A STUDY CASE ON HARMONIC DISTORTION CREATED BY WIND TURBINES

Similar documents
Harmonic resonances due to transmission-system cables

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Resonances in Collection Grids of Offshore Wind Farms

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

ADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS

Harmonic Planning Levels for Australian Distribution Systems

System Requirements for Wind Farms and Distributed Generation. Giuseppe Di Marzio

Aspects of Network Harmonic Impedance Modelling in High Voltage Distribution Networks

MAINS SIGNAL PROPAGATION THROUGH DISTRIBUTION SYSTEMS. J. Stones*, S. Perera*, V. Gosbell* and N. Browne**

Published in: Proceedings of the 2016 IEEE International Conference on Power Electronics, Drives and Energy Systems (PEDES)

In Class Examples (ICE)

Harmonic distortion analysis on the MV and LV distribution networks: problems, influencing factors and possible solutions

Experience in the application of IEC/TR to harmonic allocation in transmission systems

Exercises on overhead power lines (and underground cables)

INVESTIGATION INTO THE HARMONIC BEHAVIOUR OF MULTIPULSE CONVERTER SYSTEMS IN AN ALUMINIUM SMELTER

METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE

Power Quality Requirements for Connection to the Transmission System

STUDY OF THE EFFECTS OF HARMONICS IN THE DESIGN OF TRANSMISSION NETWORK SHUNT COMPENSATORS: NETWORK SIMULATION AND ANALYSIS METHODS

, ,54 A

A robust voltage unbalance allocation methodology based on the IEC/TR guidelines

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

Wind power plant resonances 风力发电厂的共振

Harmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems

Grid Impact of Neutral Blocking for GIC Protection:

High Voltage DC Transmission 2

Harmonic Design Considerations for Wind Farms

Wind Power Plant Transmission System Modelling for Harmonic Propagation and Small-signal Stability Analysis

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

HARMONICS ANALYSIS USING SEQUENTIAL-TIME SIMULATION FOR ADDRESSING SMART GRID CHALLENGES

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

DESIGN AND ANALYSIS OF ELIMINATION OF HARMONICS USING WIND ENERGY CONVERSION SYSTEMS

Power Systems Modelling and Fault Analysis

QUESTIONNAIRE for Wind Farm Power Stations only

Harmonic Filtering in Variable Speed Drives

A Reduction of harmonics at the Interface of Distribution and Transmission Systems by using Current Source active Power Filter

Flicker Attenuation Part II: Transfer Coefficients for Regular Voltage Fluctuations in Radial Power Systems With Induction Motor Loads

Introduction to Harmonic Analysis Basics

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS

Impact Assessment Generator Form

Modeling of the behavior of power electronic equipment to grid ripple control signal

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

HV AC TESTING OF SUPER-LONG CABLES

Conventional Paper-II-2013

Voltage and Current Waveforms Enhancement using Harmonic Filters

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

Frequency Domain Analysis of Capacitor Transient Overvoltages

Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System

Induction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Incorporation of Self-Commutating CSC Transmission in Power System Load-Flow

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

Some aspects regarding harmonic s distortions propagation in large medium voltage distribution system

Considerations on Harmonic Impedance Estimation in Low Voltage Networks

IMPLICATIONS OF APPLYING DIFFERENT VAR SUPPORT TECHNOLOGIES IN THE ESKOM TRANSMISSION NETWORK WITH PARTICULAR EMPHASIS ON THE LIFECYCLE COST

Short Circuit Calculation in Networks with a High Share of Inverter Based Distributed Generation

AC Power Instructor Notes

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Some European experiences with renewable installations

A Comprehensive Approach for Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Harmonic models of a back-to-back converter in large offshore wind farms compared with measurement data

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Effects of Harmonic Distortion I

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

Power Factor & Harmonics

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

A Guide to the DC Decay of Fault Current and X/R Ratios

Control Strategies and Inverter Topologies for Stabilization of DC Grids in Embedded Systems

Power System Studies

Power Quality Summary

Compensation of Reactive Power Case Study

Insights in the impact of special projects on voltage quality in the HV/EHV networks

