ENHANCEMENT OF POWER QUALITY USING 9-LEVEL CASCADED H-BRIDGE BASED D-STATCOM WITH IRP THEORY SK. Meeravali* 1, Dr. K.

Similar documents
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based Dstatcom

Power Control Scheme of D-Statcom

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

ISSN Vol.02,Issue.19, December-2013, Pages:

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

A Five Level DSTATCOM for Compensation of Reactive Power and Harmonics

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Simulation of D-STATCOM for Power Quality Improvement With Fuzzy Based Phase Locked Loop Control Strategy

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

A NOVEL APPROACH TO ENHANCE THE POWER QUALITY USING CMLI BASED CUSTOM POWER DEVICES

Investigation of D-Statcom Operation in Electric Distribution System

International Journal of Scientific & Engineering Research, Volume 6, Issue 8, August ISSN

Harmonic Immunity And Power Factor Correction By Instantaneous Power Control Of D-STATCOM

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions

Mitigation of Flicker Sources & Power Quality Improvement by Using Cascaded Multi-Level Converter Based DSTATCOM

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

Level Shifted Pulse Width Modulation in Three Phase Multilevel Inverter for Power Quality Improvement

FUZZY CONTROLLED DSTATCOM FOR HARMONIC COMPENSATION

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

29 Level H- Bridge VSC for HVDC Application

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Comparison of Three leg and Four Leg VSC DSTATCOM for Power Quality Assessment

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Power Control and Quality Management in DG Grid Interfaced Systems

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

Total Harmonic Distortion Analysis of Three Phase Nonlinear Load Using H-Bridge Vsi Topology Based_ Dstatcom

Dynamic Modeling and Simulation of Unified Power Quality Conditioner

Enhancement of Power Quality with Multifunctional D-STATCOM Operated under Stiff Source for Induction Motor Applications

MMC based D-STATCOM for Different Loading Conditions

ROLE of DC-MLI based D-STATCOM in Distribution Network with FOC Induction Motor Drive

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

A Review on Improvement of Power Quality using D-STATCOM

PI Controller Based Shunt Active Power Filter with Cascaded Multilevel Inverter

DESIGN A D STATCOM FOR VOLTAGE HARMONIC SUPPRESSION IN DISTRIBUTION SYSTEM

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER

Power Quality enhancement of a distribution line with DSTATCOM

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

ABSTRACT I. INTRODUCTION

A NOVEL SWITCHING PATTERN OF CASCADED MULTILEVEL INVERTERS FED BLDC DRIVE USING DIFFERENT MODULATION SCHEMES

2020 P a g e. Figure.2: Line diagram of series active power filter.

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Power Quality Improvement using Shunt Passive Filter

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Design of Shunt Active Filter to Improve Power Quality using Pq Theory

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

Harmonic Reduction of Arc Furnaces Using D-Statcom

Compare Stability Management in Power System Using 48- Pulse Inverter, D-STATCOM and Space Vector Modulation Based STATCOM

Enhancement of Power Quality in Distribution System Using D-Statcom

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

Enhanced Performance of Multilevel Inverter Fed Induction Motor Drive

Modeling of Statcom. P.M. Sarma and Dr. S.V. Jaya Ram Kumar. Department of Electrical & Electronics Engineering GRIET, Hyderabad, India

ISSN: [Yadav* et al., 6(5): May, 2017] Impact Factor: 4.116

Experimental Results of a Single-Phase Shunt Active Filter Prototype with Different Switching Techniques

IJESR/Nov 2012/ Volume-2/Issue-11/Article No-21/ ISSN International Journal of Engineering & Science Research

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Enhancement of Power Quality by using D- STATCOM

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

Power Quality Improvement By Using DSTATCOM Controller

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3

ANFIS based 48-Pulse STATCOM Controller for Enhancement of Power System Stability

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

A NOVEL APPROACH ON INSTANTANEOUS POWER CONTROL OF D-STATCOM WITH CONSIDERATION OF POWER FACTOR CORRECTION

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Comparison of Reference Current Extraction Methods for Shunt Active Power Filters

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

A Hybrid Cascaded Multilevel Inverter for Interfacing with Renewable Energy Resources

