MODBUS Protocol for CS1 network card family 1
MODBUS tables Please note that not all the data are available for all UPSs. The addresses are in PLC mode (base 1). Type: U means without arithmetic sign, S means with arithmetic sign. Single phase UPS Address Function Type Description Notes 40001-40007 UPS Company Name 2 each register 40008-40012 UPS Model Name 2 each register 40013-40017 UPS Firmware Version 2 each register 40018-16 40025 CS1 Firmware Version 2 each register 40026 U Battery Status rmal 3 - battery low 40027 U Seconds on Battery [seconds] 40028 U Battery Capacity [%] 40029 U Battery Voltage [V * 0] 400 U Battery Temperature [ C * ] 401 S Battery Current [A * ] 402 U Total Battery Voltage [V * 0] 40040 U Input Line Voltage [V * ] 40041 U Input Max Line Voltage [V * ] 40042 U Input Min Line Voltage [V * ] 40043 U Input Frequency [Hz * ] 40044 U Input Current [A * ] 40045 U Input True Power [W] 40050 U Output Status rmal 3 - battery 4 - boost 5 - sleeping 6 - bypass 7 - rebooting 8 - standby 9 - buck 40051 U Output Voltage [V * ] 40052 U Output Frequency [Hz * ] 40053 U Output Load [%] 40054 U Output Current [A * ] 40055 U Output True Power [W] 40060 U Rating Voltage [V * ] 40061 U Rating Power [VA] 40062 U Rating Battery Voltage [V * 0] 2
40063 U Rating Frequency [Hz * ] 40064 U Utility Fail 40065 U UPS Failed 40066 U Test in Progress 40067 U Shutdown Active 40068 U Beeper ON 40070 06 / 16 U Config UPS Switch off Delay 40071 06 / 16 U Config UPS Sleep Time 1-9999 40080 06 / 16 U Control UPS Switch off 2 - turn OFF UPS The delay in seconds the UPS remains on after being told to turn off. Allowed values are [seconds]: 12, 18, 24, 30, 36, 42, 48, 54, 60, 120, 180, 240, 300, 360, 420, 480, 540, 600 40081 06 / 16 U Control UPS Reboot 2 - reboot UPS 40082 06 / 16 U Control UPS Sleep 1 - no put UPS to sleep 2 - put UPS to sleep 40083 06 / 16 U Control Simulate Power Failure 2 - simulate Power Failure 40084 06 / 16 U Control Flash and Beep 2 - enable flash and beep 40085 06 / 16 U Control Turn ON UPS Load 2 - enable flash and beep 40090 06 / 16 U Test Diagnostics 2 - smart control turn ON UPS load 40091 U Test Diagnostics Results 1 - ok 2 - failed 3 - invalid test 4 - test in progress 3
Three-phase UPS Address Function Type Description Notes 40001-40007 UPS Company Name 2 each register 40008-40012 UPS Model Name 2 each register 40013-40017 UPS Firmware Version 2 each register 40018-16 40025 CS1 Firmware Version 2 each register 40026 U Battery Status rmal 3 - battery low 40027 U Seconds on Battery [seconds] 40050 U Output Status rmal 3 - battery 4 - boost 5 - sleeping 6 - bypass 7 - rebooting 8 - standby 40070 06 / 16 U Config UPS Switch off Delay 40071 06 / 16 U Config UPS Sleep Time 1-9999 40080 06 / 16 U Control UPS Switch off 2 - turn OFF UPS 9 - buck The delay in seconds the UPS remains on after being told to turn off. Allowed values are [seconds]: 12, 18, 24, 30, 36, 42, 48, 54, 60, 120, 180, 240, 300, 360, 420, 480, 540, 600 40081 06 / 16 U Control UPS Reboot 2 - reboot UPS 40082 06 / 16 U Control UPS Sleep 1 - no put UPS to sleep 2 - put UPS to sleep 40083 06 / 16 U Control Simulate Power Failure 2 - simulate Power Failure 40084 06 / 16 U Control Flash and Beep 2 - enable flash and beep 40085 06 / 16 U Control Turn ON UPS Load 2 - smart control turn ON UPS load 40090 06 / 16 U Test Diagnostics 2 - start test diagnostic 40091 U Test Diagnostics Results 1 - ok 2 - failed 3 - invalid test 4 - test in progress 400 U Battery Voltage [V * ] 401 U Battery Capacity [%] 402 U Battery Time Remaining [minutes] 401 S Battery Current [A * ] 404 U Battery Temperature [ C * ] 401 U Input Frequency [Hz * ] 40111 U Input Voltage (L1) [V * ] 40112 U Input Voltage (L2) [V * ] 40113 U Input Voltage (L3) [V * ] 40120 U Output Frequency [Hz * ] 4
40121 U Output Voltage (L1) [V * ] Output Voltage if the UPS has only one 40122 U Output Voltage (L2) [V * ] 40123 U Output Voltage (L3) [V * ] 40124 U Output Load (L1) [% * ] Output Load if the UPS has only one 40125 U Output Load (L2) [% * ] 40126 U Output Load (L3) [% * ] 40130 U Bypass Frequency [Hz * ] 40131 U Bypass Voltage (L1) [V * ] 40132 U Bypass Voltage (L2) [V * ] 40133 U Bypass Voltage (L3) [V * ] 400 U DC and Rectifier Status RecRotError 401 U DC and Rectifier Status LowBatteryShutdown 402 U DC and Rectifier Status LowBattery 403 U DC and Rectifier Status 2 - one output phase InAndOut 3 - three output phases 404 U DC and Rectifier Status 4 - backup BatteryStatus 5 - AC normal 405 U 6 - boost DC and Rectifier Status 7 - float ChargeStatus 406 U DC and Rectifier Status RecOperating 407 U UPS Status Bypass 408 U Frequency Fail UPS Status Manual Bypass Breaker 409 U UPS Status AC Status 40150 U 401 U 40160 U 40161 U 40162 U UPS Status Static Switch Mode UPS Status Inverter Operating Fault Status Emergency Stop Fault Status High DC Shutdown Fault Status Bypass Breaker 40163 U Fault Status Over Load 40164 U 40165 U Fault Status Inverter Output Fail Fault Status Over Temperature 8 - closed 9 - open 8 - normal 9 - abnormal 12 - inverter mode 13 - bypass mode 5
40166 U Fault Status Short Circuit 40170-40176 Rating Rectifier Voltage 2 each register Rating Rectifier 40177 U [Hz] Frequency 40178 - Rating Source Bypass 2 each register 40184 Voltage Rating Bypass Source 40185 U [Hz] Frequency 40186 - Rating Output Voltage 2 each register 40192 40193 U Rating Output Frequency [Hz] 40194 U Rating Battery Voltage [V] 40195 - Rating Power 2 each register 40199 6