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

Challenges with Harmonic Compensation at a Remote Bus in Offshore Wind Power Plant

Generalized Theory Of Electrical Machines

Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

Attenuation and propagation of voltage unbalance in radial distribution networks

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Prepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

7/15/2002 PP.AFD.08 1 of 28

SYNCHRONOUS MACHINES

RECENTLY, the harmonics current in a power grid can

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

A novel method to improve Power quality by using wind and solar hybrid system

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

2. Current interruption transients

Selected Problems of Induction Motor Drives with Voltage Inverter and Inverter Output Filters

1 INTRODUCTION 2 MODELLING AND EXPERIMENTAL TOOLS

Transcription:

C I R E D 8 th International Conference on Electricity Distribution Turin, 6-9 June 5 A STUDY CASE ON HARMONIC DISTORTION CREATED BY WIND TURBINES Stavros PAPATHANASSIOU Michael PAPADOPOULOS National Technical University of Athens - Greece e-mail: st@power.ece.ntua.gr SUMMARY The grid-side converters of variable speed wind turbines inject harmonic currents in the network, which may potentially create voltage distortion problems. In this paper, a case study is presented for a wind farm, intended to be connected to a network with extended HV subsea cable lines. First, the system modelling approach is presented and the harmonic load flow calculation is outlined. Then, the harmonic impedance of the system is calculated for a variety of configurations and operating conditions, and its main characteristics are discussed. Harmonic load flow results are then provided, to indicate potential voltage distortion problems.. INTRODUCTION Although variable speed wind turbines (WTs) are gridfriendly machines in most power quality respects, harmonics generated by the grid-side power converters may be of concern in networks with possible harmonic resonance conditions. Such a case is presented in this paper, dealing with a x5 kw wind farm, intended to be connected to the Medium Voltage (MV) network of the Greek island of Kefalonia, situated in the Ionian Sea, in western Greece. The islands Kefalonia, Lefkas and Zakynthos are connected to the mainland 5 kv grid by successive overhead and submarine line sections of significant length, as shown in Fig. 3 (Section 3). Due to the large capacitance of the submarine cables, which might give rise to resonances, an investigation was deemed necessary to rule out possible harmonic distortion problems. In Section of the paper, the modelling methodology is briefly outlined. The studied system is presented in Section 3, where results are provided from the harmonic simulation. First, the harmonic impedance of the system is calculated at selected buses, its characteristics are discussed and its sensitivity with respect to various parameters is investigated. Then, harmonic load flow results are given, to indicate potential voltage distortion issues.. MODELLING OF THE SYSTEM. Fundamental principles The modelling approach presented in this paper permits the basic representation of the system harmonic impedance variation at all buses and the execution of harmonic load flow calculations, to determine the resulting voltage distortion for a given harmonic excitation. The modelling approach adopted is based on IEC 6-3-6 [], CIGRE Guides [-4] and IEEE Task Force recommendations [5], as well as on other relevant literature (e.g [6]) and attempts to maintain a balance between the required modelling complexity, on one hand, and the ease of implementation and scarcity of reliable data for actual systems, on the other hand. Fundamental assumptions and considerations are the following: o Harmonic sources are the power electronics converters at the output of the WTs, modelled as current injections of given amplitudes per frequency. This is a justified assumption for current controlled converters with PWM hysteresis controllers, as in the present case. o A direct harmonic solution ([6]) is obtained, that is the coupling between harmonics of different order is ignored. o In the general case, the network is modelled by its 3-phase equivalent, transformed in the symmetrical component domain. This is required, to properly represent the propagation of zero sequence harmonics, as well as to cater for asymmetries of the harmonic sources. The overall harmonic model has been implemented in the software package WindNet, developed for the analysis of the impact from the connection of WTs to the grid, [7].. Harmonic load flow The harmonic load flow at frequency f h =h f (where h is not necessarily an integer) is based on the solution of the set of linear equations: [ I h ] = [ Yh ][ Vh ] () where [I h ] is the vector of the harmonic current injections of each busbar [V h ] is the vector of the resulting voltage harmonics [Y h ] is the network admittance matrix at f h =hf Formulation of the admittance matrix of the network is a standard power system analysis practice, using the characteristic equations of all network elements (lines, transformers, rotating machines etc.), discussed in the following sections. In this case, the sequence equivalents of the network are employed (positive, negative and zero sequence), as mentioned in Section... Eq. () can be solved independently for each one of the three sequences, or simultaneously, as a set of 3Nx3N equations, where N is number of system buses. In the latter case, each element of vectors [I h ] and [V h ] is a 3x sub-vector, comprising the three sequence components of the harmonic current or voltage of a specific bus. Similarly, each element of matrix [Y h ] is a 3x3 sub-matrix, the non-diagonal elements of which are zero for symmetrical network elements. The network harmonic impedance matrix, [Z h ], is the inverse of the admittance matrix, [Y h ]. Its diagonal elements are the CIRED5