Chapter 4. Hybrid series active filter. 4.1 Introduction

Reduction of Harmonics and Torque Ripples of BLDC Motor by Cascaded H-Bridge Multi Level Inverter Using Current and Speed Control Techniques

Transcription:

ISSN 2277-2685 IJESR/June 2014/ Vol-4/Issue-6/309-318 SK. Meeravali et al./ International Journal of Engineering & Science Research ENHANCEMENT OF POWER QUALITY USING 9-LEVEL CASCADED H-BRIDGE BASED D-STATCOM WITH IRP THEORY SK. Meeravali* 1, Dr. K. Chandrasekhar 2 1 Department of Electrical & Electronics Engineering, R.V.R & J.C College of Engineering, Chowdavaram Guntur (A.P), India. 2 Professor & Head, Department of Electrical & Electronics Engineering, R.V.R & J.C College of Engineering, ABSTRACT Chowdavaram, Guntur (A.P), India. This paper presents cascaded multilevel voltage source inverter based active filter for power line conditioning to improve power quality in the distribution network. Cascaded multilevel configuration of the inverter has the advantage of its simplicity and modularity over the configurations of the diode-clamped and flying capacitor multilevel inverters. Shunt compensation for medium voltage distribution systems requires higher rating for voltage source converters (VSCs). Ratings of the semiconductor devices in a VSC are always limited; therefore, for higher rated converters it is desirable to distribute the stress among the number of devices using multilevel topology. The DSTATCOM helps to improve the power factor and eliminate the Total Harmonics Distortion (THD) drawn from a Non-Liner Diode Rectifier Load (NLDRL). The proposed compensation process is based on concept of instantaneous real power theory. The proposed system is simulated in the MATLAB environment using simulink and results are discussed. Keywords: DSTATCOM, Cascaded H-Bridge Inverter, Power Quality, IRP Theory, MATLAB. 1. INTRODUCTION In present day s power distribution systems is suffering from severe power quality problems. These power quality problems include high reactive power burden, harmonic(s) currents, load unbalance, excessive neutral current etc. Some remedies to these power quality [7] problems are reported in the literature. A group of controllers together called Custom Power Devices (CPD), which include the DSTATCOM [4] (distribution static compensator), The DSTATCOM [2-4], is a shunt-connected device, which takes care of the power quality problems in the currents. Three phase four-wire distribution systems are used to supply single-phase low voltage loads. The proposed DSTATCOM is modelled and its performance is simulated and verified for power factor correction and voltage regulation along with neutral current compensation, harmonic elimination and load balancing with linear loads and non-linear loads. When the STATCOM [2] is applied in distribution system is called DSTACOM (Distribution-STATCOM) and its configuration is the same, or with small modifications, oriented to a possible future amplification of its possibilities in the distribution network. At low and medium voltage, implementing the function so that we can describe as flicker damping, harmonic filtering and hole and short interruption compensation. Distribution STATCOM (DSTATCOM) exhibits high speed control of reactive power to provide voltage stabilization, flicker suppression, and other types of system control. The DSTATCOM [2] utilizes a design consisting of a GTO- or IGBT-based voltage sourced converter connected to the power system via a multi-stage converter transformer The DSTATCOM protects the utility transmission or distribution system from voltage sags and/or flicker caused by rapidly varying reactive current demand. In utility applications, a DSTATCOM provides leading or lagging reactive power to achieve system stability during transient conditions. The DSTATCOM can also be applied to industrial facilities to compensate for voltage sag and flicker caused by non-linear dynamic loads, enabling such problem loads to co-exist on the same feeder as more sensitive loads. The DSTATCOM instantaneously exchanges reactive power with the distribution system without the use of bulky capacitors or reactors. A D-STATCOM [1-4] (Distribution Static *Corresponding Author www.ijesr.org 309

