CI-tronic Analogue Power Controller ACI 30-1 and ACI 50-1

Similar documents
CI-tronic Analogue Power Controller ACI 30-1 and ACI 50-1

CI-tronic Soft start motor controller

Switching power supplies CP range, Linear power supplies CP-L range. Content

RN Thyristor Controllers

celduc SIL Phase angle controller Output : VAC 32A(*) Input : Analog 0-10V celpac r e l a i s Proud to serve you

Type 3RW RW40 7. Control electronics Rated values. Terminal. external DC supply (to DIN 19240) through terminals and IN Relay outputs

celduc SIM Phase angle controller Output : VAC 40A(*) Input : Analog 0-10V r e l a i s celpac

Type CP-S, CP-C & CP-A Switch mode

Power supply CP-E 24/0.75

Solid State Relays 1- and 2 Pole SOLITRON With Integrated Heatsink

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

77 Series - Modular Solid State Relay 5 A. Features. Timers and Monitoring relays

Electronic timer CT-SDD.22

Electronic timer CT-TGD.22

Power supply CP-D 24/4.2 Primary switch mode power supply

celduc SILD Output : VAC 32A(*) Input : 3-32VDC - I<10mA Diagnostic : 30VDC - 100mA r e l a i s celpac P roud to serve you

Power supply CP-E 24/2.5

CP-E range Benefits and advantages

Power supply CP-E 24/20.0

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

Output Voltage* (nom.)(adjustable)

celduc SIM Phase angle controller Output : VAC 40A(*) Input : Analog 0-10V celpac r e l a i s Proud to serve you

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

Electronic timer CT-SDS.22

Power supply CP-E 24/2.5

Power supply CP-D 24/1.3

To be automatically connected to the nearest North American Technical Sales Office:

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

CP-T range Product group picture

Primary switch mode power supplies Product group picture

SELECTION GUIDE. BULLETIN 156 Solid-State Contactors

Power Electronics. POWERSWITCH Semiconductor Contactor BF 9250, BH 9250

Power supply CP-T 48/5.0 Primary switch mode power supply

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

High precision measurement system for current and voltage IHC-A/B-RM01/03

CP-T range Benefits and advantages

Soft starters with internal by-pass

Power supply CP-D 12/2.1

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

Power supply CP-T 48/20.0 Primary switch mode power supply

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

Zelio Control Measurement Relays

27/04/2015

Transformers, Power Supply Units and Socket Outlets

Output of three-phase motors at 50 Hz and 400 V

Power supply CP-T 24/10.0 Primary switch mode power supply

Contactors and Contactor Assemblies

Power supply CP-T 24/40.0 Primary switch mode power supply

Power Electronics. POWERSWITCH Solid-State Contactor BF 9250, BH 9250

Electronic timer CT-MFS.21

Rated power VA (50 Hz)/W 0.6/ / / /0.3 Operating range V AC (50/60 Hz)

3RF A A 0 2. Switching function. Control voltage Operating voltage with heat sink 10 = 10.5 A. A = Zero-point switching

TeSys H. Protection. Motor controllers. Reliable. Motor starters. Contactors. Circuit breakers. Smart. Ultra-compact 22.5 mm motor starters

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

IGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards

celduc SILD r e l a i s celpac PATENTED! AC Semiconductor Contactor pitch 22,5mm with Diagnostic compact size and DIN rail mounting.

Power supply CP-T 24/20.0 Primary switch mode power supply

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240

02/11/2015

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

QUINT-PS-24DC/24DC/10

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

TeSys contactors. TeSys D contactors. IEC/EN , IEC/EN , UL 508, CSA C22.2 n 14. Protection against direct fi nger contact IP 2X

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

QUINT-PS/ 3AC/24DC/10

02/11/2015

Solid State Relays 1-Phase, Zero Cross or Instant On Switching 25 AAC, 230 VAC with LED and Built-in Transil Types RF1A, RF1B

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

ATS01N125FT soft starter for asynchronous motor - ATS01-25 A V KW

ATS01N112FT soft starter for asynchronous motor - ATS01-12 A V KW

ATS48D75Y soft starter for asynchronous motor - ATS48-65 A V KW

Solid State Relays Industrial, 1-Phase ZS, Standard Range Types RA /RA /RA

CB Scheme UL508 UL ATEX II3G

02/11/2015

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Characteristics 5 TeSys k contactors and reversing contactors

ATS01N103FT soft starter for asynchronous motor - ATS01-3 A V KW

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

NS..S contactor relays - with spring terminals AC operated

Semiconductor contactors, Solid-state relays

s s s 3-60 s min min 3-60 min h h 3-60 h V AC, 50/60 Hz

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

LC1D25BL TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 24 V DC coil

Electronic timer CT-SDE Star-delta change-over with 1 n/c + 1 n/o contact

EMD-FL-3V-400. Electronic monitoring relay for voltage monitoring in three-phase networks. INTERFACE Data sheet _en_03. 1 Description.