C I R E D 8 th International Conference on Electricity Distribution Turin, 6-9 June 5 harmonic impedances of the respective system buses. Hence, a frequency scan, to reveal possible harmonic resonance conditions at specific buses, is simply performed by calculating [Z h ] for varying frequencies f h =hf..3 Harmonic sources Representing harmonic sources as current injections, a 3- phase source would be completely described by the magnitude and angle of each phase current per harmonic frequency. Data available in practice, however, usually comprise only a current magnitude per frequency (as in the power quality certificates per IEC 64- [8]). Based on such data, the modelling should properly represent superposition (summation) effects of harmonics from different sources, as well as harmonic current asymmetries, inherent in hysteretic PWM controllers. For the summation of harmonic sources connected to the same bus, the nd summation law of [] is adopted: a I h = a I h, k () k where I h,k is the h th order contribution from source k. The summation exponent is α=. for h<5, α=.4 for 5 h and α=. for h>, reflecting the fact that the phase angles tend to become uncorrelated random variables, as the harmonic frequency increases. For harmonic sources connected to neighbouring buses, the phase angles of each source may be considered to be random variables with increasing variance, as the harmonic order h increases, to create the summation effect of eq. (). With respect to the current symmetry, it may be assumed that all three phases have the same current magnitude, but the phase angles can be properly randomized for higher order harmonics, to create current asymmetries. Attention should be paid to exclude zero sequence components from the harmonic currents, when the source connection does not permit them..4 System load The system load may be simulated using any of the three models shown in Fig. ([-5]). In all cases R, X are the fundamental frequency resistance and reactance. Proper selection of the load model is very important for correctly assessing the magnitude of possible resonances. However, no generally applicable harmonic model exists and case-specific measurements and evaluations are needed for detailed studies. Α h R h R jhx.9. h jhx Β C R jx +.9 +.h Figure. Alternative harmonic models considered for the system load. equivalent circuit, referred to harmonic frequency f h =h f, shown in Fig.(a). R B and X B are the blocked-rotor test resistance and reactance. Factor α=r /R B, where R is the resistance of the stator (typical value a=.45). The slip at frequency f h =h f is given by ± hω ω r sh = (3) ± hω where ω r is the rotor speed and the + or sign depends on the sequence (positive or negative) of the considered harmonics. More accurate results may be obtained using the steady-state equivalent for double-cage rotor. RB a jhx Β ( a) ± h h + sh hr jhx (a) (b) Figure. (a) Induction and (b) synchronous machine harmonic equivalents. Synchronous machines are simulated as shown in Fig. (b), where R and X are the negative sequence resistance and reactance, often approximated using the d and q axis subtransient reactances, as. For the zero X = ( X d + X q ) / sequence, the neutral grounding impedance of the stator is taken into account. In the positive and negative sequence, transformers are modelled by their series short-circuit harmonic impedance Z k,h =R k,h +jhx k, where: R k,h =R k (c +c h b +c h ) (4) R k and X k, are the fundamental frequency short-circuit resistance and reactance. Values for the parameters of eq. (4) are given in [4]. In the zero-sequence, the transformer equivalent circuit takes into account the connection of the windings and the neutral grounding impedance. The phase shift angle associated with the transformer vector group is also taken into account..6 Transmission lines and shunt elements Overhead lines and cables are modelled using multiple π- equivalent sections, connected in series. For the analysis extending to the 5 th harmonic order, satisfactory results are obtained using one π-section every km of 5 kv overhead lines or.5 km of 5 kv submarine cable line. The application of more sophisticated line models has not been favoured because it is contradicted by the lack of data for the rest of the system. Shunt elements considered are basically compensating reactor coils and capacitors, which are modelled as concentrated impedances..5 Electric machines and transformers Asynchronous machines are simulated using their simplified CIRED5