Compensator), which is schematically depicted in Fig.1, consists of a two-level Voltage Source Converter (VSC), a dc energy storage device, a coupling transformer connected in shunt to the distribution network through a coupling transformer. Fig 1: DSTATCOM The VSC converts the dc voltage across the storage device into a set of three-phase ac output voltages. These voltages are in phase and coupled with the ac system through the reactance of the coupling transformer. Suitable adjustment of the phase and magnitude of the D-STATCOM output voltages allows effective control of active and reactive power exchanges between the DSTATCOM and the ac system. Such configuration allows the device to absorb or generate controllable active and reactive power. The VSC connected in shunt with the ac system provides a multifunctional topology which can be used for up to three quite distinct purposes: 1. Voltage regulation and compensation of reactive power; 2. Correction of power factor; and 3. Elimination of current harmonics. Here, such device is employed to provide continuous voltage regulation using an indirectly controlled converter. To understand P and Q flow in a transmission system, consider a simple system that is made up of sending and receiving buses with a transmission cable in between as shown in Fig 2. Fig 2: Simple line presentation of generating distribution network Thus for small line resistances, R< <X, the active and reactive power components can be approximated to sin (1) (2) It can be seen from the above approximated power components that power flow is dependent on four controlling variables VS, VR, X and s- R. Employing shunt compensation at midpoint in the transmission line increases both the active and reactive components of the injected power. For lossless compensator and transmission lines VS= VR= V, the injected power at midpoint is now given by (3) (4) Meanwhile, employing series compensation at midpoint with voltage Vc in quadrature with respect to the line current allows the compensating elements to assist only in the reactive power control. The result in the injected power is given by Copyright 2013 Published by IJESR. All rights reserved 310

= sin (5) sin (6) Where r is the degree of series compensation (0 r I). 2. OPERATION OF D-STATCOM D-STATCOM controllers can be constructed based on both VSI topology and Current Source Inverter (CSI) topology (Fig 3). Regardless of topology, a controller is a compound of an array of semiconductor devices with turn off capability (i.e., IGBT, GTO, IGCT etc.) connected to the feeder via a relative small reactive filter. The VSI converter is connected to the feeder via reactor LF and has a voltage source (capacitor CD) on the DC side. The CSI converter is connected on the AC side via capacitor CF and has a current source (inductor LD) on the DC side. In practice, CSI topology is not used for DSTATCOM [4]. The reason for this is related to the higher losses on the DC reactor of CSI compared to the DC capacitor of VSI. Moreover, a CSI converter requires reverse blocking semiconductor switches, which have higher losses than reverse conducting switches of VSI. And, finally, the VSI-based topology has the advantage because an inductance of a coupling transformer Tr (if present) can constitute, partially or completely, the inductance of an AC filter. The following text will describe the properties of VSI-topology based DSTATCOM only, but in many respects they are the same as for CSIbased controllers. The VSI converters for D-STATCOM [3] are constructed based on multi-level topologies, with or without use of a transformer. These solutions provide support for operation with a high level of terminal voltage. Additionally, DSTATCOM controllers can be a compound of several converters configured to various topologies, to achieve higher rated power or lower PWM-related current ripples. The exemplary topologies are presented in Fig 4. In the parallel configuration (Fig 4a) converters are controlled to share the generated power equally, or at a given ratio, for example proportional to the rated power of the particular converter. (a) (b) Fig 3: General topology of VSI-based and CSI-based DSTATCOM In this solution it is necessary to provide inter converter communication at the control level to distribute information about set controller power or currents. The cascade multi converter topology (Fig 4b) is similar to the parallel configuration, but in this case the constituent converters do not share power equally, but successively, depending on the requirement. In this case, no communication between constituent converters is required, but on the other hand it is also not possible to use common PWM strategy. The converters in this case are exactly the same as for standalone operation. In Fig 4c, d are presented series and parallel master-slave typologies, respectively. The master-slave topologies require a high degree of integration between constituent converters including a control system, and are treated and realised as single, multi converter controller. The master converter (called a "slow converter") has substantially higher rated power and, in consequence, considerably lowers PWM carrier frequency than the slave converter (called a ''fast converter"). The task of the master converter is to cover the requirements for power, while the. Slave has to. Compensate AC current/voltage ripples using series superposition of voltages (Fig 4 c) or parallel superposition of currents (Fig 4 d). Copyright 2013 Published by IJESR. All rights reserved 311

