the measured and the calculated energy consumption did not show any huge differences. However, from the utility company side, it will be affected by the non-linear load because the harmonics are not considered in the energy consumption for the digital watt-hour single phase meter measurement. 60 50 40 30 20 10 0 Ep Erms Ef Ee 0.9 9.6 11.5 14.2 17.7 20.7 26.5 36.5 THDi (%) Fig 4. Energy consumption with different current types under different THDi As a result, the utility company will be losing more when the consumer uses moderate or heavy THDi load. From the graph, THDi more than 15% will significantly affected the utility company losses. IV. CONCLUSION Digital watt-hour meter is widely used to replace the conventional electromechanical analog meter to measure the energy consumption by the customer. Although the technique to measure energy consumption for this digital watt-hour meter is totally different compared to the analog meter, coincidently this meter also has the same problem with the analog meter. This digital meter also cannot measure accurately the energy consumption from the nonlinear load especially when moderate to heavy distortion is subjected to it. RMS current is still the main parameter used to measure the energy consumption in the digital meter. Although THDi did not influence the consumer s energy bill but the utility company will bear the losses when the harmonics are not taken into account. However, if THDi needs to be considered in the energy consumption billing, the bill tariff should be tailored accordingly to include the distortion into account. ACKNOWLEDGMENT The work described in this paper was fully supported by a grant from Universiti Sains Malaysia (Grant no. 1001/PELECT/814252). REFERENCES [1] C. Venkatesh, D. S. K., D.V.S.S. Siva Sarma, M. Sydulu (2008). "Modelling of Nonlinear Loads and Estimation of Harmonics in Industrical Distribution System." Fifteenth National Power System Conference (NPSC), IIT. [2] A.Priyadharshini, N. D., AR.Uma saranya, R.Anit (2012). "Survey of Harmonics in Non Linear Loads." International Journal of Recent Technology and Engineering (IJRTE) Volume-1(Issue 1): 6. [3] Shmilovitz, D. (2005). "On the Definition of Total Harmonic Distortion and Its Effect on Measurement Interpretation." IEEE Transactions On Power Delivery Vol. 20(No. 1): 3. [4] W. Mack Grady, S. S. (20011). "Understanding Power System Harmonics." Ieee Power Eng. Rev. 21: 3. [5] Indrajit Pukrayastha, P. J. S. (1990). "Effect of Harmonics on Power Measurement." Transactions On Industry Applications: 3. [6] R. M. H. E. E. D. Prof. Ahmed A. Hossam-Eldin, Alexandria University Alexandria, Egypt, "Study of The Effect of Harmonics On Measurements of The Energy Meters," presented at the Power Systems Conference, 2006. MEPCON 2006. Eleventh International Middle East, El-Minia, 2006. BIOGRAPHIES Syafrudin Masri received the M.Sc. degree in electrical engineering and the Ph.D. degree in electrical engineering from the Institut Teknologi Bandung, Indonesia in 1992 and 2000 Copyright to IJIREEICE DOI 10.17148/IJIREEICE.2017.5218 101

respectively. Currently, he is an associate professor in the electrical and electronic department Universiti Sains Malaysia. He was the electrical engineering program chairman from 2006 to 2015. His research interests cover the power quality, power system, electrical machines and drives and also renewable energy systems. Mohd Nadzri Mamat received the M.Sc. degree in electrical engineering from the Universiti Sains Malaysia in 2010. Currently, he is a senior research officer in the electrical and electronic department Universiti Sains Malaysia. His research interests cover the design and analysis of various electrical machines, power system, energy conversion and also renewable energy systems. Mohd Yuzair Yahya received the Bachelor degree in electrical engineering from the Universiti Sains Malaysia in 2015. His research interests are in power quality and renewable energy. Copyright to IJIREEICE DOI 10.17148/IJIREEICE.2017.5218 102