C I R E D 8 th International Conference on Electricity Distribution Turin, 6-9 June 5 5 kv submarine cable line 3xx3 mm Cu Oil insulated - Single armour 5 kv overhead line 3x7 mm Al (ACSR) x/5 MVA 5/5 kv u k=5% 3. km 5 kv overhead line x3xacsr-95 x.5 MVAr x6. MVAr ~ 7 x 5 kw LEFKADA 3. km Ω 5 kv 6.3 / 7.7 MW cosφ=.9 4 4.36 km 5.8 km 3. km R= Ω KASTRAKI AKTIO 5 Ω FISKARDO ARGOSTOLI 3.85 km kv 5 kv.48 km 6 8 KATELIO.3 km 5 kv 64.64 km 4.7 / 3. MW cosφ=.9 ZAKYNTHOS 5 kv Ω 9 x/5 MVA 5/5 kv u k=5% 5 kv 5.4 / 7.5 MW cosφ=.9 ~ x/5 MVA 5/ kv u k=5% 3 x.5 MVAr x6. MVAr Figure 3. One line diagram of the studied system. 3. APPLICATION RESULTS 3. The study case system X k=4.5 Ω 5 kv S k=5 MVA In Fig. 3 the one line diagram of the system under study is shown. The mainland grid is represented by its Thevenin equivalent circuit at Kastraki. Reactors are connected to the island substations, to compensate the high capacitance of the oil-insulated submarine cables. The x5 kw wind farm is intended to be connected to the Argostoli 5 kv busbars, via a dedicated double circuit, overhead line. The MV network of the Argostoli substation comprises several hundred km of overhead 5 kv lines, as well as a 6.5 km long submarine cable line. The overall shunt capacitance of this network affects the first order harmonic resonance at the Point of Common Coupling (PCC) of the wind farm. It has been roughly evaluated at 4 kvar and it is assumed connected to the MV busbars of the substation. In Fig. 4 measured values are shown of the -min average harmonic currents (up to the 5 th order) for the examined wind turbine type. The main spectral content between. and.5 khz is due to the hysteresis PWM current controllers used in the WT grid-side converters. Magnitude (%).5.5.5 Fundamental = % THD = 4.9% 5 9 3 7 5 9 33 37 4 45 49 Harmonic order Figure 4. Measured WT output current harmonics. 3. Harmonic impedance characteristics The voltage harmonic distortion, U h, created by the injection of harmonic current I h at a certain node of a system is simply given by: U h = Z h I h (5) where Z h is the harmonic impedance of the upstream system, as viewed from the terminals of the specific node. Given the harmonic current injection, application of eq. (5) to find U h becomes then an issue of evaluating Z h. The harmonic impedance at a specific bus will depend on the load level and harmonic representation. To illustrate the effect of the load, the harmonic impedance of the system is calculated for minimum and maximum load conditions, at the Point of Common Coupling (PCC) of the wind farm, i.e. at the 5 kv busbars of Argostoli substation, as well as at the 5 kv side of the substation. The results are shown in Fig. 5. It is observed that at light load conditions the impedance magnitude increases by a factor of., since lightly loaded systems are known to exhibit more pronounced resonance peaks. The harmonic impedance at the 5 kv side is very little affected by variations of the load. It is noted that the compensating coils are connected only at minimum load conditions. It can be shown, however, that they do not have a significant impact on the harmonic impedance in the frequency range of interest. Observation of Fig. 5 reveals the fundamental harmonic characteristics of the studied system, which remain the same, regardless of the load level. At the MV busbars, the variation of the harmonic impedance is dominated by the first parallel resonance of the aggregate busbar capacitance (Q c =4 kvar) with the upstream system inductive impedance (short circuit capacity S k 45 MVA). Up to this frequency, between.-.5 khz, the system is basically inductive, becoming capacitive thereafter. At the HV side, the diagram exhibits several resonance peaks, associated with the multiple cable/line sections. These are not affected by variations of the load, with the exception of the lowest frequency peak at approximately Hz (also discernible in Fig. 5), which is associated with the first order resonance of the total shunt capacitance with the upstream system series inductance. At higher frequencies the system impedance is inductive, up to.-.5 khz. CIRED5

