Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

Similar documents
Field Instruction Switching Activities. Purpose. Scope. Objective. Safety

Guideline for Creating Disconnection Points and Establishing a Not Electrically Connected Area

Industrial and Commercial Power Systems Topic 7 EARTHING

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

AC Voltage- Pipeline Safety and Corrosion MEA 2015

ACCESS TO HIGH VOLTAGE APPARATUS

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

Education & Training

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS

Earthing, HV Switching and Associated Operational Equipment. Approval: Chief Operating Officer

Section 3. Test Procedures

Guidelines for the design, installation, testing and maintenance of main earthing systems in substations

HV Substation Earthing Design for Mines


Status Date Prepared Reviewed Endorsed Approved

High Voltage Pylon Earth Measurements

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

Earthing of Electrical Devices and Safety

CROSS-CONNECT CABINET

Reference Number PDS 04 (RIC Standard: EP SP)

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy

Guidance for UK Fire and Rescue Services. Dealing with incidents on or near National Grid high voltage overhead lines

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance

25kV A.C. Electrified Lines - Traction Bonding

Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies

CONTINUING EDUC ATION

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

Overvoltage Protection

Lightning Protection Guide. Rack-mountable Devices

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.

Agenda. Earthing of Telecom Installations using Single Point Earthing. Reference Documents. How many earths? Earthing Issue...

What Are We Protecting? Over-Voltage Protection for CP Systems. Personnel (primary) Equipment (secondary)

EPR Safety Mat Modelling & Field Testing Summary Report

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

Appendix B to Working on Exposed Energized Parts

60Hz Ratings. Typical Applications. Features & Characteristics. Ratings

Field Instruction. This instruction outlines the safe method for joining/assembling and lifting in-ground mounted two piece steel power poles.

6. Internal lightning protection

EI HIGH VOLTAGE INSULATION TESTING POLICY

DESIGN STANDARD DS 23

LONGITUDINAL INDUCTION VOLTAGE MEASUREMENT ON COMMUNICATION CABLES RUNNING PARALLEL TO OVERHEAD LINES

PME specialises in developing, implementing and maintaining solutions to the Mining industry.

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

6B.6 Substation Grounding

FAQ ON EARTHING STANDARDS 16/08/2018

kv AC substation

Underground System Design TADP 547

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES

Options to Improve the MEN System into the 21 st Century

Grounding and Bonding

ABSTRACT 1 INTRODUCTION

APPLICATION OF A HIGH RESISTANCE GROUNDING (HRG) UNIT TO AN ESP WITHIN A HAZARDOUS AREA 2014 EUALF

De-energized Lines. 1. Buzzing. 2. Light Emitting Devices. Methods for Detecting Induced Voltages. 3. Noise Producing Devices

Equipment Description Quantity as per drawings Actual quantity

Grounding for Power Quality

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

ER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA)

Endeavour Energy Electrical Safety Rules. October 2013

IMP/010/011 Code of Practice for Earthing LV Networks and HV Distribution Substations

ACCURATE SIMULATION OF AC INTERFERENCE CAUSED BY ELECTRICAL POWER LINES: A PARAMETRIC ANALYSIS

Transmission of Electrical Energy

Stake-less earth / ground testing

Earthing Guidance Notes

A New Technology. for Measuring Overhead Line and Cable Impedance Values and the Ground Impedance of Large Substations. Feature

Curriculum Document. Name Phone Logo. TETA House 344 Pretoria Avenue Randburg Gauteng. Physical Address. Postal Address

2 Grounding of power supply system neutral

Fatima Michael college of Engineering and Technology

3.7 Grounding Design for EAST Superconducting Tokamak

RADIO AND TELEVISION SATELLITE EQUIPMENT

UNCONTROLLED COPY. Queensland Electricity Entity Standard for Safe Access to High Voltage Electrical Apparatus. August 2015

7P Series - Surge Protection Device (SPD) Features 7P P P

Electrical Measurement Safety. Sponsored By:

Article 225: Outside Branch Circuits And Feeders

Wisconsin Contractors Institute Continuing Education

The Isolator/Surge Protector (ISP)

The Isolator/Surge Protector (ISP)

ECP HV INSULATION TESTING

ULC STANDARDS TECHNICAL WORK PROGRAM (WTO) Last modified on:

Company Directive STANDARD TECHNIQUE: TP21D/2. 11kV, 6.6kV and LV Earthing

Tower Grounding Training For Telecommunications Networks

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

ECE 528 Understanding Power Quality

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

American Electrical Institute

Modeling insulation in high-voltage substations

HIGH VOLTAGE RULES. Document Owner: HV Group. Authorised: Electrical Services Manager Liberty Primary Steel