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

DSR120 Series. xxx Series. 120 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details

Current monitoring relays CM-SRS.1 For single-phase AC/DC currents

Semiconductor contactors, Solid-state relays

48 Series - Relay interface modules A. Features

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Modular equipment. Presentation, standards. Standard contactors TeSys GC

Electronic timer CT-MVS.12 Multifunctional with 1 c/o (SPDT) contact

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

Transcription:

MAKING MODERN LIVING POSSIBLE Technical brochure CI-tronic Analogue Power Controller ACI 30-1 and ACI 50-1 www.danfoss.com

Contents Page Features... 3 Description... 3 Selection... 3 Technical data... 4 Operating at high temperature... 4 Control selection... 5 Function mode selection... 5 Wiring... 5 Applications (heater load)... 6 Application (transformer load)... 6 Overhead protection... 7 EMC specification... 7 Dimensions... 8 Mounting instruction... 8 2 IC.PD.C50.C2.02-520B4172

Features Phase angle or burst firing control mode Current loop control, 4-20 ma, 20-4 ma, 0-20 ma and 20-0 ma Voltage control, 0-10 V d.c. and 10-0 V d.c. Potentiometer control, 0-10 kω and 10-0 kω Rated operational voltage, 230 and 480 V Control voltage, 19-28 V a.c./d.c. DIN-rail mountable Built-in varistor protection LED status identification IP 20 protection Compact modular design Easy and quick installation Specification acc. to industrial standard CE, CSA, UL and C-tick Description The versatile ACI analogue power controller is designed for very precise temperature and transformer control. Due to the built-in microprocessor the controller can operate in phase angle as well as in burst firing control mode. The controller automatically adapts to the load to ensure a smooth inrush, and in burst firing mode it will further eliminate the unwanted effects of DC magnetizing on transformers. The ACI unit is easily connected to a PLC/regulator by means of one of the selectable input signals. The analogue controller ACI is typically used as controller for heaters and infrared lamps but also ideal on transformer controlled processes. Selection guide Operational voltage V a.c. Operational current A Supply voltage V a.c. / d.c. Dimensions mm Type Code no. 208-240 30 45 ACI 30-1 037N0057 380-480 30 45 ACI 30-1 037N0059 19-28 208-240 50 90 ACI 50-1 037N0058 380-480 50 90 ACI 50-1 037N0060 IC.PD.C50.C2.02-520B4172 3

Technical data Output specifications Operational current max. AC-51 (heater load) Operational current max. AC-56a (transformer load Operational voltage 50/60 Hz Leakage current max. Operational current min. 30 A 50 A 30 A 30 A 230 V / 480 V 1 ma 10 ma Control method Phase angle control Burst firing control Semiconductor protection fusing Type 1 co-ordination Type 2 co-ordination I2t(t=10 ms) Control circuit specifications Control supply voltage Control signals Current loop control (voltage drop < 3 V) Voltage control (input resistance > 300 kw) Potentiometer control Selectable linear power or linear voltage Selectable cycle time : 0.4-60 seconds 50 A gl/gg 1800 A2s 19-28 V a.c./d.c. 4-20 ma, 20-4 ma, 0-20 ma and 20-0 ma 0-10 V d.c. and 10-0 V d.c. 0-10 kω and 10-0kΩ Isolation Control input Floating control input Voltage line to control 2.5 kv a.c. Voltage supply to control 500 V a.c. Protection Supply and control inputs are protected against overload and over voltage EMC immunity Meets requirements of EN 50082-1 and EN 50082-2 Insulation Rated insulation voltage, Ui Rated impulse withstand voltage, Uimp Installation category 660 V 4 kv III Thermal specification Power dissipation, continuous duty 1.2 W/A Power dissipation, intermittent duty 1.2 W/A x duty cycle Ambient temperature range -5 C to 40 C Cooling method Natural convection Mounting Vertical (see general mounting instructions) Max. ambient temperature with limited current 60 C, see derating for high temperatures in chart below Storage temperature range -20 C to 80 C Protection degree/ pollution degree IP20/ 3 Material Housing Heatsink Base Self exstinguishing PPO UL 94V1 Aluminium black anodised Electroplated steel Operating at high temperature Ambient temperature ACI 30 ACI 50 40 C 30A 50A 50 C 25 A 40 A 60 C 20 A 30 A 4 IC.PD.C50.C2.02-520B4172