C I R E D 8 th International Conference on Electricity Distribution Turin, 6-9 June 5 6 5 4 3 MV busbars 5 5 5 3 5 5 5 5 5 3 Figure 5. Magnitude of the harmonic impedance at the MV and HV busbars of Argostoli substation, for maximum and minimum load conditions. 8 6 4 Load model A Load model B Load model C 5 5 5 3 Figure 6. Magnitude of the harmonic impedance at the MV busbars of Argostoli substation, for the three load models of Fig.. 8 6 4 HV busbars Q c = kvar Q c =4 kvar Q c =8 kvar 5 5 5 3 Figure 7. Magnitude of the harmonic impedance at the MV busbars of Argostoli substation, for different MV aggregate capacitance. The diagrams in Fig. 5 present the positive/negative harmonic impedance. The zero sequence impedance is not shown, as no zero sequence harmonic excitation exists, due to the D- connected MV windings of the WT transformers. An issue equally important to the load level is the harmonic model used to represent loads. In Fig. 6 the results obtained for the MV bus at Argostoli are shown, using the three different models of Fig.. It is noted that the load modelling is critical for the local MV bus impedance, but not so much for the HV system. Model C expectably yields too optimistic results at high frequencies. This is actually an empirical model, based on measurements on a specific MV network, and it is suitable for low order harmonics. Concerning Models A and B, the latter tends to underestimate the damping effect of the load due to the series RL connection. Model A is considered to be more appropriate here, its shunt inductance corresponding to the aggregate load of small induction motors within each MV network, which do not provide essential damping at high frequencies. Hence, Model A is used for the results presented in this paper. Since the current spectrum of the considered harmonic sources is concentrated around the 5 th order (Fig. 4), variations of the PCC harmonic impedance in the frequency range -.5 khz are most critical. The resonance frequency in this range varies inversely with the aggregate capacitance Q c connected to the MV busbars, as shown in Fig. 7. Q c represents the total shunt capacitance of the whole MV network and therefore its exact value is unknown. The adopted value Q c =4 kvar, besides being a reasonable estimation, based on available network data, represents also a worst-case scenario, producing a resonance within the high distortion area of the harmonic excitation spectrum in Fig. 4. 3.3 Harmonic load flow results After presenting the characteristics of the system harmonic impedance, results are now presented from the harmonic load flow. Inputs are the harmonic injections of the wind turbines, whose magnitude per harmonic order is given in Fig. 4. These currents are reported to have been measured at the MV output of the Dyn WT transformer. Therefore, they cannot include any zero sequence components (not even the triplen ones), a situation possible with hysteresis PWM current controllers. THD (%).8.6.4..8.6.4. 3 4 5 6 7 8 9 Bus number Figure 8. Calculated THD coefficient at all system buses, at minimum and maximum load conditions. The calculated voltage THD coefficients for the buses of the system (Fig. 3) are shown in Fig. 8, for minimum and maximum load conditions. Expectedly, the harmonic distortion of the voltage is high near the wind farm (local MV network - buses 7 and ) and it increases at minimum load. Nevertheless, the calculated THD values are too small to be of any concern. CIRED5