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

Practical Lightning Mitigation

ECP HV INSULATION TESTING

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

The Lightning Event. White Paper

CHANCE Proximity Voltage Indicator

Transcription:

8.3 Induced Voltage Purpose The purpose of this instruction is to provide awareness of Electrostatic and Electromagnetic induced voltages and the method required to reduce or eliminate it. An induced voltage is often simply referred to as induction. There are several potentially hazardous conditions routinely found on equipment connected to the electrical network including earthing conductors and interconnected structures. These hazardous conditions can cause a fatal electric shock and include: Induced voltages from electromagnetic induction and capacitance Transient voltages from lightning and some high voltage (HV) switching surges Earth potential rise (EPR) and the resulting step and touch potential While these conditions are more likely to be found during a fault somewhere on the electrical network or during storm conditions, they can also occur during normal working conditions. Scope This instruction applies to all Horizon Power workers who work on Horizon Power electrical networks and assets that are or have the potential to cause Induced Voltages, and must be complied with at all times when working: On or near Horizon Power s electrical networks and assets Safety Before the commencement of work, a risk assessment must be carried out using the Risk Analysis Procedure (OSH-3.6-1-02), to identify and document the hazards and risks associated with the task and ensure appropriate control measures are implemented. It is important that, appropriate control measures must be identified, documented and implemented to lessen or control the identified hazards. Instruction Induced voltages that are generated may be as little as a few volts and as high as many kilovolts and could be hazardous or life threatening if the correct procedures are not followed. Induced voltages can occur in overhead lines, underground cables, or in switchyards. Wherever a line is adjacent to or connected to lines/cables which run near live parts of the system, induced voltages can develop (particularly if a fault occurs on the other line). Induced voltages most often occur between an energised line and a non-energised line, but can occur wherever there are parallel conductors. CS10 # 2226639 FI 8.3 Induced Voltage Page 1 of 6

Induced voltages may occur (especially during fault conditions) in the following: Out of service power cables Aerial pilot cables and earth Communication cables wires Overhead conductors Cable sheaths Cross-bonding cables Steel and concrete poles Double-circuit lines Lines running together for part of their length Catenary wires Pipelines Conveyors. Factors affecting the level of induced voltage are: Strength of the electromagnetic field being produced around the energised conductors Distance that the lines/cables runs parallel to each other, and Proximity (closeness) of the lines/cables to each other. The value of an Electrostatic induced voltage depends on the voltage of the inducing conductor/line (energised apparatus) or changes in voltage due to switching or faults. The value of an Electromagnetic induced voltage depends on the: Distance that new or isolated aerial conductors run parallel to an inducing conductor/line that can considerably increase the amount of induced voltage. Separation distance between the inducing conductor/line and the new or isolated apparatus. Amount of current flowing in the inducing conductor/line due to load or faults. In some cases, an inducing conductor/line crossing at right angles to a new or isolated line can create induced voltages. Electrical apparatus such as transformers and cables, including the associated metalwork, which is close to live HV apparatus, can have a voltage induced into it. The value of an induced voltage will influence the number of working earths required and the proximity of the working earths to a person s working position. Job Risk Assessments (JRA) must take into consideration the effects of induced voltages for all tasks that involve working on new or isolated electrical apparatus. Transient Voltages During a lightning strike and during some switching operations on the electrical network, large voltages and currents can be transferred onto other equipment (such as listed above) and to remote locations of the network. Switching surges and lightning transient voltages and currents can present a serious hazard. Certain parts of the electrical network (such as cable screens, earth continuity conductors and neutral conductors) must remain earthed whenever in service. They should not be disconnected from earth unless required as part of replacement or planned work. CS10 # 2226639 FI 8.3 Induced Voltage Page 2 of 6