(a) parallel (b) master-slave series (c) cascade (d) master-slave parallel Fig 4: Multi converter topologies of D-STATCOM Controller: (a) parallel; (b) master - slave series; (c) cascade; (d) master - slave parallel 3. PROPOSED INSTANTANEOUS POWER THEORY The instantaneous power theory or p-q theory was introduced by Akagi in 1983. This method uses algebra transformation also knows as Clarke transform for three phase voltage and current. The three phase voltage and current are converted into α-β using eq. (4) and eq. (5), where iabc are three phase line current and vabc are three phase line voltage.[6].the proposed instantaneous real-power (p) theory derives from the conventional p-q theory or instantaneous power theory concept and uses simple algebraic calculations [7]. It operates in steadystate or transient as well as for generic voltage and current power systems that allowing to control the active power filters in real-time. The active filter should supply the oscillating portion of the instantaneous active current of the load and hence makes source current sinusoidal. Fig 5: α-β coordinates transformation The p-q theory performs a Clarke transformation of a stationary system of coordinates a bc to an orthogonal reference system of coordinates α,β. In abc coordinates axes are fixed on the same plane, apart from each other by 120that as shown in Fig 5. The instantaneous space vectors voltage and current Va, ia are set on the a-axis, Vb, ib are on the b axis, and Vc, ic are on the c axis. These space vectors are easily transformed into α,β Copyright 2013 Published by IJESR. All rights reserved 312

coordinates. The instantaneous source voltages vsa, vsb, vsc are transformed into the α,β coordinate s voltage by Clarke transformation as follows: Similarly, the instantaneous source current isa, isb, isc also transformed into the α,β coordinate s current by Clarke transformation that is given as; Where α and β axes are the orthogonal coordinates. They Vα, iα are on the α-axis, and Vβ, iβ are on the β-axis. Real-Power (p) calculation Let the instantaneous real-power calculated from the α-axis and β- axis of the current and voltage respectively. These are given by the conventional definition of real-power as: Pac = Vα iα+vβ iβ This instantaneous real-power Pac is passed to first order Butterworth design based 50 Hz low pass filter (LPF) for eliminating the higher order components; it allows the fundamental component only. These LPF indicates ac components of the real-power losses and it s denoted as Pac. The DC power loss is calculated from the comparison of the dc-bus capacitor voltage of the cascaded inverter and desired reference voltage. The proportional and integral gains (PI Controller) are determining the dynamic response and settling time of the dcbus capacitor voltage. The DC component power losses can be written as The instantaneous real-power P is calculated from the AC component of the real-power loss pac and the DC power loss PDC (Loss)); it can be defined as follows; P = Pac + PDC (Loss) The instantaneous current on the αβ coordinates of Icα and icβ are divided into two kinds of instantaneous current components; first is real-power losses and second is reactive power losses, but this proposed controller computes only the real-power losses. So the α,β coordinate currents icα,icβ are calculated from the Vα, Vβ voltages with instantaneous real power p only and the reactive power q is assumed to be zero. This approach reduces the calculations and shows better performance than the conventional methods. The α,β coordinate currents can be calculated as From this equation, we can calculate the orthogonal coordinate s active-power current. The α-axis of the instantaneous active current is written as: Similarly, the β-axis of the instantaneous active current is written as: Let the instantaneous powers p(t) in the α-axis and the β - axis is represented as pα and pβ respectively. They are given by the definition of real-power as follows Copyright 2013 Published by IJESR. All rights reserved 313

P(t) = vαp(t ) iαp(t) + vβp(t) iβp(t) The AC and DC component of the instantaneous power p(t) is related to the harmonics currents. The instantaneous real power generates the reference currents required to compensate the distorted line current harmonics and reactive power. 4. MATALB/SIMULINK RESULTS The D-STATCOM model is established based on Matlab/Simulink Platform. Here simulation is carried out in different cases such as 1) Implementation of 5-Level D-Statcom using proposed IRP Theory. 2). Implementation of 7-Level D-Statcom using proposed IRP Theory. 3) Implementation of 9-Level D-Statcom using proposed IRP Theory. Case 1: Implementation of 5-Level D-Statcom using proposed IRP Theory Fig 6: Matlab/Simulink Model of proposed Compensator using IRP Controller Fig.6 shows the Matlab/Simulink Model of proposed Compensator using IRP Controller based CHB D- STATCOM. Fig 7: Source Voltage, Source Current, Load Current with 5-Level DSTATCOM based IRP Controller based Compensator Fig.7 shows the Source Voltage, Source Current, Load Current with 5-Level Compensator, due to non-linear diode rectifier pollutes source side current, with IRP Controller based compensator we get source current is sinusoidal. Fig 8: Source Side Power Factor with 5-level DSTATCOM with IRP Controller Copyright 2013 Published by IJESR. All rights reserved 314