C I R E D 8 th International Conference on Electricity Distribution Turin, 6-9 June 5 Magnitude (%).8.6.4..8.6.4..8.6.4..8.6.4. Argostoli MV busbars Vh at MV busbars IEC Planning Level IEC Compatibility Limit 5 9 3 7 5 9 33 37 4 45 49 Harmonic order Argostoli HV busbars Vh at HV busbars IEC Planning Level IEC Compatibility Limit 5 9 3 7 5 9 33 37 4 45 49 Figure 9. Calculated voltage distortion per harmonic order at Argostoli substation MV and HV busbars, for minimum load conditions. The situation, however, is not equally good when the individual voltage harmonics are examined and compared to limit values. This is shown in Fig. 9 for the MV and HV buses at Argostoli (minimum load). A relatively high voltage distortion appears at the MV busbars between.-.5 khz, associated with the coincidence of the resonant impedance peak (Fig. 5) with the harmonic excitation spectrum (Fig. 4). At the HV side, the voltage distortion is very reduced. The compatibility limit and indicative planning levels of IEC 6-3-6 are also marked on the diagrams, for comparison purposes. If these planning levels were used by the utility as permissible distortion values for the specific wind farm, violations would occur for even and triplen harmonics between. and.5 khz. The situation would be have been aggravated if the utility applied a limit allocation procedure ([,9]), in which case an individual user of the network is allocated a part of the total available voltage distortion limit. Reduction of the calculated voltage harmonics is obtained if the shunt capacitance of the internal MV cable network of the wind farm is considered, in which case the planning limit violations are much reduced. Further reduction of the voltage distortion, even below the set limit, could be easily achieved if an increased capacitance (in fact a high-pass filter) were considered either at the Argostoli MV busbars, or at the wind farm connection point. At this point, the limitations of the modelling approach should be pointed out, with respect to the load representation, as well as the crude modelling of the whole MV network, which has been reduced to an aggregate capacitance, connected to the busbars. A detailed and reliable evaluation of the harmonic distortion would require a more detailed representation of the MV network of the substation (rather than the HV system) and its load. On the other hand, in real world situations it is difficult to imagine that a modelling and analysis, even of the detail and sophistication presented in this paper, would be undertaken by the average utility for a single MW wind farm. For this reason, even more simplified analysis methods are applied in practice, which provide fast and safe (albeit, too conservative in many cases) estimations (e.g. [9]). 4. CONCLUSIONS In this paper a harmonic penetration study is presented, for a wind farm consisting of variable speed turbines, scheduled to be connected to a network with extended submarine cable sections. After presenting the system modelling approach, frequency scan and harmonic load flow results are given. The current harmonics of the wind turbine output converters fall near a parallel resonance of the system, resulting in a marginally acceptable situation regarding the voltage harmonic distortion. 5. REFERENCES [] IEC 6-3-6 (996) Electromagnetic Compatibility (EMC) Part 3: Limits Section 6: Assessment of emission limits for distorting loads in MV and HV power systems Basic EMC Publication. [] CIGRE WG 36-5, Harmonics, Characteristic parameters, Methods of study, Estimates of existing values in the network. ELECTRA No. 77, July 98. [3] CIGRE WG CC, Guide for assessing the network harmonic impedance. ELECTRA No. 67, Aug.996. [4] CIGRE JTF 36.5./4.3.3, AC System modelling for AC filter design An overview of impedance modelling. ELECTRA No. 64, Febr. 996. [5] IEEE Task Force on Harmonics Modelling and Simulation, Modelling and simulation of the propagation of harmonics in electric power networks Parts I and II. IEEE Trans. on Power Delivery, Vol., No., Jan. 996. [6] J. Arrillaga, B.C. Smith, N.R. Watson, A.R. Wood, Power System harmonic Analysis, John Wiley & Sons Ltd., 998. [7] S. Papathanassiou, N. Boulaxis, M. Papadopoulos, A Simulation Code for Power Systems with High Wind Penetration. Proc. EWEC, July, Copenhagen. [8] IEC 64- (): Wind turbine generator systems - Measurement and assessment of power quality characteristics of grid connected wind turbines. [9] S.A. Papathanassiou, Interconnection of DG to the Grid. In review for IEEE Trans. on Energy Conversion. CIRED5