Earth-Potential Rise Earth potential rise (EPR) occurs when electrical current enters the ground (e.g. due to a flash-over or fallen or damaged cables) and can lead to a Step and Touch Potential and/or a Transferred Earth Potential hazard. Step and Touch Potential Step and touch potential issues are shock hazards resulting from an earth potential rise. Step potential occurs when you have your feet at different points in the potential gradient. The resulting potential difference can result in a shock. Touch potential is the potential difference between the ground on which you are standing and a metal object which might be touched (such as a fence, a water tap or earthed equipment in the electrical network). Transferred Earth Potential During fault conditions, the earth potential rise can be transferred along any conductor to a remote location. A person may receive a shock by touching the conductor and the local soil. Some examples of transferred earth potential rise include: metal pipes (water or gas pipes) copper (or other metallic) wires, such as cable screens or armouring fencing (especially if a neighbouring fence connects to a substation fence) railway lines underground cables concrete (such as a steel reinforced concrete driveway next to a substation) Working on conductors exposed to induced voltages To ensure no potential difference exists across the worker s body, and all personnel are fully protected from induced voltage, evaluate from the risk assessment the appropriate action using one or more of these methods: apply earths, as specified in Field Instruction 6.1 Portable Earthing Requirements apply equipotential bonding methods and/or use insulating techniques Important When working on de-energised power lines, the installation of remote programmed earths may not always protect the workers from the dangers of induced voltage. Always maintain working earths within five metres of the worksite on each incoming power line (box in) or as close as practicable to the worksite. CS10 # 2226639 FI 8.3 Induced Voltage Page 3 of 6

Working Earths Where the job risk assessment suspects induced voltages are present, additional working earths must be installed at the work-site to eliminate the effects of any induced voltage. Working earths may be periodically moved or placed at the immediate work-site to ensure induced voltages are eliminated or kept to a minimum. Where additional working earths are placed either side of the immediate work-site or open point, the earth grounding leads must be bonded together at the earthing point to create an equipotential work zone. Uninsulated Elevated Work Platform (EWP) Uninsulated EWP s working within substation sites must: Have the basket bonded to the electrical apparatus being worked on; and The vehicle earthed to a known earth point using the approved earthing leads (either bolted or clamped). Where possible, leave all Earth Switches ON at substation sites, unless they are required to be opened for testing purposes. Before any Earth Switches are opened, ensure all personnel are made aware of the changes to the yard configuration / earthing arrangements within their relevant work area. Earthing the EWP When travelling in a live substation, securely attach a trailing 10 mm diameter bright or galvanised drag chain to the EWP (minimum 150 mm of chain in contact with ground). Earth the EWP to the substation earth grid. Before use, inspect the earth lead and confirm: that the test date is not expired the tightness of bolted connections the general condition of earthing leads When working in a substation the earth leads must be a minimum of 150 mm² aluminium. Note: When using multiple uninsulated access equipment (EWP s and scaffolding) ensure all pieces of equipment are bonded together. CS10 # 2226639 FI 8.3 Induced Voltage Page 4 of 6

Transmission Power lines entering Substations When disconnecting an incoming transmission power line from the substation, establish an equipotential zone using the techniques below: Bond the power line outside the substation to the first tower or to the running earth Use bridging conductors when breaking a conductor. Bond the tower or running earth to the substation earth grid (see Figure 11 below) Situate working earths within five metres of each side of the work area. Another measure to consider is an earth mat around the base of the tower if the risk assessment indicates a high risk of induced voltage. Note: Higher voltages, higher currents and longer areas of close proximity between energised and de-energised conductors/cables, all contribute to increasing the risk and severity of induction on the de-energised conductors/cables. CS10 # 2226639 FI 8.3 Induced Voltage Page 5 of 6

References Occupational Safety & Heath Act 1984 Occupational Safety & Health Regulations 1996 SHMS OSH-3.6-1-02 Job Risk Analysis (JRA) Procedure SHMS OSH-3.6-1-26 Personal Protective Equipment Electrical Safety Standards Field Instruction 2.5 Other Personal Protective Equipment Field Instruction 2.6 Worksite Clothing / Personal Protective Equipment Requirements Field Instruction 2.7 Safety Requirements when Working from an EWP Field Instruction 2.13 Vehicle and Plant Earthing Requirements Field Instruction 2.17 Safe Approach Distances Field Instruction 2.23 Job Hazard and Risk Management (JRA) Field Instruction 2.25 Test Before You Touch Prior to Commencement with Work Field Instructions 4.1 Substation Entry Requirements Field Instruction 4.3 Substation Clearances Field Instruction 5.4 Testing and use of High Voltage Insulated Equipment Field Instruction 8.1 Portable Earthing Requirements Further Reading Electricity Engineers Association New Zealand, Work on De-Energized Distribution Overhead Lines, January 2008, Issue 2 Electricity Supply Association of Australia, Work on Cables Under Induced Voltages Application Guide, D(b)26-1995 International Electro Technical Commission, Live working Guidelines for the installation of transmission line conductors and earth-wires Stringing equipment and accessory items IEC/TR 61328:2003, 12 March 2003 CS10 # 2226639 FI 8.3 Induced Voltage Page 6 of 6