Fig.8 shows the Source side Power Factor, both voltage & current are maintained sinusoidal and in phase condition. Fig 9: FFT Analysis of source current with 5-level compensator using IRP Controller Fig.9 shows the FFT Analysis of source current with 5-level compensator using IRP Controller, we get THD is 6.22%. Fig 10: Five Level Output Voltage Case 2: Implementation of 7-Level D-Statcom using proposed IRP Theory Fig 11: Source Voltage, Source Current, Load Current with IRP Controller based 7-level Compensator Fig.11 shows the Source Voltage, Source Current, Load Current with 7-Level Compensator, due to non-linear diode rectifier pollutes source side current, with IRP Controller based compensator we get source current is sinusoidal. Copyright 2013 Published by IJESR. All rights reserved 315

Fig 12: Source Side Power Factor with 7-Level Compensator Fig 12 shows the Source side Power Factor, both voltage & current are maintained sinusoidal and in phase condition. Fig 13: FFT Analysis of source current with 7-level compensator using IRP Controller Fig. 13 shows the FFT Analysis of source current with 7-level compensator using IRP Controller, we get THD is 5.34%. Fig 14: 7- Level Output Voltage Case 3: Implementation of 9-Level D-Statcom using proposed IRP Theory Fig 15: Source Voltage, Source Current, Load Current with IRP Controller based 9-level Compensator Copyright 2013 Published by IJESR. All rights reserved 316

Fig. 15 shows the Source Voltage, Source Current, Load Current with 9-Level Compensator, due to non-linear diode rectifier pollutes source side current, with IRP Controller based compensator we get source current is sinusoidal. Fig 16: 9- Level Output Voltage Fig 17: FFT Analysis of source current with 9-level compensator using IRP Controller Fig 17 shows the FFT Analysis of source current with 9-level compensator using IRP Controller, we get THD is 4.76%. 5. CONCLUSION The cascaded inverter switching signals are generated using triangular-sampling current controller; it provides a dynamic performance under transient and steady state conditions, THD analysis also within the IEEE standards. Instantaneous real-power theory based cascaded multilevel inverter based DSTATCOM is connected in the distribution network at the PCC through filter inductances and operates in a closed loop. A five level & seven as well as nine level cascaded multilevel voltage source inverter based DSTATCOM using instantaneous realpower controller is found to be an effective solution for power line conditioning to compensate harmonics, reactive power and power factor with the IRP controller reduces harmonics and provides reactive power compensation due to non-linear load currents; as a result source current(s) become sinusoidal and unity power factor is also achieved under both transient and steady state conditions. THD analysis also within the IEEE standards. This proposed model is implemented using Matlab/Simulink software and the obtained results. REFERENCES [1] Lasseter RH. Micro Grids. PES Winter Meeting 2002; l: 305-308. [2] Ledwich G, Ghosh A. A flexible DSTATCOM operating in voltage or current control mode. lee Proc.- Gener. Trunsm. Distrbi. 2002; 149(2). Copyright 2013 Published by IJESR. All rights reserved 317

[3] Prasad KNV, Kumar GR, Kiran TV, Satyanarayana G. Comparison of different topologies of cascaded H- Bridge multilevel inverter. Computer Communication and Informatics (ICCCI), International Conference. Jan. 2013; 1(6): 4-6. [4] Singh B, Solanki J. A Comparison of Control Algorithms for Dstatcom. IEEE T Ransactions On Industrial Elect Ronics 2009; 56(7). [5] Renewable Energy Policy Network for the 21st Century, Renewable Global Status Report 2009 Update, REN21, 2009. [6] Manel Carrasco l. Power electronic system for grid integration of renewable energy source: A survey. IEEE Trans. Ind. Electron 2006; 53(4): 1002-1014. [7] Satyanarayana G, Prasad KNV, Kumar GR, Ganesh KL. Improvement of power quality by using hybrid fuzzy controlled based IPQC at various load conditions. Energy Efficient Technologies for Sustainability (ICEETS), 2013 International Conference 10-12 April 2013; 1243, 1250. Copyright 2013 Published by IJESR. All rights reserved 318