Control mode selection Selection of control signal The type of control signal, current, voltage or potentiometer can be selected on the rotary switch. Protection The control input is protected against overload. If the current exceeds 25 ma, the loop will switch OFF and the LEDs will indicate failure. The input will not be damaged if the 24 V supply by mistake is connected to the signal input. Control input terminals are marked with + and -. Correct polarity must be observed. The control input is floating. Insulation voltage Line voltage to control: 2500 V a.c. Supply to control: 500 V a.c. Function mode selection Phase angle Phase angle control is used for control of infrared lamps or heaters in IR heating applications. Two different operation modes can be selected Linear voltage: The load voltage varies linearly with the control signal. Linear power: The power delivered to the load varies linearly with the control signal. Phase angle Burst firing Time cycle 0.4-60 sec. Burst firing In burst firing mode full sine waves are supplied to the load. Consequently DC magnetizing of the supply transformer is avoided. The number of sine waves varies linearly with the control signal. Adjustable cycle times from 400 ms to 60 sec. Wiring 24V AC/DC 30 ma max. IC.PD.C50.C2.02-520B4172 5

Applications (heater load) Single-phase 230 V a.c. (400 V a.c.) Phase angle and burst firing mode Three-phase with neutral Phase angle and burst firing mode Three phase with single-phase contactor ECI-1 as slave Only burst firing mode R: 230 V a.c. Varistor, min. 20 mm diameter Max. load at: 230 V 400V ACI 30-1 6.9 kw 12 kw ACI 50-1 11.5 kw 20 kw Max. load at: 230 V 3 x ACI 30-1 20.7 kw 3 x ACI 50-1 34.5 kw Max. load at: ACI 30-1 ACI 50-1 400 V 20.7 kw 34.5 kw Application (transformer loads) Transformer loads ACI load driving capability includes transformer applications which means that low voltage loads can be controlled via an isolation transformer without any surge or DC magnetising of the transformer. Switching transformers The problem in transformer switching is the magnetic circuit. When the transformer is switched off, (H = 0) the field (B) remains on a high level due to the high remanence of modern transformer core material. At initial turn-on where the remanence is unknown the ACI will soft start to avoid the high current surge and at repetitive turn-on the switch-off polarity is remembered so next turn-on will be in the opposite polraty, thereby eliminating the high current surge normally seen in transformer applications. DC magnetising is eliminated by operating in full cycle mode only. Burst firing mode An initial turn on ACI will soft start the transformer to full on mode. The controller will only allow full cycles to be supplied to the transformer hereby eliminating current surges and DC saturation of the transformer Phase angle mode An initial turn on ACI will soft start the transformer to the voltage level set by the analogue input. 6 IC.PD.C50.C2.02-520B4172

Applications (transformer loads) Overhead protection If required the power controller can be protected against overheating by inserting a thermostat in the slot on the right-hand side of the controller. Order: UP 62 thermostat 037N0050 The thermostat is connected in series with the control circuit of the main contactor. When the temperature of the heat sink exceeds 100 C the main contactor will be switched OFF. A manual reset is necessary to restart this circuit. EMC specification The power controller ACI is in conformity with the standard IEC/EN 60947-4-3 AC Semiconductor Controllers and Contactors for non motor loads. Burst firing control mode: No action necessary Phase angle control mode: I <10 A, no action necessary I >10 A, connect 1uF capacitor from N/L to L1 as shown above. IC.PD.C50.C2.02-520B4172 7

Dimensions mm (inch) Mounting instruction The controller is designed for vertical mounting. If the controller is mounted horizontally, the load current must be reduced by 50%. The controller needs no side clearance. Clearance between two vertical mounted controlls must be minimum 80 mm (3.15 ). Clearance between controller and top and bottom walls must be minimum 30 mm (1.2 ). Danfoss A/S 07-2010/ AC-SMC/mr IC.PD.C50.C2.02-520B4172 8